Title Block Line 1 Project Title: Sample Project Title

You can change this area Engineer: Project ID: X1A


using the "Settings" menu item Project Descr: Sample Project Description
and then using the "Printing &
Title Block" selection.
Title Block Line 6 Printed: 2 FEB 2017, 3:21PM
File = c:\Users\DHAFIR\DOCUME~1\ENERCA~1\examples.ec6
Concrete Slender Wall ENERCALC, INC. 1983-2016, Build:6.16.8.31, Ver:6.16.8.31
Lic. # : KW-06000001 Licensee : MORRISON-MAIERLE, INC.
Description : Sample Concrete Slender Wall Calc

Code References
Calculations per ACI 318-11 Sec 14.8, IBC 2012, CBC 2013, ASCE 7-10
Load Combinations Used : IBC 2012
General Information
f'c : Concrete 28 day strength = 3.0 ksi Wall Thickness 8.0 in Temp Diff across thickness = deg F
Fy : Rebar Yield = 60.0 ksi Rebar at each face Min Allow Out-of-Plane Defl Ratio = L / 0
Ec : Concrete Elastic Modulus = 3,122.0 ksi Rebar "d" distance 6.0 in Minimum Vertical Steel % = 0.00150
: Lt Wt Conc Factor = 1.0 Lower Level Rebar . . . Using Stiff. Reduction Factor per ACI R.10.12.3
Fr : Rupture Modulus = 410.792 psi Bar Size # 7
Max % of balanced = 0.01355 Bar Spacing 12.0 in
Max Pu/Ag = f'c * = 0.060
Concrete Density = 145.0 pcf
Width of Design Strip = 12.0 in
One-Story Wall Dimensions
A Clear Height = 25.0 ft
B Parapet height = 3.250 ft B
Roof Attachment
Wall Support Condition Top & Bottom Pinned

Floor Attachment

Vertical Loads
Vertical Uniform Loads . . . ( Applied per foot of Strip Width) DL : Dead Lr : Roof Live Lf : Floor Live S : Snow W : Wind
Ledger Load Eccentricity 6.750 in 0.30 0.280 0.240 k/ft
Concentric Load k/ft
Vertical Concentrated Loads . . . ( Applied to full "Strip Width" ) DL : Dead Lr : Roof Live Lf : Floor Live S : Snow W : Wind
Beam Load #1 Eccentricity 8.0 in 6.0 5.0 5.50 k
Dist. from Base 24.0 ft
Lateral Loads
Wind Loads : Seismic Loads :
Full area WIND load 25.0 psf Wall Weight Seismic Load Input Method : ASCE seismic factors entered

SDS Value per ASCE 12.11.1 S DS * I = 0.850


Fp = Wall Wt. * 0.340 = 32.867 psf
Title Block Line 1 Project Title: Sample Project Title
You can change this area Engineer: Project ID: X1A
using the "Settings" menu item Project Descr: Sample Project Description
and then using the "Printing &
Title Block" selection.
Title Block Line 6 Printed: 2 FEB 2017, 3:21PM
File = c:\Users\DHAFIR\DOCUME~1\ENERCA~1\examples.ec6
Concrete Slender Wall ENERCALC, INC. 1983-2016, Build:6.16.8.31, Ver:6.16.8.31
Lic. # : KW-06000001 Licensee : MORRISON-MAIERLE, INC.
Description : Sample Concrete Slender Wall Calc

DESIGN SUMMARY Results reported for "Strip Width" of 12.0 in


Governing Load Combination . . . Actual Values . . . Allowable Values . . .
PASS Moment Capacity Check Maximum Bending Stress Ratio = 0.7170
+1.20D+1.60Lr+0.50W Max Mu 12.934 k-ft Phi * Mn 18.039 k-ft
PASS Service Deflection Check Actual Defl. Ratio L/ 182 Allowable Defl. Ratio 150
+D+0.750Lr+0.450W Max. Deflection 1.651 in
FAIL Axial Load Check Max Pu / Ag 208.662 psi Max. Allow. Defl. 2.0 in
+1.20D+1.60Lr+0.50W Location 18.750 ft 0.06 * f'c 180.0 psi
PASS Reinforcing Limit Check
Controlling As/bd 0.008333 As/bd = 0.0 rho bal 0.01355

Maximum Reactions . . . for Load Combination....


