DESIGN OF MODULAR TELECOM ROOM

FOUNDATION

TABLE OF CONTENT

S.NO DESCRIPTION PAGE NO

1 INTRODUCTION 03

2 WIND CALCULATION 04

3 STABILTY CHECK & DESIGN 05


As per ASCE Standard
7-05

DESCRIPTION REFERENCE

WIND COEFFICIENT FOUNDATION PLAN


5.31
2.705 2.705
0.7

0.8 0.5 X AXIS


TELECOM SHELTER
3.21

4.81
0.7
0.5
Centres of the footing = 2.705 m
Length of the footing = 4.81 m
Breadth of the footing = 0.5m
Depth of the footing = 0.55 m
Self weight of footing = 31.75 kN
Area of the footing, A = ( x ) = 2.405 m2
Section modulus of footing along, Zz
= 0.5 x 4.81 ^2/6 = 1.93 m3
Section modulus of footing along, Zx
= 4.81 x 0.5 ^2/6 = 0.20 m3

Check for Bearing Pressure :


Total working load on each the pedestal = 113.26 kN
( 5000 + 25567.65 + 3409.02 ) x 10 /(1000 x 3)
Wind Force Calculation:
Wind force in the shelter along X axis = (0.8+0.5) x 100 x 3.21 x 2.98
= 12.19926 kN
Moment due to wind in shelter along x axis = 18.18 kN.m
Wind force in the shelter along Z axis = (0.8+0.5) x 100 x 5.31 x 2.98
= 20.18009 kN
Moment due to wind in shelter along z axis = 30.07 kN.m
Total load acting on the pedestal, P = 113.26+3.13
= 116.3856 kN
Base pressure in the footing = P/A + Mz / Zz
= (116.39/2.405)+(15.04/1.93)
= 56.19 kN/m2 < 150 kN/m2
= Safe
Check for Over Turning:

Moment due to wind force along x axis = 18.18 / 2


= 9.09 kN.m / pedestal
Moment due to wind force along z axis = 30.07 / 2
= 15.03 kN.m / pedestal

DESCRIPTION REFERENCE

Restoring Moment :
Load due to Telecom shelter = 113.2556 kN
Self weight of footing = 31.75 kN
Restoring moment along z axis = (113.26 + 31.75) x 4.81/2
= 348.7384 kN.m
Restoring moment along x axis = (113.26 + 31.75) x 0.5/2
= 36.25139 kN.m