You are on page 1of 19

NOTES :

1) SCHEME SHOWS BREAKER TRIPPED, WITHOUT SF6 GAS PRESSURE


AND CLOSING SPRING CHARGED

2) CONTACTORS SHOWN IN DE-ENERGISED CONDITION

3) PANEL WIRED WITH FRLS COPPER WIRE SIZE OF 1.5 Sq.mm

4) COLOUR OF WIRES: BLACK - AC CIRCUIT, GREY - DC CIRCUIT, GREEN - EARTH

5) CONTINUOUS POWER USED FOR SUPERVISION OF COILS SHOULD


NOT EXCEED 4 WATT

6) ALL TERMINALS USED IN MECHANISM CUBICLE ARE OF SCREW TYPE


WITH SINGLE LOCK NUT OF PHOENIX MAKE - MODEL UK-5N

7) LOCATION REFERENCE

MULTICORE TERMINAL

DM DENSIMETER
MC MECHANISM CUBICLE

8) GAS PRESSURE

SF6 PRESSURE MPa


FILLING 0.74 0.64
ALARM (P1) 0.64 0.54
LOCKOUT (P2) 0.61 0.51
MOTOR CIRCUIT HEATING AND LIGHTING CIRCUIT

TB1 MCB1 TB1 MCB2


220V DC M1 220V AC H1 H3
(+VE) (+) (-) (Ph.) 1 2
4 1
M3

LS
1 1

2 DS TH
2 2

M5

H5 H7
X1
A1
M
TR1
M X1
1
A2 IL
H
X2 2
X2

M6

LS

M4

TB1 MCB1 TB1 MCB2


220V DC M2 220V AC H2 H4
(-VE) (-) (+) (N) 3 4
5 2
TB1 15 TB1 14 TB1 18 TB1 19 TB1 17 TB1 16 TB1 11 TB1 12 TB1 13 TB1 29 TB1 28 TB1 25 TB1 26 TB1 27

220V DC1 K9A K9 K17 K71 K13 K3 K5 K7 220V DC2 K313 K303 K305 K307
(+VE) (+VE)
TB1 MCB3 TB1 MCB4
J1 K71 J5 K371
(+) (-) (+) (-)
7 9

3
3
3
PBS1 PBS2
4 PBS2
4
4

TB1 20 TB1 21 TB1 30


K21 K321

7 5 11 9
3 1
L O R L O R
L O R
43A 1 3 43A 5
43A

6 10 P2
2 P1 P2

2 4 6
K11

21 TB1 23 TB1 24 TB1 32

94 21 21

22 A3 A4
K701 22 22
31

A3
1 11 13
32 13 3
5
94 S1 S1 S1
K703 S1
S1
14 2 12 14
31 4
6
A4

32

K705

S1

10

K707
9

LS

10

K709 K79 K25 K73 K173 K325 K373

1 A1 1 A1 A1 1 A1

52CC 94 52TC1 A2 A3 52TC2 A4


2 A2 2 A2 A2 2 A2

220V DC1 220V DC2


(-VE) (-VE)
TB1 MCB3 TB1 MCB4
J2 K72 J6 K372
(-) (+) (-) (+)
8 10

TB1 22 TB1 31
TB1
TB1

MCB1
MOTOR SUPPLY MCB TRIPPED ALARM

12
11

34
33

X1-2
X1-1

TB1
TB1

MCB2
HEATING & LIGHTING SUPPLY MCB TRIPPED ALARM

12
11

36
35

X1-4
X1-3

TB1
TB1

MCB3
CLOSING & TRIPPING COIL 1 SUPPLY MCB TRIPPED ALARM

12
11

38
37

X1-6
X1-5

TB1
TB1

MCB4
TRIPPING COIL 2 SUPPLY MCB TRIPPED ALARM

12
11

40
39

X1-8
X1-7

TB1
TB1

A2
SF6 PRESSURE 1ST STAGE (ALARM)
14
13

42
41

X2-2
X2-1

TB1
TB1

A3

SF6 PRESSURE 2ND STAGE (LOCKOUT)


