You are on page 1of 6

Comparison of carrier-based pulse-width modulation techniques

for three-phase four-leg inverters


Igor Musulin*
*GE Power Conversion, Rugby, UK, igor.musulin@ge.com

shown in Figure 1. AC auxiliary converter loads can include


Keywords: auxiliary power supply converter, carrier-based multiple air-conditioning units, evaporators, condenser blow-
pulse-width modulation, non-symmetrical load, three-phase er fans, main and ambient lighting, passenger information and
four-leg inverter. entertainment equipment, auxiliary and main inverter fans,
transformer fans and 230 VAC general purpose power sockets
Abstract for passenger use depending on the train or tram model. This
means that converter, i.e. three-phase inverter, must be able to
In this paper comparison of constant switching frequency generate three-phase as well as single-phase output. In mod-
carrier-based pulse-width modulation techniques for three- ern auxiliary power supply converters this is achieved using
phase four-leg inverters is presented. Space vector, one-sixth following solutions: a) single-phase 400/230 VAC transformer,
and one-fourth third-harmonic injection and sinusoidal pulse- b) delta-wye three-phase transformer connected to the invert-
width modulation are compared based on output voltage total er outputs or c) split DC-link capacitors with neutral ground-
harmonic distortion, power losses and DC voltage utilization. ed point connected to the DC-link capacitor midpoint, Table
If switching frequency of the fourth leg for sinusoidal modu- 1. Advantages and disadvantages of each solution are already
lation is equal to switching frequency of the phase legs an well-known and documented in technical papers, including
optimal compromise between power losses and voltage dis- the paper previous published by the author [1]. Even though
tortion is achieved. In case of symmetrical loads one-sixth three-phase four-leg inverter topology presents a promising
third-harmonic injection exhibits highest DC voltage utiliza- alternative it has not been extensively used in commercial
tion while lowest voltage distortion is obtained for one-fourth applications mainly due to its complex space vector control
third-harmonic injection. In case of non-symmetrical loads an scheme. Therefore, simple, easy-to-implement and fast execu-
improved algorithm for calculating third-harmonic injection tion carrier-based PWM control strategies are investigated in
waveform is proposed that reduces output voltage harmonic this paper.
content. All modulations are implemented in Texas Instru-
ments DSP environment and tested using hardware-in-the- In Chapter II a short overview of three-phase four-leg inverter
loop setup. topology is given. Different constant frequency carrier-based
PWM methods are described in Chapter III and the improved
1 Introduction algorithm for calculating third-harmonic waveform that re-
duces output voltage harmonic content is proposed. In Chap-
Today in modern railway vehicles various sub-systems are ter IV simulation model and comparison criteria are covered
present: communication and information system (SCADA), including power loss calculation algorithm. Chapter V and VI
power supply system (AC and DC), energy storage systems, presents simulation and experimental results with discussion.
etc. Auxiliary power supply converter supplies many of these Paper ends with the conclusion.
sub-systems via 230 / 400 VAC or 24 VDC voltage output as
option
Step down chopper DC/DC converter Three-phase inverter Manufacturer Power*, kVA
= = = 1 a) b) c)
2
A 24 / 2,2
VDC
3
3400 VAC
+
A 55 / 2,3
= = ~
~ 230 VAC
B 80 / 3,7
N
Battery charger
B 15 .. 120 /
= C 50 / 3,4
C 42,5 / 2,5
24 VDC
D 135 / 2
= E 13 / 4
* Three-phase / single-phase output
Figure 1: Example of a block diagram of an auxiliary power
supply converter; AC outputs: line-to-line 400 VAC (12, Table 1: List of manufacturers of auxiliary power supply con-
23, 31) and line-to-neutral 230 VAC (1N, 2N, 3N) verters for railway vehicles

