You are on page 1of 16

Equipotential

Planes
for
Stray Voltage
Reduction

A SELF-HELP GUIDE FROM


Table of Contents

Introduction ....................................................................................................................... 1
What is Stray Voltage? ..................................................................................................... 2
What is an Equipotential Plane? ................................................................................... 2
National Electrical Code .................................................................................................. 3
A Properly Installed Equipotential Plane .................................................................... 3
Wire mesh ..................................................................................................................... 3
Bonding ......................................................................................................................... 3
Equipment Grounding ............................................................................................... 4
Transition Area ............................................................................................................ 5
Installation Methods ......................................................................................................... 6
New Construction....................................................................................................... 6
Retrofit Construction................................................................................................. 6

Design and Installation Figures


1. Equipotential Plane in a Milking Parlor ........................................................... 7
2. Bonding to Stainless Steel Milk Line ................................................................ 8
3. Retrofit Equipotential Plane in a Milking Parlor ............................................ 8
4. Equipotential Plane in a Milking Parlor Holding Area ................................. 9
5. Equipotential Plane in a Free-Stall Barn .......................................................... 9
6. Transition Area/Voltage Ramp ......................................................................... 10
7. Equipotential Plane in a Stanchion/Tie-Stall Barn ...................................... 11
8. Retrofit Equipotential Plane in a Stanchion/Tie-Stall Barn ...................... 12
9. Equipotential Plane in a Building with Slatted Floors ............................... 13
10. Equipotential Plane around a Waterer or Feed Bunk .............................. 13
Acknowledgements ......................................................................................................... 13
References ......................................................................................................................... 13
Introduction 1

T
he term stray voltage has been used for An EQP is one way to protect against stray
the past 40 years to describe a special voltage on a farm, but it will not eliminate the
case of voltage developed on the source of the voltage. The sources of stray
grounded-neutral wiring system on a farm. If voltage should always be determined before any
this voltage reaches sufficient levels, animals corrective measures are taken and the safest and
coming into contact with grounded devices may most cost-effective solution should always be
receive a mild electrical shock. At voltage levels implemented. Never violate electrical codes or
that are just perceptible to the animal, behav- compromise the safety of your electrical system
iors indicative of perception such as flinches in an attempt to deal with a stray voltage prob-
may result with little change in normal routines. lem!
At higher levels avoidance behaviors may re- THIS PUBLICATION WILL:
sult. You can find out more about the causes X Explain the function of an EQP
and effects of stray voltage by visiting the X Explain how an EQP reduces the incidence of
MREC web site listed at the end of this publica- stray voltage
tion. X Provide recommendations for EQP installation.
A properly installed equipotential plane
The installation guidelines in this publication
(EQP) will protect animals and people from
are research-based and comply with the National
stray voltage and other electrical hazards by
Electrical Code (NEC). While the examples in
eliminating contact voltages in livestock confine-
this publication are of dairy facilities as ex-
ment areas. An EQP will also improve the
amples, the recommendations and procedures
electrical grounding and enhance electrical
apply to any livestock containment facility.
safety on the farm.
Stray Voltage & Equipotential Planes 2
WHAT IS STRAY VOLTAGE? the electrical current generated by them and they will not receive a
a voltage and not to the voltage shock (like a bird on a wire).