14
13

44
43

X3-12
X3-11

TB1
TB1

A4

SF6 PRESSURE 2ND STAGE (LOCKOUT)


14
13

46
45

X3-22
X3-21

43A
TB1

TB1
L

LOCAL SELECTION
15
48

X4-2

14

47
X4-1
R
13
TB1

REMOTE SELECTION
49

X4-3

TR1

TB1
TB1

SPRING CHARGE FAILURE ALARM


16 18
15

51
50

X5-2
X5-1

TB1
TB1

LS

SPRING CHARGE INDICATION ALARM


12
11

53
52

X6-2
X6-1
TB2 1 TB2 3 TB2 5 TB2 7 TB2 9 TB2 11 TB2 13 TB2 15 TB2 17 TB2 19 TB2 21 TB2 23

U1 U3 U5 U7 U9 U11 U13 U15 U17 U19 U21 U23

1 3 5 7 1 3 5 7 1 3 5 7
S2 S2 S2 S2 S3 S3 S3 S3 S4 S4 S4 S4
2 4 6 8 2 4 6 8 2 4 6 8

U2 U4 U6 U8 U10 U12 U14 U16 U18 U20 U22 U24

TB2 2 TB2 4 TB2 6 TB2 8 TB2 10 TB2 12 TB2 14 TB2 16 TB2 18 TB2 20 TB2 22 TB2 24

TB2 25 TB2 27 TB2 29 TB2 31 TB2 33 TB2 35 TB2 37 TB2 39 TB2 41 TB2 43 TB2 45 TB2 47

U25 U27 U29 U31 U33 U35 U37 U39 U41 U43 U45 U47

9 11 13 15 9 15 9 11
11 13 13 15

S2 S2 S2 S2 S3 S3 S3 S4 S4
S3 S4 S4
10 12 14 16 10 16 10 12
12 14 14 16

U26 U28 U30 U32 U34 U36 U38 U40 U42 U44 U46 U48

TB2 26 TB2 28 TB2 30 TB2 32 TB2 34 TB2 36 TB2 38 TB2 40 TB2 42 TB2 44 TB2 46 TB2 48
TAGNAME DESCRIPTION SPECIFICATION MAKE MODEL ALTERNATE MAKE ALTERNATE MODEL QUANT PANEL NUMBER
43A LOCAL / OFF/REMOTE SELECTOR SWITCH LOCAL-OFF-REMOTE NONLOCKABLE SWITCH,25 AMP, POLE:4 KRAUS & NAIMER CHR16-A213-600 GIOVENZANA/SALZER/EQUIVALENT - 1 MC
52CC CLOSING COIL BREAKER COIL 345W, 220V DC, 4W CONTINUOUS ALSTOM HEH4910211023 - - 1 MC
52TC1 TRIPPING COIL 1 BREAKER COIL 345W, 220V DC, 4W CONTINUOUS ALSTOM HEH4910211023 - - 1 MC
52TC2 TRIPPING COIL 2 BREAKER COIL 345W, 220V DC, 4W CONTINUOUS ALSTOM HEH4910211023 - - 1 MC
94 ANTIPUMPING AUX.CONTACTOR 2NO+2NC 220V DC SIEMENS 3RH21 22-1BM40 CA3KN22MD/DILA-22(220VDC) 1 MC
A2 SF6 LOW PRESSURE ALARM AUX.CONTACTOR 2NO+2NC 220V DC SIEMENS 3RH21 22-1BM40 CA3KN22MD/DILA-22(220VDC) 1 MC
A3 SF6 LOW PRESSURE LOCKOUT 1 AUX.CONTACTOR 2NO+2NC 220V DC SIEMENS 3RH21 22-1BM40 CA3KN22MD/DILA-22(220VDC) 1 MC
A4 SF6 LOW PRESSURE LOCKOUT 2 AUX.CONTACTOR 2NO+2NC 220V DC SIEMENS 3RH21 22-1BM40 CA3KN22MD/DILA-22(220VDC) 1 MC
DM DENSIMETER DENSIMETER 3NC (P1- ALARM & P2- LOCKOUT) WIKA 233.52.100-7878984 EQUIVALENT - 1 MC
DS DOOR SWITCH PUSHBUTTON 1NC BLOCK ALLEN-BRADLEY 800F-BX01 EQUIVALENT - 1 MC
H HEATER HEATER 75W, 120-240V AC STEGO HG140 (14006.0-00) EQUIVALENT - 1 MC
IL CUBICLE ILLUMINATION LAMP 11W, 230V AC TYPE: CFL,MODEL : B22 PHILIPS B22-230V EQUIVALENT - 1 MC
