200-320 SED (AUG 08) BCS SERIES GALVANIZED STEEL PRODUCT COOLERS
Page 4 SPECIFICATIONS - ENGINEERING DATA - DIMENSIONS
The BC Series Product cooler is the most extensive and highest OPTIONAL ARRANGEMENTS
quality line of product coolers available to our industry.
Insulated Drain Pan
Available in more than 1700 models with one to four fans, nu-
merous fan HP selections and a variety of available fin spacing, High-efficiency foam insulation is located between the inner
the variety of selections is unparalleled. drain pan and outer cover. Both the inner drain pan and outer
cover are fabricated from mill galvanized steel as standard.
STANDARD FEATURES
Hot Gas Heated Drain Pan
Casing
A pan coil is attached to the underside of the inner pan. This
The unit casing is fabricated with heavy gauge, corrosion resis- allows access to the drain pan and a smooth surfaced pan in-
tant mill galvanized steel. Fan sections are compartmented with terior for ease of cleaning. The coil is circuited to provide fast,
continuous tube sheets to allow fan cycling and to prevent idle efficient defrost. Pan coils are piped in series with the cooling
fans from turning in reverse. Fan panels have deep spun orifices coil to provide a single hot gas inlet for certain liquid overfeed
for efficient fan performance. applications. For selected liquid overfeed applications, the pan
coil can be piped in parallel to the cooling coil.
Coil
Pan Coil Check Valve
The cooling coil is constructed with steel tubes staggered in the
direction of air flow to ensure maximum air turbulence and coil A check valve with piping can be provided to connect the pan
heat transfer efficiency. coil outlet with the cooling coil hot gas inlet, isolating the pan
coil from refrigerant circulation during the refrigeration cycle.
The coil is available with 3 or 4 fins per inch with tubes and fins
supported by heavy gauge flanged tube sheets. The entire coil Water Defrost
assembly is hot-dip galvanized after fabrication. Coils are tested
Water connections feed a distribution pan providing uniform
before and after galvanizing with 450 psig air pressure.
water distribution across the top of each coil section. With this
Each coil is circuited for the operating conditions to which it will unique design, the additional height required for water defrost is
be exposed. This ensures proper gas velocities through the tubes minimized by comparison to other water distribution methods.
and that refrigerant pressure drops will be kept to a minimum.
Optional Motors
All coils can be circuited for: Two-speed motors at 1750/1160 RPM, 1160/870 RPM, and
Liquid Recirculation Direct Expansion 1750/870 RPM are available.
Flooded Feed Brine Circulation Hostile environment or wash-down-duty motors are also avail-
Controlled Pressure able.
Drain Pan Long Air Throw Nozzles
The drains pan is constructed of heavy gauge galvanized steel Long air throw nozzles attached to the fan housing increase the
and shipped in place on the unit. All pans are smooth surfaced, air-leaving velocity by reducing the discharge outlet area. Long
sloped end to end to ensure rapid and complete drainage. air throw nozzles will increase air throw up to 50% longer than
Motors and Fans standard. They are shipped loose for field installation.
Motors are totally enclosed, 208-230/460/3/60 or 575/3/60, 870, Fan Arrangements
1160, or 1750 RPM, ball bearing. Motor leads are extended To provide air discharge in the desired direction for product
through each fan panel to a junction box. Motors can be cycled coolers mounted in penthouse configurations, a variety of
individually as fan sections are compartmented. preengineered fan arrangements are available. These include a
Direct drive axial-propeller fans are of cast aluminum construc- 45 downblow and a space-saver 90 downblow (to minimize
tion. PVC coated fan guards meet OSHA standards. duct sizes or roof openings).
As the wider fin spacing on the air-entering side of the coil re- 4. Fan motor heat is not included in the ratings and must be
duces effective surface area and therefore coil capacity, please added to the load estimate. Add 3000 BTUH per horsepower
refer to the Capacity Correction Factors and adjust product to the room load.
cooler capacities accordingly.
5. Brine applications require factory engineered selections.
Variable fin spacing is not available for product coolers with Provide BTUH capacity, room temperature, brine type and
direct expansion refrigerant feed. concentration, supply temperature, and GPM.
