You are on page 1of 21

8.

2 Airhandler and Building Conditioning Controls


B. G. LIPTK (1985, 1995, 2005)

INTRODUCTION %
30 60
%
The main components of HVAC control systems include 1) the 50
various comfort sensors, such as thermostats and humidistats

Relative humidity (% RH)


(Section 7.9 in Chapter 7) and pressure sensors (Chapter 5 in %

Enthalpy (BTU/lbm)
40
Volume 1), 2) the control systems for heat and coolant supply
systems, the boilers (Section 8.6), chillers (Sections 8.12 and 25
Ideal
8.13), and the cooling towers (8.16 and 8.17), 3) the air and 30%
water transportation controls, including the fans and blowers
(Section 8.25) and pumping stations (Section 8.34), and 4) the
final control elements, including the dampers (Section 7.1), 20%
control valves (Chapter 6), and variable-speed drives 20
(Sections 7.10). For more information on the above topics the
reader is referred to the noted sections. USA 68 70 75 80F
This section will concentrate on the control and optimi- ASHRAE Temperature
zation of the total space conditioning system. This will be 20 24 27C
approached by first discussing the process being controlled Note: BTU/lbm = 2,326 J/Kg
and its various operating modes as the seasons change. Once
FIG. 8.2a
the personality of the process has been described, the con- 1
Comfort zones are defined in terms of temperature and humidity.
trol of the various comfort-related variables (temperature,
humidity, and air quality) will be discussed. The emphasis
will be placed on systems in which air is the final carrier of Whereas other unit operations have benefited substan-
heat or cooling into the conditioned spaces, although brief tially from the advances in process control, airhandlers have
mention will also be made of the more traditional, but still not. Airhandlers today are frequently controlled the same way
used, water-based systems. as they were 20 or 30 years ago. For this reason, airhandler
In the second half of this section, the emphasis will be optimization can result in much greater percentages of sav-
on the optimization of the total process by such methods as ings than can the optimization of almost any other unit oper-
making the buildings self-heating and by eliminating the ation. Optimization can sometimes cut the cost of airhandler
chimney effects. operation in half a savings that can seldom be achieved in
any other type of unit operation.
Some of the optimization goals and strategies include the
THE AIRHANDLER following:

The airhandler is the basic unit operation of space condition- Let the building heat itself
ing. It is used to keep occupied spaces comfortable Use free cooling or free dying
(Figure 8.2a) or unoccupied spaces at desired levels of tem- Benefit from gap control or zero energy band (ZEB)
perature and humidity. In addition to supplying or removing Eliminate chimney effect
heat or humidity from the conditioned space, the airhandler Optimize start-up timing
also provides ventilation and fresh air makeup. Depending Optimize air makeup (CO2)
on the type of space involved, from 75,000300,000 BTU/ Optimize supply air temperature
2
year (19,00076,000 cal/year) are required to condition 1 ft Minimize fan energy use
2
(0.092 m ) of office space. Depending on the energy sources Automate the selection of operating modes
used, this corresponds to a yearly operating cost of a few Minimize reheat
dollars per square foot of floor space. Automate balancing of air distribution

1507

2006 by Bla Liptk


1508 Control and Optimization of Unit Operations

PE XP TE RHE PE
11 17 08 10 20
EA FC FE
14 RA from
EAD RF other zones
03 Typical
TC 68F (20C)
FE 22 zone
13 +0.1'' (+25 Pa)
Typical R/A
78F
FO airhandler HWS RHC (25.6C)
FC R/A TC
RAD TCV FO
23
04 22
VAV
HWS 23
or CHWR
FC STM FC TE
TE RHE TE 07
06 12 TCV TCV
09
FC 01 02 SA to
OA H C FE other zones
F C C H SF 15
OAD RHCV
05 XP RHE PE
16
18 21 19
CHWS
STM FC

CC = Cooling coil FO = Fail open RA = Return air SF = Supply fan


CHWR = Chilled water return H = Humidier RAD = Return air damper STM = Steam
EA = Exhaust air HC = Heating coil RF = Return fan TCV = Temperature control valve
EAD = Exhaust air damper HWS = Hot water supply RHC = Reheat coil TE = Temperature element
F = Filter OA = Outside air RHCV = Relative humidity control valve VAV = Variable air volume damper
FC = Fail closed OAD = Outside air damper RHE = Relative humidity element XP = Positioner for fan volume control,
FE = Flow element PE = Pressure element SA = Supply air such as a blade pitch positioner

FIG. 8.2b
A typical major airhandler has these components and controls.

Airhandler Components from the zones is transported by the variable-volume return-


air fan station. If the amount of available return air exceeds
The purpose of heating, ventilation, and air conditioning the demand for it, the excess air is exhausted by the exhaust
(HVAC) controls is to provide comfort in laboratories, clean- air damper (EAD-03). The conditioned spaces are typically
rooms, warehouses, offices, and manufacturing spaces. Sup- pressurized to about 0.1 in. H2O (25 Pa), relative to the
ply air is the means of providing comfort in the conditioned barometric pressure on the outside. This pressurization
zone. The air supplied to each zone must provide heating or results in some air leakage through the walls and windows,
cooling, raise or lower humidity, and provide air refreshment. which varies with the quality of construction. Therefore, the
To satisfy these requirements, it is necessary to control the air balance around the system is:
temperature, humidity, and fresh-air ratio in the supply air.
Figure 8.2b illustrates the main components of an airhan- OA = EA + pressurization loss 8.2(1)
dler. The term airhandler refers to the total system, including
fans, heat-exchanger coils, dampers, ducts, and instruments. Under normal operation, the airhandler operates with
The system operates as follows: Outside air is admitted by about 10% outside air. In the purge or free cooling
the outside air damper (OAD-05) and is then mixed with the modes, RAD is closed, OAD is fully open, and the airhandler
return air from the return air damper (RAD-04). The resulting operates with 100% outside air.
mixed air is filtered (F), heated (HC) or cooled (CC), and As can be seen, the HVAC process is rather simple. Its
humidified (H) or dehumidified (CC) as required. The result- process material is clean air, its utility is water or steam, and
ing supply air is then transported to the conditioned zones its overall system behavior is slow, stable, and forgiving. For
(groups of offices) by the variable-volume supply fan station. precisely these reasons, it is possible to obtain acceptable
Variable volume means that the air flow rate generated by HVAC performance using inferior-quality instruments that are
the fan(s) is variable. configured into poorly designed loops. Yet, there is an advan-
In each zone, the variable air volume damper (VAV-23) tage in applying state-of-the-art process control to the HVAC
determines the amount of air required, and the reheat coil process, because it can provide a drastic reduction in operating
(RHC) adjusts the air temperature as needed. The return air costs, attributable to increased efficiency of operation. Some

2006 by Bla Liptk


8.2 Airhandler and Building Conditioning Controls 1509

of the more efficient control concepts are described in the Q6 = (Fe) (He)
paragraphs below. Return fan

Q5 = Fan heat
Operating Mode Selection

The correct identification and timing of the various operating


modes can contribute to the optimization of the building. The Hot deck Zones Cold deck
normal operating modes include start-up, occupied, night, at Th at Tc
and purge.
Optimizing the time of start-up will guarantee that the min-
Heater and Cooler and
imum required cost is invested in getting the building ready
humidier dehumidier
for occupancy. This is done by automatically calculating the Q3 = Fh (Th Tm) Q4 = Fc (Tm Tc)
amount of heat that needs to be transferred and dividing it
according to the capacity of the start-up equipment. A computer-
optimized control system will serve to initiate the unoccupied Supply Tm
(night) mode of operation; it will also recognize weekends Q1 = (Fo ) (Ho) fan
and holidays and, in general, provide a flexible means of time- Q2 = Fan heat
of-day controls. Fc = Cold deck ow Ho = Outside air enthalpy
The purge mode is another convenient tool of optimiza- Fe = Exhaust air ow Tc = Cold deck temperature
tion. Whenever the outside air is preferred to the return air, Fh = Hot deck ow Th = Hot deck temperature
the building is automatically purged. In this way, free cool- He = Exhaust air enthalpy Tm = Mixed air temperature
Net airhandler load = Q0 = Q1 + Q2 + Q3 Q4 + Q5 Q6
ing can be obtained on dry summer mornings, or free heat-
ing can be provided on warm winter afternoons. Purging is FIG. 8.2c
the equivalent of opening the windows in a home. In com- When the net airhandler load is negative, summer mode is required;
puter-optimized buildings, an added potential is to use the when it is positive, winter mode is required.
building structure as a means of heat (or coolant) storage. In
this case, the purge mode can be automatically initiated during
cold nights prior to hot summer days, thereby bringing the require it. Table 8.2d lists the status of each fan, damper, and
building temperature down and storing some free cooling in valve in each of the operating modes. In a computer-opti-
the building structure. mized control system, both the mode selection and the setting
of the actuated devices is done automatically.
Summer/Winter Mode Reevaluation Another important When a smoke or fire condition is detected by sensors
mode selection involves switching from summer to winter S/F-4 or S/F-8 in Figure 8.2e, the fans stop, the OADs and
mode and vice versa. Conventional systems are switched RADs close, the EAD opens, and an alarm is actuated. The
according to the calendar, whereas optimized ones recognize operator can switch the airhandler into its purge mode, so
that there are summer-like days in the winter and winter-like that the fans are started, OAD and EAD are opened, and RAD
hours during summer days. Seasonal mode switching is there- is closed. If the smoke/fire emergency requires, the fire com-
fore totally inadequate. mand panel (FC in Figure 8.2e) can be used by firefighters.
Optimized building operation can be provided only by From this panel, the fire chief can operate all fans and damp-
making the summer/winter selection on an enthalpy basis: If ers as needed for safe and orderly evacuation and protection
heat needs to be added, it is winter; if heat needs to be of the building.
removed, it is summer, regardless of the calendar. In those In another emergency condition, a freezestat switch on
airhandlers that serve a variety of zones, it is essential to first one of the water coils is actuated. These switches are usually
determine if the unit is in a net cooling (summer) or net set at approximately 35F (1.5C) and serve to protect from
heating (winter) mode before the control system can decide coil damage resulting from freeze-ups. Multistage freezestat
if free cooling (or free heating) by outside air can be used to units might operate as follows:
advantage.
Figure 8.2c illustrates the heat balance evaluation that is At 38F (3C): close OAD
required to determine the prevailing overall mode of opera- At 36F (2C): fully open water valve
tion. This type of heat balance calculation, which must be At 35F (1.5C): stop fan
reevaluated every 15 to 30 minutes, can be implemented only
through the use of computers. If single-stage freezestats are used, they will stop the fan,
close the OAD, and activate an alarm.
Emergency Mode In addition to the above operating modes, Yet another type of emergency is signaled by excessive
the airhandler can also be placed in an emergency mode, if pressures in the ductwork on the suction or discharge sides
fire, smoke, freezing temperature, or pressure conditions of the fans, resulting from operation against closed dampers