LS LIMIT SWITCH AUX. SWITCH CONTACTS: 4NO + 4NC, 15AMP ALSTOM JE4910510001 - - 1 MC
M SPRING CHARGING MOTOR 220-250V AC/DC,380 WATT AGNI HRCC4100028-2 (S311-220) GROSCHOPP/WUXI/EQUIVALENT - 1 MC
MCB1 MINIATURE CIRCUIT BREAKER - MOTOR SUPPLY MCB-DC 6A 2P 6KA EATON PLS6-C6/2-DC SCHNEIDER/GE/EQUIVALENT C60H-A9N61526 1 MC
MCB1 MCB-AUX.CONTACT MOTOR SUPPLY FAILURE MCB AUX CONTACT 1NO+1NC EATON ZP-1HK SCHNEIDER/GE/EQUIVALENT A9N26924 1 MC
MCB2 MINIATURE CIRCUIT BREAKER - HEATING & LIGHTING MCB-AC 6A DP 10KA EATON PLSM-C6/2 SCHNEIDER/GE/EQUIVALENT XC60-A9N2P06C 1 MC
MCB2 MCB-AUX.CONTACT HEAT & LIGHT SUPPLY FAIL MCB AUX CONTACT 1NO+1NC EATON ZP-1HK SCHNEIDER/GE/EQUIVALENT A9N26924 1 MC
MCB3 MINIATURE CIRCUIT BREAKER - DC SUPPLY 1 MCB-DC 6A 2P 6KA EATON PLS6-C6/2-DC SCHNEIDER/GE/EQUIVALENT C60H-A9N61526 1 MC
MCB3 MCB-AUX.CONTACT DC SUPPLY 1 FAILURE MCB AUX CONTACT 1NO+1NC EATON ZP-1HK SCHNEIDER/GE/EQUIVALENT A9N26924 1 MC
MCB4 MINIATURE CIRCUIT BREAKER - DC SUPPLY 2 MCB-DC 6A 2P 6KA EATON PLS6-C6/2-DC SCHNEIDER/GE/EQUIVALENT C60H-A9N61526 1 MC
MCB4 MCB-AUX.CONTACT DC SUPPLY 2 FAILURE MCB AUX CONTACT 1NO+1NC EATON ZP-1HK SCHNEIDER/GE/EQUIVALENT A9N26924 1 MC
PBS1 PUSHBUTTON - CLOSE PUSHBUTTON GREEN +1NO BLOCK SIEMENS 3SB50 00-0AE01+3SB54 00-0B SCHNEIDER/GE/EQUIVALENT XB5AA31N 1 MC
PBS2 PUSHBUTTON - TRIP 1 PUSHBUTTON RED +1NO BLOCK SIEMENS 3SB50 00-0AC01+3SB54 00-0B SCHNEIDER/GE/EQUIVALENT XB5AA41N 1 MC
PBS2 PUSH BUTTON ADD ON BLOCK-TRIP 2 PUSHBUTTON 1NO ADDON BLOCK SIEMENS 3SB54 00-0B SCHNEIDER/GE/EQUIVALENT ZBE101N 1 MC
S1 AUXILIARY SWITCH AUX. SWITCH CONTACTS: 4NO + 4NC, 15AMP ALSTOM JE4910510001 - - 1 MC
S2 AUXILIARY SWITCH AUX. SWITCH CONTACTS: 4NO + 4NC, 15AMP ALSTOM JE4910510001 - - 1 MC
S3 AUXILIARY SWITCH AUX. SWITCH CONTACTS: 4NO + 4NC, 15AMP ALSTOM JE4910510001 - - 1 MC
S4 AUXILIARY SWITCH AUX. SWITCH CONTACTS: 4NO + 4NC, 15AMP ALSTOM JE4910510001 - - 1 MC
TH THERMOSTAT THERMOSTAT 0deg. TO 60deg. C STEGO KTO 011 (01146.9-00) EQUIVALENT - 1 MC
TR1 TIME DELAY RELAY - SPRING CHARGE FAILURE TIMING : 0.05-100 HR , 2CO, 24-220V AC/DC SIEMENS 3RP15 25-1BW30 ALLENBRADLEY/EQUIVALENT FSM4UU18 1 MC
TB1 TERMINAL BLOCK TYPE : UK5N PHOENIX UK5N EQUIVALENT - 51 MC
TB2 TERMINAL BLOCK TYPE : UK5N PHOENIX UK5N EQUIVALENT - 48 MC
TB1 TERMINAL BLOCK TYPE : UK5N PHOENIX UK5N EQUIVALENT - 2 MC
TB2 TERMINAL BLOCK TYPE : UK5N PHOENIX UK5N EQUIVALENT - 2 MC
SPECIFICATION BREAKER COIL 345W, 220V DC, 4W CONTINUOUS
1