Variable Fin Spacing Factors 6. Relative sound level in dBA is per fan manufacturers data
Entering Air Remaining Rows Deep Multiply By and is an average sound pressure reading considering the
2 Rows FPI Rows FPI 6 8 10 (Rating) entire performance range of the fan. It represents the noise
1.5 3 0.90 0.91 0.92 3 FPI that might be expected at a distance of 6 feet from the fan in
2 4 0.88 0.90 0.92 4 FPI a room having a combination of hard and soft surfaces. In
Motor Control Centers multiple unit applications, the sound levels will be higher.
Overall sound pressure will vary with room size, shape,
Factory mounted and wired motor control center features main temperature, and acoustic absorption.
disconnect with branch fuse protection, motor contactors and
overloads in a NEMA 12 enclosure. 115/1/60 control power by 7. Controlled Pressure Receiver:
others. Liquid feed from controlled pressure receivers will be at
Prewired Motor Disconnect mixed liquid temperature between the saturated temperature
at receiver pressure and the return liquid temperature from the
Factory wired nonfused disconnect in a NEMA 4 enclosure is accumulator. Special circuiting limitation and defrost piping
furnished in lieu of the standard junction box. options may apply. Mixed liquid temperature and receiver
Rating Data pressure must be furnished with the order.
1. All coil capacities are based on sensible heat removal and 8. Direct Expansion Feed Limitations:
frosted coil operation using liquid overfeed or flooded ammo- Liquid feed to thermostatic expansion valves must have at
nia. See Capacity Correction Factors for other applications. least 5F liquid subcooling year round.
2. Temperature difference is the difference in degree F between The liquid temperature entering the expansion valve must be
the air entering the evaporator, or room air, and the coil at least 30F higher than coil suction temperature.
saturated suction temperature as measured at the suction
connection with a pressure gauge. A temperature difference of at least 10F is required between
room air and coil saturated suction temperature.
3. Multiply BTUH/TD ratings by TD to determine product
cooler sensible heat capacity. Use capacity correction multi-
pliers as required.
FLOODED AMMONIA
CAPACITY LIQUID SUCTION TEMPERATURE (F)
(TONS) CONN +40 +30 +20 +10 0 -10 -20 -30 -40 -50
(NPS) SUCTION CONNECTIONS (NPS)
5 1 1 1 1 1 1 2 2 2 2 2
10 2 2 2 2 2 2 2 2 2 3 3
15 2 2 2 2 2 3 3 3 3 4 4
20 3 2 3 3 3 3 3 4 4 4 4
25 3 3 3 3 3 4 4 4 4 4 4
30 3 3 4 4 4 4 4 4 4 4 5
35 4 4 4 4 4 4 4 4 4 5 5
40 4 4 4 4 4 4 4 5 5 5 5
45 4 4 4 4 4 4 5 5 5 5 5
50 4 4 4 4 4 5 5 5 5 5 6
55 4 4 4 4 5 5 5 5 5 5 6
60 4 4 4 5 5 5 5 5 5 6 6
65 5 4 5 5 5 5 5 5 6 6 6
70 5 5 5 5 5 5 5 5 6 6 6
75 5 5 5 5 5 5 5 6 6 6 6
80 5 5 5 5 5 5 5 6 6 6 6
DX AMMONIA
SUCTION TEMPERATURE (F)
LIQUID CONN
+40 +30 +20 +10 0
(NPS)
SUCTION CONNECTIONS (NPS)
See Note 4 1 1 1 1 1
See Note 4 1 1 1 1 1
See Note 4 1 1 1 1 2
See Note 4 1 1 1 2 2
See Note 4 1 1 2 2 2
See Note 4 1 2 2 2 2
See Note 4 2 2 2 2 2
See Note 4 2 2 2 2 2
See Note 4 2 2 2 2 3
See Note 4 2 2 2 2 3
See Note 4 2 2 2 3 3
BCS SERIES GALVANIZED STEEL PRODUCT COOLERS 200-320 SED (AUG 08)
SPECIFICATIONS - ENGINEERING DATA - DIMENSIONS Page 7
DX R-507
"Capacity LIQUID SUCTION TEMPERATURE (F)
(TONS" CONN +40 +30 +20 +10 0 -10 -20 -30 -40 -50
(NPS) SUCTION CONNECTIONS (NPS)