2006 by Bla Liptk


1510 Control and Optimization of Unit Operations

TABLE 8.2d
The Status of Various Actuated Devices during Various Operating Modes
Operating Mode
or Emergency Supply Return Outside Air Exhaust Air Return Air Coil Control
Condition Fan Fan Damper Damper Damper Valves Alarm

Off C C O C
On On On Modulating
Warm-up On On C C O O(HC)
Cool-down On On C C O O(CC)
Night Cycled to maintain required nighttime temperature
Purge On On O O C Modulating
PSH-2 Off C Yes
PSL-3 Off C Yes
S/F-4 Off Off C O C C Yes
TSL-5 Off C O C Yes
PSL-6 Off C O Yes
PSH-7 Off C O Yes
S/F-8 Off Off C O C C Yes

or from other equipment failures. When this happens, the modulates the supply air fan station to match the demand
associated fan is stopped and an alarm is actuated. (Figure 8.2f). When the PIC-19 output has increased the fan
capacity to its maximum, PSH-19 actuates and starts an addi-
Fan Controls tional fan. Inversely, as the demand for supply air drops, FSL-
15 will stop one fan unit whenever the load can be met by
The standard fan controls are shown in Figure 8.2f. Each fewer fans than the number in operation. The important point
zone shown in Figure 8.2b is supplied with air through a to remember is that in cycling fan stations, fan units are
thermostat-modulated damper, also called a variable air vol- started on pressure and are stopped on flow control. The
ume box (VAV-23). operating cost of such a fan station is 2040% lower than if
The VAV box openings in the various zones determine constant-volume fans with conventional controls were used
the total demand for supply air. The pressure in the supply (Figure 8.2g).
air (SA) distribution header is controlled by PIC-19, which

EA FC FE
PSH RF RA
EAD PSL S/F 14
2 3 4
PIC FC
RF RA XP
EA On 11 PIC
17
O RA 20
FSL Stops PSH D/A
RAD SS Warm-up fan
FC Fire command
FC 14 20 Starts
1 Cool-down panel
Night SP = 90% FFIC fan
6 Purge <
14
Freezestat
TSL
5 PSH S/F
PSL FE SA
OAD 7 8
6 SF
SA 15
CC/ SF
Stops FSL PIC
DA HC
FC fan 15 19
Starts PSH R/A
FIG. 8.2e XP
fan 19
18
The safety and operating mode selection instruments used on an
airhandler. Most abbreviations used on this figure have already been
defined in connection with Figure 8.2b; S/F = smoke and fire detec- FIG. 8.2f
tor, SS = selector switch, FC = fire command panel. Variable-volume fan controls operate as shown here.

2006 by Bla Liptk


8.2 Airhandler and Building Conditioning Controls 1511

110

100

90

80
% Full load fan HP

70 ane
let v
able in
60 Vari

50 Enlarged view of
Energy saving blade seal

e
40

iv
dr
n
fa Pressure
30 eects
d
ee

seal
sp

20
le
iab
r
Va

10

0 10 20 30 40 50 60 70 80 90 100
% Full load
High pressure Low pressure
FIG. 8.2g side side
Using variable-speed fans can save significant amounts of energy.
(Courtesy of Dana Corp.)

FIG. 8.2h
Because the conditioned zones are pressurized slightly, Low-leakage damper designs increase the efficiency of HVAC
some of the conditioned air will leak into the atmosphere, systems.
creating pressurization loss. Being able to control the pres-
3 2
surization loss is one of the advantages of the control system [0.15 (m /min)/m ], because the resulting savings over the life
described in Figure 8.2f. The flow ratio controller FFIC-14 of the buildings will be much greater than the increase in initial
is set at 90%, meaning that the return-air fan station is modu- investment for better dampers (Figure 8.2h).
lated to return 90% of the air supplied to the zones. Therefore,
pressurization loss is controlled at 10%, which corresponds to Dampers and Pressure Distribution In order for dampers
the minimum fresh-air makeup requirement, resulting in a to give good control, a fair amount of pressure drop should
minimum-cost operation. be assigned to them. They should be sized for a P of about
Because the conditioned zones represent a fairly large 10% of the total system drop. On the other hand, excessive
capacity, a change in supply air flow will not immediately damper drops should also be avoided, because they will
result in a need for a corresponding change in the return air increase the operating costs of the fans. A good sizing basis
flow. Thus, PIC-20 (Figure 8.2f) is included in the system to for outside and return air fans is to size them for 1500 fpm
prevent the flow-ratio controller from increasing the return (457 m/min) velocity at maximum flow.
air flow rate faster than required. This dynamic balancing In locations where two air streams are mixed, such as when
eliminates cycling and protects against collapsing the duct- outside and return airs are ratioed (RAD-04 and OAD-05 in
work under excessive vacuum. Closure of the exhaust-air Figure 8.2b), it is important that the damper P be rela-
damper by PIC-11 indicates that the control system is prop- tively constant as the ratio is varied. Figure 8.2i shows that
erly tuned and balanced and is operating at maximum effi- parallel blade dampers give a superior performance in this
ciency. Under such conditions, the outside air admitted into service.
the airhandler exactly matches the pressurization loss, and Figure 8.2j illustrates the pressure levels in the various
no return air is exhausted. portions of typical airhandlers. It can be seen that the kind
To maximize the benefits of such an efficient configuration, of pressure drops that would be required by opposed blade
the dampers must be of tight shut-off design. When exposed dampers (Figure 8.2i) are simply not available. Therefore, if
to a pressure difference of 4 in. H2O (996 Pa), a closed con- such dampers were installed, the airhandler would be starved
2
ventional damper will leak at a rate of approximately 50 cfm/ft for air (the dampers could not pass the design flow) whenever
3 2 2
[15.2 (m /min)/m ]. In the HVAC industry, a 5 cfm/ft [1.52 the ratio was near 50:50 (percent).
3 2
(m /min)/m ] leakage rate is considered to represent a tight Figure 8.2j also shows that in traditional airhandlers more
shut-off design. Actually, it is cost-effective to install tight fan energy is used than necessary. This is because the return
2
shut-off dampers with leakage rates of less than 0.5 cfm/ft air fan is sized to generate the pressure needed to exhaust the

2006 by Bla Liptk


1512 Control and Optimization of Unit Operations

Top 1'' 3'' 3''


EA + + + RF 1''
4 4 4
4
1''
Joint unsupported P =
2
by vertical Traditional
edge stop
1'' Building
P = 1
2 envelope
Air ow Vertical edge stop

Filter Coils 1''


Joint supported
1'' 3'' 1'' SF + 2 2
by vertical 2
edge stop
OA 4 4 1'' 2
Joint unsupported 1''
Top and bottom by vertical P =
2
leaf edges edge stop
deect toward
horizontal 1''
+
edge stop under EA 4 RF 3''
1''
pressure 4 4
Parallel Bottom
1''
damper opposed blade proportioning P =
2
(unirotational damper
louvre) (counterrotational louvre) Alternate
1''
P = Building
2
envelope
Pressure dierential across device,

2.5 Opposed Filter Coils 1''


blades, 1'' 3'' 1'' SF + 2 2
2
8000 SCFM* OA 4 4 1'' 2
2.0
*In 1''
WG = 250 Pa
in. WG *

