You are on page 1of 4

AcuSplitCT Series 200/250/300/400A

Split Core Current Transformer

The Accuenergy split core CTs are compact and low-


cost current transformers with high accuracy. The
CTs are ideal for quick and easy installation without E359521

disconnecting cables during installation. Multiple


installation mechanisms provide stable and durable
current measurement.

FEATURES
Most cost-effective
Safe and easy installations
Multiple installation mechanisms
All mounting accessories included

SPECIFICATIONS DIMENSIONS
Unit : mm (inches)
Rated Primary current 200A, 250A, 300A, 400A
40.00mm (1.57'')
Rated Secondary current 5A, 1A 89.00mm (3.50'')

Burden 1.5VA
Accuracy 1% 21.00mm (0.83")
Withstand Voltage 3,000Vac
Frequency range 50-400Hz
Operating Temperature -15C - 60C
Standard IEC 60044-1 105.00mm (4.13")
31.00mm (1.22")

Case Material UL flame retardant rating 94-V0


Certifications UR & CE approved, RoHS
compliant

ORDERING INFORMATION
Rated Input

Ordering Number: AcuCT- 0812 - -


51.00mm (2.00'')

Ordering Example: AcuCT- 0812 - 200 - 5

200: 200A 5: 5A
50.00mm (1.97'')

250: 250A 1:1A


300: 300A
400: 400A

Accuenergy Corp.
Los Angeles-Toronto-Beijing
North America Toll Free: 1-877-721-8908
Web: www.accuenergy.com
Email: marketing@accuenergy.com Your Power and Automation Partner
AcuSplitCT Series 400/600/800/1000A
Split Core Current Transformer

The Accuenergy split core CTs are compact and low-


cost current transformers with high accuracy. The
E359521
CTs are ideal for quick and easy installation without
disconnecting cables during installation. Multiple
installation mechanisms provide stable and durable
current measurement.

FEATURES
Most cost-effective
Safe and easy installations
Multiple installation mechanisms

SPECIFICATIONS DIMENSIONS
Unit : mm (inches)
Rated Primary Current 400A, 600A, 800A, 1000A 114.00mm (4.49'')
Rated Secondary Current 5A, 1A 50.00mm (1.97'')
50.00mm (1.97'')

Burden 2.5VA
Accuracy 0.5%
Withstand Voltage 3,000Vac
Frequency Range 50-400Hz
Operating Temperature -15C - 60C
Standard IEC 60044-1 145.00mm (5.71'')
80.00mm (3.15'')

Case Material UL flame retardant rating 94-V0


Certifications UR, CE approved & RoHS
compliant

ORDERING INFORMATION
Rated Input

Ordering Number: AcuCT- 2031 - - 78.00mm (3.07'')

Ordering Example: AcuCT- 2031 - 600 - 5

400: 400A 5: 5A
50.00mm (1.97'')

600: 600A 1:1A


800: 800A
1000: 1000A

Accuenergy Corp.
Los Angeles-Toronto-Beijing
North America Toll Free: 1-877-721-8908
Web: www.accuenergy.com
Email: marketing@accuenergy.com Your Power and Automation Partner
AcuSplitCT Series 1000/1200/1600A
Split Core Current Transformer

The Accuenergy split core CTs are compact and low-


cost current transformers with high accuracy. The
CTs are ideal for quick and easy installation without E359521

disconnecting cables during installation. Multiple


installation mechanisms provide stable and durable
current measurement.

FEATURES
Most cost-effective
Safe and easy installations
Multiple installation mechanisms

SPECIFICATIONS DIMENSIONS
Unit : mm (inches)
Rated Primary Current 1000A, 1200A, 1600A 144.00mm (5.67'')
50.00mm (1.97'')
Rated Secondary Current 5A, 1A 80.00mm (3.15'')
Burden 7.5VA
Accuracy 0.5%
Withstand Voltage 3,000Vac
Frequency range 50-400Hz
Operating Temperature -15C - 60C
Standard IEC 60044-1 185.00mm (7.28'')
120.00mm (4.72'')

Case Material UL flame retardant rating 94-V0


Certifications UR, CE approved & RoHS
compliant

ORDERING INFORMATION
Rated Input

Ordering Number: AcuCT- 3147 - - 108.00mm (4.25'')

Ordering Example: AcuCT- 3147 - 1600 - 5


1000: 1000A 5: 5A
50.00mm (1.97'')

1200: 1200A 1:1A


1600: 1600A

Accuenergy Corp.
Los Angeles-Toronto-Beijing
North America Toll Free: 1-877-721-8908
Web: www.accuenergy.com
Email: marketing@accuenergy.com Your Power and Automation Partner
AcuSplitCT Series 2000/2500/3000/4000/5000A
Split Core Current Transformer

The Accuenergy split core CTs are compact and low-


cost current transformers with high accuracy. The
E359521
CTs are ideal for quick and easy installation without
disconnecting cables during installation. Multiple
installation mechanisms provide stable and durable
current measurement.

FEATURES
Most cost-effective
Safe and easy installations
Multiple installation mechanisms

SPECIFICATIONS DIMENSIONS
Unit : mm (inches)
Rated Primary current 2000, 2500, 3000, 4000, 5000A 176.00mm (6.93'')
70.00mm (2.76'')
Rated Secondary current 5A, 1A 80.00mm (3.15'')
Burden 15VA
Accuracy 0.5%
Withstand Voltage 3,000Vac
Frequency range 50-400Hz
Operating Temperature -15C - 60C
Standard IEC 60044-1 247.00mm (9.72'')
160.00mm (6.30'')

Case Material UL flame retardant rating 94-V0


Certifications UR, CE approved & RoHS
compliant

ORDERING INFORMATION
Rated Input

Ordering Number: AcuCT- 3163 - -


120.00mm (4.72'')

Ordering Example: AcuCT- 3163 - 2500 - 5

2000: 2000A 5: 5A
50.00mm (1.97'')

2500: 2500A 1:1A


3000: 3000A
4000: 4000A
5000: 5000A

Accuenergy Corp.
Los Angeles-Toronto-Beijing
North America Toll Free: 1-877-721-8908
Web: www.accuenergy.com
Email: marketing@accuenergy.com Your Power and Automation Partner