L
ow levels of AC voltage on the
grounded conductors of an directly. To relate voltage measure- The National Electric Code
electrical wiring system are a ments to current, a worst case (500 requires that any conductive object
normal and unavoidable conse- Ohms) or more realistic (1000 in a livestock facility that could
quence of operating electrical Ohms) animal impedance should be come into contact with a live wire
equipment. Stray voltage is a used in the animal contact measure- (water pipes, stanchions, metal
voltage that develops on the ment circuit. The USDA suggests buildings, etc.) must be connected
grounded neutral system of either that animal contact voltage in to the electrical grounding system.
the farm wiring or utility distribu- excess of 2 to 4 Volts is excessive This is necessary to maintain the
tion system. These voltages are and should be reduced. Only under safety of the electrical system. As a
termed stray voltage when they result, a small amount of electrical
can be measured between two current will be present on these
objects that are contacted simulta- grounded objects. The presence of
neously by livestock. The voltage is the current cannot be completely
a result of the current flow on the
An equipotential plane eliminated on a safely wired farm.
neutral wire and the resistance of minimizes the risk of The best way to protect livestock is
the grounded neutral network. stray voltage in livestock to make sure your farm is wired
Stray voltage can be reduced by: confinement areas according to the NEC so that the
X Reducing the resistance of the current and voltage on the
grounded neutral system. Proper grounded-neutral system is low
sizing, installation and mainte- enough so that it will not cause a
nance of wiring systems is problem. The installation of an EQP
required to keep the resistance the most unusual circumstance can reduces the risk by further reducing
of the grounded neutral system a cow detect voltage less than 0.5 to contact voltages and providing
low. 1.0 V. Thus attempts to reduce cow protection in the event that an
X Reducing the current on the contact voltages to below 0.5 to electrical wiring problem does
farms neutral system. Current 1.0 V are unwarranted and unneces- develop.
flow on the neutral wire can be sary. Electrical current will only
reduced by balancing 120 V WHAT IS AN EQUIPOTENTIAL travel through an object if it is in
loads between the phase wires, PLANE? contact with different electrical
eliminating fault conditions, and potentials (voltage levels). This is
An equipotential plane is an electri-
using 240-volt equipment when- similar to the way in which water
cally conductive grid that is embed-
ever possible. will only flow downhill. If you can
ded in a concrete floor and con-
measure a voltage between two
X reducing contact voltages by nected to the electric grounding
surfaces, they are at different
improved grounding and/or system. The electrical connection
electrical potentials. When a con-
EQP installation between the floor and all grounded
ductive object (like livestock)
USDA recommendations for safe metal objects on or near it elimi-
touches both surfaces, a path is
exposure levels for stray voltage are nates voltage differences (poten-
created for current to flow from one
expressed in terms of AC voltages tials) between the floor and these
surface to the other. For example, if
(measured as an rms average) metal objects. If two parts of an
a voltage can be measured between
because voltage is the easiest and animal or person cannot come into
a water bowl and the stanchion
most commonly made measure- contact with a voltage difference
floor two objects that livestock
ment. However, animals respond to then no current will flow through
National Electrical Code 3
come into contact with some electrical inspector if there is any patterns. If steel wire or reinforcing
electrical current could flow question. The definition of an EQP rods are used they should be placed
through the animal when touching in Article 547 of the NEC is: a grid pattern not larger than 18
these two points simultaneously. If inches.
enough current flows the animal Equipotential Plane: An area where Copper wire may serve as the
will experience a sensation. wire mesh or other conductive conductive element where fiber
An equipotential plane causes elements are embedded in or mesh or non-reinforced concrete is
the water bowl and stanchion floor placed under concrete, bonded to used. A maximum spacing of 30 to
to be at the same voltage potential. all metal structures and fixed 45 cm (12 to 18 inches) with No. 8
Therefore, no current can flow nonelectrical equipment that may CU or larger conductor is recom-
through livestock when drinking. become energized, and connected mended. Multiple interconnections
Current may still be present on the to the electrical grounding system should be used to assure long-term
grounding system, but now it has a to prevent a difference in voltage electrical continuity (ASAE 473.2,
much lower resistance path to from developing within the plane. Section 6.1.3).
follow one that does not include (NEC, Article 547.2) Make bonds where reinforcing
livestock. steel or wires cross. The mesh
You can see an example of how AN EQUIPOTENTIAL PLANE should be embedded at least one
this works by watching a bird land HAS FOUR PARTS: inch into the concrete to protect it
on electrical wires. Utility lines are 1. Conductive network in floor from corrosion due to moisture and
typically energized at 7,200 volts or (usually reinforcing rod or wire manure.
more and are not covered with mesh) 2. BONDING NETWORK
electrical insulation. The bird is able An EQP must have electrical
2. Bonding network
to rest on them without harm continuity throughout the wire
because everything that it touches 3. Equipment grounding
mesh in the floor as well as metal
is at the same voltage potential. The 4. Transition area (voltage ramp) objects embedded in the floor, such
electrical current stays in the wire as metallic animal stall posts.
and does not pass through the bird. 1. CONDUCTIVE NETWORK Electrical continuity will be inter-
The same is true for livestock While the conductive network rupted if plastic or non-conductive
standing or lying on a barn floor embedded in the floor is referred to materials are used to join two
equipped with an EQP. as wire mesh in the NEC, there conductive elements. The EQP must
are several materials that can be also be bonded to the ground bar in
THE NATIONAL ELECTRICAL used: the service entrance panel. Accord-
CODE X Welded-steel wire mesh not ing to ASAE Standards.
smaller than No. 10 gauge