P =
SCFM = 0.472 slps 2
1.5 Note: 1'' H2O = 250 Pa
Parallel FIG. 8.2j
1.0 blades,
8000 SCFM*
Damper pressure drops and the typical pressure levels in the various
segments of airhandlers.
0.5
0 10 20 30 40 50 60 70 80 90
Damper Outside air damper
opening, Temperature Controls
deg 90 80 70 60 50 40 30 20 10 0
Return air damper
Space temperatures are controlled by thermostats. The tradi-
FIG. 8.2i tional thermostat is a proportional-only controller (see also
When outside and return air dampers are throttled to vary their Section 2.2). The pressure of the output signal from a pneu-
ratio at constant total flow, the required pressure drop varies with matic stat is a near straight-line function of the measure-
damper design (see upper portion of figure). The lower portion of
ment, described by the following relationship:
this figure shows the results of American Warming and Ventilating
Co. tests (per AMCA Standard 500) of pressure drops across parallel- O = Kc(M Mo) + Oo 8.2(2)
2
blade and opposed-blade outside and return air damper sets.
where
O = output signal
air from the building. A consequence of this is that the pres- Kc = proportional sensitivity (Kc can be fixed or adjust-
sure drop of 11/2 in. H2O (375 Pa) across the return air damper able, depending on the design)
is three times greater than what is necessary (1/2 in. H2O, or M = measurement (temperature)
125 Pa). Mo = normal value of measurement, corresponding to
The alternate system shown in the lower portion of the center of the throttling range
Figure 8.2j eliminates this waste of fan energy. Here, only the Oo = normal value of the output signal, corresponding
supply fan (SF) operates continuously, which reduces the pres- to the center of the throttling range of the control
sure drop across the return air damper to 1/2 in. H2O (125 Pa). valve (or damper)
The return fan (RF) is started only when air needs to be
relieved, and its speed is varied to adjust the amount of air to Another term used to describe the sensitivity of thermo-
be exhausted. Relocating RF also removes its heat input, stats is throttling range. As shown in Figure 8.2k, this term
which, in the traditional system, represents an added load on refers to the amount of temperature change that is required
the cooling coil. to change the thermostat output from its minimum to its

2006 by Bla Liptk


8.2 Airhandler and Building Conditioning Controls 1513

Thermostat
output (PSIG)
Cold air Range: 4090F
FC Normal: 72F
13 813 TC PB = 5%
PSIG D/A
Flowsheet representation

Output signal 0
Oset error, which
(PSIG)
is also called
throttling range
15 2F
3 14 Maximum cooling (damper open)
Temperature 13 Normal
(F) Spring 12 condition
Throttling Oo = 10.5 PSIG
range 11
range 10
(5 PSIG) Operating
9 Minimum cooling (damper closed)
8 line
FIG. 8.2k 7
6
Throttling range can be defined as the temperature change required 5 Measurement
to change the thermostat output from its minimum to its maximum 4
3 M (F)
value.
Note: 40 50 60 70 80 90
C = F 32 Mo = 72 F
maximum value, such as from 3 to 13 PSIG (21 to 90 kPa). 1.8
1 PSIG = 6.9 kPa Scale range = 4090 F
The throttling range is usually adjustable from 2 to 10F (1
to 5C). Slope of operating line = Proportional sensitivity = 2.5 PSIG/F =
One important point to remember is that thermostats do Proportional band = 5% = Gain = 20
not have set points, in the sense of having a predetermined FIG. 8.2l
temperature to which they would seek to return the controlled A fixed proportional band thermostat has a fixed throttling range
space. (Integral action must be added in order for a controller and no setpoint.
to be able to return the measured variable to a set point after
a load change.) Mo does not represent a set point; it only
identifies the space temperature that will cause the cooling one value to the other actuates switching devices in the ther-
damper in Figure 8.2l to be 50% open. This can be called a mostat and indexes them from day to night or vice versa.
normal condition, because relative to this point the ther- Supply air mains are often divided into two or more
mostat can both increase and decrease the cooling air flow circuits so that switching can be accomplished in various
rate as space temperature changes. areas of the building at different times. For example, a school
If the cooling load doubles, the damper will need to be building may have separate circuits for classrooms, offices
fully open, which cannot take place until the controlled space and administrative areas, the auditorium, and the gymnasium
temperature has risen to 73F (23C). As long as the cooling and locker rooms. In some of the electric designs, dedicated
load remains that high, the space temperature must also stay clocks and switches are built into each thermostat.
up at the 73F (23C) value. Similarly, the only way this The heatingcooling or summerwinter thermostat can
thermostat can reduce the opening of the cooling damper have its action reversed and, if desired, can have its set point
below 50% is to first allow the space temperature to drop changed by means of indexing. This thermostat is used to
below 72F (23C). Thus, thermostats have throttling ranges, actuate controlled devices, such as valves or dampers, that
not set points. If a throttling range is narrow enough, this gives regulate a heating source at one time and a cooling source at
the appearance that the controller is keeping the variable near another. It is often manually indexed in groups by a switch,
the set point, when in fact the narrow range only allows the or automatically by a thermostat that senses the temperature
variable to drift within limits. of the water supply, the outdoor temperature, or another
suitable variable.
Special-Purpose Thermostats Day-night, set-back, or dual In the heatingcooling design, there are frequently two
room thermostats will operate at different normal temper- bimetallic elements, one being direct acting for the heating
ature values for day and night. They are provided with both mode, the other being reverse acting for the cooling mode.
a day and a night setting dial, and the change from day The mode is switched automatically in response to a change
to night operation can be made automatic for a group of in the air supply pressure, much as the daynight thermostats
thermostats. The pneumatic day-night thermostat uses a two- operate.
pressure air supply system, the two pressures often being 13 The limited control range thermostat usually limits the
and 17 PSIG (89.6 and 177 kPa) or 15 and 20 PSIG (103.35 room temperature in the heating season to a maximum of
and 137.8 kPa). Changing the pressure at a central point from 75F (24C), even if the occupant of the room has set the

2006 by Bla Liptk


1514 Control and Optimization of Unit Operations

thermostat beyond these limits. This is done internally, with- Heating Cooling
out placing a physical stop on the setting knob. load load
A slave or submaster thermostat has its set point raised
Conventional control
or lowered over a predetermined range, in accordance with 100% 100%
ZEB control
variations in the output from a master controller. The master
controller can be a thermostat, manual switch, pressure con- Resulting saving
troller, or similar device. For example, a master thermostat
measuring outdoor air temperature can be used to adjust a
submaster thermostat controlling the water temperature in a 0% 0% Room
55 65 75 85 95 temperature
heating system. Mastersubmaster combinations are some- (F)
ZEB
times designated as single-cascade action. When action is (adjustable)
accomplished by a single thermostat having more than one
measuring element, it is referred to as compensated control. FIG. 8.2m
Multistage thermostats are designed to operate two or Zero energy band (ZEB) control is designed to save energy by not
more final control elements in sequence. using any when the room is comfortable.
A wet-bulb thermostat is often used for humidity control,
as the difference between wet- and dry-bulb temperature is
an indication of moisture content. A wick or other means for Zero Energy Band Control A recent addition to the available
keeping the bulb wet and rapid air motion to ensure a true thermostat choices is the zero energy band design. The idea
wet-bulb measurement are essential. behind ZEB control is to conserve energy by not using any
A dew-point thermostat is a device designed to control when the room is comfortable. As illustrated by Figure 8.2m,
humidity on the basis of dew point temperatures. the conventional thermostat wastes energy by continuing to
A smart thermostat is usually a microprocessor-based use it when the areas temperature is already comfortable.
unit with RTD-type or transistorized solid-state sensor. It is The comfort gap or ZEB on the thermostat is adjustable
usually provided with its own dedicated memory and intel- and can be varied to match the nature of the particular space.
ligence, and it can also be equipped with a communication ZEB control can be accomplished in one of two ways.
link (over a shared data bus) to a central computer. Such units The single set point and single output approach is illustrated
can minimize building operating costs by combining time- on the left side of Figure 8.2n. Here the cooling valve fails
of-day controls with intelligent comfort gap selection and closed and is shown to have an 811 PSIG (5576 kPa) spring
maximized self-heating. range, while the heating valve is selected to fail open and

Dual output
pressure from
thermostat
Output pressure (PSIG)
of single Full heating Full cooling
thermostat
Gain = 0.75 PSI/F 13
(PSIG)
12
Cooling valve open 11
11
10
10
9 Zero
9
Cooling valve closed 8 energy
8 band
7
7
6 Heating 6
valve closed 5
5
4 Heating 4
valve
3 3
open
2 2 Heat Cooling
1 o o
1
Space
0 Space 0
67 71 75 79 64 66 68 70 72 74 76 78 80 82 temperature
temperature
Heat ZEB Cool F
F Dual set point system
Single set point splitrange system

FIG. 8.2n
ZEB control schemes include the single setpoint split range approach (shown on left) and the dual set point approach (shown on right).