5 See Note 4 1.25 1.25 1.25 1.5 1.5 1.5 1.5 2 2 2.5
10 See Note 4 1.25 1.5 2 2 2 2 2 2.5 2.5 3
15 See Note 4 1.5 2 2 2.5 2.5 2.5 2.5 3 3 4
20 See Note 4 2 2 2.5 2.5 3 3 3 3 4 4
25 See Note 4 2 2.5 2.5 3 3 3 3 4 4 5
30 See Note 4 2 2.5 3 3 3 3 4 4 4 5
35 See Note 4 2.5 3 3 4 4 4 4 4 5 5
40 See Note 4 2.5 3 3 4 4 4 4 4 5 6
45 See Note 4 2.5 3 4 4 4 4 4 4 5 6
50 See Note 4 3 3 4 4 4 4 4 5 5 6
55 See Note 4 3 3 4 4 4 4 4 5 5
60 See Note 4 3 4 4 4 4 4 5 5
65 See Note 4 3 4 4 4 4 5 5 5
70 See Note 4 3 4 4 4 5 5 5 5
NOTES
1. Liquid and suction connection sizes may not be equal to a particular systems design line sizes.
2. Pumped liquid feed ammonia connection capacities are based on 3:1 overfeed.
3. Pumped liquid feed R-507 connection capacities are based on 2:1 overfeed.
4. Direct expansion feed liquid connection sizes are dependent upon distributor selection and require evaluation on a case-by-case basis.
5. Flooded feed suction connections can be sized to match suction stop valves, if located at the same level as the coil connection, or risers.The
suction connections in the table are sized to match suction stop valves. Connections sized to match risers will generally be smaller to ensure
that vapor will entrain liquid to surge drum.
6. For best results with flooded feed, customers should should advise factory of suction stop valve location, size, and type, when used
7. For best performance, the surge drum should be located close to and directly above flooded feed coil connections. The factory should be advised
of any special surge drum location requirements or restrictions.
9. Refer to customer submittal drawings for connection sizes of specific applications.
10. Liquid connection sizes in above tables are for a single connection. In some cases a particular coil may require more than one liquid connection.
200-320 SED (AUG 08) BCS SERIES GALVANIZED STEEL PRODUCT COOLERS
Page 8 SPECIFICATIONS - ENGINEERING DATA - DIMENSIONS
1, 2 = BASE MODELS (WITH FAN ARRANGEMENTS) 21, 22 = CIRCUIT QUANTITY (The code 00 is used at time order is
BB - Horizontal Discharge, Blow through placed. A circuit quantity code will be added to the unit code
BC - Horizontal Discharge, Draw through on the customer submittal drawing)
BD - 45 Down Discharge, Draw through 00 - Circuit quantity is not known
BP - Penthouse Space Saver 90 Down Discharge, Draw through 01 - 1 circuit
3 = COIL CONSTRUCTION 02 - 2 circuits
S - Hot dipped galvanized steel 03 - 3 circuits, and so on.
Options:
Stainless steel pan and cover
Insulation on sides as well as bottom
All welded construction
Includes heat trace.