1
2 Three-phase four-leg topology by comparing high-frequency triangular carrier waveform and
control waveforms (va0, vb0, vc0 and vn0), Figure 3.a).
Although today some applications using three-phase four-leg
inverter are commercially available, mainly in the field of V max
active power filters to the best knowledge of the author this  2 , V min ! 0
topology, despite its obvious advantages, has not been used in V
v n0 
min
, V max  0 (1)
auxiliary power supply converters for rail vehicles. The neu- 2

tral wire is connected to the neutral point of the fourth leg to  V max  V min , otherwise
make a return path for the current when non-symmetrical 2
conditions are present (in = (ia + ib + ic)), Figure 2. There is
no need to use bulky transformers (option a) and b)) or high where Vmin = min (va0, vb0, vc0), and Vmax = max (va0, vb0, vc0).
capacity DC capacitors to stabilize input DC voltage oscilla-
tions (c)). Other advantage is higher utilization of input volt- Zero-sequence component does not affect line-to-line (l-l)
age of more than 15 % (depending on the modulation) com- output voltage since it cancels between phases. This means
pared to classical three-leg inverter. Although complex space that an amplitude modulation index can be increased beyond
vector modulation and large number of semiconductor devic- one without entering overmodulation region. Same is with
es can be considered as a disadvantage, this type of the in- line-to-neutral (l-n) voltages where zero-sequence voltage
verter offers an optimal solution for four-wire systems sup- cancels between phase and neutral leg and only fundamental
plying non-symmetrical and single-phase loads since it allows waveform is present. When three-phase three-leg inverters are
independent control of voltages of each phase. used l-l voltage contains only fundamental harmonic, while l-
n voltage contains zero-sequence component. For that reason
3 Three-phase four-leg control space vector and any zero-sequence based modulation are not
suitable for supplying single-phase loads using option c). In
One of the main challenges when using three-phase four-leg case of three-phase four-leg inverter modulation signal of the
inverter is the control of semiconductor switches, especially fourth leg must be equal to the zero-sequence waveform vn0.
those of the fourth leg. Two control strategies are often used:
i) carrier-based pulse-width modulation, and ii) three dimen- 3.2 Third-harmonic injection pulse-width modulation
sional (3D) space vector PWM.
Concept of third-harmonic injection PWM techniques is al-
For this paper the author has chosen to primarily deal with the ready well-known from the control of the three-phase three-
constant frequency carrier-based PWM techniques. Although leg inverter-fed induction motors. There it is used to increase
in [2] it is shown that in the case of hysteresis control when
the switching frequency of the fourth leg is square pulse of
constant frequency, hysteresis controllers of the phase legs VDC/2
tune themselves to the same switching frequency; it is not a
carrier-based modulation. Also, 3D space vector modulation
is excluded from the comparison since this algorithm is not van va0

+

based on a carrier-based principle. + + S1


va0
vn0
+
S2
3.1 Space vector carrier-based pulse-width modulation vbn vb0

+

+ + S3
If zero-sequence voltage from Equation (1) is added to con- +
vn0
vb0
trol waveforms switching states equal to symmetrical space S4

vector PWM are achieved [3]. Switching states are obtained vcn vc0
+

+ + S5
vc0
vn0
+
S6

van vn0
+

vbn + S7
+ S7 S1 S3 S5 vcn
VDC (1) vn0
2 ia Lf 1 R3f
S8
a
i)
Lf V12 V31 R3f
ib 2
0 n b 3rd harmonic 3rd harmonic Const.
V23 vn0 van vn0 vn0
ic Lf 3 R3f vbn 0
+ c vcn
VDC
2 Cf Cf Cf R1f
S8 S2 S4 S6

ii) iii) iv)
V3N

in Ln N
Figure 3: Carrier-based PWM block diagram for three-phase
four-leg inverter; i) space vector, third-harmonic injection
Figure 2: Topology of three-phase four-leg inverter; single- in case of ii) symmetrical loads and iii) non-symmetrical
phase load is connected between terminals 1 and N loads (see Figure 5 for details) and iv) sinusoidal

2
fundamental harmonic of l-l voltage and achieve better utili- 0,5
zation of DC voltage. PWM voltage for one phase leg can be vn01

+
written as va0 = van + vn0, while for neutral leg is equal to vn0. + +
m3
Subtracting two phase legs voltages or phase and neutral leg
van
voltage vn0 is eliminated. One-sixth third-harmonic injection vbn
vcn
abc/
0
0/
r
r/ 0/
abc
Const. 0
produces maximum increase of fundamental component while 1
0
injection of one-fourth third-harmonic leads to maximum vn02
reduction of voltage distortion [4]. r/ 0/
0 abc