MAKE ALSTOM

2
MODEL HEH4910211023

TAG DESCRIPTION PANEL REF COIL

52CC CLOSING COIL MC SHT.4/2G


52TC1 TRIPPING COIL 1 MC SHT.4/2F
52TC2 TRIPPING COIL 2 MC SHT.4/2C

SPECIFICATION AUX. SWITCH CONTACTS: 4NO + 4NC, 15AMP


1 3 5 7 9 11 13 15

MAKE ALSTOM

2 4 6 8 10 12 14 16
MODEL JE4910510001

TAG DESCRIPTION PANEL REF NO NO NO NO NO NO NO NO

LS LIMIT SWITCH MC SHT.3/3F SHT.3/2F SPARE SPARE SHT.4/2G SHT.5/2C SPARE SPARE
S1 AUXILIARY SWITCH MC SHT.4/2F SHT.4/2F SHT.4/2C SPARE SHT.4/2G SHT.4/2E SHT.4/2B SPARE
S2 AUXILIARY SWITCH MC SHT.6/3F SHT.6/3F SHT.6/3F SHT.6/3E SHT.6/2F SHT.6/2F SHT.6/2F SHT.6/2E
S3 AUXILIARY SWITCH MC SHT.6/3E SHT.6/3E SHT.6/3D SHT.6/3D SHT.6/2E SHT.6/2E SHT.6/2D SHT.6/2D
S4 AUXILIARY SWITCH MC SHT.6/3D SHT.6/3C SHT.6/3C SHT.6/3C SHT.6/2D SHT.6/2C SHT.6/2C SHT.6/2C