E
xperts who review and adopt
changes to the electrical X Reinforcing steel not smaller A means of bonding the equipoten-
codes recognize the benefits than No. 3 gauge (3/8-inch tial plane via a copper equipment
of the equipotential plane. The diameter) grounding conductor to the electri-
installation of an equipotential X Bare copper wire not smaller cal grounding system of the facility
plane is required by the NEC in than No. 8 AWG (copper wire is should be provided (ASAE 473.2,
newly constructed and extensively easier to install in retrofit appli- Section 6.2). The equipment
remodeled livestock confinement cations). grounding conductor should be
areas. Most states have adopted the Welded-steel wire mesh gener- located and routed so it is pro-
NEC meaning that EQPs are re- ally is available in 6-inch by 6-inch tected from physical damage
quired. Check with your state (ASAE 473.2, Section 6.2).
Equipment Grounding 4
An electrically conductive bond when mounted on concrete founda-
can be created by using any of the tions or walls in which a grounded
following methods: conductive element is installed. No be sure equipment is
X Gas or electric weld further direct bonding of slats,
walkways, f loors or troughs,
wired in accordance with
X Chemical weld
including those troughs on slats, is electrical codes and
X Brazed bond
needed. properly grounded
X Approved clamps
X approved brass, copper or
Where for purpose of good animal
copper alloy compression con- husbandry a concrete f loor may
nectors not be acceptable in a specific
X *Exothermic weld (CADWELD)TM
entrance panel.
area, the equipotential plane can The bond between the equipo-
be omitted from that area. Electri- tential plane and the building
* CADWELDTM should be used when cally heated waterers and general grounding electrode system must
bonding copper to any other metal. purpose outlets serving these areas be exposed (not buried in concrete
should have ground fault circuit or earth) so that it may be in-
Multiple bonding between the wire interrupter protection (ASAE spected. Any of the following meth-
mesh, reinforcing rods, copper 473.2, Section 6.4-6.5). ods can be used to produce an
wire, stall pipes, and other metal
exposed bond:
equipment is desirable. Every 40 to 3. EQUIPMENT GROUNDING X Steel reinforcing rods not
60 cm (18 to 24 inches), the welded Stray voltage is often attribut- smaller than No. 3 (3/8-inch
wire mesh should be bonded to the able to improper wiring and diameter) can be bonded to the
crosswise reinforcing rod where grounding of electrical equipment mesh and left protruding from
they intersect. Multiple bonds will on farms. Electrical equipment the concrete. The protruding
provide a networking of electrical should be wired in accordance with rods are then connected to the
continuity in case some connec- the NEC and properly grounded, building grounding electrode
tions fail. (ASAE 473.2, Section especially in animal confinement system to produce the visible
6.3). areas. bond.
Each building service panel X Bare copper conductors can be
All conductive objects on or must have a grounding electrode
near the EQP should be bonded to bonded to the mesh and left
system that may include one or protruding from the concrete.
the wire mesh including: more of the following:
X Stanchions
The exposed conductors are then
X metal underground water pipes;
connected to the building
X Stall partitions X grounded metal building frame; grounding electrode system to
X Metal posts or columns X concrete-encased electrode produce the visible bond.
X Water lines (if metal) (building footings); X Bare copper conductors can be
X Metallic Waterers X a made electrode of ground connected between the building
X Metallic Feeders rods. grounding electrode system and
X Livestock crates stanchion metal or other metal-
Refer to the NEC for installation work that has been bonded at
methods to connect the grounding numerous locations to the wire
Slatted f loors, precast concrete
electrode system to the neutral mesh.
troughs, and suspended walkways
and f loors are considered to be conductor at the electrical service The exposed bonding conductor
part of an equipotential plane
5
from the EQP can be connected ductive elements and must have a 4. TRANSITION AREAS
directly to the building grounding connection to the buildings Install voltage ramps where
electrode system at the buildings grounding system. The connec- livestock enter or exit an equipotential
service entrance panel, or to any tion to the milk line requires a plane. Voltage ramps create a gradual
equipment that is, in turn, electri- stainless clamp with a copper change in the voltage potential that
cally connected to the electrode grounding lug attached or other minimizes the contact voltage as
system at the service entrance (e.g., similar method. Prefabricated animals walk on to or off of an EQP.
a metal water line). stainless steel milk line-bonding An effective transition area can be
The NEC specifies the required clamps may be obtained from constructed by extending the equipo-
size of the bonding conductor. The dairy equipment dealers. If the tential plane outward and downward.
size of this conductor depends on milk line is not electrically One way to do this is to drive copper-
the size (ampacity) of the service continuous (some manufacturers clad ground rods or No. 6 reinforcing
entrance, but cannot be smaller use plastic elbows) each section rods into the ground spaced 12 inches
than a No. 8 AWG bare copper must be bonded. Do not allow apart along the width of the transition
conductor. The NEC requires that copper or steel to come into area. The rods should be driven at a
conductors smaller than No. 6 AWG direct contact with a stainless 45-degree angle (1:1 slope) to the
have physical protection, such as a steel milk line or corrosion may surface and bonded to the equipoten-
conduit. result. tial plane before the concrete is
poured.
Stainless steel milk lines are con-
Size of largest service entrance conductor Recommended grounding
conductor size
Copper Aluminum