Bottom
Sides and Bottom
Face Area Surface Area (sq ft) Coil Volume Shipping Weight (lb)
Model Rows Deep
(sq ft) 3 FPI 4 FPI (cu ft) 3 FPI 4 FPI
01506 15.00 6 1,018 1,319 2.1 1,350 1,460
01508 15.00 8 1,357 1,759 2.8 1,562 1,708
01510 15.00 10 1,696 2,198 3.5 1,774 1,957
01706 16.88 6 1,145 1,484 2.4 1,471 1,595
01708 16.88 8 1,527 1,979 3.2 1,703 1,867
01710 16.88 10 1,908 2,473 3.9 1,934 2,140
01806 18.75 6 1,272 1,649 2.6 1,589 1,726
01808 18.75 8 1,696 2,198 3.5 1,839 2,022
01810 18.75 10 2,120 2,748 4.4 2,088 2,317
01906 18.89 6 1,282 1,661 2.6 1,598 1,736
01908 18.89 8 1,709 2,215 3.5 1,849 2,033
01910 18.89 10 2,136 2,768 4.4 2,099 2,330
02006 20.63 6 1,399 1,814 2.9 1,703 1,854
02008 20.63 8 1,866 2,418 3.9 1,971 2,171
02010 20.63 10 2,332 3,023 4.8 2,238 2,490
02106 21.25 6 1,442 1,869 3.0 1,741 1,896
02108 21.25 8 1,922 2,491 4.0 2,014 2,221
02110 21.25 10 2,403 3,114 5.0 2,287 2,546
02206 22.50 6 1,527 1,979 3.2 1,939 2,104
02208 22.50 8 2,036 2,638 4.2 2,224 2,444
02210 22.50 10 2,544 3,298 5.3 2,509 2,784
02306 23.61 6 1,602 2,076 3.3 1,879 2,052
02308 23.61 8 2,136 2,768 4.4 2,174 2,404
02310 23.61 10 2,670 3,460 5.5 2,469 2,757
02406 24.38 6 1,654 2,143 3.4 2,048 2,226
02408 24.38 8 2,205 2,858 4.6 2,350 2,587
02410 24.38 10 2,756 3,572 5.7 2,651 2,949
02606 25.97 6 1,762 2,284 3.6 2,138 2,328
02608 25.97 8 2,350 3,045 4.8 2,454 2,708
02610 25.97 10 2,937 3,806 6.1 2,771 3,087
02706 26.25 6 1,781 2,308 3.7 2,154 2,346
02708 26.25 8 2,375 3,078 4.9 2,472 2,729
02710 26.25 10 2,968 3,847 6.1 2,791 3,111
02806 28.13 6 1,908 2,473 3.9 2,258 2,464
02808 28.13 8 2,544 3,298 5.3 2,593 2,868
02810 28.13 10 3,180 4,122 6.6 2,928 3,271
02906 28.33 6 1,922 2,491 4.0 2,270 2,477
02908 28.33 8 2,563 3,322 5.3 2,606 2,883
02910 28.33 10 3,204 4,153 6.6 2,943 3,289
03106 30.69 6 2,083 2,699 4.3 2,398 2,623
03108 30.69 8 2,777 3,599 5.7 2,755 3,055
03110 30.69 10 3,471 4,499 7.2 3,112 3,487
03306 33.06 6 2,243 2,907 4.6 2,524 2,766
03308 33.06 8 2,990 3,876 6.2 2,901 3,223
03310 33.06 10 3,737 4,845 7.7 3,278 3,681
03506 35.42 6 2,403 3,114 5.0 2,647 2,907
03508 35.42 8 3,204 4,152 6.6 3,044 3,389
03510 35.42 10 4,004 5,191 8.3 3,440 3,872
BCS SERIES GALVANIZED STEEL PRODUCT COOLERS 200-320 SED (AUG 08)
SPECIFICATIONS Page 11
2-FAN UNIT
Face Area Surface Area (sq ft) Coil Volume Shipping Weight (lb)
Model Rows Deep
(sq ft) 3 FPI 4 FPI (cu ft) 3 FPI 4 FPI
03006 30.00 6 2,035 2,638 4.2 2,592 2,812
03008 30.00 8 2,714 3,517 5.6 2,999 3,292
03010 30.00 10 3,392 4,397 7.0 3,406 3,772
03406 33.75 6 2,290 2,968 4.7 2,825 3,072
03408 33.75 8 3,053 3,957 6.3 3,269 3,598
03410 33.75 10 3,816 4,946 7.9 3,713 4,124
03606 37.50 6 2,544 3,298 5.3 3,051 3,326
03608 37.50 8 3,393 4,397 7.0 3,530 3,896
03610 37.50 10 4,240 5,496 8.8 4,010 4,467
03806 37.78 6 2,563 3,322 5.3 3,068 3,344
03808 37.78 8 3,418 4,429 7.1 3,549 3,918