+
If three-phase four-leg inverter is used then the control signal
0,5
of the fourth leg must be equal to the injected waveform in 2/3
vn03
order for l-n voltages to contain only fundamental harmonic, +
Figure 3.b). However, there it is assumed that voltages van, vbn 4/3
and vcn have the same amplitude modulation index and that
the third-harmonic amplitude modulation index is calculated Figure 5: Proposed modifications of third-harmonic algorithm
only as a function of a single voltage. For non-symmetrical for calculating zero-sequence voltage
loads where the amplitudes of control waveforms are not
equal zero-sequence voltage has to be calculated as a function there must also be used three polar coordinates: radial dis-
of these waveforms and input voltage as in Equation (1). For tance r, azimuth angle and polar angle . Third-harmonic
that reason modification of zero-sequence waveform calcula- waveform is calculated using two different approaches, thus
tion algorithm is proposed. two modifications are presented. Third-modification is only
combination of first two. For first modification azimuth angle
Firstly, depending on the load characteristics injected pre- is neglected, i.e. multiplied by 0, radial distance r is multi-
defined third-harmonic waveform is not in phase with control plied with third-harmonic magnitude and polar angle is shift-
voltages. While elimination of injected waveform is still hap- ed by 2/3 and 4/3 and added to get 3 50 Hz = 150 Hz
pening slight difference in phase leads to increase in harmon- oscillations. From there polar to Cartesian and 0/abc trans-
ic distortion of output voltages. Secondly, in case of non- formation gives three in-phase third-harmonic waveforms.
symmetrical loads injected third-harmonic waveform stays They are still symmetrical in regards to x-axis, but now in
symmetrical in regards to x-axis, Figure 4. Therefore zero- phase with phase leg control voltages. In order to add oscilla-
sequence voltage should be in phase with control voltages and tions characteristic to non-symmetrical loads control voltages
oscillate at third-harmonic frequency. van, vbn and vcn are added, scaled by 0,5 and added to in-
phase third-harmonic waveform thus producing vn01. For sec-
Three modifications of injected harmonic calculation algo- ond modulation azimuth angle is not neglected while scal-
rithm are proposed and tested, Figure 5. In order to get third- ing of r and adding of shifted is done as in previous case.
harmonic waveform in phase with control voltages van, vbn and After 0/abc transformation three oscillating third-harmonic
vac these voltages are transformed to 0 reference frame fol- waveforms are obtained. The waveform in phase with angle
lowed by Cartesian to polar transformation. Since for non- is chosen as vn02. Later in this paper under Simulation results
symmetrical systems all three voltages in 0 frame are used section it will be shown that these modification reduce har-
monic distortion is opposite phases. In order to get optimal
reduction of THD optimal zero-sequence voltage waveform
vn03 is calculated as arithmetical mean of vn01 and vn02. In Fig-
vn0
ure 6 zero sequence waveforms are shown for all three modi-
Voltage, V

0
fications. In case of symmetrical load oscillation is zero, i.e.
azimuth angle is zero, sum of controller voltages is zero and
only in-phase third-harmonic is obtained equal in all three
0 5 10 15 20
modifications.
Time, ms

vn01
vn03vn02
Voltage, V
Voltage, V

vn0
0 0

0 5 10 15 20 0 5 10 15 20

Time, ms Time, ms

Figure 4: One-fourth third-harmonic injection and space vec- Figure 6: One-fourth third-harmonic injection waveforms for
tor (dashed line) zero-sequence voltage for symmetrical non-symmetrical loads; waveforms vn01, vn02 and vn03 are
(top) and non-symmetrical loads (bottom) calculated according to algorithms proposed in Figure 5