Top Horizontal E Only 0.5246 k
Base Horizontal W Only 0.4573 k
Vertical Reaction +D+0.750Lr+0.450W 15.574 k
Design Maximum Combinations - Moments Results reported for "Strip Width" = 12 in.
Axial Load Moment Values 0.6 *
Load Combination Pu 0.06*f'c*b*t Mcr Mu Phi Phi Mn As As Ratio rho bal
k k k-ft k-ft k-ft in^2
+1.40D at 21.67 to 22.50 9.712 17.280 4.38 5.28 0.90 16.66 0.600 0.0083 0.0135
+1.20D+0.50Lr at 21.67 to 22.50 10.966 17.280 4.38 6.16 0.90 16.87 0.600 0.0083 0.0135
+1.20D at 21.67 to 22.50 8.324 17.280 4.38 4.47 0.90 16.44 0.600 0.0083 0.0135
+1.20D+1.60Lr at 21.67 to 22.50 16.776 17.280 4.38 9.98 0.90 17.82 0.600 0.0083 0.0135
+1.20D+1.60Lr+0.50W at 18.33 to 19.17 20.032 17.280 4.38 12.93 0.90 18.04 0.600 0.0083 0.0135
+1.20D+0.50W at 20.00 to 20.83 11.388 17.280 4.38 6.77 0.90 16.94 0.600 0.0083 0.0135
+1.20D+0.50Lr+W at 17.50 to 18.33 17.189 17.280 4.38 11.64 0.90 17.89 0.600 0.0083 0.0135
+1.20D+W at 17.50 to 18.33 14.548 17.280 4.38 9.64 0.90 17.45 0.600 0.0083 0.0135
+1.20D+E at 15.83 to 16.67 9.001 17.280 4.38 6.38 0.90 16.55 0.600 0.0083 0.0135
+0.90D+W at 17.50 to 18.33 12.346 17.280 4.38 8.24 0.90 17.09 0.600 0.0083 0.0135
+0.90D+E at 15.83 to 16.67 6.750 17.280 4.38 5.16 0.90 16.18 0.600 0.0083 0.0135
Design Maximum Combinations - Deflections Results reported for "Strip Width" = 12 in.
Axial Load Moment Values Stiffness Deflections
Load Combination Pu Mcr Mactual I gross I cracked I effective Deflection Defl. Ratio
k k-ft k-ft in^4 in^4 in^4 in
D Only at 14.17 to 15.00 7.661 4.38 2.57 512.00 143.19 384.000 0.247 1,215.2
+D+Lr at 14.17 to 15.00 12.941 4.38 5.45 512.00 152.33 208.984 1.089 275.4
+D+0.750Lr at 15.00 to 15.83 11.541 4.38 4.83 512.00 149.93 269.058 0.816 367.5
+D+0.60W at 14.17 to 15.00 11.105 4.38 5.85 512.00 149.16 185.694 1.261 237.9
+D+0.70E at 15.00 to 15.83 7.581 4.38 4.54 512.00 143.05 325.018 0.656 457.1
+D+0.750Lr+0.450W at 13.33 to 14.17 14.285 4.38 7.21 512.00 154.61 156.315 1.651 181.7
+D+0.450W at 15.00 to 15.83 10.164 4.38 5.08 512.00 147.54 234.841 0.939 319.3
+D+0.5250E at 13.33 to 14.17 7.742 4.38 3.79 512.00 143.33 384.000 0.373 804.2
+0.60D+0.60W at 15.00 to 15.83 7.992 4.38 4.32 512.00 143.75 384.000 0.574 522.8
+0.60D+0.70E at 12.50 to 13.33 4.693 4.38 3.13 512.00 137.91 384.000 0.310 967.3
Lr Only at 14.17 to 15.00 5.280 4.38 2.11 512.00 138.95 384.000 0.203 1,476.0
W Only at 13.33 to 14.17 5.740 4.38 4.11 512.00 139.80 384.000 0.402 746.6
E Only at 11.67 to 12.50 0.000 4.38 2.48 512.00 129.42 384.000 0.231 1,300.0
Reactions - Vertical & Horizontal Results reported for "Strip Width" = 12 in.
Load Combination Base Horizontal Top Horizontal Vertical @ Wall Base
D Only 0.2 k 0.16 k 9.031 k
+D+Lr 0.3 k 0.29 k 14.311 k
Title Block Line 1 Project Title: Sample Project Title
You can change this area Engineer: Project ID: X1A
using the "Settings" menu item Project Descr: Sample Project Description
and then using the "Printing &
Title Block" selection.
Title Block Line 6 Printed: 2 FEB 2017, 3:21PM
File = c:\Users\DHAFIR\DOCUME~1\ENERCA~1\examples.ec6
Concrete Slender Wall ENERCALC, INC. 1983-2016, Build:6.16.8.31, Ver:6.16.8.31
Lic. # : KW-06000001 Licensee : MORRISON-MAIERLE, INC.
Description : Sample Concrete Slender Wall Calc

Reactions - Vertical & Horizontal Results reported for "Strip Width" = 12 in.
Load Combination Base Horizontal Top Horizontal Vertical @ Wall Base
+D+0.750Lr 0.3 k 0.26 k 12.991 k
+D+0.60W 0.4 k 0.00 k 12.475 k
+D+0.70E 0.4 k 0.21 k 9.031 k
+D+0.750Lr+0.450W 0.5 k 0.13 k 15.574 k
+D+0.450W 0.4 k 0.04 k 11.614 k
+D+0.5250E 0.4 k 0.11 k 9.031 k
+0.60D+0.60W 0.4 k 0.05 k 8.863 k
+0.60D+0.70E 0.4 k 0.27 k 5.419 k
Lr Only 0.1 k 0.14 k 5.280 k
W Only 0.5 k 0.25 k 5.740 k
E Only 0.4 k 0.52 k 0.000 k