03810 37.78 10 4,271 5,537 8.8 4,031 4,492
04206 41.25 6 2,799 3,627 5.8 3,271 3,573
04208 41.25 8 3,732 4,836 7.7 3,784 4,185
04210 41.25 10 4,664 6,046 9.6 4,298 4,801
04306 42.50 6 2,883 3,737 6.0 3,342 3,653
04308 42.50 8 3,845 4,983 7.9 3,867 4,281
04310 42.50 10 4,805 6,229 9.9 4,391 4,910
04406 45.00 6 3,053 3,957 6.3 3,733 4,063
04408 45.00 8 4,071 5,276 8.4 4,280 4,720
04410 45.00 10 5,088 6,595 10.5 4,827 5,376
04606 47.22 6 3,204 4,152 6.6 3,607 3,953
04608 47.22 8 4,272 5,537 8.8 4,174 4,635
04610 47.22 10 5,339 6,921 11.0 4,740 5,316
04806 48.75 6 3,308 4,287 6.8 3,941 4,298
04808 48.75 8 4,410 5,716 9.1 4,521 4,997
04810 48.75 10 5,512 7,145 11.4 5,101 5,695
05206 51.94 6 3,524 4,568 7.3 4,116 4,496
05208 51.94 8 4,699 6,090 9.7 4,722 5,229
05210 51.94 10 5,873 7,613 12.1 5,329 5,963
05406 52.50 6 3,562 4,617 7.4 4,145 4,529
05408 52.50 8 4,750 6,155 9.8 4,757 5,269
05410 52.50 10 5,936 7,694 12.3 5,369 6,009
05706 56.25 6 3,816 4,946 7.9 4,346 4,757
05708 56.25 8 5,089 6,595 10.5 4,989 5,538
05710 56.25 10 6,360 8,244 13.1 5,632 6,318
05606 56.67 6 3,845 4,983 7.9 4,367 4,782
05608 56.67 8 5,126 6,644 10.6 5,014 5,567
05610 56.67 10 6,407 8,305 13.2 5,661 6,352
06206 61.39 6 4,165 5,398 8.6 4,615 5,064
06208 61.39 8 5,554 7,198 11.5 5,300 5,899
06210 61.39 10 6,941 8,997 14.3 5,985 6,734
06606 66.11 6 4,485 5,813 9.3 4,856 5,340
06608 66.11 8 5,981 7,751 12.3 5,580 6,225
06610 66.11 10 7,475 9,689 15.4 6,303 7,109
07006 70.83 6 4,806 6,229 9.9 5,093 5,612
07008 70.83 8 6,408 8,305 13.2 5,854 6,545
07010 70.83 10 8,009 10,381 16.5 6,614 7,478
200-320 SED (AUG 08) BCS SERIES GALVANIZED STEEL PRODUCT COOLERS
Page 12 SPECIFICATIONS
3-FAN UNIT
Face Area Surface Area (sq ft) Coil Volume Shipping Weight (lb)
Model Rows Deep
(sq ft) 3 FPI 4 FPI (cu ft) 3 FPI 4 FPI
04506 45.00 6 3,053 3,957 6.3 3,847 4,176
04508 45.00 8 4,071 5,276 8.4 4,452 4,891
04510 45.00 10 5,088 6,595 10.5 5,056 5,605
05106 50.63 6 3,435 4,452 7.1 4,193 4,564
05108 50.63 8 4,580 5,936 9.5 4,853 5,347
05110 50.63 10 5,724 7,420 11.8 5,511 6,129
05506 56.25 6 3,816 4,946 7.9 4,529 4,940
05508 56.25 8 5,089 6,595 10.5 5,241 5,790
05510 56.25 10 6,360 8,244 13.1 5,952 6,638
05806 56.67 6 3,845 4,983 7.9 4,553 4,968
05808 56.67 8 5,126 6,644 10.6 5,269 5,822
05810 56.67 10 6,407 8,305 13.2 5,984 6,675
06306 61.88 6 4,198 5,441 8.7 4,854 5,307
06308 61.88 8 5,598 7,255 11.6 5,618 6,219
06310 61.88 10 6,996 9,068 14.4 6,380 7,134
06406 63.75 6 4,325 5,606 8.9 4,960 5,426
06408 63.75 8 5,767 7,474 11.9 5,740 6,362
06410 63.75 10 7,208 9,343 14.9 6,519 7,296
06706 67.50 6 4,580 5,936 9.5 5,545 6,039
06708 67.50 8 6,107 7,914 12.6 6,358 7,017
06710 67.50 10 7,632 9,893 15.8 7,170 7,993
06906 70.83 6 4,806 6,229 9.9 5,354 5,873
06908 70.83 8 6,408 8,305 13.2 6,196 6,887
06910 70.83 10 8,009 10,381 16.5 7,037 7,901
07206 73.13 6 4,961 6,430 10.2 5,854 6,389