3
3.3 Sinusoidal pulse width modulation manufacturers also have their own power loss calculation
tools, e.g. Semisel (Semikron), Iposim (Infineon), Melcosim
The sinusoidal Pulse-Width Modulation is the most used (Mitsubishi), etc. Since PWM control of the fourth leg is not
modulation for three-phase inverters in general, including the standard one, Matlab Simulink subsystem is built based
application in auxiliary power supply converters, due to its on the look-up table. Data from a Semikron SKM150GB12V
simplicity of implementation and low voltage distortion. Un- (VCE = 1200 V, IC = 150 A) IGBT module used in Kontrac PN
like previously described modulation techniques, sinusoidal 35 DC auxiliary power converter are used for power losses
modulation can be used to supply single-phase loads using all calculation. It is important to note that losses are calculated
mentioned options from Chapter I. When implementing in for the junction temperature of 150 C.
DSP or any real time processor, commercially available pro-
gramming tools often contain pre-defined sinusoidal modula- Switching loss calculation
tion blocks based on look-up tables or calculation of switch- Since in the simulations switching voltage and current rise
ing pulses duration. For this reason, using any of the previ- and fall are instantaneous, switching duration is equal to the
ously mentioned modulation techniques would require addi- one sample period Ts. Switching turn-on and turn-off energy
tional coding and optimization. are obtained from the look-up table corresponding to the cur-
rent during turn-on and turn-off, respectively. Energy is
When PWM reference waveforms are sinusoidal fourth leg scaled based on an input DC-link voltage, Figure 7.a) and
should be switched to achieve zero average. This is achieved 7.b).
using a square pulse of constant frequency (50 % duty cycle)
[4], Figure 3 d). However, authors do not further discuss this Conduction loss calculation
modulation or give optimal switching frequency of the fourth Conduction losses are calculated simply by multiplying cur-
leg. Therefore, additional research is conducted to determine rent and on-state voltage across the IGBT. Voltage vCE is cal-
the optimal switching frequency of the fourth leg. culated from the pre-defined look-up table, which stores volt-
age as a function of a current iC and is obtained from a data
4 Simulation model and comparison criteria sheet, Figure 7.c).
Three-phase four-leg inverter model is simulated using
Matlab Simulink environment. Input voltage is set to 670 V, 5 Simulation results and discussion
switching frequency is 4 kHz and resonant filter frequency is First a simulation to determine the optimal switching frequen-
chosen above 1,6 kHz. Output l-l voltage is 400 V, maximum cy of the fourth leg using sinusoidal modulation is conducted.
output three-phase power is 35 kW and minimum is 3,5 kW. Switching frequency of the phase legs is set to 4 kHz, while
Two types of simulations are done. First, an amplitude modu- the switching frequency of the fourth leg is varied from 1 kHz
lation index is varied and voltage distortion and DC voltage to 8 kHz. From results it can be see that higher the switching
utilization are measured for symmetrical load. Then single- frequency higher the losses. Regarding the power losses of
phase load is connected and power losses and total harmonic the phase legs there is no significant difference between test-
distortion are measured for tested modulations for P3max and ed fourth leg switching frequencies as well as tested modula-
P3min while single-phase load is changed from P3max (11,67 tion techniques. Lowest harmonic distortion of output l-n
kW) to 0,8 kW.
Look-up
table
Regarding the calculation of total harmonic distortion it is iC EOFF

important to note that voltage distortion depends on the cur- 0

rent distortion which further depends on load characteristics Pulse change


detection

and filter parameters. For that reason a weighted total har- S1 1 VDC VCC
0
monic distortion is used for comparing different pulse switch-
ing frequency of the fourth leg for sinusoidal pulse width a)
modulation. When calculating WTHD, load is characterized Look-up
table

by lossy inductance which is inductance with a relatively iC EON



small resistance [4]. This means that different modulation 0

techniques can be compared independent of the load and filter Pulse change
detection
S1 VDC VCC
parameters. However, since this value is not mentioned in any 0
1


relevant standards THD is calculated for other modulations
b)
and used for comparison.
Look-up
table
iC vCE
4.1 Power loss calculation

iC
Today numerous analytical approximation techniques for
semiconductor power loss calculation exist and many of them c)
are described in the literature. Some of the parameters can be
obtained from data sheets (vCE0, vD0, rC, rD) while others must Figure 7: Block diagram for calculating power losses: a) turn-
be calculated (iCav, iCr.m.s.). Additionally, many semiconductor off losses, b) turn-on losses and c) conduction losses