2006 by Bla Liptk


8.2 Airhandler and Building Conditioning Controls 1515

has a 25 PSIG (1434 kPa) range. Therefore, between 5 and Air


BT
8 PSIG (34 and 55 kPa), both valves are closed; no pay energy U/l
bm
is expended while the thermostat output is within this range.
40
The throttling range is usually adjustable from 5 to 25F (3 Interior
(summer)
to 13C). Thus, if the ZEB is 30% of the throttling range, it
can be varied from a gap size of 1.5F (0.85C) to 7.5F 30
(4.2C) by changing the throttling range (or gain). Perimeter 60% RH
Although the split-range approach is a little less expen- (winter)
sive than the dual set-point scheme (shown on the right of 20
Figure 8.2n), it is also less flexible and more restrictive.
The two basic limitations of the split-range approach are:
1) The gap width can be adjusted only by also changing 30% RH
the thermostat gain; maximum gap width is limited by the 68F 78F
Return air enthalpy line in cooling mode
minimum gain setting of the unit. 2) The heating valve corresponding to 33 BTU/lb
must fail open, which is undesirable in terms of energy Return air enthalpy line in heating mode
conservation. corresponding to 21 BTU/lb
These limitations are removed when a dual set point, dual Note: BTU/lbm = 0.555 Kcal/Kg
output thermostat is used. Here both valves can fail closed,
and the bandwidth and the thermostat gain are independently FIG. 8.2o
The building can be made self-heating, because the return air can
adjustable. The gains of the heating and cooling thermostats
transport about 10 BTU/lbm to the perimeter spaces, which in the
are also independently adjustable. In Figure 8.2n, the heating winter, because of the windows, do require heat.
thermostat is reverse-acting and the cooling thermostat is
direct-acting.
The most recent advances in thermostat technology are
the microprocessor-based units. These are programmable
devices with memory capability. They can be monitored and ual zone thermostats. As such, it can be implemented by all
reset by central computers, using telephone wires or other levels of automation, but the flexibility and ease of adjustment
communication links. Microprocessor-based units can be of the computerized systems make them superior in those
supplied by continuously recharged backup batteries and applications in which the gap limits of the various zones are
accurate room temperature sensors. They can also operate likely to change frequently.
without a host computer (in stand-alone mode). In this case, Figure 8.2a illustrates the concept of comfort envelopes. Any
the user manually programs the thermostat to maintain var- combination of temperature and humidity conditions within
ious room temperatures as a function of the time of day and such envelopes is considered to be comfortable. Therefore, as
other considerations. long as the space conditions fall within this envelope, there is
no need to spend money or energy to change those conditions.
This comfort gap is also referred to as zero energy band, mean-
Gap Control and the Self-Heating Building The winter and ing that if the space is within this band, no pay energy of any
summer enthalpy settings of a building are illustrated in type will be used. This concept is very cost-effective.
Figure 8.2o. The concept of gap control is simple: When When a zone of the airhandler in Figure 8.1b is within
comfort level in a zone is somewhere between acceptable the comfort gap, its reheat coil is turned off and its VAV box
limits, the use of pay energy is no longer justified. Allowing is closed to the minimum flow required for air refreshment.
the zones to float between limits instead of maintaining them When all the zones are inside the ZEB, the HW, CHW, and
at arbitrarily fixed conditions can substantially reduce the STM supplies to the airhandler are all closed and the fan is
operating cost of the building. operated at minimum flow. When all other airhandlers are
The savings come from two sources. First, there is a direct also within the ZEB, the pumping stations, chillers, cooling
trade-off between the selected acceptable limits of discomfort towers, and HW generators are also turned off.
and the yearly total of required degree days of heating and With larger buildings that have interior spaces that are heat-
cooling. Second, there is the added side benefit that the build- generating even in the winter, ZEB control can make the build-
ing becomes self-heating during winter conditions. This ing self-heating. Optimized control systems in operation today
occurs because during winter conditions, gap control auto- are transferring the interior heat to the perimeter without
matically transfers the heat generated in the inside of the requiring any pay heat until the outside temperature drops
building to the perimeter areas, where heating is needed. This below 10 to 20F (2.3 to 6.8C). In regions in which winter
can result in long periods of building operation without the temperature does not drop below 10F (2.3C), ZEB control
use of any pay energy. can eliminate the need for pay heat altogether. In regions far-
Gap control can be looked upon as an override mode of ther north, ZEB control can lower the yearly heating fuel bill
control that is superimposed on the operation of the individ- by 3050%.

2006 by Bla Liptk


1516 Control and Optimization of Unit Operations

Economizer signal started by opening TCV-02. In such split-range systems, the


Minimum outside for free cooling from Optimized possibility of simultaneous heating and cooling is eliminated.
air signal EL in Figure 8.2v temperature
setpoint
Also eliminated are interactions and cycling.
SP
Figure 8.2p also shows some important overrides. TIC-
Free cooling 12, for example, limits the allowable opening of OAD-05, so
> TIC
07 that the mixed-air temperature will never be allowed to drop
Humidity to the freezing point and permit freeze-up of the water coils.
control
signal The minimum outdoor air requirement signal guarantees
> received that the outside air flow will not be allowed to drop below
from RHIC-10 in
Figure 8.2q this limit.
TCV TCV The economizer signal allows the output signal of TIC-
01 02 07 to open OAD-05 only when free cooling is available.
>
(A potential for free cooling exists when the enthalpy of the
HW CHW outdoor air is below that of the return air.)
RA FO FC
OAD TIC 36 # 1215 # Finally, the humidity controls will override the TIC-07
05 12 (0.20.4 bar) (0.81.0 bar) signal to TCV-02 when the need for dehumidification
OA H C SF requires that the supply air temperature be lowered below the
SA
C C set point of TIC-07.
FC
711 #
(0.480.76 bar) Humidity Controls

Pay heat Free cooling Pay cooling Humidity in the zones is controlled according to the moisture
O C C O C O
TCV01 OAD05 TCV02 content of the combined return air (see Figure 8.2q). The
0.2 0.28 0.35 0.40 0.48 0.55 0.60 0.69 0.76 0.80 0.90 0.97 1.0 bar

3 4 5 6 7 8 9 10 11 12 13 14 15 PSIG Temperature
Output signal from TIC07 control RA
signal from
FIG. 8.2p TIC-07 in Figure 8.2 p Non-linear RHIC
Illustration of a fully coordinated, pneumatic, split-range tempera- gap control 10
D/A
(3050% RH)
ture control system. Such controls can reduce the yearly operating
8
costs by more than 10%. TDIC > >
07
Supply Air Temperature Control A substantial source of
inefficiency in conventional HVAC control systems is the TCV RHCV
02 16
uncoordinated arrangement of temperature controllers. Two CHW
or three separate temperature control loops in series are not FC
Note
uncommon. For example, one of these uncoordinated con- 1215 PSIG RP
#2
(0.81.0 bar) STM SP = 90% RH
trollers may be used to control the mixed air temperature, FC RHIC
another to maintain supply (SA) temperature, and a third to 21 D/A
control the zone-reheat coil. Such practice can result in simul- # C # H SF
taneous heating and cooling and, therefore, in unnecessary SA
2 C 1
waste. Using a fully coordinated split-range temperature con-
trol system, such as that shown in Figure 8.2p, will reduce
yearly operating costs by more than 10%. Note #1
In this control system, the SA temperature set point (set by
the temperature controller, TIC-07) is continuously modulated FIG. 8.2q
to follow the load. The methods of finding the correct set point Humidity is controlled in the combined return air. Note 1: When the
will be discussed under Optimizing Strategies. The loop auto- need for dehumidification (in the summer) overcools the supply air
matically controls all heating or cooling modes. When the TIC- and therefore increases the need for reheat at the zones, this pump-
07 output signal is low 36 PSIG (20.741.3 kPa) heating around economizer loop is started. TDIC-07 will control the pump
is done by TCV-01. As the output signal reaches 6 PSIG to pump around only as much heat as is needed. Note 2: This
(41.3 kPa), heating is terminated; if free cooling is available, reversing positioner functions as follows:
it is initiated at 7 PSIG (48.2 kPa). When the output signal Input from Output to
reaches 11 PSIG (75.8 kPa) the point at which OAD-05 is RHIC-10 RHCV-16
fully open the cooling potential represented by free cooling 3 PSIG = 0% 100% (open)
is exhausted, and at 12 PISG (82.7 kPa), pay cooling is 9 PSIG = 50% 0% (closed)