07208 73.13 8 6,615 8,574 13.7 6,715 7,429
07210 73.13 10 8,268 10,717 17.1 7,575 8,468
07806 77.92 6 5,286 6,851 10.9 6,112 6,683
07808 77.92 8 7,049 9,135 14.5 7,014 7,775
07810 77.92 10 8,810 11,419 18.2 7,915 8,866
08106 78.75 6 5,343 6,925 11.0 6,156 6,733
08108 78.75 8 7,124 9,233 14.7 7,066 7,834
08110 78.75 10 8,904 11,542 18.4 7,973 8,934
08406 84.38 6 5,725 7,419 11.8 6,454 7,071
08408 84.38 8 7,633 9,893 15.8 7,410 8,233
08410 84.38 10 9,540 12,366 19.7 8,364 9,393
08506 85.00 6 5,767 7,474 11.9 6,486 7,108
08508 85.00 8 7,690 9,966 15.9 7,447 8,277
08510 85.00 10 9,611 12,458 19.8 8,407 9,443
09206 92.08 6 6,248 8,097 12.9 6,853 7,527
09208 92.08 8 8,330 10,796 17.2 7,871 8,770
09210 92.08 10 10,412 13,496 21.5 8,888 10,012
09906 99.17 6 6,728 8,720 13.9 7,211 7,937
09908 99.17 8 8,971 11,627 18.5 8,287 9,254
09910 99.17 10 11,212 14,534 23.1 9,360 10,570
10706 106.25 6 7,209 9,343 14.9 7,563 8,341
10708 106.25 8 9,612 12,457 19.8 8,694 9,730
10710 106.25 10 12,013 15,572 24.8 9,822 11,118
BCS SERIES GALVANIZED STEEL PRODUCT COOLERS 200-320 SED (AUG 08)
SPECIFICATIONS Page 13
4-FAN UNIT
Face Area Surface Area (sq ft) Coil Volume Shipping Weight (lb)
Model Rows Deep
(sq ft) 3 FPI 4 FPI (cu ft) 3 FPI 4 FPI
06006 60.00 6 4,071 5,276 8.4 5,076 5,515
06008 60.00 8 5,428 7,035 11.2 5,873 6,459
06010 60.00 10 6,784 8,794 14.0 6,670 7,402
06806 67.50 6 4,580 5,936 9.5 5,533 6,027
06808 67.50 8 6,107 7,914 12.6 6,402 7,060
06810 67.50 10 7,632 9,893 15.8 7,270 8,094
07306 75.00 6 5,089 6,595 10.5 5,975 6,524
07308 75.00 8 6,785 8,794 14.0 6,914 7,646
07310 75.00 10 8,480 10,992 17.5 7,852 8,767
07606 75.56 6 5,126 6,644 10.6 6,007 6,561
07608 75.56 8 6,835 8,859 14.1 6,951 7,688
07610 75.56 10 8,543 11,073 17.6 7,894 8,815
08306 82.50 6 5,597 7,255 11.6 6,405 7,009
08308 82.50 8 7,464 9,673 15.4 7,411 8,212
08310 82.50 10 9,328 12,091 19.3 8,416 9,423
08606 85.00 6 5,767 7,474 11.9 6,545 7,166
08608 85.00 8 7,690 9,966 15.9 7,572 8,401
08610 85.00 10 9,611 12,458 19.8 8,600 9,637
09006 90.00 6 6,106 7,914 12.6 7,322 7,981
09008 90.00 8 8,142 10,552 16.8 8,393 9,271
09010 90.00 10 10,176 13,190 21.0 9,464 10,562
09406 94.44 6 6,408 8,305 13.2 7,064 7,756
09408 94.44 8 8,544 11,073 17.6 8,174 9,095
09410 94.44 10 10,679 13,842 22.0 9,283 10,435
09606 97.50 6 6,615 8,574 13.7 7,729 8,443
09608 97.50 8 8,821 11,432 18.2 8,864 9,816
09610 97.50 10 11,024 14,290 22.8 9,999 11,189
10606 103.89 6 7,049 9,135 14.5 8,070 8,831
10608 103.89 8 9,398 12,181 19.4 9,259 10,272
10610 103.89 10 11,746 15,226 24.2 10,447 11,714
10506 105.00 6 7,124 9,233 14.7 8,128 8,897
10508 105.00 8 9,499 12,311 19.6 9,326 10,351
10510 105.00 10 11,872 15,389 24.5 10,524 11,805
11206 112.50 6 7,633 9,893 15.8 8,521 9,344
11208 112.50 8 10,178 13,190 21.0 9,780 10,878
11210 112.50 10 12,720 16,488 26.3 11,039 12,412
