Whydoesadelta/wyetransformermake30degreesphaseshift?

I'vheardthatadelta/deltaorWye/Wyetransformersdonotmakeanyphaseshift.Indelta/wyeorwye/deltatransformers,
Thereisa30degreesphaseshiftbetweentheprimaryandsecondarycoils.So,Whyisthereaphaseshift?andWhyisit30
degrees?..Whynot60or120?

IgoogledandIfoundcalculationswithphasordiagramsthatprovesthe30degreesphasebutI'mconfusedbecauseoftoo
manycalculationsanddiagrams,Ididn'tgetit.

Wouldyougivemeasimpleanswer,please?andIpreferthephysicalmeaningsandconceptsratherthanequationsand
mathematics.

Thankyouverymuch,

transformer threephase powerengineering phaseshift delta

askedSep19'15at15:00
MichaelGeorge
1,679 3 17 42

2Answers

Let'scallthe3phasesA,BandCandlet'ssaywenotionallyhaveaneutralwire.
Neutralisbasically0Vinthesystem.

The"A"phasevoltage(toneutral)ismychosenreferencethatallothervoltage
phaseanglesaremeasuredfromhence,VB is120laggingVA andVC is120
degreesleadingVA .

OKsofar?

WhataboutthevoltagebetweenlineAandlineB(akaVAB )thisiscalledline
voltage(nottobemistakenwithvoltagesbetweenphaseandneutral).Line

voltagesare3timesbiggerthanphasevoltages.

OKsofar?

Ifyouarenotjustexaminewhathappenshere:

https://electronics.stackexchange.com/questions/191232/whydoesadeltawyetransformermake30degreesphaseshift 1/3
4/16/2017 Whydoesadelta/wyetransformermake30degreesphaseshift?ElectricalEngineeringStackExchange

IfyouusetrigonometryandresolveallthetrianglesyoucanfindthelengthofVAB

itis3timesbiggerthaneitherAorBtoneutral.

It'salso30degreesleadingAandthisiswherethe30degreescomesfrom.

So,adeltaprimarywillreceiveprimarylinevoltagesofVAB .VBC andVC A .

Giventhatatransformerdoesn'tinherentlyphaseshiftanything(otherthanthe
trivialcasesof0degreesand180degrees),anysecondarywindingvoltagemustbe
inphasewiththeirrespectiveprimaryvoltagenomatterwhetherthesecondaryis
connecteddeltaorwye.

OKsofar?

Thenyouhaveitbecause,adeltaprimaryworkswithlinevoltagesandtheseare30
degreesshiftedtotheirnearestphasevoltage.Thesecondaryoutputsarealso30
degreesshiftedandhenceawyesecondarywillproduceaphasevoltagethatis30
degreesshiftedfromtheequivalent(butnotdirectlyconnectedto)phasevoltageon
theprimary.

It'strivialtodothewyedeltatransformersoI'llleaveittosomeoneelse.

editedSep19'15at16:06 answeredSep19'15at16:00
Andyaka
170k 7 114 265

Heh.Lookslikeoneofmyillustrations.:)LiaungYipSep20'15at5:05

@LiaungYipwellthankyoudearchap.Ifounditontheinternet(images)kindofrandomlysoInever
botheredtotrackdownthesourcebutthankyou.AndyakaSep20'15at8:55

ItwasactuallyonEE.SEinthefirstplace,sofairgame.LiaungYipSep20'15at9:54

electronics.stackexchange.com/questions/92678/LiaungYipSep20'15at12:30

Whatyouarelookingformyfriendisanintuitiveunderstandingofwhywehavethe
phaseshiftbetweentheHVwindingandtheLVwindingoftheDeltaWye
transformerconnection.Youwon'treallyunderstandthisunlessyousitdownand
startingdrawingthephasordiagramsasillustratedbyAndy.

https://electronics.stackexchange.com/questions/191232/whydoesadeltawyetransformermake30degreesphaseshift 2/3
4/16/2017 Whydoesadelta/wyetransformermake30degreesphaseshift?ElectricalEngineeringStackExchange
Iwouldrecommendwatchingthisvideotutorialthatgoesthroughtheentirephasor
diagramprocessstepbystep:http://gpac.link/1OfN591

FromwhatIunderstandletssupposeyouhaveaTransformerTurnsRatioof1:1
ifyoulookatthelinetogroundvoltageontheDeltasideandcompareittothe
linetogroundvoltageontheWyesideyouwillseea30degreephaseshiftand
squareroot3magnitudedifference.

Whydoesthisoccur?It'seasierifyoujustwatchthevideos:)
http://generalpac.com

Ihopethishelps:)

answeredMar8'16at20:13