Professional Documents
Culture Documents
INTRODUCTION %
30 60
%
The main components of HVAC control systems include 1) the 50
various comfort sensors, such as thermostats and humidistats
Enthalpy (BTU/lbm)
40
Volume 1), 2) the control systems for heat and coolant supply
systems, the boilers (Section 8.6), chillers (Sections 8.12 and 25
Ideal
8.13), and the cooling towers (8.16 and 8.17), 3) the air and 30%
water transportation controls, including the fans and blowers
(Section 8.25) and pumping stations (Section 8.34), and 4) the
final control elements, including the dampers (Section 7.1), 20%
control valves (Chapter 6), and variable-speed drives 20
(Sections 7.10). For more information on the above topics the
reader is referred to the noted sections. USA 68 70 75 80F
This section will concentrate on the control and optimi- ASHRAE Temperature
zation of the total space conditioning system. This will be 20 24 27C
approached by first discussing the process being controlled Note: BTU/lbm = 2,326 J/Kg
and its various operating modes as the seasons change. Once
FIG. 8.2a
the personality of the process has been described, the con- 1
Comfort zones are defined in terms of temperature and humidity.
trol of the various comfort-related variables (temperature,
humidity, and air quality) will be discussed. The emphasis
will be placed on systems in which air is the final carrier of Whereas other unit operations have benefited substan-
heat or cooling into the conditioned spaces, although brief tially from the advances in process control, airhandlers have
mention will also be made of the more traditional, but still not. Airhandlers today are frequently controlled the same way
used, water-based systems. as they were 20 or 30 years ago. For this reason, airhandler
In the second half of this section, the emphasis will be optimization can result in much greater percentages of sav-
on the optimization of the total process by such methods as ings than can the optimization of almost any other unit oper-
making the buildings self-heating and by eliminating the ation. Optimization can sometimes cut the cost of airhandler
chimney effects. operation in half a savings that can seldom be achieved in
any other type of unit operation.
Some of the optimization goals and strategies include the
THE AIRHANDLER following:
The airhandler is the basic unit operation of space condition- Let the building heat itself
ing. It is used to keep occupied spaces comfortable Use free cooling or free dying
(Figure 8.2a) or unoccupied spaces at desired levels of tem- Benefit from gap control or zero energy band (ZEB)
perature and humidity. In addition to supplying or removing Eliminate chimney effect
heat or humidity from the conditioned space, the airhandler Optimize start-up timing
also provides ventilation and fresh air makeup. Depending Optimize air makeup (CO2)
on the type of space involved, from 75,000300,000 BTU/ Optimize supply air temperature
2
year (19,00076,000 cal/year) are required to condition 1 ft Minimize fan energy use
2
(0.092 m ) of office space. Depending on the energy sources Automate the selection of operating modes
used, this corresponds to a yearly operating cost of a few Minimize reheat
dollars per square foot of floor space. Automate balancing of air distribution
1507
PE XP TE RHE PE
11 17 08 10 20
EA FC FE
14 RA from
EAD RF other zones
03 Typical
TC 68F (20C)
FE 22 zone
13 +0.1'' (+25 Pa)
Typical R/A
78F
FO airhandler HWS RHC (25.6C)
FC R/A TC
RAD TCV FO
23
04 22
VAV
HWS 23
or CHWR
FC STM FC TE
TE RHE TE 07
06 12 TCV TCV
09
FC 01 02 SA to
OA H C FE other zones
F C C H SF 15
OAD RHCV
05 XP RHE PE
16
18 21 19
CHWS
STM FC
FIG. 8.2b
A typical major airhandler has these components and controls.
of the more efficient control concepts are described in the Q6 = (Fe) (He)
paragraphs below. Return fan
Q5 = Fan heat
Operating Mode Selection
TABLE 8.2d
The Status of Various Actuated Devices during Various Operating Modes
Operating Mode
or Emergency Supply Return Outside Air Exhaust Air Return Air Coil Control
Condition Fan Fan Damper Damper Damper Valves Alarm
Off C C O C
On On On Modulating
Warm-up On On C C O O(HC)
Cool-down On On C C O O(CC)
Night Cycled to maintain required nighttime temperature
Purge On On O O C Modulating
PSH-2 Off C Yes
PSL-3 Off C Yes
S/F-4 Off Off C O C C Yes
TSL-5 Off C O C Yes
PSL-6 Off C O Yes
PSH-7 Off C O Yes
S/F-8 Off Off C O C C Yes
or from other equipment failures. When this happens, the modulates the supply air fan station to match the demand
associated fan is stopped and an alarm is actuated. (Figure 8.2f). When the PIC-19 output has increased the fan
capacity to its maximum, PSH-19 actuates and starts an addi-
Fan Controls tional fan. Inversely, as the demand for supply air drops, FSL-
15 will stop one fan unit whenever the load can be met by
The standard fan controls are shown in Figure 8.2f. Each fewer fans than the number in operation. The important point
zone shown in Figure 8.2b is supplied with air through a to remember is that in cycling fan stations, fan units are
thermostat-modulated damper, also called a variable air vol- started on pressure and are stopped on flow control. The
ume box (VAV-23). operating cost of such a fan station is 2040% lower than if
The VAV box openings in the various zones determine constant-volume fans with conventional controls were used
the total demand for supply air. The pressure in the supply (Figure 8.2g).