SPECIFICATION AUX.CONTACTOR 2NO+2NC 220V DC


A1 13 21 31 43

MAKE SIEMENS

A2 14 22 32 44
MODEL 3RH21 22-1BM40

TAG DESCRIPTION PANEL REF COIL NO NC NC NO

94 ANTIPUMPING MC SHT.4/2G SHT.4/2G SHT.4/3G SPARE SPARE


A2 SF6 LOW PRESSURE ALARM MC SHT.4/2D SHT.5/2E SPARE SPARE SPARE
A3 SF6 LOW PRESSURE LOCKOUT 1 MC SHT.4/2D SHT.5/2E SHT.4/3F SHT.4/3G SPARE
A4 SF6 LOW PRESSURE LOCKOUT 2 MC SHT.4/2A SHT.5/2E SHT.4/3C SHT.4/2G SPARE

SPECIFICATION TIMING : 0.05-100 HR , 2CO, 24-220V AC/DC A1 15 25

MAKE SIEMENS

MODEL 3RP15 25-1BW30 A2 16 18 26 28

TAG DESCRIPTION PANEL REF TIMER C/O C/O

TR1 TIME DELAY RELAY - SPRING CHARGE FAILURE MC SHT.3/3F SHT.5/2D SPARE
SPECIFICATION PUSHBUTTON 1NC BLOCK 1

MAKE ALLEN-BRADLEY

MODEL 800F-BX01
2
TAG DESCRIPTION PANEL REF

DS DOOR SWITCH MC SHT.3/3C

SPECIFICATION 11W, 230V AC TYPE: CFL,MODEL : B22


X1

MAKE PHILIPS
X2

MODEL B22-230V

TAG DESCRIPTION PANEL REF

IL CUBICLE ILLUMINATION LAMP MC SHT.3/3C

SPECIFICATION PUSHBUTTON RED +1NO BLOCK


3 3

MAKE SIEMENS

4 4
MODEL 3SB50 00-0AC01+3SB54 00-0B

TAG DESCRIPTION PANEL REF PB NO NO

PBS2 PUSHBUTTON - TRIP 1 MC SHT.4/4F SHT.4/4C

SPECIFICATION PUSHBUTTON GREEN +1NO BLOCK


3

MAKE SIEMENS

4
MODEL 3SB50 00-0AE01+3SB54 00-0B

TAG DESCRIPTION PANEL REF PB NO

PBS1 PUSHBUTTON - CLOSE MC SHT.4/4G


REMOTE
LOCAL
SPECIFICATION LOCAL-OFF-REMOTE NONLOCKABLE SWITCH,25 AMP, POLE:4

OFF
3 1 7 5 11 9 15 13

MAKE KRAUS & NAIMER


2 6 10 14
MODEL CHR16-A213-600

TAG DESCRIPTION PANEL REF

43A LOCAL / OFF/REMOTE SELECTOR SWITCH MC SHT.4/3G SHT.4/3F SHT.4/3C SHT.5/2D

SPECIFICATION MCB-DC 6A 2P 6KA


23 11
(+) (-)

MAKE EATON

24 12
MODEL PLS6-C6/2-DC (-) (+)

TAG DESCRIPTION PANEL REF POLE 1 POLE 2 NO NC

MCB2 MINIATURE CIRCUIT BREAKER - HEATING & LIGHTING MC SHT.3/3C SHT.3/2C SPARE SHT.5/2F

SPECIFICATION MCB-DC 6A 2P 6KA


23 11
(+) (-)

MAKE EATON

24 12
MODEL PLS6-C6/2-DC (-) (+)

TAG DESCRIPTION PANEL REF POLE 1 POLE 2 NO NC

MCB1 MINIATURE CIRCUIT BREAKER - MOTOR SUPPLY MC SHT.3/3F SHT.3/2F SPARE SHT.5/2G
MCB3 MINIATURE CIRCUIT BREAKER - DC SUPPLY 1 MC SHT.4/4H SHT.4/1H SPARE SHT.5/2F
MCB4 MINIATURE CIRCUIT BREAKER - DC SUPPLY 2 MC SHT.4/4C SHT.4/1C SPARE SHT.5/2F
SPECIFICATION HEATER 75W, 120-240V AC
1
MAKE STEGO
2