11306 113.33 6 7,689 9,966 15.9 8,563 9,393
11308 113.33 8 10,253 13,288 21.2 9,829 10,935
11310 113.33 10 12,814 16,610 26.4 11,095 12,478
12306 122.78 6 8,330 10,796 17.2 9,047 9,946
12308 122.78 8 11,107 14,395 22.9 10,389 11,587
12310 122.78 10 13,882 17,994 28.6 11,731 13,229
13206 132.22 6 8,971 11,627 18.5 9,521 10,488
13208 132.22 8 11,962 15,503 24.7 10,937 12,227
13210 132.22 10 14,950 19,378 30.9 12,353 13,966
14206 141.67 6 9,612 12,457 19.8 9,984 11,021
14208 141.67 8 12,816 16,610 26.4 11,474 12,856
14210 141.67 10 16,018 20,763 33.1 12,963 14,691
200-320 SED (AUG 08) BCS SERIES GALVANIZED STEEL PRODUCT COOLERS
Page 14 DIMENSIONS
1
FAN
2
FAN
Discharge opening = L x W
W = 26" on 42" diameter fan.
W = 23" on 36" diameter fan.
W = 20" on 30" diameter fan.
3 L = 48" on all fans.
FAN
4
FAN
NOTES:
1. Unit hangers are 13/16" diameter. Leg supports are 9/16" diameter.
2. Bolt centers in hanger and leg support are the same. Legs are removable except the BP 90.
3. Right hand units shown, F = 19" and G = 7". Left hand units have drain connection and headers on opposite end, F = 17" and G = 9".
4. For shipping add 1" to height.
5. For water defrost add 4" to height and 10.5" to the overall width.
6. BC units with 10 rows, 7 hp - 1200 rpm motor or 15 hp - 1800 rpm motor add 4" to the overall width and hanger width dimensions for stan-
dard discharge models.
7. Do not use information for construction purposes. Dimensions are subject to change without notice.
BCS SERIES GALVANIZED STEEL PRODUCT COOLERS 200-320 SED (AUG 08)
DIMENSIONS Page 15
1
FAN
2
FAN
Discharge opening = L x W
W = 26" on 42" diameter fan.
W = 23" on 36" diameter fan.
W = 20" on 30" diameter fan.
3 L = 48" on all fans.
FAN
4
FAN
NOTES:
1. Unit hangers are 13/16" diameter. Leg supports are 9/16" diameter.
2. Bolt centers in hanger and leg support are the same. Legs are removable except the BP 90.
3. Right hand units shown, F = 19" and G = 7". Left hand units have drain connection and headers on opposite end, F = 17" and G = 9".
4. For shipping add 1" to height.
5. For water defrost add 4" to height and 10.5" to the overall width.
6. BC units with 10 rows, 7 hp - 1200 rpm motor or 15 hp - 1800 rpm motor add 4" to the overall width and hanger width dimensions for stan-
dard discharge models.
7. Do not use information for construction purposes. Dimensions are subject to change without notice.
BCS SERIES GALVANIZED STEEL PRODUCT COOLERS 200-320 SED (AUG 08)
DIMENSIONS Page 17
technology...
Connect Your PC
with QUANTUMLX !
Q-NET ... supports open-protocols for SCADA systems (i.e. Allen-Bradley DF1, Modbus RTU,
Modbus ASCII, and Industrial Ethernet Protocols)
Q-NET ... connects instantly for local or remote access; no software required
Available on Frick screw compressors, condensers, evaporators, AcuAir hygienic air handlers,
and refrigerant vessels.