AWG 1/0 or smaller AWG 3/0 or smaller AWG 6-CU

AWG 2/0 through AWG 3/0 AWG 4/0 through 250 kcmil AWG 4-CU

over AWG 3/0 through 350 kcmil over 250 kcmil through 500 kcmil AWG 2-CU
Installation Methods 6
INSTALLATION METHODS 1. GROOVE EXISTING FLOOR This method can also be used in
EQP design and installation Use a concrete saw to cut milking parlors and holding areas. If
guidelines for various applications grooves 1 inch deep by -inch wide a retrofit equipotential plane is
are presented in the figures in the in the floor in areas where animals installed in a milking parlor, a wire
following section. could come into contact with may be required where livestock
grounded devices or electrical stand to be milked and also under
NEW CONSTRUCTION equipment. Next, place bare copper the worker area of the pit floor and
wires No. 4 AWG are recom- the livestock walk aisles. To ensure

T
he NEC requires that an EQP
be installed in all newly mended in the grooves and bond all cow contact areas are bonded
constructed livestock confine- them together at several points together, bond the EQP to milking
ment facilities. There are several along the length of the barn. The stalls and feeders if present.
ways to install an EQP. Make number of bonding points and their
certain that the mesh is bonded to locations will depend upon the 2. CAP EXISTING FLOOR
all equipment, stalls and partitions layout of the facility but at mini- Another retrofit method in-
that will be embedded in the floor mum, bond the wires at each end of volves laying mesh on the old
before the concrete is poured. the barn and to the stall work, concrete and bonding it (as de-
Make sure the bonds in the grid waterline and any other metal scribed in the previous section) to
have been thoroughly checked for structures in the barn. All bonding all metal components before cap-
continuity. Also make sure that you should be done by welding or by ping the floor, by pouring a new 2-
have made provision to bond all using pressure-type connections. inch layer of concrete.
equipment on or near the EQP that Use a quick-setting grout to fill the This method has the disadvan-
will not be embedded in the floor to grooves and finish the installation tages of being time-consuming to
the mesh. process. An FDA-approved grout construct, and the level of the barn
RETROFIT CONSTRUCTION must be in feeding areas. This floor is increased. It also may be
Livestock facilities that were method will cause the least interrup- inconvenient if livestock require
built without an EQP can be retrofit tion to normal farm operations. access to the construction area
to provide a similar level of animal In dairy barns copper wire during installation. However, if
safety. This may be an appropriate should be embedded in the feed corroded stanchions are to re-
and cost effective method of mini- manger, front- and rear-hoof areas in placed, this method may be the
mizing existing stray voltage levels. stalls and, walk alleys. One groove most cost effective.
Consult a trained professional for an should be located in the feed man-
analysis of the sources and levels of ger approximately 8-12 inches from
stray voltage. This will determine the curb, two grooves in the front-
hoof area approximately 8-12 inches
whether installation of an equipo-
from the curb and 12 inches apart,
The National Electric
tential plane is appropriate. In Code requires that an
addition, this analysis will assist in and two grooves in the rear-hoof
determining where an equipotential areas approximately 8-12 inches equipotential plane be
