You are on page 1of 1

GENERAL REQUIREMENTS 2019

4.25.5.7 The isolation valves serving the pressure mainte- 4.27.2.2 An air gap shall be provided in accordance with the
nance pump shall not be required to be supervised. manufacturers recommendations.
4.25.6 The primary or standby fire pump shall not be used as 4.27.2.3 Water discharge from the relief valve shall be readily
a pressure maintenance pump. visible or easily detectable.
4.25.7 The controller for a pressure maintenance pump shall 4.27.2.4 Performance of the requirements in 4.27.2.1
be listed but shall not be required to be listed for fire pump ser- through 4.27.2.3 shall be documented by engineering calcula-
vice. tions and tests.
4.25.8 The pressure maintenance pump is not required to 4.27.3 Devices in Suction Piping. Where located in the suc-
have secondary or standby power. tion pipe of the pump, check valves and backflow prevention
devices or assemblies shall be located a minimum of 10 pipe
4.26 Summary of Centrifugal Fire Pump Data. The sizes indi-
diameters from the pump suction flange.
cated in Table 4.26(a) and Table 4.26(b) shall be used as a
minimum. 4.27.3.1 Where a backflow preventer with butterfly control
valves is installed in the suction pipe, the backflow preventer is
4.27 Backflow Preventers and Check Valves.
required to be at least 50 ft (15.2 m) from the pump suction
4.27.1 Check valves and backflow prevention devices and as- flange (as measured along the route of pipe) in accordance
semblies shall be listed for fire protection service. with 4.14.5.2.
4.27.2 Relief Valve Drainage. 4.27.4 Evaluation.
4.27.2.1 Where the backflow prevention device or assembly 4.27.4.1 Where the authority having jurisdiction requires the
incorporates a relief valve, the relief valve shall discharge to a installation of a backflow prevention device or assembly in con-
drain appropriately sized for the maximum anticipated flow nection with the pump, special consideration shall be given to
from the relief valve. the increased pressure loss resulting from the installation.

Table 4.26(a) Summary of Centrifugal Fire Pump Data (U.S. Customary)

Minimum Pipe Sizes (Nominal) (in.)

Number and Hose


Pump Rating Relief Valve Size of Hose Header
(gpm) Suction* Discharge* Relief Valve Discharge Meter Device Valves Supply

25 1 1
34 1 114 1 112 1
50 112 114 114 112 2 1 112 112
100 2 2 112 2 212 1 212 212
150 212 212 2 212 3 1 212 212
200 3 3 2 212 3 1 212 212

250 312 3 2 212 312 1 212 3


300 4 4 2 1 2 312 312 1 212 3
400 4 4 3 5 4 2 212 4
450 5 5 3 5 4 2 212 4
500 5 5 3 5 5 2 212 4

750 6 6 4 6 5 3 212 6
1000 8 6 4 8 6 4 212 6
1250 8 8 6 8 6 6 212 8
1500 8 8 6 8 8 6 212 8
2000 10 10 6 10 8 6 212 8

2500 10 10 6 10 8 8 212 10
3000 12 12 8 12 8 12 212 10
3500 12 12 8 12 10 12 212 12
4000 14 12 8 14 10 16 212 12
4500 16 14 8 14 10 16 212 12
5000 16 14 8 14 10 20 212 12

Notes:
(1) The pressure relief valve shall be permitted to be sized in accordance with 4.18.2.1.
(2) The pressure relief valve discharge shall be permitted to be sized in accordance with 4.18.6.2.
(3) The flowmeter device shall be permitted to be sized in accordance with 4.19.2.2.
(4) The hose header supply shall be permitted to be sized in accordance with 4.19.3.4.
*Actual diameter of pump flange is permitted to be different from pipe diameter.

Applies only to that portion of suction pipe specified in 4.14.3.4.

2010 Edition

Copyright National Fire Protection Association


Provided by IHS under license with NFPA
No reproduction or networking permitted without license from IHS

The Standard is downloaded from www.bzfxw.com Standard Sharing

You might also like