4
voltage is achieved if the switching frequency is equal to the 6,5

switching frequency of the phase legs. Harmonic distortion 6,0


vn0 for space vector
vn01 for 3rd
for l-l voltage is similar regardless of the fourth leg switching 5,5
vn02 for 3rd

THD V12, %
frequencies. Based primarily on the harmonic distortion crite- 5,0 vn03 for 3rd
ria switching frequency of the fourth leg is chosen to be equal 4,5

to the switching frequency of the phase legs. In auxiliary 4,0

power supply converter application in traction vehicles sin- 3,5


gle-phase current is not expected to be higher than 15 A ( 0 10 20 30 40 50 60

Curren t, A
3,5 kW, Table 1) so this frequency gives an optimal trade-off 6,5
between the (W)THD and power losses in this range (0 .. 15
6,0
A).
5,5

THD V23, %
Comparison of DC voltage utilization in case of three-phase 5,0
vn0 for space vector

symmetrical loads gives highest increase in linearity for space 4,5 vn01 for 3rd
vn02 for 3rd
vector and one-sixth third-harmonic injection PWM. Regard- 4,0
vn03 for 3rd
ing the harmonic distortion, in Chapter III it was already men- 3,5
0 10 20 30 40 50 60

tioned that one-fourth third-harmonic injection PWM has Curren t, A

lowest THD followed by symmetrical space vector. All tested 6,5

modulations have THD values below the compliance limit 6,0

according to IEC 61000-4-30. 5,5

THD V31, %
5,0
vn0 for space vector
Comparison of modulation techniques is also given in case of 4,5 vn01 for 3rd
non-symmetrical loads. Load in one phase is increased by 4,0 vn02 for 3rd
connecting a single-phase load between the phase and neutral. 3,5
vn03 for 3rd

Unlike in previous case under symmetrical loads where THD 0 10 20 30 40 50 60

Curren t, A
is equal for all phase, here it depends on the load. For that 6,5
reason all four THD values are given (three l-l outputs and l-n vn0 for space vector
6,0
output), Figure 8. First it can be seen that THD values depend vn01 for 3rd
5,5
on the load of that phase. For l-l outputs 23 and 31 there is no
THD V1n, %

vn02 for 3rd


vn03 for 3rd
additional load so THD is slightly higher. When proposed 5,0

modification of third-harmonic injection waveform calcula- 4,5

tion algorithm is used THD values of single-phase output and 4,0

output 12 for all three cases are almost the same for different 3,5
0 10 20 30 40 50 60

single-phase loads. For other two l-l outputs first modification Curren t, A

(vn01) reduces THD in one phase while increases in another.


Opposite situation is with second modification (vn02). There- Figure 8: Comparison of voltage THD for non-symmetrical
fore third one (vn03) as a combination of two previously pro- loads for one-fourth third harmonic injected waveform as
posed modifications is simulated and results show reduction function of r.m.s. neutral current in with P3max, upper three
in THD for all outputs. Results are even better that those ob- figures show l-l voltages, bottom shown l-n voltage
tained for optimal space vector modulation. Similar results
are also obtained in case of P3min and again third modification control is used to control the output AC voltage independent
exhibits best results regarding the THD. of the load parameters. Input source DC voltage is set to 670
VDC. Maximum three-phase load is 35 kW and single-phase
Input DC voltage is set to achieve unit modulation index for load is 2,3 kW.
defined reference AC output for sinusoidal modulation. How-
ever in case of non-symmetrical loads overmodulation of In Figure 9 input control voltage waveforms are shown in
PWM waveform can be expected. For that reason, sinusoidal case of symmetrical loads. In the first window van, vbn and vcn
PWM exhibits significantly higher THD results due to its waveform are shown, while in the second scaled va0, vb0, vc0
reduced linear DC voltage utilization operation. and vn0 waveforms for space vector PWM are shown. It can
be seen that for sinusoidal PWM input DC voltage is not high
6 Experimental results and discussion enough to remain in the linear region since one half of DC
voltage is below the maximum amplitude of the above vxn. If
Modulation techniques are tested using hardware-in-the-loop space vector PWM is used an operation in the linear region is
setup. Three-phase four-leg topology is implemented in Ty- achieved and vx0 is below limits of 1. In second case single-
phoon HIL 600 platform and the modulation algorithm is phase load is switched on and the same waveforms are rec-
coded in Texas Instruments TMS320F28335 controlCARD orded. Since a single-phase load is less than 10 % of a three-
using GRAP, graphical based block-diagram programming phase load, compensating change in the amplitude is small.
tool. Output l-n voltage reference is set to 230 VAC. Dual loop For that reason bigger single-phase load equal to of the
control strategy with proportional-integral-resonant (PIR) three-phase load is simulated, Figure 10. From there it can be

