Clause Discription
Uninterruptable Power Supply (UPS) Overview
The UPS unit shall be provided at each POP rooms and ACC rooms (Command and Control Centre and
Rack Room) to backup entire AITL devices & switches, emergency lights and Fire detections system. UPS
system shall provide a redundant power supply to the following needs:
Servers and important network and storage equipment;
Access control, Fire Detection & suppression system and surveillance system.
usiness Requirements
The UPS unit shall be provided with external batteries as needed to support the run- time requirements.

All AITL equipment installed at POP and ACC shall be connected on the UPS.
The quantity of batteries required for the UPS, shall be calculated based on the equipment load and
run-time.
The UPS units shall provide backup power to critical load. In addition, UPS shall also provide cleansed
power to these equipment.
al Requirements
The UPS unit shall be 3:1 Phase on-line UPS with extendable rack system.
The UPS design shall ensure that a single component/ device failure shall not result in failure of the
entire UPS system. The design of UPS System shall be modular to permit easy maintenance.

The various overload capacities of inverters, static switch, and step down transformer/voltage
stabilizer as specified herein are the minimum requirements.
The UPS system to be supplied by the MSI shall have maximum humming noise level of 65 DB one meter
away from the UPS cabinets. This shall not exceed 69 dBA measured 5 feet from surface of the UPS.

Requirements
The MSI shall provide the calculations to support the UPS rating and number of batteries as part of the
Bid submission. UPS shall be provided as N+1 redundant configuration.
The UPS unit shall include Valve Regulated Sealed Maintenance Free Lead Acid Batteries shall be used
with a 20 hours discharge rating with a typical lifetime of five (5) years and minimum reserve time of
four (4) hours under full load conditions.
The battery system design shall be provided with necessary devices to prevent deep discharge beyond
recommended limits to prevent the batteries discharging beyond
end cell voltage specified by the battery maker. The connections from battery to battery shall be by
using copper bus bar strips.
The UPS unit shall provide an output of 230V AC 50 Hz. If the rating of UPS increases above 15KVA at
particular location, it should be consider as 3:3 phase UPS and specification should be considered
accordingly. If the rating is below 15KVA, it remains as 3:1 phase UPS. The MSI shall be responsible for
any conversions needed to support this output configuration.

The UPS and batteries shall be mounted in a separate cabinet & the enclosure shall be under lock & key,
utilising the minimum possible space and arranged in an aesthetic manner.
The UPS shall be of True online with double conversion topology. It shall support an output power factor
at full load as 1.
The UPS shall have a microprocessor-based unit status and control display with the status and alarm
indicators displayed on the status LED indicator and LCD display.
The UPS unit shall have load level indicators that display the approximate electrical load placed upon
the UPS. The UPS unit shall have a row of battery level indicators that display the approximate battery
capacity.
The UPS shall have self-diagnostic functionality to detect any failure/fault in the UPS
system and shall display the same on the LCD display of the UPS.
The UPS unit shall have a minimum of the following LED indicators: UPS Mode: On-line, Backup/Battery
and Bypass;
Over Load Indicator: This will display when UPS is running on overload;
Battery Status Indicator: This will illuminate when battery is low or faulty/disconnected; and

System Fault: This will illuminate when there is some fault or interruption in UPS.
The UPS unit shall have minimum of the following audible alarms:
Line Failure: This will be audible when required input electrical supply to UPS is not available;
Battery Low: This will be audible when battery voltage falls below the threshold value; Bypass Mode:
This will be audible when UPS is running on bypass mode; and System Fault: Audible alarm will be
generated when any fault is detected in the UPS
system.
The UPS unit shall have following readings on the LCD panel as minimum:
Voltage and frequency Levels: This shall display input and output voltage and frequency levels;
Battery Voltage: This shall display battery voltage in Volts;
Load: This shall display the load connected in percentage to the UPS output; and
Temperature: This shall display the internal temperature of UPS unit for overheating.
The UPS unit shall include full-time protection from sudden voltage increase with inrush protection and
AC line filtering.
UPS shall provide an overload alarm and circuit breaker designed to operate at an overload of 200%
surge.
The UPS unit shall include Ethernet communication port to support remote management and
monitoring capabilities using SNMP including alarm contacts and
remote shutdown. Remote monitoring and testing software shall be included. The manufacturer shall
provide all SNMP traps.
The UPS unit shall be capable of starting without input power. The unit shall start up and operate from
the battery, with output frequency same as the last operating frequency.
The UPS unit shall include automatic restart. Upon restoration of utility AC power after complete battery
discharge, the UPS shall automatically restart and resume operation.
The UPS unit shall be enclosed to prevent accidental contact with energized parts.
The UPS unit shall have a built-in input fuse and/or a circuit breaker for protection from over voltage
and current variations.
The UPS unit shall provide an over voltage shutdown and shall have overvoltage protection.
The UPS unit shall provide short circuit shutdown protection.
External battery charger (if required) for the specified battery bank shall be provided. The battery
charger shall automatically recharge the battery.
The external battery charger shall be provisioned to be mounted in the cabinet or UPS itself. Except this,
no separate space will be provided for mounting of the external charger.
The UPS unit shall be compliant to IEC 62040-1 safety standards as a minimum.
The UPS system shall have an operating temperature of 0 degrees to 40 degrees C.
Any field UPS system (as per MSIs design) shall be supplied with an environmentally rated cabinet for
installation of the UPS and batteries. The cabinet shall have a rating of IP 55. The cabinet shall be
supplied with in-built fans and proper ventilation as needed to ensure that the temperature inside the
cabinet does not exceed 40 degrees C at any given point in time.
Compliance (Yes/No)

Yes

Yes

Yes
Yes

Yes

Yes
Yes

Yes

Yes

As per BOQ shared

Yes

Yes

Yes

Yes

Yes

0.8

Yes

Yes

Yes
Yes

Yes
Yes

Yes
Yes
Yes
Yes

Yes
Yes
Yes
Yes
Yes
Yes

Yes

Yes

Yes

Yes for 5KVA

Yes

Yes
Yes

Yes
Yes
Yes

Yes

Yes
Yes
IP 20