MODEL HG140 (14006.0-00)

TAG DESCRIPTION PANEL REF

H HEATER MC SHT.3/3B

SPECIFICATION THERMOSTAT 0deg. TO 60deg. C 1

MAKE STEGO

MODEL KTO 011 (01146.9-00)


2
TAG DESCRIPTION PANEL REF

TH THERMOSTAT MC SHT.3/3B

SPECIFICATION DENSIMETER 3NC (P1- ALARM & P2- LOCKOUT)


1 3 5

MAKE WIKA

2 4 6
MODEL 233.52.100-7878984

TAG DESCRIPTION PANEL REF NC NC NC

DM DENSIMETER MC SHT.4/3D SHT.4/3D SHT.4/3A

SPECIFICATION 220-250V AC/DC,380 WATT


X1

MAKE AGNI
M
MODEL HRCC4100028-2 (S311-220) X2

TAG DESCRIPTION PANEL REF

M SPRING CHARGING MOTOR MC SHT.3/3F


CUSTOMER INTERFACING MECHANISM PANEL CUSTOMER INTERFACING MECHANISM PANEL

MC
TB1

53 X6-2 MC
SPRING CHARGE INDICATION ALARM
52 X6-1 TB2
51 X5-2
SPRING CHARGE FAILURE ALARM
50 X5-1 50
REMOTE SELECTED
49 X4-3 49
LOCAL SELECTED
48 X4-2 48 U48
LOCAL/REMOTE COMMON
47 X4-1 47 U47
46 X3-22 46 U46
SF6 GAS PRESS. LOCKOUT 1 ALARM
45 X3-21 45 U45
44 X3-12 44 U44
SF6 GAS PRESS. LOCKOUT 1 ALARM
43 X3-11 43 U43
42 X2-2 42 U42
SF6 GAS PRESS. LOW ALARM
41 X2-1 41 U41
40 X1-8 40 U40
TRIPPING COIL 2 SUPPLY MCB TRIPPED ALARM
39 X1-7 39 U39
38 X1-6 38 U38
CLOSING & TRIPPING COIL 1 SUPPLY MCB TRIPPED ALARM
37 X1-5 37 U37
36 X1-4 36 U36
HEATING & LIGHTING MCB TRIPPED ALARM
35 X1-3 35 U35
34 X1-2 34 U34
MOTOR SUPPLY TRIPPED ALARM
33 X1-1 33 U33
6 C1
32 K373 32 U32
31 K372 31 U31
5
30 K371 30 U30
REMOTE TRIP 2 +VE
29 K371 29 U29
REMOTE TRIP 2
28 K313 28 U28
TRIP 2 PRECLOSE SUPVN.
27 K307 27 U27
TRIP 2 POST CLOSE SUPVN.
26 K305 26 U26
PROTECTION TRIP 2
25 K303 25 U25
4
24 K173 24 U24
2
23 K73 23 U23
22 K72 22 U22
3
21 K71 21 U21
1
20 K71 20 U20
REMOTE CLOSE/TRIP 1 +VE
19 K71 19 U19
REMOTE CLOSE
18 K17 18 U18
AUTO RECLOSE
17 K11 17 U17
REMOTE TRIP 1
16 K13 16 U16
15 K9A 15 U15
LOCAL CLOSE INTERLOCK
14 K9 14 U14
TRIP 1 PRECLOSE SUPVN.
13 K7 13 U13
TRIP 1 POST CLOSE SUPVN.
12 K5 12 U12
PROTECTION TRIP 1
11 K3 11 U11
-VE
10 J6 10 U10
DC SUPPLY 2 +VE
9 J5 9 U9
-VE
8 J2 8 U8
DC SUPPLY 1 +VE
7 J1 7 U7
6 6 U6
(-VE)
5 M2 5 U5
MOTOR SUPPLY (+VE)
4 M1 4 U4
3 3 U3
(N)
2 H2 2 U2
AC INCOMING SUPPLY (PH) 12 NO +12 NC AUXILIARY CONTACTS
1 H1 1 U1
3990