5
Figure 9: Control waveforms for space vector PWM with Figure 10: Control waveforms for space vector PWM with
symmetrical three-phase load 35 kW non-symmetrical single-phase load 17,5 kW
UASIN = van, UBSIN = vbn, UCSIN = vcn, UDC05A = UASIN = van, UBSIN = vbn, UCSIN = vcn, UDC05A =
VDC, VDC,
U1DLTTHI = va0, U2DLTTHI = vb0, U3DLTTHI = vc0, U1DLTTHI = va0, U2DLTTHI = vb0, U3DLTTHI = vc0,
U4DLTTHI = vn0 U4DLTTHI = vn0

seen that the input PWM voltage is non-symmetrical in order


to compensate for non-symmetrical loads according to Ohms All compared modulations are implemented in DSP and test-
law. This is important to keep in mind when determining min- ed on a target system. In case of non-symmetrical loads, input
imum input DC voltage. If set to low in some cases an over- PWM voltage can get outside the linear region so special con-
modulation can be expected. sideration has to be taken into account when selecting appro-
priate DC voltage and/or modulation strategy.
7 Conclusion
Acknowledgements
In this paper carrier-based space vector PWM, one-sixth and
one-fourth third-harmonic injection PWM and sinusoidal The author would like to acknowledge the help of Josip Babi
PWM techniques for control of three-phase four-leg inverter and Ante Knezovi from Konar Electrical Engineering Insti-
are compared. tute Inc.

First an optimal switching frequency of the fourth leg for si- References
nusoidal modulation is determined. The results show that the
best compromise between the voltage distortion and power [1] I. Musulin, . Jakopovi, Three-Phase Inverters Sup-
loss is achieved if the switching frequency of the fourth leg is plying Non-Symmetrical, Non-Linear and Single Phase
equal to the switching frequency of the phase legs. Power Loads, Proceedings of EDPE 2013 - 17th International
losses of the fourth leg can be further minimized by selecting Conference on Electrical Drives and Power Electronics,
IGBTs with lower current rating. Next modulation techniques Oct., 2-4, 2013, Dubrovnik, Croatia pp. 184-192
are evaluated base on the power loss, output voltage distortion [2] A. Able and G. Vincent, A Constant Switching Fre-
and DC voltage utilization criteria in case of the symmetrical quency DSTATCOM Operating under Non-Stiff Source
loads. The results show that there is no significant difference Condition, Proceedings of NCTT 09 - 10th National
in power losses between modulations. Regarding the voltage Conference on Technological Trends, Nov., 6-7, 2009,
distortion, the lowest one is achieved for one-fourth third- Kerala, India, pp. 124-128
harmonic injection followed by space vector. The highest DC [3] K. Zhou and D. Wang, Relationship between Space-
voltage utilization is obtained for one-sixth third-harmonic vector Modulation and Three-phase Carrier-based
injection, followed by space vector. Finally voltage distortion PWM: A Comprehensive Analysis, IEEE Transactions
is measured in case of non-symmetrical loads. For third- on Industrial Electronics, 49(1), pp. 186-196.
harmonic injection modulations voltage distortion is meas- [4] D. Holmes and T. Lipo, Pulse Width Modulation for
ured with and without the improved algorithm for calculating Power Converters: Principles and Practice, Wiley-IEEE
injected waveform. The results show improvement in THD Press, Oct. 2003
when modification is applied. The lowest voltage total har-
monic distortion is achieved for one-fourth third-harmonic
injection.

You might also like