AIR QUALITY

SERIES AVFS

AIR FLOWSWITCH
Monitors Flow in Ducts with Contact Output and Local LEDIndication POTENTIOMETER
5-33/64 [140.00]
2 LED

29/32
[23.00]

The SERIES AVFS Adjustable Air Flow Switch is specifically designed to monitor air SPECIFICATIONS
flow in ducts and provides a 3 A contact output to indicate a change or loss of flow. The Air Velocity Range:197-1969 FPM Response Time: 3-60 seconds. Varies
AVFS provides a +/-5% set-point repeatability across a full scale range of 1-10 m/s (1-10 m/s). with flow and set point.
(197-1969 fpm) and includes a mounting bracket for quick duct mounting. TemperatureLimits: 5 to 122F Power Requirement: AVFS-1: 80 to 250
(-10 to 50C). AC/DC (47 to 63 Hz AC); AVFS-2: 24
FEATURES/BENEFITS Humidity Limits: 0-90% RH. VDC 25%.
Integral red/green air flow status LEDs Wetted Materials: PBT body, titanium Power Consumption:3 VA.
Flush sensor design limits issues due to dust or particulate in the air flow sensor. Electrical Connection:6.5 ft (2 m)
IP65 construction Pressure Limit: 14.7 psig (1 bar). cable.
Housing:PBT. Enclosure Rating:IP65.
APPLICATIONS Repeatability: 5% FS. Display: 1 Red LED/1 Green LED.
Fan monitoring Switch Type: N.O. SPST. Weight: 7.2 oz (203 g).
Filter monitoring Electrical Rating: 3 A @ 30 VDC/250 Agency Approvals: CE.
Damper feedback VAC.
Air handlers
MODEL CHART
Model Description
AVFS-1 80-250 AC/DC power thermo air flow switch
AVFS-2 24 VDC power thermo air flow switch

SERIES AVU

AIR VELOCITY TRANSMITTER


Ideal for Building Automation Systems, 5% or 8% Full Scale Accuracy

Air Flow Switches


3-11/32
3/4 [19.0] [85.0]

51/64
[2.0]
8-55/64 [225.0]
9-29/64 [240.0] 2-1/4
[57.0]

The SERIES AVU Air Velocity Transmitter is ideal for a wide range of HVAC SPECIFICATIONS
measurement and control applications, particularly in complete building control and Service: Clean air and compatible, non- Max. Start Up Current: 85 mA; 10 V.
energy management systems. combustible gases. Output Current Limit: (-V models) >10
The Series AVU Transmitter operates by measuring the heat loss from one of the two Accuracy: AVU: 5% of FS; AVUB: 8% mA.
sensing elements in the air stream, then calculating the air velocity. Units are virtually of FS. Electrical Connections: Screw terminal.
immune to drift due to the design of the sensing element, which makes the transmitter Response Time (90%): 5 sec (typical). Cable gland for 4-8 mm wire (16 gauge
accurate over the whole air velocity range. Temperature Limits: 32 to 122F (0 to wire).
50C). Enclosure Rating: NEMA 6 (IP67)
FEATURES/BENEFITS Humidity Limit: 0-90% RH, non- except sensing point.
4 to 20 mA or 0 to 10 V output versions condensing. Probe Dimensions: 9.45 x .75 (240 x
NEMA 6 (IP67) enclosure rating Power Requirements: -A models 24 19 mm).
AC or DC powered (loop version DC only) VDC +10% -15%; -V models 24 VDC or Mounting Orientation: Unit not position
5% or 8% accuracy 24 VAC +10% - 15%. sensitive. Probe must be aligned with
Output Signal: -A models 4 to 20 mA airflow.
APPLICATIONS current loop; -V models 0-10 VDC. Weight: 8.8 oz (250 g).
Zone control in HVAC systems Loop Resistance: (-A models) 700 . Agency Approvals: CE.
Supply and exhaust fan tracking Current Consumption: 60 mA + output
Clean room systems current.
Air pollution studies and manufacturing
MODEL CHART
Model Range fpm (m/s) Output Accuracy
AVU-1-A 0 to 785 (0 to 4) 4 to 20 mA 5%
AVU-2-A 0 to 1575 (0 to 8) 4 to 20 mA 5%
OPTION AVU-3-A 0 to 3150 (0 to 16) 4 to 20 mA 5%
Use order code: Description AVU-1-V 0 to 785 (0 to 4) 0 to 10 VDC 5%
AVU-2-V 0 to 1575 (0 to 8) 0 to 10 VDC 5%
NISTCAL-AV1 NIST traceable velocity calibration certificate
AVU-3-V 0 to 3150 (0 to 16) 0 to 10 VDC 5%
AVUB-1-V 0 to 785 (0 to 4) 0 to 10 VDC 8%
AVUB-2-V 0 to 1575 (0 to 8) 0 to 10 VDC 8%
AVUB-3-V 0 to 3150 (0 to 16) 0 to 10 VDC 8%