plane is necessary. Once it has been from the gutter and 12 inches apart. installed in all newly
determined that an equipotential Due to the limitations of the con- constructed or remodeled
plane would be beneficial in an crete sawing equipment, the exact
location of the grooves depends on livestock confinement
existing barn, there are three
the arrangement of the stall dividers facilities
difference installation methods that
may be used: and stanchions.
7
3. NEW FLOOR Several other methods of install-
Another option is to completely ing an equipotential plane have
remove the old concrete floor and been tried. These include
build a new floor with an embedded conductive concrete, conductive
EQP. The installation method is the f loor/mats and conductive
same as for new construction. This coatings. These methods are
method is also inconvenient if presently undergoing study;
livestock require access to the and, while they may have
construction area during installa- potential in the future, they are
tion. However, may be preferable if not recommended at this time.
barn remodeling is in order.

Figure 1. Equipotential Plane Details in a Milking Parlor


Installation Methods 8
Figure 2. Bond to Stainless Steel Milkline

Figure 3. Retrofit Equipotential Plane Layout in a Milking Parlor


9
Figure 4. Equipotential Plane in a Milking Parlor/Holding Area

6 X 6, No. 10 gauge welded-wire mesh in holding


area, milking parlor and milking pit floors

Figure 5. Equipotential Plane in a Free-Stall Barn

Voltage Ramps at Animal


Entrances and Exits
Installation Methods 10
Figure 6. Transition Area/Voltage Ramp
11
Figure 7. Equipotential Plane in a Stanchion/Tie-Stall Barn
Installation Methods 12
Figure 8. Retrofit Equipotential Plane in a Stanchion/Tie-Stall Barn
Acknowledgments & References 13
Figure 9. Equipotential Plane in a Building with Partly Slatted Floors
Acknowledgments
This publication was revised in
2004/5 by a subcommittee of the
Midwest Rural Energy Council
(MREC). We wish to recognize the
contributions of Dale Bowe
(representative of WI Public Service
Corp.), Tony Harvey and Robert Fick
(Alliant Energy), Jason Kollwalter
(We Energies) and Steve Lynse (Xcel
Energy).
The original publication was
produced by the MREC in 1996.

Equipotential Plane in a Building with Fully Slatted Floors


References
ASAE, EP473.2, 2001. Engineering
Practice: Equipotential Planes in
Animal Containment Areas. ASAE,
2950 Niles Rd., St. Joseph, MI 49085-
9659.

Kammel, D.W. (1988). Guidelines for


Installing an Equipotential Plane.
Extension Publication A3433.
University of Wisconsin Extension.

National Electric Code (NFPA 70),


2005. National Fire Protection
Association.
Figure 10. Equipotential Plane in a Water and Bunk Feeder Area
T his publication was developed by the
Midwest Rural Energy Council.
The MREC is a membership organization whose mission
is to support outreach, education and research on rural
energy issues for the benefit of:
X Farms and other rural energy consumers
X Rural energy suppliers
X Farm organizations and agricultural trade associations
X Electrical equipment and allied industries
X Government regulatory agencies

Related Publications from the


Midwest Rural Energy Council
Farming Safely and Efficiently with Electricity
Planning Electrical Systems for Dairy Expansions
Power Quality and Computers on the Farm
Installation and Operation of Electric Fences, Cow Trainers
and Crowd Gates
Stray Voltage Detection, A Self-Help Guide

Midwest Rural Energy Council

01-06

You might also like