2006 by Bla Liptk


8.2 Airhandler and Building Conditioning Controls 1517

process controlled by RHIC-10 is slow and contains large Temperature control


dead-time and transport-lag elements. In other words, a signal from TIC-07
change in the SA humidity will not be detected by RHIC-10 in Figure 8.2 p RA
until some minutes later. During the winter, it is possible for
RHT
RHIC-10 to demand more and more humidification. To pre- Note
vent possible saturation of the supply air, the RHIC-10 output Vent #1
signal is limited by RHIC-21. In this way, the moisture con- EL TT
tent of the supply air is never allowed to exceed 90% RH. Free FE FY +
For best operating efficiency, a nonlinear controller with cooling 13 05
RHT TT
a neutral band is used at RHIC-10. This neutral band can FE SA
be set to a range of humidity levels say, between 30% OA SF
15
and 50% RH. If the RA is within these limits, the output OAD
of RHIC-10 is at 50%, and neither humidification nor dehu- 05 TIC
midification is demanded. This arrangement can lower the 12
<
cost of humidity control during the spring and fall by
approximately 20%.
The same controller (RHIC-10) controls both humidifi- FIC SP = 10%
>
cation (through the relative humidity control valve, RHCV- 05
16) and dehumidification (through the temperature control
valve, TCV-02) on a split-range basis. As the output signal FIG. 8.2r
increases, the humidifier valve closes, between 3 and 9 PSIG Outside air control loops provide fresh air or free cooling. Note:
(20.7 and 62 kPa). At 9 PSIG (62 kPa), RHCV-16 closes and The enthalpy logic unit (EL) compares the enthalpies of the outside
and return airs and vents its output signal if free cooling is available.
remains so, as the output signal increases to 12 PSIG
Therefore, the economizer cycle is initiated whenever Hoa < Hra.
(82.7 kPa). At this condition, TCV-02 starts to open.
Dehumidification is accomplished by cooling through
TCV-02. This chilled water valve is controlled by humidity of people in the building or of the airs carbon dioxide content.
(RHIC-10) or temperature (TIC-07). The controller that In most conventional systems, the minimum outdoor air is
requires more cooling will be the one allowed to throttle provided by keeping 10% of the area of the outdoor air damper
TCV-02. always open when the building is occupied.
Subcooling the air to remove moisture can substantially This method is inaccurate, because a constant damper
increase operating costs if this energy is not recovered. The opening does not result in a constant air flow. This flow varies
dual penalty incurred for overcooling for dehumidification with fan load, because changes in load will change the fans
purposes is the high chilled water cost and the possible need suction pressure and will therefore alter the P across the
for reheat at the zone level. The savings from a pump-around damper. This conventional design results in waste of air-
economizer can eliminate 80% of this waste. In this loop, conditioning energy at high loads and insufficient air refresh-
whenever TDIC-07 detects that the chilled water valve (TCV- ment at low loads.
02) is open more than would be necessary to satisfy TIC-07, The control system depicted in Figure 8.2r reduces oper-
the pump-around economizer is started. This loop in coil #1 ating costs while maintaining a constant minimum rate of air
reheats the dehumidified supply air, using the heat that the refreshment, which is unaffected by fan loading. Direct mea-
pump-around loop removed from the outside air in coil #2 surement of outdoor airflow is usually not possible because of
before it entered the main cooling coil. space limitations. For this reason, Figure 8.2r shows the
In this way, the chilled-water demand is reduced in the outdoor air flow as being determined as the difference
cooling coil (TCV-02), and the need for reheating at the zones between FE-15 and FE-13. FIC-05 controls the required min-
is eliminated. Although Figure 8.2q shows a modulating con- imum outdoor airflow by throttling OAD-05.
troller setting the speed of a circulating pump, it is also pos-
sible to use a constant-speed pump operated by a gap switch.
CO2-Based Ventilation In conventional installations the
amount of outdoor air admitted is usually based on one of the
Outdoor Air Controls following criteria:
Outdoor air is admitted to satisfy the requirements for fresh 2 2
air or to provide free cooling. Both control loops are shown 0.10.25 cfm/ft (3076 lpm/m ) of floor area
in Figure 8.2r. 1025% of total air supply rates
The minimum requirement for fresh outdoor air while the About 5 cfm (25 lps) volumetric rate per person
building is occupied is usually 10% of the airhandlers capac-
ity. In most advanced control systems, this value is not con- These criteria all originated at a time when energy con-
trolled as a fixed percentage but as a function of the number servation was no serious consideration; therefore, their aim

2006 by Bla Liptk


1518 Control and Optimization of Unit Operations

was to provide simple, easily enforceable rules that will guar-


antee that the outdoor air intake always exceeds the required
minimum. Today the goal of such systems is just the opposite:
It is to make sure that air quality is guaranteed at minimum Zone
#1
cost. As the floor does not need oxygenonly people do 33 BTU/lb (minimum OA)
some of the above rules make little sense. (18 Cal/Kg) Sum
mer
There is a direct relationship between savings in building RA (78F at 60% RH)
operating costs and reduction in outdoor air admitted into the
4
building. According to one study in the United States, infil-
tration of outdoor air accounted for 55% of the total heating
5
load and 42% of the total cooling load. Another survey Zone Zone
showed that 75% of fuel oil consumed in New York City Zone #2A #2B #3
schools was devoted to heating ventilated air. Because build- (OA throttled for cooling) (Max. OA) (OA throttled for drying)
ing conditioning accounts for nearly 20% of all the energy
6
consumed in the U.S., optimized admission of outdoor air
Cold deck
can make a major contribution to reducing our national temperature
energy budget. This goal can be well served by CO2-based set point 78 degrees F
ventilation controls. Note: 1.0 BTU/lbm = 0.55 Cal/Kg
The purpose of ventilation is not to meet some arbitrary
FIG. 8.2s
criteria, but to maintain a certain air quality in the conditioned Free cooling and drying can often be obtained in the summer,
space. Smoke, odors, and other air contaminant parameters depending on the zone where the outside air falls relative to the
7
can all be correlated to the CO2 content of the return air. return air.
This then becomes a powerful tool of optimization, because
the amount of outdoor air required for ventilation purposes
can be determined on the basis of CO2 measurement, and the
time of admitting this air can be selected so that the air air, they disregard all the other possibilities of using the out-
addition will also be energy efficient. With this technique, door air to advantage.
health and energy considerations will no longer be in conflict, Advanced, microprocessor-based economizers overcome
but will complement each other. both of these limitations. They use accurate sensors and the
CO2-based ventilation controls can easily be integrated psychrometric chart to evaluate all potential uses of outside
with the economizer cycle and can be implemented by use air, not only free cooling. Figure 8.2s illustrates the various
of conventional or computerized control systems. Because zones of operation, based on the relative conditions of the
the rate of CO2 generation by a sedentary adult is 0.75 cfh outside and return airs.
(27 lph), control by CO2 concentration will automatically If the enthalpy of the outside air falls in zone 1 (that is,
8
reflect the level of building occupancy. Energy savings of if its BTU content exceeds 33), no free cooling is available;
9
40% have been reported by converting conventional venti- therefore, the use of outside air should be minimized in the
lation systems to intermittent CO2-based operation. summer. In the winter or fall, it is possible that the enthalpy
of the outside air on sunny afternoons will exceed the return
air enthalpy, which in the winter is about 21 BTU/lbm
Economizer Cycles The full use of free cooling can reduce (11.6 cal/kg). Under such conditions, free heating can be
the yearly air-conditioning load by more than 10%. The enthalpy obtained by admitting the outside air in zone 1.
logic unit (EL) in Figure 8.2r will allow the temperature- If the condition of OA corresponds to zone 2 (BTU < 33
controller signal (TIC-07 in Figure 8.2p) to operate the outdoor and temperature < 78F), free cooling is available. If the
air damper whenever free cooling is available. This economizer condition of OA corresponds to zone 3 (BTU < 33 and
cycle is therefore activated whenever the enthalpy of the outdoor temperature > 78F), free dehumidifying (latent cooling) is
air is below that of the return air. available.
Free cooling can also be used to advantage while the When there are both cold and hot air ducts in the building
building is unoccupied. Purging the building with cool out- (dual duct system), the control system in zone 2 will function
door air during the early morning results in cooling capacity differently depending on whether the outside air temperature
being stored in the building structure, reducing the daytime is above or below the cold deck temperature. If it is above
cooling load. that temperature (zone 2B), maximum (100%) outside air can
The conventional economizers such as the one shown be used; if it is below that temperature (zone 2A), the use of
in Figure 8.2r are rather limited devices for two reasons. outside air needs to be modulated or time-proportioned.
First, they determine the enthalpy of the outdoor and return Therefore, in zone 2A, where the outside air is cooler
air streams, using somewhat inaccurate sensors. Secondly, than the cold deck temperature, free cooling is available, but
although they consider the free cooling potential of the outside only some of the total potential can be used. The OA damper

2006 by Bla Liptk


8.2 Airhandler and Building Conditioning Controls 1519

See
Figure SP = 10% SP = 68F (20C)
SP Least open TCV From
8.2 p TIC TC R/A
VPC < other
07 07 Note #1 zones 22
D/A

FB VPA VPS
FB to VPC 07 07

TCV
SP = 90% 22
TT Set point Most-open TCV From
to TIC on VPC > other HWS
07 22 Note #1 FC
HWS zones
D/A
FB R SA
SF H
At xed C
VAV minimum
To other 23 opening
zones Typical zone

FIG. 8.2t
Optimization of air and water temperatures during heating (winter) mode of airhandler operation is designed to distribute the heat load
efficiently between the main heating coil and the zone reheat coils. Note: Valve position controllers (VPCs) are provided with integral action
only for stable floating control. The integral time is set to be 10 times the integral time of the associated TIC. External feedback is provided
to eliminate reset wind-up when VPC output is overruled by the setpoint limit on TIC-07.

therefore must be either positioned or cycled to admit enough Temperature Optimization in the Winter
cold outside air to lower the mixed air temperature to equal
the cold deck temperature set point. This way the need for In the winter, the goal of optimization is to distribute the heat
pay cooling is eliminated. load between the main heating coil (HC in Figure 8.2p) and
When the outside air is in zone 3 (hot but dry), the control the zone reheat coils (RHC in Figure 8.2t) most efficiently.
system should admit some of it to reduce the overall need The highest efficiency is obtained if the SA temperature is high
for latent cooling. The amount of outside air admitted under enough to meet the load of the zone when the zone load is
these conditions should be controlled so that the resulting minimum. In this way, the zone reheat coils are used only to
mixed-air dew point temperature will equal the desired cold provide the difference between the loads of the various zones,
deck dew point. This method takes full advantage of the free whereas the base load is continuously followed by TIC-07.
drying potential of the outside air. In Figure 8.2t the set point of TIC-07 is adjusted to keep
As can be seen from the above, the use of the economizer the least-open TCV-22 only about 10% open. First, the least-
cycles is similar to opening the windows in a room to achieve open TCV-22 is identified and its opening (in the valve posi-
maximum comfort with minimum use of pay energy. tion controller, VCP-07) is compared with the desired goal
of 10%. If the valve opening is more than 10%, the TIC-07
set point is increased; if less, the set point is lowered. Stable
operation is obtained by making VPC-07 an integral-only
OPTIMIZING STRATEGIES controller with an external feedback to prevent reset wind-up.
In Figure 8.2t it is assumed that the hot water supply
The main goal of airhandler optimization is to match the (HWS) temperature is independently adjustable and will be
demand for conditioned air with a continuous, flexible, and modulated by VPC-22 so that the most-open TCV-22 will
efficient supply. This requires the floating of both air pressures always be 90% open. The advantages of optimizing the HWS
and temperatures to minimize operating costs while following temperature include:
the changing load.
In traditional HVAC control systems, the set point of TIC- Minimizing heat-pump operating costs by minimizing
07 in Figure 8.2p is set manually and is held as a constant. HWS temperature
This practice is undesirable, because for each particular load Reducing pumping costs by opening all TCV-22
distribution, the optimum SA temperature is different. If the valves in the system
manual setting is less than that temperature, some zones will Eliminating unstable (cycling) valve operation, which
become uncontrollable. If it is more than optimum, operating occurs in the nearly closed position, by opening all
energy will be wasted. TCV-22 valves

2006 by Bla Liptk


1520 Control and Optimization of Unit Operations

In Figure 8.2t, a valve position alarm (VPA-07) is also loop, as long as the most-open valve is less than 90% open,
provided to alert the operator if this heating control system the SA temperature is set to keep the least open TCV-22 at
is incapable of keeping the openings of all TCV-22 valves 10% open (zone A). When the most-open valve reaches 90%
between the limits of 10% and 90%. Such alarms will occur open, control of the least-open valve is abandoned and the
if the VPCs can no longer change the TIC set point(s), loop is dedicated to keeping the most-open TCV-22 from
because their maximum (or minimum) limits have been becoming fully open (zone B). This, therefore, is a classic
reached. This condition will occur only if the load distribution case of herding control, in which a single constraint envelope
was not correctly estimated during design or if the mechan- herds all TCV openings to within an acceptable band and,
ical equipment was not correctly sized. thereby, accomplishes efficient load following.
If the HWS temperature cannot be modulated to keep the
most-open TCV-22 from opening to more than 90%, then the
control loop depicted in Figure 8.2u should be used. In this Temperature Optimization in the Summer

In the cooling mode during the summer, the SA temperature


is modulated to keep the most-open variable volume box
SP = 68F (20C) (VAV-23) from fully opening. Once a control element is fully
Set point to TC open, it can no longer control; therefore, the occurrence of
TIC on HWS FB 22
See such a state must be prevented. On the other hand, it is
Least- R/A
Figure generally desirable to open throttling devices such as VAV
8.2 p SP open TCV From
TIC VPC < other boxes to accomplish the following goals:
07 Note 07 D/A zones
#1 SP
1. Reduce the total friction drop in the system
VPA VPS 2. Eliminate cycling and unstable operation (which is
07 07
more likely to occur when the VAV box is nearly
FB to Y
X From closed)
VPC-07
f (x) > other 3. Allow the airhandler to meet the load at the highest
To Most-open zones
other TCV possible supply air temperature
TCV
TT zones 22
07 At xed VAV HWS This statement does not apply if air transportation costs
minimum 23 FC
exceed cooling costs (for example, undersized ducts, ineffi-
opening R SA
SF H cient fans). In this case, the goal of optimization is to trans-
C port the minimum quantity of air. The amount of air required
to meet a cooling load will be minimized if the cooling
Typical zone
capacity of each unit of air is maximized. Therefore, if fan
operating cost is the optimization criterion, the SA tempera-
%Y = SP
(least open TCV) ture is to be kept at its achievable minimum, instead of being
controlled as in Figure 8.2v.
Zone A Zone B
If the added feature of automatic switchover between
10 winter and summer modes is desired, the control system
depicted in Figure 8.2w should be used.
5 When all zones require heating, this control loop will
behave exactly as does the one shown in Figure 8.2u; when
%X
all zones require cooling, it will operate as does the system
0
25 50 75 100 (Most-open shown in Figure 8.2v. In addition, this control system will
TCV) operate automatically with maximum energy efficiency during
5
the transitional periods of fall and spring. This high efficiency
is a result of the exploitation of the self-heating effect.
10
If some zones require heating (perimeter offices) and
others require cooling (interior spaces), the airhandler will
FIG. 8.2u automatically transfer this free heat from the interior to the
This alternative method of air supply temperature optimization in
perimeter zones by intermixing the return air from the various
the winter should be used when the HWS temperature cannot be
modulated. Note: Valve position controllers (VPCs) are provided
zones and moving it through the 10 zero energy band
with integral action only for stable floating control. The integral (between the settings of TC-22 and TC-23. When the zone
time is set to be 10 times the integral time of the associated TIC-07. temperatures are within this comfort gap of 68F (20C) to
External feedback is provided to eliminate reset wind-up when 78F (26C), no pay energy is used and the airhandler is in
TICVPC-07 output is overruled by the set-point limit on TIC-07. its self-heating, or free-heating, mode. This is an effective

2006 by Bla Liptk


8.2 Airhandler and Building Conditioning Controls 1521

See means of reducing operating costs in buildings. The savings


Figure can amount to more than 30% during the transitional seasons.
8.2 p TIC SP When the temperature in one of the zones reaches 78F
07 (26C), the air supply temperature set point will be lowered
by DPC-23 and the air-side controls will be automatically
FB to switched to cooling (as depicted in Figure 8.2v). If, at the
To Typical zone
DPC-23
other same time, some other zone temperatures drop below 68F
TT zones O (20C), requiring heating, their heat demand will have to be
07 VAV met by the heat input of the zone-reheat coils only. This mode
23 of operation is highly inefficient because of the simultaneous
FO R
SA
SF H cooling and reheating of the air.
From C
other Fortunately, this combination of conditions is highly
zones unlikely, because under proper design practices, the zones
Most-
open
served by the same airhandler should display similar load char-
FB DPC VAV acteristics. The advantage of the control loop in Figure 8.2w is
<
23 that it can automatically handle any load or load combination,
SP = 90% RA including this unlikely, extreme case.
note #1 TC
D/A 23
SP = 78F (25.6C)
AutoBalancing of Buildings

In computerized building control systems, the optimization


FIG. 8.2v
This method of air supply temperature optimization in summer
potentials are greater than those that have been discussed up
(cooling mode) should be used if fan operating costs are less than to this point. When all zone conditions are detected and
cooling costs. Note: The damper position controller (DPC) has controlled by the computer, it can optimize not only the
integral action only, with its setting being 10 times the integral time normal operation but also the start-up of the building.
of TIC-07. External feedback is provided to eliminate reset wind-up. The optimization of airhandler fans is directed at two
goals simultaneously. The first goal is to find the optimum
value for the set point of the supply air pressure controller
SP = 68F (20C) (PIC-19 in Figure 8.2f). Generally, the supply air pressure is
Set point to TC at an optimum value when it is at the lowest possible value,
TIC on HWS FB 22 while all loads are satisfied. As the supply pressure is low-
Least R/A
open TCV From ered, the fan operating cost is reduced, but with lowered
< VPC < other
07 D/A
supply pressures the VAV boxes serving the individual zones
zones
See SP (VAV-23 in Figure 8.2b) will have to open up so that the
Figure SP airflow to the zones will not be reduced. Therefore, the opti-
8.2 p TIC VPA VPS mum setting for PIC-19 is that pressure at which the most
07 07 07 open VAV box is nearly 100% open, while all other VAV
Y From boxes are less than 100% open.
FB X
f (x) < other TCV
Most-open 22
The second goal of optimization is to automatically rebal-
zones
TCV ance the air distribution in the building as the load changes.
TT HWS
07 VAV
If the VAV boxes (VAV-23 in Figure 8.2b) are not pressure
FC
23 FO R
independent (are not able to maintain constant air flow when
SA
SF H the supply pressure changes), manual rebalancing is required
From
C every time the load distribution changes. Naturally this is a
To
other very labor-demanding and inefficient operation. The optimi-
other Typical zone
zones zones zation strategy described below serves the multiple purposes
Most- of automatic rebalancing and finding the optimum set points
FB open VAV for the supply air pressure and temperature.
DPC <
23 Figure 8.2x illustrates an airhandler that is serving several
SP = 90%, D/A R/A zones. The abbreviations used in that figure and in the algo-
note in Figure 8.2v TC rithm tables that follow are listed below:
23
SP = 78F (25.6C)
AI-1 to AI-N: Analog inputs (zone temperatures)
FIG. 8.2w AI-AT: Analog input (air supply temperatures)
This control system optimizes the water and air temperatures in AI-RT: Analog input (return air temperature)
both summer and winter. See also Figures 8.2u and 8.2v. AO-1 to AO-N: Analog output (zone VAV opening)

2006 by Bla Liptk


1522 Control and Optimization of Unit Operations

EA Start-Up Algorithm
RA
All VAV boxes are set to their minimum openings required
Return TT for ventilation purposes (XMIN), such as 25%. Therefore, at
air fan
the time of start-up, AO-1 through AO-N are all set for 25%.
SP
RA PIC is set to mid-scale; therefore, the start-up value of its
AI-RT SP = 50%. TIC is set for (TL + 25)F in the heating mode and
AO-1 for (TH - 25)F in the cooling mode.
PIC
Zone 1 After 5 min of operation, the zone temperatures are
Coils PT AI1 detected (ZT5-1, ZT5-2, and so on), and after 10 min of
SA operation they are detected again (ZT10-1, ZT10-2, and so
OA
ZT on). At the end of the first 10 min of operation, the supply air
VAV-1
Supply 1 temperature is also measured as AT10 and the return air tem-
TT
air fan SP AO-2 perature as RT10.
Zone 2 Once the above readings are obtained, they are entered
AI2 into a table such as Table 8.2y, which serves as the basis for
determining the required start-up openings of each of the
TIC ZT
VAV-2 VAV boxes (XSET-1, XSET-2, and so on). The purpose of
2
this table is to select the initial opening for each VAV box
AIAT
in a logical manner. Therefore, if the zone temperature after
10 minutes of operation is already within 5F of reaching
the comfort zone, the VAV box can be left at its minimum
opening.
AO-N If comfort is not yet within 5F, a higher opening is
Zone N needed. The initial VAV opening is increased on the basis of
AIN the zones performance during the previous 5 minutes. The
larger the temperature change experienced by the zone during
ZT the previous 5 minutes, the sooner it will reach the comfort
VAV-N
N
zone and therefore the smaller the opening that is required.
By this logic, the VAV boxes on those zones that are furthest
FIG. 8.2x from comfort and that are moving most slowly toward comfort
Airhandler optimization and auto-balancing can be handled effi-
will be given the highest openings.
ciently by computer.

Normal Algorithm for VAV Throttling


AT: Supply air temperature
EA: Exhaust air The initial VAV opening for each zone (XSET), which is
OA: Outside air determined by the methods above, is then used as the max-
PIC: Pressure controller (supply air) imum limit on the VAV opening (XMAX) during the first 5
PT: Pressure transmitter minutes of normal operation. The value of XMAX is reeval-
RA: Return air uated every 5 minutes, as shown in Table 8.2z. The logic here
RT: Return air temperature is to increase the maximum limit on VAV opening (XMAX)
SA: Supply air to any zone in which the VAV has been open on its maximum
SP: Set point limit for 5 minutes. Similarly, this logic will lower the XMAX
TH: Upper limit of comfort zone (Figure 8.2a) (maximum limit if the VAV damper was at its XMIN during the previous
allowable zone temperature) 5 minutes. If a VAV damper has been throttled somewhere
TIC: Temperature controller (air supply) in between these two limits (XMAX and XMIN), its limit
TL: Lower limit of comfort zone (Figure 8.2a) (minimum will not be altered. The change increment of 10% shown in
allowable zone temperature) Table 8.2z is adjustable for maximum flexibility.
VAV-1 to VAV-N: Variable air volume boxes The algorithm described above and illustrated in Table 8.2z
ZT-1 to ZT-N: Zone temperatures guarantees that changes in load distribution will not result in
ZT5-1 to ZT5-N: ZT 5 min after start-up starving some zones; the building will be automatically rebal-
ZT10-1 to ZT10-N: ZT 10 minutes after start-up anced in an orderly manner. The value of XMAX from
XMIN: Minimum VAV opening required for ventilation Table 8.2z and the permanent values of XMIN, determined by
XSET-1 to XSET-N: Initial VAV opening after start-up ventilation requirements, are used to reevaluate the individual
XMAX-1 to XMAX-N: Maximum limit on VAV opening VAV openings every 2 minutes, as described by the algorithm
during normal operation in Table 8.2aa.

2006 by Bla Liptk


8.2 Airhandler and Building Conditioning Controls 1523

TABLE 8.2y
Algorithm to Determine Start-Up Openings of Individual VAV Boxes (XSET)
Input Conditions Output

Approach between Zone Amount of Temperature Change Initial Value of XSET to be


Operating Mode and Supply Temperatures During Last 5 Minutes of Start-Up Used for AO-1 to AO-N (%)

(ZT10 ZT5) < 0.5F 100


(ZT10 ZT5) 0.51F 90
(ZT10 ZT5) 11.5F 80
Heating (AT > RT) (TL ZT10) > 5F (ZT10 ZT5) 1.52F 70
(ZT10 ZT5) 23F 60
(ZT10 ZT5) 34F 50
(ZT10 ZT5) 45F 40
(ZT10 ZT5) > 5F 30
(TL ZT10) < 5F Disregard 25
(ZT5 ZT10) < 0.5F 100
(ZT5 ZT10) 0.51F 90
(ZT5 ZT10) 11.5F 80
Cooling (AT < RT) (ZT10 - TH) > 5F (ZT5 ZT10) 1.52F 70
(ZT5 ZT10) 23F 60
(ZT5 ZT10) 34F 50
(ZT5 ZT10) 45F 40
(ZT5 ZT10) > 5F 30
(ZT10 - TH) < 5F Disregard 25

Note: C = ( F 32)/1.8.

The main optimizing and auto-balancing feature of this air transportation and conditioning. These two cost factors
algorithm is that whenever a zone is inside the comfort gap, tend to change in opposite directions; minimizing the cost of
its VAV opening is reduced to XMIN. This reduces the load one will increase the cost of the other. Therefore, it is impor-
on the fans and also provides more air to the zones experi- tant to monitor both the transportation and the conditioning
encing the highest loads. costs continuously and to minimize the larger one when
optimizing the system. Computerized control systems allow
Optimization of Air Supply Pressure and Temperature these costs to be readily calculated on the basis of utility
costs and quantities.
Optimization means that the load is met at minimum cost.
The cost of operating an airhandler is the sum of the cost of
TABLE 8.2aa
Algorithm to Determine Analog Outputs, Setting the Openings of
TABLE 8.2z VAV Boxes
Reevaluation of Value of XMAX
Output
Input Conditions Output Input Conditions
Required VAV
Has VAV been Has VAV been Incremental Change Operating Opening: AO-1 to
Continuously Open Continuously Throttled to in Value of XMAX Mode Control Criteria AO-N is to be Equal
to its XMAX During its XMIN During the Last at the End of
Last 5 Minutes? 5 Minutes? 5-Minute Period Heating ZT < (TL 1) XMAX
(AT > ZT) (TL 1) < ZT < (TL + 1) No change
Yes Yes Leave XMAX =
XMIN ZT > (TL + 1) XMIN
No Increase by 10% Cooling ZT > (TH + 1) XMAX
(AT < ZT) (TH 1) < ZT < (TH + 1) No change
No Yes Decrease by 10%
No Leave as is ZT < (TH 1) XMIN

2006 by Bla Liptk


1524 Control and Optimization of Unit Operations

TABLE 8.2bb
Optimization of Supply Air Pressure and Temperature, When Fan Costs Exceed Conditioning Costs (Frequency = 5
min)
Incremental Ramp Adjustment in
the Set Points of

VAV Status Airhandler Mode Is TIC SP at Its Limit? TIC PIC

None at 100% for 15 Heating (AT > RT) Yes, at max. 2F N.C.* (at min.)
minutes continuously No 1F N.C. (at min.)
Cooling (AT < RT) Yes, at min. + 2F N.C. (at min.)
No + 1F N.C. (at min.)
Not more than one at Heating (AT > RT) Yes, at max. N.C. (at max.) N.C.
100% for more than No N.C. N.C.
30 minutes continuously
Cooling (AT < RT) Yes, at min. N.C. (at max.) N.C.
No N.C. N.C.
More than one at 100% Heating (AT > RT) Yes, at max. (at max.) + 0.25 in. H2O
for more than 30 minutes No + 1F N.C.
continuously
Cooling (AT < RT) Yes, at min. (at min.) + 0.25 in. H2O
No 1F N.C.
More than one at 100% for Heating (AT > RT) Yes, at max. (at max.) + 0.5 in. H2O
more than 60 minutes No + 2F N.C.
continuously
Cooling (AT < RT) Yes, at min. (at min.) + 0.5 in. H2O
No 2F N.C.

*N.C. = No change is made at the end of that 5-minute period.

For example, if the transportation cost exceeds the con- summer or the winter. Under such conditions, the supply pres-
ditioning cost, the optimization goal is to minimize fan oper- sure is maximized before the supply air temperature is increased
ation. This is achieved by conditioning the space with as little in the winter or lowered in the summer. When none of the VAV
air as possible. The quantity of air transported can be mini- boxes in Figure 8.2x are fully open, the PIC set point is lowered,
mized if each pound of air is made to transport more condi- while the TIC set point is at or near minimum in the winter
tioning energy; that is, if each pound of air carries more (maximum in summer). When more than one VAV box is fully
cooling or heating BTUs. Therefore, when the goal is to open, the PIC set point is increased to its maximum setting.
minimize fan costs, the air supply pressure is held as low as When that is reached, the supply temperature starts to be
possible, and the air supply temperature is maximized in the increased in the winter (decreased in the summer).
winter and minimized in the summer. Fan costs tend to The algorithms described above provide the dual advan-
exceed conditioning costs when the loads are low, such as in tages of automatic balancing and minimum operating cost.
the spring or fall, or when the economizer cycle is used to They eliminate the need for manual labor or for the use of
provide free cooling. pressure-independent VAV boxes, while reducing operating
Table 8.2bb describes the algorithm used to achieve this cost by about 30%. They also provide the flexibility of assign-
goal. When none of the VAV boxes (Figure 8.2x) are fully ing different comfort envelopes (different TL and TH values)
open, indicating that all loads are well satisfied, the air pres- to each zone. Thereby, as occupancy or use changes, the
sure (PIC set point) is kept at a minimum, and the air tem- comfort zone assigned to the particular space can be changed
perature (TIC set point) is lowered in the winter and raised automatically.
in the summer. When more than one VAV boxes are fully
open, the air supply temperature is increased in the winter
(lowered in the summer). When its limit is reached, the algo- ELIMINATION OF CHIMNEY EFFECTS
rithm will start raising the PIC set point.
Table 8.2cc describes the algorithm used when the condi- In high-rise buildings, the natural draft resulting from the
tioning costs are higher than the fan operating costs. This is chimney effect tends to pull in ambient air at near ground
likely to be the case when the loads are high, such as in the elevation and to discharge it at the top of the building.

2006 by Bla Liptk


8.2 Airhandler and Building Conditioning Controls 1525

TABLE 8.2cc
Optimization of Supply Air Pressure and Temperature, When Conditioning Costs Exceed Fan Costs (Frequency = 5 min)
Incremental Ramp Adjustment in the Set
Points of
Is PIC Set Point at Its
VAV Status Airhandler Mode Maximum? TIC PIC

None at 100% for Heating (AT > RT) Yes 1F 0.5 in. H2O
15 minutes continuously No N.C.* (at min.) 0.25 in. H2O
Cooling (AT < RT) Yes + 1F 0.5 in. H2O
No N.C. (at max.) 0.25 in. H2O
Not more than one at Heating (AT > RT) Yes N.C. N.C. (at max.)
100% for more than No N.C. N.C.
30 minutes continuously
Cooling (AT < RT) Yes N.C. N.C. (at max.)
No N.C. N.C.
More than one at 100% for Heating (AT > RT) Yes + 1F (at max.)
more than 30 minutes No N.C. + 0.25 in. H2O
continuously
Cooling (AT < RT) Yes 1F (at max.)
No N.C. + 0.25 in. H2O
More than one at 100% for Heating (AT > RT) Yes + 2F (at max.)
more than 60 minutes No N.C. + 0.5 in H2O
continuously
Cooling (AT < RT) Yes 2F (at max.)
No N.C. + 0.5 in H2O

* N.C. = No change.

Although eliminating the chimney effect can lower the oper- the square of flow and the pressure at the end of the distri-
ating cost by approximately 10%, few systems with this bution headers (cascade masters PC-1 and PC-6) remains
capability are yet in operation. constant. This control approach results in the most efficient
Figure 8.2dd shows the required pressure controls. The operation of variable-air volume fans.
key element of this control system is the reference riser, which If the building is maintained at a constant pressure that
allows all pressure controllers in the building to be referenced equals the pressure at ground elevation plus 0.1 in. H2O, this
to the barometric pressure of the outside atmosphere at a will result in higher pressure differentials on the higher floors,
selected elevation. Using this pressure reference allows all as the barometric pressure on the outside drops. Therefore,
zones to the operated at 0.1 in. H2O (25 Pa) above that refer- air losses due to out-leakage and pressure differentials on the
ence pressure (PC-7) and permits this constant pressure to be windows will both rise. If the pressure reference is taken at
maintained at both ends of all elevator shafts (PC-8 and -9). some elevation above ground level, these effects will be
If the space pressure is the same on the various floors of reduced on the upper floors, but on the lower floors the
a high-rise building, there will be no pressure gradient to windows will be under positive pressure from the outside and
motivate the vertical movement of the air, and as a conse- air infiltration will be experienced.
quence, the chimney effect will have been eliminated. A side
benefit of this control strategy is the elimination of all drafts
or air movements between zones, which also minimizes the CONCLUSIONS
dust content of the air. Another benefit is the capability of
adjusting the pressurization loss of the building by varying The airhandler is just one of the industrial unit operations. The
the setting of PC-7, -8, and -9. process of air conditioning is similar to all other industrial
Besides reducing operating costs, the use of pressure- processes. Fully exploiting state-of-the-art instrumentation and
controlled elevator shafts increases comfort because drafts control results in dramatic improvements. There are few other
and the associated noise are eliminated. processes in which the use of optimization and of instrumen-
Figure 8.2dd also shows the use of cascaded fan controls. tation know-how alone can halve the operating cost of a process.
The set points of the cascade slaves (PC-2 and PC-5) are The control and optimization strategies described in this
programmed so that the air pressure at the fan is adjusted as chapter can be implemented by pneumatic or electronic

2006 by Bla Liptk


1526 Control and Optimization of Unit Operations

Ambient pressure
reference at
selected elevation
Typical zone
1/4'' +1''
(62.5 Pa) R PC + 0.1'' (+25 Pa) TC (+250 Pa)
PC R/A 7 D/A PC
R R
1 6
VAV
RA SA
FC FO

50 to 100% 0 to 50%
PC output PC output
FC FO
RA SA

+ 0.1'' (+25 Pa)


PC R
8 D/A
Open reference riser

Typical
elevator
shaft
+ 0.1'' (+25 Pa)
PC R
9 D/A

RA SA
R FC FO
50 to 100% 0 to 50%
To all PC output PC output
Control
other
EA > signal from
PCs OA TIC-07 in SP
D/A D/A Fig 8.2 p
SP +1/4'' PC
1/4'' R
(+ 62.5 Pa) FC (62.5 Pa) 5
R PC FC D/A
2 PC PC R
R/A R 4
3
SF
RF
FO
FC

FIG. 8.2dd
Chimney effects in high-rise buildings can be eliminated by using the proper pressure controls.

instruments and can be controlled by analog or digital sys- 2. Avery, G., VAV Economizer Cycle, Heating, Piping, Air Condition-
tems. The type of hardware used in optimization is less ing, August 1984.
3. Liptk, B. G., Reducing the Operating Costs of Buildings by the Use
important than the understanding of the process and of the
of Computers, ASHRAE Transactions, 83:1, 1977.
control concepts that are to be implemented. The main advan- 4. Kovach, E. G., Technology of Efficient Energy Utilization: The
tage of digital and computerized systems is their flexibility Report of a NATO Science Committee Conference Held at Les Arcs,
and convenience in making changes, without the need to France, 812 October, 1973, Scientific Affairs Division, NATO, Brus-
modify equipment or wiring. sels, Belgium.
5. Liu, S. T., et al., Research, Design, Construction and Evaluating an
Energy Conservation School Building in New York City, NBSIR.
6. Stanford Research Institute, Patterns of Energy Consumption in the
References United States, prepared for the Office of Science and Technology,
Washington, D.C.
1. Liptk, B. G., Applying the Techniques of Process Control to the 7. Nomura, G., and Yamada, Y., CO2 Respiration Rate for the Ventilation
HVAC Process, ASHRAE Transactions, Paper No. 2778, Vol. 89, Part Calculation, Transaction of Japanese Architectural Society Meetings,
2A, 1983. October 1969.

2006 by Bla Liptk


8.2 Airhandler and Building Conditioning Controls 1527

8. Department of Defense, Environmental Engineering for Shelters, Haines, R. W., and Wilson, C. L., HVAC Systems Design Handbook, New
TR-20-Vol. 3, Department of Defense, Office of Civil Defense, May York: McGraw-Hill, 2003.
1969. Luciano, J. R., Energy Conservation Techniques for Hospital Operating
9. Kusuda, T., Intermittent Ventilation for Energy Conservation, NBS Rooms, ASHRAE Journal, May 1983.
report of ASHRAE Symposium in Dallas, TX, February 1976. Nordeen, H., Control of Ventilation Air in Energy Efficient Systems,
ASHRAE Symposium #20, Paper #3.
Ozawa, K., Noda, Y., et al., A Tuning Method for PID Controller Using
Optimization Subject to Constraints on Control Input, ASHRAE
Bibliography Annual Meeting, Kansas City, 2003.
Rosaler, R. C., HVAC Maintenance and Operations Handbook, New York:
American Institute of Architects, The Architects Handbook of Professional McGraw-Hill, 1997
Practice, with CD, 13th edition, New York: John Wiley & Sons, Inc. Shih, J. Y., Energy Conservation and Building Automation, ASHRAE
ASHRAE Standard 62-2001, Ventilation for Acceptable IAQ, ASHRAE, Paper #2354.
2001. Spielvogel, L. G., Exploding Some Myths about Building Energy Use,
Bell, A. A., Jr., HVAC Equations New York: McGraw-Hill, 2000. Architectural Record, February 1976.
Cooper, F. G., Low Pressure Sensing and Control, InTech, September Stillman, R. B., Systems Stimulation, engineering report prepared for
1992. IBM-RECD, 1971.
Daryani, S., Design Engineers Guide to Variable Air-Volume Systems, Turk, A., Gaseous Air Cleaning, ASHRAE Journal, May 1983.
Actual Specifying Engineer, July 1974. Woods, J. E., Impact of ASHRAE Ventilation Standards 62-73 on Energy
DHO/Atlanta Corp., Conserving Energy, Powered Induction Unit (Data Use, ASHRAE Symposium #20, Paper #1.
Sheet #1), Atlanta, GA: DHO/Atlanta Corp., 1974.

2006 by Bla Liptk

You might also like