air (SA) distribution header is controlled by PIC-19, which
EA FC FE
PSH RF RA
EAD PSL S/F 14
2 3 4
PIC FC
RF RA XP
EA On 11 PIC
17
O RA 20
FSL Stops PSH D/A
RAD SS Warm-up fan
FC Fire command
FC 14 20 Starts
1 Cool-down panel
Night SP = 90% FFIC fan
6 Purge <
14
Freezestat
TSL
5 PSH S/F
PSL FE SA
OAD 7 8
6 SF
SA 15
CC/ SF
Stops FSL PIC
DA HC
FC fan 15 19
Starts PSH R/A
FIG. 8.2e XP
fan 19
18
The safety and operating mode selection instruments used on an
airhandler. Most abbreviations used on this figure have already been
defined in connection with Figure 8.2b; S/F = smoke and fire detec- FIG. 8.2f
tor, SS = selector switch, FC = fire command panel. Variable-volume fan controls operate as shown here.
110
100
90
80
% Full load fan HP
70 ane
let v
able in
60 Vari
50 Enlarged view of
Energy saving blade seal
e
40
iv
dr
n
fa Pressure
30 eects
d
ee
seal
sp
20
le
iab
r
Va
10
0 10 20 30 40 50 60 70 80 90 100
% Full load
High pressure Low pressure
FIG. 8.2g side side
Using variable-speed fans can save significant amounts of energy.
(Courtesy of Dana Corp.)
FIG. 8.2h
Because the conditioned zones are pressurized slightly, Low-leakage damper designs increase the efficiency of HVAC
some of the conditioned air will leak into the atmosphere, systems.
creating pressurization loss. Being able to control the pres-
3 2
surization loss is one of the advantages of the control system [0.15 (m /min)/m ], because the resulting savings over the life
described in Figure 8.2f. The flow ratio controller FFIC-14 of the buildings will be much greater than the increase in initial
is set at 90%, meaning that the return-air fan station is modu- investment for better dampers (Figure 8.2h).
lated to return 90% of the air supplied to the zones. Therefore,
pressurization loss is controlled at 10%, which corresponds to Dampers and Pressure Distribution In order for dampers
the minimum fresh-air makeup requirement, resulting in a to give good control, a fair amount of pressure drop should
minimum-cost operation. be assigned to them. They should be sized for a P of about
Because the conditioned zones represent a fairly large 10% of the total system drop. On the other hand, excessive
capacity, a change in supply air flow will not immediately damper drops should also be avoided, because they will
result in a need for a corresponding change in the return air increase the operating costs of the fans. A good sizing basis
flow. Thus, PIC-20 (Figure 8.2f) is included in the system to for outside and return air fans is to size them for 1500 fpm
prevent the flow-ratio controller from increasing the return (457 m/min) velocity at maximum flow.
air flow rate faster than required. This dynamic balancing In locations where two air streams are mixed, such as when
eliminates cycling and protects against collapsing the duct- outside and return airs are ratioed (RAD-04 and OAD-05 in
work under excessive vacuum. Closure of the exhaust-air Figure 8.2b), it is important that the damper P be rela-
damper by PIC-11 indicates that the control system is prop- tively constant as the ratio is varied. Figure 8.2i shows that
erly tuned and balanced and is operating at maximum effi- parallel blade dampers give a superior performance in this
ciency. Under such conditions, the outside air admitted into service.
the airhandler exactly matches the pressurization loss, and Figure 8.2j illustrates the pressure levels in the various
no return air is exhausted. portions of typical airhandlers. It can be seen that the kind
To maximize the benefits of such an efficient configuration, of pressure drops that would be required by opposed blade
the dampers must be of tight shut-off design. When exposed dampers (Figure 8.2i) are simply not available. Therefore, if
to a pressure difference of 4 in. H2O (996 Pa), a closed con- such dampers were installed, the airhandler would be starved
2
ventional damper will leak at a rate of approximately 50 cfm/ft for air (the dampers could not pass the design flow) whenever
3 2 2
[15.2 (m /min)/m ]. In the HVAC industry, a 5 cfm/ft [1.52 the ratio was near 50:50 (percent).
3 2
(m /min)/m ] leakage rate is considered to represent a tight Figure 8.2j also shows that in traditional airhandlers more
shut-off design. Actually, it is cost-effective to install tight fan energy is used than necessary. This is because the return
2
shut-off dampers with leakage rates of less than 0.5 cfm/ft air fan is sized to generate the pressure needed to exhaust the
P =
SCFM = 0.472 slps 2
1.5 Note: 1'' H2O = 250 Pa
Parallel FIG. 8.2j
1.0 blades,
8000 SCFM*
Damper pressure drops and the typical pressure levels in the various
segments of airhandlers.
0.5
0 10 20 30 40 50 60 70 80 90
Damper Outside air damper
opening, Temperature Controls
deg 90 80 70 60 50 40 30 20 10 0
Return air damper
Space temperatures are controlled by thermostats. The tradi-
FIG. 8.2i tional thermostat is a proportional-only controller (see also
When outside and return air dampers are throttled to vary their Section 2.2). The pressure of the output signal from a pneu-
ratio at constant total flow, the required pressure drop varies with matic stat is a near straight-line function of the measure-
damper design (see upper portion of figure). The lower portion of
ment, described by the following relationship:
this figure shows the results of American Warming and Ventilating
Co. tests (per AMCA Standard 500) of pressure drops across parallel- O = Kc(M Mo) + Oo 8.2(2)
2
blade and opposed-blade outside and return air damper sets.
where
O = output signal
air from the building. A consequence of this is that the pres- Kc = proportional sensitivity (Kc can be fixed or adjust-
sure drop of 11/2 in. H2O (375 Pa) across the return air damper able, depending on the design)
is three times greater than what is necessary (1/2 in. H2O, or M = measurement (temperature)
125 Pa). Mo = normal value of measurement, corresponding to
The alternate system shown in the lower portion of the center of the throttling range
Figure 8.2j eliminates this waste of fan energy. Here, only the Oo = normal value of the output signal, corresponding
supply fan (SF) operates continuously, which reduces the pres- to the center of the throttling range of the control
sure drop across the return air damper to 1/2 in. H2O (125 Pa). valve (or damper)
The return fan (RF) is started only when air needs to be
relieved, and its speed is varied to adjust the amount of air to Another term used to describe the sensitivity of thermo-
be exhausted. Relocating RF also removes its heat input, stats is throttling range. As shown in Figure 8.2k, this term
which, in the traditional system, represents an added load on refers to the amount of temperature change that is required
the cooling coil. to change the thermostat output from its minimum to its
Thermostat
output (PSIG)
Cold air Range: 4090F
FC Normal: 72F
13 813 TC PB = 5%
PSIG D/A
Flowsheet representation
Output signal 0
Oset error, which
(PSIG)
is also called
throttling range
15 2F
3 14 Maximum cooling (damper open)
Temperature 13 Normal
(F) Spring 12 condition
Throttling Oo = 10.5 PSIG
range 11
range 10
(5 PSIG) Operating
9 Minimum cooling (damper closed)
8 line
FIG. 8.2k 7
6
Throttling range can be defined as the temperature change required 5 Measurement
to change the thermostat output from its minimum to its maximum 4
3 M (F)
value.
Note: 40 50 60 70 80 90
C = F 32 Mo = 72 F
maximum value, such as from 3 to 13 PSIG (21 to 90 kPa). 1.8
1 PSIG = 6.9 kPa Scale range = 4090 F
The throttling range is usually adjustable from 2 to 10F (1
to 5C). Slope of operating line = Proportional sensitivity = 2.5 PSIG/F =
One important point to remember is that thermostats do Proportional band = 5% = Gain = 20
not have set points, in the sense of having a predetermined FIG. 8.2l
temperature to which they would seek to return the controlled A fixed proportional band thermostat has a fixed throttling range
space. (Integral action must be added in order for a controller and no setpoint.
to be able to return the measured variable to a set point after
a load change.) Mo does not represent a set point; it only
identifies the space temperature that will cause the cooling one value to the other actuates switching devices in the ther-
damper in Figure 8.2l to be 50% open. This can be called a mostat and indexes them from day to night or vice versa.
normal condition, because relative to this point the ther- Supply air mains are often divided into two or more
mostat can both increase and decrease the cooling air flow circuits so that switching can be accomplished in various
rate as space temperature changes. areas of the building at different times. For example, a school
If the cooling load doubles, the damper will need to be building may have separate circuits for classrooms, offices
fully open, which cannot take place until the controlled space and administrative areas, the auditorium, and the gymnasium
temperature has risen to 73F (23C). As long as the cooling and locker rooms. In some of the electric designs, dedicated
load remains that high, the space temperature must also stay clocks and switches are built into each thermostat.
up at the 73F (23C) value. Similarly, the only way this The heatingcooling or summerwinter thermostat can
thermostat can reduce the opening of the cooling damper have its action reversed and, if desired, can have its set point
below 50% is to first allow the space temperature to drop changed by means of indexing. This thermostat is used to
below 72F (23C). Thus, thermostats have throttling ranges, actuate controlled devices, such as valves or dampers, that
not set points. If a throttling range is narrow enough, this gives regulate a heating source at one time and a cooling source at
the appearance that the controller is keeping the variable near another. It is often manually indexed in groups by a switch,
the set point, when in fact the narrow range only allows the or automatically by a thermostat that senses the temperature
variable to drift within limits. of the water supply, the outdoor temperature, or another
suitable variable.
Special-Purpose Thermostats Day-night, set-back, or dual In the heatingcooling design, there are frequently two
room thermostats will operate at different normal temper- bimetallic elements, one being direct acting for the heating
ature values for day and night. They are provided with both mode, the other being reverse acting for the cooling mode.
a day and a night setting dial, and the change from day The mode is switched automatically in response to a change
to night operation can be made automatic for a group of in the air supply pressure, much as the daynight thermostats
thermostats. The pneumatic day-night thermostat uses a two- operate.
pressure air supply system, the two pressures often being 13 The limited control range thermostat usually limits the
and 17 PSIG (89.6 and 177 kPa) or 15 and 20 PSIG (103.35 room temperature in the heating season to a maximum of
and 137.8 kPa). Changing the pressure at a central point from 75F (24C), even if the occupant of the room has set the
thermostat beyond these limits. This is done internally, with- Heating Cooling
out placing a physical stop on the setting knob. load load
A slave or submaster thermostat has its set point raised
Conventional control
or lowered over a predetermined range, in accordance with 100% 100%
ZEB control
variations in the output from a master controller. The master
controller can be a thermostat, manual switch, pressure con- Resulting saving
troller, or similar device. For example, a master thermostat
measuring outdoor air temperature can be used to adjust a
submaster thermostat controlling the water temperature in a 0% 0% Room
55 65 75 85 95 temperature
heating system. Mastersubmaster combinations are some- (F)
ZEB
times designated as single-cascade action. When action is (adjustable)
accomplished by a single thermostat having more than one
measuring element, it is referred to as compensated control. FIG. 8.2m
Multistage thermostats are designed to operate two or Zero energy band (ZEB) control is designed to save energy by not
more final control elements in sequence. using any when the room is comfortable.
A wet-bulb thermostat is often used for humidity control,
as the difference between wet- and dry-bulb temperature is
an indication of moisture content. A wick or other means for Zero Energy Band Control A recent addition to the available
keeping the bulb wet and rapid air motion to ensure a true thermostat choices is the zero energy band design. The idea
wet-bulb measurement are essential. behind ZEB control is to conserve energy by not using any
A dew-point thermostat is a device designed to control when the room is comfortable. As illustrated by Figure 8.2m,
humidity on the basis of dew point temperatures. the conventional thermostat wastes energy by continuing to
A smart thermostat is usually a microprocessor-based use it when the areas temperature is already comfortable.
unit with RTD-type or transistorized solid-state sensor. It is The comfort gap or ZEB on the thermostat is adjustable
usually provided with its own dedicated memory and intel- and can be varied to match the nature of the particular space.
ligence, and it can also be equipped with a communication ZEB control can be accomplished in one of two ways.
link (over a shared data bus) to a central computer. Such units The single set point and single output approach is illustrated
can minimize building operating costs by combining time- on the left side of Figure 8.2n. Here the cooling valve fails
of-day controls with intelligent comfort gap selection and closed and is shown to have an 811 PSIG (5576 kPa) spring
maximized self-heating. range, while the heating valve is selected to fail open and
Dual output
pressure from
thermostat
Output pressure (PSIG)
of single Full heating Full cooling
thermostat
Gain = 0.75 PSI/F 13
(PSIG)
12
Cooling valve open 11
11
10
10
9 Zero
9
Cooling valve closed 8 energy
8 band
7
7
6 Heating 6
valve closed 5
5
4 Heating 4
valve
3 3
open
2 2 Heat Cooling
1 o o
1
Space
0 Space 0
67 71 75 79 64 66 68 70 72 74 76 78 80 82 temperature
temperature
Heat ZEB Cool F
F Dual set point system
Single set point splitrange system
FIG. 8.2n
ZEB control schemes include the single setpoint split range approach (shown on left) and the dual set point approach (shown on right).
Pay heat Free cooling Pay cooling Humidity in the zones is controlled according to the moisture
O C C O C O
TCV01 OAD05 TCV02 content of the combined return air (see Figure 8.2q). The
0.2 0.28 0.35 0.40 0.48 0.55 0.60 0.69 0.76 0.80 0.90 0.97 1.0 bar
3 4 5 6 7 8 9 10 11 12 13 14 15 PSIG Temperature
Output signal from TIC07 control RA
signal from
FIG. 8.2p TIC-07 in Figure 8.2 p Non-linear RHIC
Illustration of a fully coordinated, pneumatic, split-range tempera- gap control 10
D/A
(3050% RH)
ture control system. Such controls can reduce the yearly operating
8
costs by more than 10%. TDIC > >
07
Supply Air Temperature Control A substantial source of
inefficiency in conventional HVAC control systems is the TCV RHCV
02 16
uncoordinated arrangement of temperature controllers. Two CHW
or three separate temperature control loops in series are not FC
Note
uncommon. For example, one of these uncoordinated con- 1215 PSIG RP
#2
(0.81.0 bar) STM SP = 90% RH
trollers may be used to control the mixed air temperature, FC RHIC
another to maintain supply (SA) temperature, and a third to 21 D/A
control the zone-reheat coil. Such practice can result in simul- # C # H SF
taneous heating and cooling and, therefore, in unnecessary SA
2 C 1
waste. Using a fully coordinated split-range temperature con-
trol system, such as that shown in Figure 8.2p, will reduce
yearly operating costs by more than 10%. Note #1
In this control system, the SA temperature set point (set by
the temperature controller, TIC-07) is continuously modulated FIG. 8.2q
to follow the load. The methods of finding the correct set point Humidity is controlled in the combined return air. Note 1: When the
will be discussed under Optimizing Strategies. The loop auto- need for dehumidification (in the summer) overcools the supply air
matically controls all heating or cooling modes. When the TIC- and therefore increases the need for reheat at the zones, this pump-
07 output signal is low 36 PSIG (20.741.3 kPa) heating around economizer loop is started. TDIC-07 will control the pump
is done by TCV-01. As the output signal reaches 6 PSIG to pump around only as much heat as is needed. Note 2: This
(41.3 kPa), heating is terminated; if free cooling is available, reversing positioner functions as follows:
it is initiated at 7 PSIG (48.2 kPa). When the output signal Input from Output to
reaches 11 PSIG (75.8 kPa) the point at which OAD-05 is RHIC-10 RHCV-16
fully open the cooling potential represented by free cooling 3 PSIG = 0% 100% (open)
is exhausted, and at 12 PISG (82.7 kPa), pay cooling is 9 PSIG = 50% 0% (closed)
See
Figure SP = 10% SP = 68F (20C)
SP Least open TCV From
8.2 p TIC TC R/A
VPC < other
07 07 Note #1 zones 22
D/A
FB VPA VPS
FB to VPC 07 07
TCV
SP = 90% 22
TT Set point Most-open TCV From
to TIC on VPC > other HWS
07 22 Note #1 FC
HWS zones
D/A
FB R SA
SF H
At xed C
VAV minimum
To other 23 opening
zones Typical zone
FIG. 8.2t
Optimization of air and water temperatures during heating (winter) mode of airhandler operation is designed to distribute the heat load
efficiently between the main heating coil and the zone reheat coils. Note: Valve position controllers (VPCs) are provided with integral action
only for stable floating control. The integral time is set to be 10 times the integral time of the associated TIC. External feedback is provided
to eliminate reset wind-up when VPC output is overruled by the setpoint limit on TIC-07.
therefore must be either positioned or cycled to admit enough Temperature Optimization in the Winter
cold outside air to lower the mixed air temperature to equal
the cold deck temperature set point. This way the need for In the winter, the goal of optimization is to distribute the heat
pay cooling is eliminated. load between the main heating coil (HC in Figure 8.2p) and
When the outside air is in zone 3 (hot but dry), the control the zone reheat coils (RHC in Figure 8.2t) most efficiently.
system should admit some of it to reduce the overall need The highest efficiency is obtained if the SA temperature is high
for latent cooling. The amount of outside air admitted under enough to meet the load of the zone when the zone load is
these conditions should be controlled so that the resulting minimum. In this way, the zone reheat coils are used only to
mixed-air dew point temperature will equal the desired cold provide the difference between the loads of the various zones,
deck dew point. This method takes full advantage of the free whereas the base load is continuously followed by TIC-07.
drying potential of the outside air. In Figure 8.2t the set point of TIC-07 is adjusted to keep
As can be seen from the above, the use of the economizer the least-open TCV-22 only about 10% open. First, the least-
cycles is similar to opening the windows in a room to achieve open TCV-22 is identified and its opening (in the valve posi-
maximum comfort with minimum use of pay energy. tion controller, VCP-07) is compared with the desired goal
of 10%. If the valve opening is more than 10%, the TIC-07
set point is increased; if less, the set point is lowered. Stable
operation is obtained by making VPC-07 an integral-only
OPTIMIZING STRATEGIES controller with an external feedback to prevent reset wind-up.
In Figure 8.2t it is assumed that the hot water supply
The main goal of airhandler optimization is to match the (HWS) temperature is independently adjustable and will be
demand for conditioned air with a continuous, flexible, and modulated by VPC-22 so that the most-open TCV-22 will
efficient supply. This requires the floating of both air pressures always be 90% open. The advantages of optimizing the HWS
and temperatures to minimize operating costs while following temperature include:
the changing load.
In traditional HVAC control systems, the set point of TIC- Minimizing heat-pump operating costs by minimizing
07 in Figure 8.2p is set manually and is held as a constant. HWS temperature
This practice is undesirable, because for each particular load Reducing pumping costs by opening all TCV-22
distribution, the optimum SA temperature is different. If the valves in the system
manual setting is less than that temperature, some zones will Eliminating unstable (cycling) valve operation, which
become uncontrollable. If it is more than optimum, operating occurs in the nearly closed position, by opening all
energy will be wasted. TCV-22 valves
In Figure 8.2t, a valve position alarm (VPA-07) is also loop, as long as the most-open valve is less than 90% open,
provided to alert the operator if this heating control system the SA temperature is set to keep the least open TCV-22 at
is incapable of keeping the openings of all TCV-22 valves 10% open (zone A). When the most-open valve reaches 90%
between the limits of 10% and 90%. Such alarms will occur open, control of the least-open valve is abandoned and the
if the VPCs can no longer change the TIC set point(s), loop is dedicated to keeping the most-open TCV-22 from
because their maximum (or minimum) limits have been becoming fully open (zone B). This, therefore, is a classic
reached. This condition will occur only if the load distribution case of herding control, in which a single constraint envelope
was not correctly estimated during design or if the mechan- herds all TCV openings to within an acceptable band and,
ical equipment was not correctly sized. thereby, accomplishes efficient load following.
If the HWS temperature cannot be modulated to keep the
most-open TCV-22 from opening to more than 90%, then the
control loop depicted in Figure 8.2u should be used. In this Temperature Optimization in the Summer
EA Start-Up Algorithm
RA
All VAV boxes are set to their minimum openings required
Return TT for ventilation purposes (XMIN), such as 25%. Therefore, at
air fan
the time of start-up, AO-1 through AO-N are all set for 25%.
SP
RA PIC is set to mid-scale; therefore, the start-up value of its
AI-RT SP = 50%. TIC is set for (TL + 25)F in the heating mode and
AO-1 for (TH - 25)F in the cooling mode.
PIC
Zone 1 After 5 min of operation, the zone temperatures are
Coils PT AI1 detected (ZT5-1, ZT5-2, and so on), and after 10 min of
SA operation they are detected again (ZT10-1, ZT10-2, and so
OA
ZT on). At the end of the first 10 min of operation, the supply air
VAV-1
Supply 1 temperature is also measured as AT10 and the return air tem-
TT
air fan SP AO-2 perature as RT10.
Zone 2 Once the above readings are obtained, they are entered
AI2 into a table such as Table 8.2y, which serves as the basis for
determining the required start-up openings of each of the
TIC ZT
VAV-2 VAV boxes (XSET-1, XSET-2, and so on). The purpose of
2
this table is to select the initial opening for each VAV box
AIAT
in a logical manner. Therefore, if the zone temperature after
10 minutes of operation is already within 5F of reaching
the comfort zone, the VAV box can be left at its minimum
opening.
AO-N If comfort is not yet within 5F, a higher opening is
Zone N needed. The initial VAV opening is increased on the basis of
AIN the zones performance during the previous 5 minutes. The
larger the temperature change experienced by the zone during
ZT the previous 5 minutes, the sooner it will reach the comfort
VAV-N
N
zone and therefore the smaller the opening that is required.
By this logic, the VAV boxes on those zones that are furthest
FIG. 8.2x from comfort and that are moving most slowly toward comfort
Airhandler optimization and auto-balancing can be handled effi-
will be given the highest openings.
ciently by computer.
TABLE 8.2y
Algorithm to Determine Start-Up Openings of Individual VAV Boxes (XSET)
Input Conditions Output
Note: C = ( F 32)/1.8.
The main optimizing and auto-balancing feature of this air transportation and conditioning. These two cost factors
algorithm is that whenever a zone is inside the comfort gap, tend to change in opposite directions; minimizing the cost of
its VAV opening is reduced to XMIN. This reduces the load one will increase the cost of the other. Therefore, it is impor-
on the fans and also provides more air to the zones experi- tant to monitor both the transportation and the conditioning
encing the highest loads. costs continuously and to minimize the larger one when
optimizing the system. Computerized control systems allow
Optimization of Air Supply Pressure and Temperature these costs to be readily calculated on the basis of utility
costs and quantities.
Optimization means that the load is met at minimum cost.
The cost of operating an airhandler is the sum of the cost of
TABLE 8.2aa
Algorithm to Determine Analog Outputs, Setting the Openings of
TABLE 8.2z VAV Boxes
Reevaluation of Value of XMAX
Output
Input Conditions Output Input Conditions
Required VAV
Has VAV been Has VAV been Incremental Change Operating Opening: AO-1 to
Continuously Open Continuously Throttled to in Value of XMAX Mode Control Criteria AO-N is to be Equal
to its XMAX During its XMIN During the Last at the End of
Last 5 Minutes? 5 Minutes? 5-Minute Period Heating ZT < (TL 1) XMAX
(AT > ZT) (TL 1) < ZT < (TL + 1) No change
Yes Yes Leave XMAX =
XMIN ZT > (TL + 1) XMIN
No Increase by 10% Cooling ZT > (TH + 1) XMAX
(AT < ZT) (TH 1) < ZT < (TH + 1) No change
No Yes Decrease by 10%
No Leave as is ZT < (TH 1) XMIN
TABLE 8.2bb
Optimization of Supply Air Pressure and Temperature, When Fan Costs Exceed Conditioning Costs (Frequency = 5
min)
Incremental Ramp Adjustment in
the Set Points of
None at 100% for 15 Heating (AT > RT) Yes, at max. 2F N.C.* (at min.)
minutes continuously No 1F N.C. (at min.)
Cooling (AT < RT) Yes, at min. + 2F N.C. (at min.)
No + 1F N.C. (at min.)
Not more than one at Heating (AT > RT) Yes, at max. N.C. (at max.) N.C.
100% for more than No N.C. N.C.
30 minutes continuously
Cooling (AT < RT) Yes, at min. N.C. (at max.) N.C.
No N.C. N.C.
More than one at 100% Heating (AT > RT) Yes, at max. (at max.) + 0.25 in. H2O
for more than 30 minutes No + 1F N.C.
continuously
Cooling (AT < RT) Yes, at min. (at min.) + 0.25 in. H2O
No 1F N.C.
More than one at 100% for Heating (AT > RT) Yes, at max. (at max.) + 0.5 in. H2O
more than 60 minutes No + 2F N.C.
continuously
Cooling (AT < RT) Yes, at min. (at min.) + 0.5 in. H2O
No 2F N.C.
For example, if the transportation cost exceeds the con- summer or the winter. Under such conditions, the supply pres-
ditioning cost, the optimization goal is to minimize fan oper- sure is maximized before the supply air temperature is increased
ation. This is achieved by conditioning the space with as little in the winter or lowered in the summer. When none of the VAV
air as possible. The quantity of air transported can be mini- boxes in Figure 8.2x are fully open, the PIC set point is lowered,
mized if each pound of air is made to transport more condi- while the TIC set point is at or near minimum in the winter
tioning energy; that is, if each pound of air carries more (maximum in summer). When more than one VAV box is fully
cooling or heating BTUs. Therefore, when the goal is to open, the PIC set point is increased to its maximum setting.
minimize fan costs, the air supply pressure is held as low as When that is reached, the supply temperature starts to be
possible, and the air supply temperature is maximized in the increased in the winter (decreased in the summer).
winter and minimized in the summer. Fan costs tend to The algorithms described above provide the dual advan-
exceed conditioning costs when the loads are low, such as in tages of automatic balancing and minimum operating cost.
the spring or fall, or when the economizer cycle is used to They eliminate the need for manual labor or for the use of
provide free cooling. pressure-independent VAV boxes, while reducing operating
Table 8.2bb describes the algorithm used to achieve this cost by about 30%. They also provide the flexibility of assign-
goal. When none of the VAV boxes (Figure 8.2x) are fully ing different comfort envelopes (different TL and TH values)
open, indicating that all loads are well satisfied, the air pres- to each zone. Thereby, as occupancy or use changes, the
sure (PIC set point) is kept at a minimum, and the air tem- comfort zone assigned to the particular space can be changed
perature (TIC set point) is lowered in the winter and raised automatically.
in the summer. When more than one VAV boxes are fully
open, the air supply temperature is increased in the winter
(lowered in the summer). When its limit is reached, the algo- ELIMINATION OF CHIMNEY EFFECTS
rithm will start raising the PIC set point.
Table 8.2cc describes the algorithm used when the condi- In high-rise buildings, the natural draft resulting from the
tioning costs are higher than the fan operating costs. This is chimney effect tends to pull in ambient air at near ground
likely to be the case when the loads are high, such as in the elevation and to discharge it at the top of the building.
TABLE 8.2cc
Optimization of Supply Air Pressure and Temperature, When Conditioning Costs Exceed Fan Costs (Frequency = 5 min)
Incremental Ramp Adjustment in the Set
Points of
Is PIC Set Point at Its
VAV Status Airhandler Mode Maximum? TIC PIC
None at 100% for Heating (AT > RT) Yes 1F 0.5 in. H2O
15 minutes continuously No N.C.* (at min.) 0.25 in. H2O
Cooling (AT < RT) Yes + 1F 0.5 in. H2O
No N.C. (at max.) 0.25 in. H2O
Not more than one at Heating (AT > RT) Yes N.C. N.C. (at max.)
100% for more than No N.C. N.C.
30 minutes continuously
Cooling (AT < RT) Yes N.C. N.C. (at max.)
No N.C. N.C.
More than one at 100% for Heating (AT > RT) Yes + 1F (at max.)
more than 30 minutes No N.C. + 0.25 in. H2O
continuously
Cooling (AT < RT) Yes 1F (at max.)
No N.C. + 0.25 in. H2O
More than one at 100% for Heating (AT > RT) Yes + 2F (at max.)
more than 60 minutes No N.C. + 0.5 in H2O
continuously
Cooling (AT < RT) Yes 2F (at max.)
No N.C. + 0.5 in H2O
* N.C. = No change.
Although eliminating the chimney effect can lower the oper- the square of flow and the pressure at the end of the distri-
ating cost by approximately 10%, few systems with this bution headers (cascade masters PC-1 and PC-6) remains
capability are yet in operation. constant. This control approach results in the most efficient
Figure 8.2dd shows the required pressure controls. The operation of variable-air volume fans.
key element of this control system is the reference riser, which If the building is maintained at a constant pressure that
allows all pressure controllers in the building to be referenced equals the pressure at ground elevation plus 0.1 in. H2O, this
to the barometric pressure of the outside atmosphere at a will result in higher pressure differentials on the higher floors,
selected elevation. Using this pressure reference allows all as the barometric pressure on the outside drops. Therefore,
zones to the operated at 0.1 in. H2O (25 Pa) above that refer- air losses due to out-leakage and pressure differentials on the
ence pressure (PC-7) and permits this constant pressure to be windows will both rise. If the pressure reference is taken at
maintained at both ends of all elevator shafts (PC-8 and -9). some elevation above ground level, these effects will be
If the space pressure is the same on the various floors of reduced on the upper floors, but on the lower floors the
a high-rise building, there will be no pressure gradient to windows will be under positive pressure from the outside and
motivate the vertical movement of the air, and as a conse- air infiltration will be experienced.
quence, the chimney effect will have been eliminated. A side
benefit of this control strategy is the elimination of all drafts
or air movements between zones, which also minimizes the CONCLUSIONS
dust content of the air. Another benefit is the capability of
adjusting the pressurization loss of the building by varying The airhandler is just one of the industrial unit operations. The
the setting of PC-7, -8, and -9. process of air conditioning is similar to all other industrial
Besides reducing operating costs, the use of pressure- processes. Fully exploiting state-of-the-art instrumentation and
controlled elevator shafts increases comfort because drafts control results in dramatic improvements. There are few other
and the associated noise are eliminated. processes in which the use of optimization and of instrumen-
Figure 8.2dd also shows the use of cascaded fan controls. tation know-how alone can halve the operating cost of a process.
The set points of the cascade slaves (PC-2 and PC-5) are The control and optimization strategies described in this
programmed so that the air pressure at the fan is adjusted as chapter can be implemented by pneumatic or electronic
Ambient pressure
reference at
selected elevation
Typical zone
1/4'' +1''
(62.5 Pa) R PC + 0.1'' (+25 Pa) TC (+250 Pa)
PC R/A 7 D/A PC
R R
1 6
VAV
RA SA
FC FO
50 to 100% 0 to 50%
PC output PC output
FC FO
RA SA
Typical
elevator
shaft
+ 0.1'' (+25 Pa)
PC R
9 D/A
RA SA
R FC FO
50 to 100% 0 to 50%
To all PC output PC output
Control
other
EA > signal from
PCs OA TIC-07 in SP
D/A D/A Fig 8.2 p
SP +1/4'' PC
1/4'' R
(+ 62.5 Pa) FC (62.5 Pa) 5
R PC FC D/A
2 PC PC R
R/A R 4
3
SF
RF
FO
FC
FIG. 8.2dd
Chimney effects in high-rise buildings can be eliminated by using the proper pressure controls.
instruments and can be controlled by analog or digital sys- 2. Avery, G., VAV Economizer Cycle, Heating, Piping, Air Condition-
tems. The type of hardware used in optimization is less ing, August 1984.
3. Liptk, B. G., Reducing the Operating Costs of Buildings by the Use
important than the understanding of the process and of the
of Computers, ASHRAE Transactions, 83:1, 1977.
control concepts that are to be implemented. The main advan- 4. Kovach, E. G., Technology of Efficient Energy Utilization: The
tage of digital and computerized systems is their flexibility Report of a NATO Science Committee Conference Held at Les Arcs,
and convenience in making changes, without the need to France, 812 October, 1973, Scientific Affairs Division, NATO, Brus-
modify equipment or wiring. sels, Belgium.
5. Liu, S. T., et al., Research, Design, Construction and Evaluating an
Energy Conservation School Building in New York City, NBSIR.
6. Stanford Research Institute, Patterns of Energy Consumption in the
References United States, prepared for the Office of Science and Technology,
Washington, D.C.
1. Liptk, B. G., Applying the Techniques of Process Control to the 7. Nomura, G., and Yamada, Y., CO2 Respiration Rate for the Ventilation
HVAC Process, ASHRAE Transactions, Paper No. 2778, Vol. 89, Part Calculation, Transaction of Japanese Architectural Society Meetings,
2A, 1983. October 1969.
8. Department of Defense, Environmental Engineering for Shelters, Haines, R. W., and Wilson, C. L., HVAC Systems Design Handbook, New
TR-20-Vol. 3, Department of Defense, Office of Civil Defense, May York: McGraw-Hill, 2003.
1969. Luciano, J. R., Energy Conservation Techniques for Hospital Operating
9. Kusuda, T., Intermittent Ventilation for Energy Conservation, NBS Rooms, ASHRAE Journal, May 1983.
report of ASHRAE Symposium in Dallas, TX, February 1976. Nordeen, H., Control of Ventilation Air in Energy Efficient Systems,
ASHRAE Symposium #20, Paper #3.
Ozawa, K., Noda, Y., et al., A Tuning Method for PID Controller Using
Optimization Subject to Constraints on Control Input, ASHRAE
Bibliography Annual Meeting, Kansas City, 2003.
Rosaler, R. C., HVAC Maintenance and Operations Handbook, New York:
American Institute of Architects, The Architects Handbook of Professional McGraw-Hill, 1997
Practice, with CD, 13th edition, New York: John Wiley & Sons, Inc. Shih, J. Y., Energy Conservation and Building Automation, ASHRAE
ASHRAE Standard 62-2001, Ventilation for Acceptable IAQ, ASHRAE, Paper #2354.
2001. Spielvogel, L. G., Exploding Some Myths about Building Energy Use,
Bell, A. A., Jr., HVAC Equations New York: McGraw-Hill, 2000. Architectural Record, February 1976.
Cooper, F. G., Low Pressure Sensing and Control, InTech, September Stillman, R. B., Systems Stimulation, engineering report prepared for
1992. IBM-RECD, 1971.
Daryani, S., Design Engineers Guide to Variable Air-Volume Systems, Turk, A., Gaseous Air Cleaning, ASHRAE Journal, May 1983.
Actual Specifying Engineer, July 1974. Woods, J. E., Impact of ASHRAE Ventilation Standards 62-73 on Energy
DHO/Atlanta Corp., Conserving Energy, Powered Induction Unit (Data Use, ASHRAE Symposium #20, Paper #1.
Sheet #1), Atlanta, GA: DHO/Atlanta Corp., 1974.