3850

1750 1750

1400

3355

3320
1770

450
2530 360

F2

F1
OFF

SPRING
CHARGED
ON

SPRING
DISCHARGED

SF6CIRCUIT BREAKER TYPE GL309


BREAKER SERIAL NUMBER
*
RATED VOLTAGE kV 72.5
NORMAL CURRENT A 2000
FREQUENCY Hz 50
RATED POWER FREQUENCY WITHSTAND VOLTAGE Ud(kv) 140
LIGHTNING IMPULSE WITHSTAND VOLTAGE kVp 350
FIRST-POLE-TO-CLEAR FACTOR 1.3
SHORT-TIME WITHSTAND CURRENT kA 31.5
DURATION OF SHORT CIRCUIT s 3
MECHANISM * FK 3-1 SHORT-CIRCUIT BREAKING CURRENT
SYMMETRICAL kA 31.5
**
ASYMMETRICAL kA 35.3
110 DC
SHORT-CIRCUIT MAKING CURRENT kAp 100
110 DC
230 AC,50Hz. OUT-OF-PHASE BREAKING CURRENT kA 10
230 AC,50Hz. OPERATING SEQUENCE O - 0.3s - CO - 3min - CO
6 MPa (abs) 0.74
110 DC
2012 130kg SF 6GAS PRESSURE Bar 6.4
TOTAL MASS OF SF GAS
6
Kg 3.5
TOTAL MASS OF THE CIRCUIT BREAKER Kg 940
REFERENCE STANDARD IEC 62271-100
CREEPAGE DISTANCE (min) MM 1813
YEAR OF MANUFACTURE 2012

CUSTOMER

NAME OF PROJECT GUJARAT WATER INFRASTRUCTURE LIMITED - NC28

P.O.No
GETCO APPROVAL REF ***
HIGH VOLTAGE SWITCHGEAR
INDIA
IL
SF6 CIRCUIT BREAKER TYPE GL312F1/4031P
BREAKER SERIAL NUMBER
RATED VOLTAGE kV
*
145
NORMAL CURRENT A 3150
FREQUENCY Hz 50
POWER FREQUENCY WITHSTAND VOLTAGE kv RMS 275
MECHANISM FK 3-1
LIGHTNING IMPULSE WITHSTAND VOLTAGE kV peak 650
FIRST-POLE-TO-CLEAR FACTOR 1.5 SERIAL NO. *
SHORT-TIME WITHSTAND CURRENT kA 40 220 DC
DURATION OF SHORT CIRCUIT s 3

300
220 DC
SHORT-CIRCUIT BREAKING CURRENT
SYMMETRICAL kA 220 DC
40

75
ASYMMETRICAL kA 46.8 220 AC,50Hz.
SHORT-CIRCUIT MAKING CURRENT kAp 100 220 DC
OUT-OF-PHASE BREAKING CURRENT kA 10 YEAR OF MFG. 2016 130kg
LINE CHARGING BREAKING CURRENT A 50
OPERATING SEQUENCE O - 0.3s - CO - 3min - CO
6 MPa (REL) 0.64
TOTAL MASS OF SF6 GAS Kg 10
TOTAL MASS OF THE CIRCUIT BREAKER Kg 1384
REFERENCE STANDARD IEC 62271-100
YEAR OF MANUFACTURE 2016
CLASSIFICATION C2-M2
96
CUSTOMER NINH BINH PC
P.O.No 1907-2016/TOJI-ALSTOM/CB DATED 19.07.2016

RATING PLATE -2

ALSTOM T&D INDIA LTD, PADAPPAI, CHENNAI

240

RATING PLATE -1 * - BREAKER SL.NO.WILL BE CONFIRMED LATER

:
:
:
:
: