Professional Documents
Culture Documents
Boiler Control
Operation Manual
750-342
01/2016
TO: Owners, Operators and/or Maintenance Personnel
This operating manual presents information that will help to properly operate and care for the equipment. Study its con-
tents carefully. The unit will provide good service and continued operation if proper operating and maintenance instruc-
tions are followed. No attempt should be made to operate the unit until the principles of operation and all of the
components are thoroughly understood.
It is the responsibility of the owner to train and advise not only his or her personnel, but the contractors' personnel who
are servicing, repairing, or operating the equipment, in all safety aspects.
Cleaver-Brooks equipment is designed and engineered to give long life and excellent service on the job. The electrical
and mechanical devices supplied as part of the unit were chosen because of their known ability to perform; however,
proper operating techniques and maintenance procedures must be followed at all times.
Any automatic features included in the design do not relieve attendants of their responsibilities. Such features merely
eliminate certain repetitive chores, allowing more time for the proper upkeep of the equipment.
It is solely the operators responsibility to properly operate and maintain the equipment. No amount of written instructions
can replace intelligent thinking and reasoning and this manual is not intended to relieve the operating personnel of the
responsibility for proper operation. On the other hand, a thorough understanding of this manual is required before at-
tempting to operate, maintain, service, or repair this equipment.
Operating controls will normally function for long periods of time and we have found that some operators become lax in
their daily or monthly testing, assuming that normal operation will continue indefinitely. Malfunctions of controls lead to
uneconomical operation and damage and, in most cases, these conditions can be traced directly to carelessness and
deficiencies in testing and maintenance.
The operation of this equipment by the owner and his operating personnel must comply with all requirements or regula-
tions of the insurance company and/or other authority having jurisdiction. In the event of any conflict or inconsistency
between such requirements and the warnings or instructions contained herein, please contact Cleaver-Brooks before pro-
ceeding.
Cleaver-Brooks
HAWK 4000
Boiler Control
Operation Manual
Please direct purchase orders for replacement manuals to your local Cleaver-Brooks authorized representative
Printed in U.S.A.
CONTENTS
Section 1
General
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Hawk 4000 System Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
New Features 2016 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Safety Provisions and Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Burner Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Boiler Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Section 2
System Components
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
PLC Rack Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Human-Machine Interface (HMI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
USB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Sensor Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Steam Systems: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Hot Water systems: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Section 3
Hardware Setup
Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
DIN Rail Latch and Expansion I/O Module Locking Levers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Panel and Field Wiring Terminations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
SM2 Module DIP Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Burner Control Modbus Address and Baud Rate - CB780E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Burner Control Modbus Address and Baud Rate - CB120E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
PLC Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Modbus Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Setting The Modbus Node Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Power/ Communications LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Moving The Actuator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Section 4
System Configuration
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Logging in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Boiler Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Configuration Screen #1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Boiler Media and Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Fuel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Actuator Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Configuration Screen #2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Flame Safeguard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Variable Frequency Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Configuration Screen #3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16
Economizer Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16
Feedwater Level Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-17
Feedwater Level Control Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-18
Configuration Screen #4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
Lead Lag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
Remote Modulation/Remote Set Point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
Dual Set Point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
Hot Standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
Configuration Screen #5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23
Boiler Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23
Configuration Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24
Auxiliary Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25
Aux Analog Input Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25
VFD Ethernet Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-26
Email Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-32
SMTP Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-32
Text/Email Contact List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-32
PanelView Plus Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-33
Installing a PV+ Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-33
Change the Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-39
Viewing the PV+ Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-41
Remote Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-41
Section 5
Commissioning
Commissioning the Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-2
Setting Combustion - Parallel Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-4
Store Purge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-5
Store Lightoff . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-7
Curve Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-8
Setting Combustion - Single Point Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-9
VFD or O2 Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-9
No VFD or O2 Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-9
Combustion Control Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-10
Firing Rate Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-10
Tuning and Trends . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-12
Alarms and Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-14
Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-16
Operating Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-16
Outdoor Temperature Reset (Hot Water only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-16
Hot Standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-16
Revert to Pilot (CB 120E only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-17
O2 Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-18
Mix O2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-19
Drive Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-19
Ethernet Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -5-19
Two Boiler Lead Lag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-20
Lead Lag Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-21
Lead Lag Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-22
Thermal Shock Routine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-23
Two-Stage Economizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-24
Section 6
Diagnostics and Troubleshooting
System Monitoring and Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Boiler Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Burner Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
System Information/PLC Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Modbus diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
PLC Output Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
PLC Hardware Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
PLC I/O Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
PLC Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Fault List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
Section 7
Parts
www.cleaverbrooks.com
Section 1 General Hawk 4000
1.1 Introduction
The Cleaver-Brooks HAWK 4000 is an exclusive Boiler Management and Control system specifically designed
to integrate the functions of a Programmable Boiler Controller and Burner Management Controller, as well as
other boiler operating and ancillary controls. The HAWK 4000 system incorporates a user-friendly, graphical
Human Machine Interface (HMI) that displays boiler parameters, fault annunciation and alarm history, as well
as providing access to boiler configuration and control functions.
CB780E
CB120E
Slot 0 Slot 1 Power Slot 2 - Digital Inputs Slot 3 - Digital Outputs Slot 4 - Analog Inputs
Processor Modbus Card Supply
Address Name Address Name Address Name
I2/0 Blower Terminal O3/0 Recycle Limit (RLR) I4/0 Steam Pressure (Supply Water
Temp HW)
I2/1 Purge O3/1 External Start Interlock I4/1 Water Level (ST)
I2/2 O2 Analyzer Status O3/2 Non-Recycle Limit I4/2 O2
(Yokogawa) (NRLR)
I2/3 VFD Status O3/3 Prove Low Fire I4/3 Remote Mod/SP or 2 BLL
Press (Water Temp)
I2/4 VFD Bypass O3/4 Start Slave Blr (2 Blr L-L)
or Revert to Pilot *
I2/5 Ready To Start/ O3/5 Prove High Fire
Limits Closed
I2/6 Ext. Device Start O3/6 Alarm Output
Interlock (FAD)
I2/7 ALFCO or Boiler Start O3/7 Boiler Ready (L-L) or
(L-L) Revert to Pilot *
I2/8 Pilot Terminal
I2/9 Main Fuel Terminal
I2/10 Fuel 1 Selected
I2/11 Fuel 2 Selected
I2/12 FSG Alarm Terminal
I2/13 LWCO Shutdown
I2/14 Rem. Mod/SP, DSP,
or Avail. (L-L)
I2/15 Burner Switch
*With 2 boiler lead lag master boiler or if no lead lag selected, revert to pilot output is O3/7. With 2 boiler lead lag slave boiler or master panel, revert to pilot
output is O3/4.
Slot 5 - Analog Outputs Slot 6 - Analog Input Module Slot 7 - Digital Inputs Slot 8 - Analog Inputs
www.cleaverbrooks.com
Section 2 System Components Hawk 4000
2.1 Overview
The principal components of the HAWK 4000 Boiler Control System are the Programmable Logic Controller
(PLC) and its associated input/output modules, the touch screen Human Machine Interface (HMI), and the
Flame Safety Control. The system also includes power supplies and various relays and circuit breakers.
The HAWK 4000 Boiler Controller is factory pre-programmed to work with most Cleaver-Brooks firetube and
watertube boilers, yet allows easy configuration for specific boiler applications. The Boiler Controller program
logic is password secured, ensuring tamper- proof controller operation. The Touch Screen HMI provides user-
friendly access to firing rate control functions, boiler diagnostics and alarm history, as well as connected
operating parameters. Burner management is handled by the proven CB780E or optional CB120E Flame
Safety Control.
Slot Module
1
0 Processor 1769-L33ER
2 1 Modbus Card 1769-SM2
3 - Power Supply 1769-PA2
4 2 Digital Inputs 1769-IA16
5 3 Digital Outputs 1769-OW8I
6 4 Analog Inputs 1769-IF4
7 5 Analog Outputs 1769-OF4
8 6 Analog Inputs 1769-IF8
9 7 Digital Inputs [optional] 1769-IA16
10 8 Analog Inputs [optional] 1769-IF8
11 9 Analog Outputs [optional] 1769-OF4
A Right End Cap Terminator is required to complete the modular communication bus. It attaches to the right
side of the last module in the rack.
Optional modules can be added to the PLC to provide additional functionality.
2.4 Communications
2.4.1 Modbus
Modbus is an open serial protocol used by the HAWK 4000 system for sending
and receiving control commands, position data, and diagnostic data between the
PLC and attached devices. Modbus communications are managed by the SM2
module located to the right of the processor in slot 1.
HAWK 4000 devices that communicate using Modbus include the burner flame
safety control and the fuel, air, and FGR actuators. The Modbus communication
network allows burner control system status and fault information to be transmitted to
the PLC and displayed on the HMI screen, and in addition is used for actuator control,
feedback, and fault information.
2.4.2 Ethernet
The HAWK 4000 uses Ethernet for several communication functions:
Communication between the PLC and HMI. The Ethernet cable connecting the PLC
and HMI can be either a straight through or a crossover type.
Connection of the boiler control system to an existing infrastructure, i.e. plant Local
Area Network (LAN) Figure 2-4. SM2
Modbus Module
Integration with a Building/Plant Automation System (BAS)
Remote monitoring of boiler control system via the customer's Wide Area Network (WAN) or via the Internet
Connection of a laptop for diagnostics
Email or texting of boiler alarms to plant or service personnel
Ethernet/IP can also be used for control functions:
Networking multiple boiler controllers with a single BAS interface
Writing remote setpoint or remote start/stop of boiler
Networking multiple boiler controllers with a Cleaver-Brooks Master Panel
2.4.3 USB
USB communications are used to connect a laptop computer to the PLC for diagnostic purposes. The HMI
has 2 USB ports that may be used for file transfer.
The HMI USB ports also support keyboard and mouse input.
BOTTOM OF CONTROLLER
PORT 1
PORT 2
USB
ETHERNET
a 1/2 NPT coupling at the right-hand side center-line of the boiler shell. If this location is not available, an
unused feedwater connection may be used.
Water Level sensor is OPTIONAL on steam boilers.
For optional 2 or 3-element feedwater control, Steam Flow and Feedwater Flow can be used in conjunction
with water level.
www.cleaverbrooks.com
Section 3 Hardware Setup Hawk 4000
! Important
The PLC and rack modules do not support removal and insertion under power. While the PLC system is under
power, any break in the connection between the power supply and the PLC rack (i.e. removing the power supply,
PLC, or an expansion module) will clear processor memory including the user program. Ensure that the electrical
power is OFF before removing or inserting any PLC device.
3.1.1 DIN Rail Latch and Expansion I/O Module Locking Levers
Before powering up the control system for the first time, check that all the DIN rail latches and expansion
module locking levers are in place (see Figure 3-1 and Figure 3-2).
DIP switch
settings: Top L,
Bottom R
The CB120E has built-in Modbus capability; for proper communications the ModBus baud rate and node
address need to be correctly set. To check the settings, the CB120E must be powered.
Press the <BACK> or <NEXT> key on the CB120E display until the screen displays PROGRAM SETUP>.
Press the <MODE> then the <NEXT> key until the screen displays BAUD RATE.
Press <MDFY> and use the <BACK> or <NEXT> key to change to 4800. Press <MDFY> to save.
Press the <NEXT> key until UNIT ADDRESS # is displayed. To change the unit address, use the <BACK>
or <NEXT> key to change to 5. Press <MDFY> to save.
Press <MODE> to exit the menu.
RUN/REM/PROG
3.1.6 PLC Switch switch
Verify that the PLC switch is in the RUN position.
SD card
The boiler will not operate if the switch is in the PROG slot
position.
The boiler will immediately stop if the switch is
moved to the PROG position.
The switch must be in the PROG position and the
Burner switch set to OFF before the PLC program can
be copied to a blank S D card in Logix folder format.
The switch can be in either PROG or RUN position
when copying a PLC program from a SD card
containing a Logix folder. No other files should be present on the SD card. The Logix folder must be located
at the root directory of the SD card (see Appendix B for program loading procedure).
It is recommended that the actuator drive shaft remain decoupled from the valve
shaft (or damper level) until the actuator Modbus address is properly set, the wiring
is proven, and the direction of rotation to open the valve/ damper is determined.
R R W
BL
BRN BRN
BRN BRN
ORG ORG
ORG ORG
BLK BLK
BLK BLK
RED RED
RED RED
G
There are open / close pushbuttons on the H M I actuator calibration screen. These pushbuttons should
be used when calibrating the actuators.
Clockwise or counter-clockwise actuator shaft rotation is as seen from the viewing perspective shown below.
Counterclockwise (CCW)
Clockwise (CW)
www.cleaverbrooks.com
Section 4 System Configuration Hawk 4000
4.1 Introduction
The Hawk 4000 is equipped with a 7 (optional 10) color touch screen Human Machine Interface (HMI).
The HMI along with the Burner Control display are the points of interface for the operator to monitor and
control the boiler, and for the technician to configure and set up the system.
This section describes the HMI screens and their functions.
For information on the Burner Control (Flame Safeguard), refer to one of the following CB publications:
CB120E Burner Control 750-264
CB780E Burner Control 750-234
4.1.1 Logging in
Certain actions on the HMI require a password before allowing user input. The Hawk 4000 employs three
levels of security: Operator, Service, and Factory. When a password is required, the login entry window is
displayed.
Pressing <User Name> or <Password> will bring up an alphanumeric keypad. Use this to enter your user
name and password. A USB keyboard may also be used.
Press Enter after typing User Name and after typing Password. When both are entered, press <Login>.
The following items are configurable when in system Figure 4-6. Warning
configuration.
Configuration Screen 1:
Boiler Media Steam or Hot Water
Boiler Type - Firetube, Flextube or M4/M5 boiler
Safety Valve Setpoint (Steam)/Max Rated Temperature (HW)
NOx Level (PPM)
Number of Fuels (up to 3)
Fuel Control Method (Parallel Positioning or Single Point)
Fuel Type and Turndown for each fuel
Steam transmitter span
FGR (Yes/No)
2nd fuel actuator (Yes/No) for each fuel
2nd Air Actuator
Configuration Screen 2:
Flame Safeguard Selection (CB780E / CB120E)
Revert to Pilot (CB120E Only)
Revert to Pilot Signal Select (CB120E Only)
VFD Model / Min.% / Bypass / Ethernet communications
Remote Modulation/Setpoint Signal Selection
O2 Analyzer
O2 Trim
Low O2 Shutdown Option
Mix O2
Configuration Screen 3:
Combustion Air Temp Option Selection
Level Master Option selection (Steam Boiler)
Expanded diagnostics (Slot 7) selection
Aux Analog Inputs (Slot 8) selection
2-Stage Economizer configuration (Steam Boiler)
Draft Control select
Feedwater level control selection and type - 1, 2, or 3-element (Steam Boiler)
Outdoor Temperature (HW)
Return Temperature (HW)
Configuration Screen 4:
2 Boiler Lead Lag / Master Panel Lead Lag select
Remote Modulation Source select (Analog Input / Communications)
Hot Standby
Remote Setpoint source select (Analog Input / Communications)
Dual Set Point
Outdoor Temp Reset (HW)
Configuration Screen 5:
Enter customer name, boiler ID and serial number, Alarm Input #1-2 name if enabled.
Pressing <Next> from Configuration Screen #5 will show the Configuration Summary screen. Configured
values will be shown for all parameters.
If the <Confirm Options (Required)> pushbutton is visible, it must be pressed to accept the new system
configuration
Note - if a configuration setting is marked with an asterisk and the setting is changed, the
Combustion Curves will be erased.
! Caution
If System Configuration is entered with the boiler running, a safety
shutdown will occur. Repeated shutdowns or nuisance shutdowns
can cause premature equipment failure.
! Caution
The following screens should only be accessed by qualified
personnel. Selections should never be made while the boiler is in
operation.
Note: The boiler will not start while a System Config screen is displayed.
Note: The firing rate will be put into manual mode upon entering the System Config screen.
The user must be logged in at the appropriate password level to change configuration data. If the user tries to
change configuration data without having proper access rights, a pop-up window will appear and a password
will be requested.
Boiler Type
The Boiler Type will display the proper Boiler graphic on the Boiler overview screen. The three choices for
Boiler Type are: Firetube, Flextube and M4/M5
Boiler Type is also used to set limits on the maximum entry allowed for Safety Valve Setpoint (steam) or Max
Rated Temperature (hot water).
! Warning
The safety valve setting is critical to the proper operation of the
boiler. An incorrect setting could lead to unsafe operation.
A hot water boiler is configured similarly. The max rated temperature of the boiler should be entered. This
number should not exceed the maximum design temperature of the boiler. Default for hot water boilers
is 250 F. Contact your local Cleaver-Brooks representative if you do not know the maximum temperature
rating of your boiler.
Steam Transmitter Span The span settings for the steam transmitter is adjustable. The Steam Transmitter
Span value cannot be set lower than the Safety Valve Setpoint and cannot be set higher than 1000. Initially
the Steam Transmitter Span is populated with a default value:
In hot water systems the supply temperature transmitter is not scalable. The transmitters used must be rated
to accommodate the required range:
If the Max Rated Temperature > 250 Deg F the Supply Temp Transmitter is set to 50-300 Deg F.
If the Max Rated Temperature = 250.1 Deg F or greater the Supply Temp Transmitter is set to 50-500 Deg F.
Note: Remote Setpoint and Dual Setpoint options are NOT available for low emission steam boilers (NOx level
less than 60.0 PPM).
Control Method
Select the type of combustion control method for this application.
Acceptable entries are Parallel Positioning or Single Point Positioning.
Fuel Type
Select the Fuel type for each fuel for this application.
When pressing the Fuel Type push button a selector is displayed:
Use the up/down arrows to select the correct fuel. Press the enter key to accept the selection. Press
<Close> to return to Configuration Screen #1.
Turndown
Enter the Turndown for each fuel for this specific application.
The turndown entry affects the boiler efficiency calculations - it has no impact on the burner's actual
turndown. Turndown ratio is established during burner commissioning by a qualified burner technician.
Revert to Pilot
Revert to Pilot is selected if Yes is displayed on the <Revert to Pilot> push button.
If Revert to Pilot is selected there are two ways to initiate the Revert to Pilot sequence - either by Process
Variable (Steam Pressure/Water Supply Temperature) or by Digital Input.
If Process Variable is selected the setpoint for Revert to Pilot must be entered from the Revert to Pilot setpoint
screen.
If Digital Input is selected, when discrete input I2/7 ALFCO is turned off, Revert to Pilot will be initiated.
! Caution
Revert to Pilot modes are to be determined in the field after careful
analysis of the load conditions that necessitate the use of this feature.
Care should be taken to avoid unnecessary recycling and damage to the
boiler equipment.
VFD Model
Select the appropriate VFD Model for this specific job. The available options are None, PowerFlex, and Other
Mfg.
VFD Minimum Percent
This is the minimum percent output that the VFD will be commanded to run.
VFD Bypass
VFD Bypass should be selected Yes if VFD Bypass is used on this specific job.
An Air/Fuel curve must be configured for each fuel while in bypass mode.
VFD bypass allows the boiler system to keep the combustion blower motor running even if the Variable
Frequency Drive is taken out of the loop for any reason.
4.6.3 Options
Oxygen Analyzer
The Oxygen (O2) Analyzer is available for monitoring stack flue gas oxygen concentration. The O2 Analyzer
transmits an analog signal to the controller. The O2 signal is used for Low O2 alarms, Low O2 Shutdown and in
calculating boiler efficiency. O2 concentration is displayed on the Boiler Overview and Firing Rate screens.
O2 Trim
02 trim control is an integral part of the HAWK 4000 system. This feature affords additional control over fuel-to-
air ratios in the event of adverse atmospheric conditions or fluctuating fuel heating values.
The HMI has an 02 trim screen that displays O2 Actual concentration and O2 Setpoints. The Screen allows for
viewing and calibrating the Cleaver Brooks O2 Sensor. The Flue Gas O2 Control Screen can be accessed from
the HMI Main screen.
To view O2 trends or to adjust the O2 Trim PID tuning, press <Tuning & Trend>.
Mix O2
This feature is for use with CB NTI burners in Ultra Low NOx applications. Mix O2 trim uses a probe mounted
in the boiler front head to monitor O2 levels in the combustion air in order to maintain optimum FGR rate.
If Mix O2 is selected in System Configuration, a Mix O2 control screen similar to Figure 4-16 will become
available, with sensor calibration, manual/auto control, and setpoint/actual value displays.
One-element control - A control signal from the water level sensor is used as
1-element level control
the process variable. This value is compared to the setpoint, and based on PID
settings a control output is calculated and sent to modulate the feedwater
valve. LT
I4/1
Operator
setpoint SP PV
PID
CONTROL
CV
O5/3
To feedwater valve
STEAM PID
FLOW FF CONTROL
I8/3
CV
O5/3
To feedwater valve
CV CV
O5/3
To feedwater valve
Figure 4-22. 3-Element Control
Feedwater Valve% of Full Travel - Used to limit the control output to the valve.
Steam Flow% required for 2/3 Element Control - Although 2 or 3 element Feedwater Level Control is
selected, the Active Control will be 1 element until the Steam Flow% becomes greater than the Steam Flow%
Required for 2/3 Element Control. Once the steam flow exceeds this value 2 or 3 element Feedwater Control
(whichever is selected) will become active.
Steam Flow must be in units of Lb/Hr. These units are automatically configured for analog input I8/3.
Feedwater Flow may be in units of Lb/Hr, GPM, or GPH. If a unit other than Lb/Hr is selected for Feedwater
Flow a calculated value in Lb/Hr will be displayed on the HMI.
If the PLC detects a bad analog signal, an alarm Remote Setpoint Signal Failure is activated and the Set
point reverts to the LOCAL setting.
! Warning
Remote Set Point control should not be used on certain Low
Emission boiler systems. Low Emission boilers can be sensitive to
changing operating set points. Contact your Cleaver-Brooks
representative to determine if Remote Set Point control is allowed on
your boiler. Failure to follow these precautions may result in
damage to equipment, serious personal injury, or death.
! Warning
Dual Set Point control should not be used on certain Low Emission
boiler systems. Low Emission boilers can be sensitive to changing
operating set points. Contact your Cleaver-Brooks representative to
determine if Dual Set Point control is allowed on your boiler. Failure
to follow these precautions may result in damage to equipment,
serious personal injury, or death.
Hot Standby can be enabled or disabled by Pressing the Hot Standby button to toggle between <Yes> and
<No>. The boiler overview and firing rate screens will indicate when the boiler is in hot standby.
Hot Stand-By can be initiated manually by pressing <Force Hot Standby> on the Firing Rate screen. The
boiler will remain in standby until the button is again pressed.
See Section 5 - Commissioning for more on Hot Standby.
Outdoor Temperature Reset (Hot Water units only) With this option selected, a correction based on the
outdoor temperature will be applied to the operating set point. An outdoor temperature transmitter is
required on An alo g I npu t I 6/ 2 for this feature. When the outdoor temperature is selected for A n a l o g
I n p u t I 6 / 2 outdoor temperature is displayed on the boiler overview screen.
When Outdoor Reset is selected, the outdoor temperature and water temperature setpoints should be entered
from the Setpoints screen (See Section 5.5 - Setpoints) after system configuration is completed.
If the system has auxiliary alarms the text that is displayed when the auxiliary alarm is triggered can be
entered. To enter this information, press the text display button beneath the description. An alphanumeric
keypad pop-up window appears.
Once all the information is entered, press the carriage return button. The auxiliary alarms are each limited to
20 characters, including spaces.
Auxiliary alarm 1 must be wired to Slot 7 Input 14
Auxiliary alarm 2 must be wired to Slot 7 Input 15
For example: If Auxiliary Alarm 1 is entered as Water Pressure Low and Discrete Input I7/14 is On the alarm
displayed on the HMI for Auxiliary Alarm 1 will read Aux 1 - Water Pressure Low.
To complete system configuration, press the <Confirm Options> pushbutton on the System Configuration
Summary Screen.
The Configuration selections may be changed after the HAWK 4000 is installed. However, for many of the
options, additional hardware is required to make the function work. Please refer to the parts section for the
required hardware.
Inputs can be monitored and trend screens accessed from <Analog Inputs [1 or 2]>:
3.Press
a.PowerFlex400: Parameter 15
b.PowerFlex70/700: Parameter 16
b.PowerFlex 753: NA
13.Reset the adapter by power cycling the drive.
a.Open the electrical disconnect.
b.Wait for capacitors to discharge (about 30-60 seconds depending on drive size).
c.Close the electrical disconnect.
The communications adapter is now configured.,
Configuring the HMI for PowerFlex drive Ethernet communication
Selecting PowerFlex as the VFD Model will make the VFD Ethernet button appear. When <VFD Ethernet>
is enabled, the VFD Type button will appear. Activate PowerFlex 400, 70, 700, or 753 based upon which
drive is used.
If <Other MFG> is selected for VFD Model, Ethernet communications are not available.
The IP address will initially be set to zeros. Also, if PowerFlex drives are de-selected, the IP address will be
zeroed. A warning will display whenever the address is not set or the PLC cannot connect to the drive. Enter
the IP address using the associated IP address octet button.
When the IP address has been entered, press the <Set VFD IP Address> button. Once Ethernet
communications have been established, the motor nameplate data and <Load C-B Defaults> buttons will
appear.
Once configured, the drive status can be monitored on the Blower VSD screen. The left-hand side of the screen
will display the drive status word as well as indicate if a drive fault or alarm is active. If a fault exists, it can
be cleared by pressing the Clear Drive Fault button or access the Drive Faults screen to view the fault and
recommended corrective actions.
The right-hand side of the screen provides visualization of the drive output.
The Output Amps gage will automatically scale based on either the motor current rating or the drive rated
amps.
The Output Power (in kilowatts) scale is preset for the PowerFlex 400, and scalable based upon the PowerFlex
70/700/753 rated kilowatts.
Fan Speed is displayed on a fixed scale of 0-4000 rpm and is based upon drive output frequency.
The Drive Faults screen will display the current drive fault (if present). Also displayed is a description of the
fault and recommended corrective actions. Press and hold the Last Drive Fault button to see the previous fault.
Figure 9. Current and Last drive fault information displayed on the Drive Faults screen.
Figure 4-34.
Press the Year, Month, and Day buttons to change the values. Press <OK> when done.
To change the time, Select Terminal Settings>Time/Date/Regional Settings>Time. values.Press the Hour,
Minute, and Seconds buttons to change the values. Press <OK> when done.
To change the time zone, select Terminal Settings>Time/Date/Regional Settings>Time Zone.
Figure 4-35.
Press the Daylight Savings button to enable or disable daylight savings for the selected time zone. Daylight
Savings is set to Yes for all time zones except for Japanese, which does not support daylight savings.
Daylight savings changes are not permanently applied until you close the Time Zone screen.
Press the <Use Daylight Savings> button to select Yes or No. Click OK when done, then <OK> again to
return to Terminal Settings.
Figure 4-36.
1.Copy the Rockwell Software folder to an appropriate memory device. There should be nothing else on the
card but this folder. If you have a zip file, the file must be unzipped.
2.The file structure where the runtime file resides must be exactly as follows.
Rockwell Software
RSViewME
Runtime
Filename.mer (example: 98500553_000.mer)
3.At this point if there is an Ethernet switch in the electrical control cabinet be sure that there are only 2
Ethernet cables plugged into the Ethernet switch. One cable from the PLC and one cable from the PV+.
4.Power up the PV+ and insert SD card or USB device into slot provided.
5.From the PV+ Configuration Mode (FactoryTalk ME Station), touch Terminal Settings [F4].
Figure 4-37.
6.From Terminal Settings, select File Management. Press the Enter arrow.
Figure 4-38.
Figure 4-39.
15.A message appears asking Do you want to replace the terminal's current communication configuration
with the application's communication configuration?
IMPORTANT: Press Yes [F7] if this is the first time loading the application and communication has yet to be
established, otherwise press NO [F8].
16.You should be back on the FactoryTalk View ME Station screen. The application Filename.mer should
appear in the Current application window. Press Terminal Settings [F4].
Figure 4-40.
21.From the IP Address screen select press the Use DHCP [F4] until the green bullet is in the No position and
the IP Address [F1] button is enabled.
Figure 4-41.
22.Press IP Address [F1] and enter the IP address with the pop-up keypad provided. The Standard IP
addresses for the PV+ are as follows:
NOTE: If the unit must be on a custom network, Ethernet parameters must be obtained from the users IT
department.
192.168.1.121 for Boiler 1
192.168.1.122 for Boiler 2
192.168.1.123 for Boiler 3
192.168.1.124 for Boiler 4
192.168.1.125 for Boiler 5
192.168.1.126 for Boiler 6
192.168.1.127 for Boiler 7
192.168.1.128 for Boiler 8
Figure 4-42.
34.Press Enter
35.Press OK [F7]
36.From the RSLinx Enterprise Configuration.
37.If the Ethernet IP address for the PV+ in this RSLinx Network needs to be revised arrow to highlight the
Ethernet IP address for the PV+.
Example: PV Plus, 192.168.1.121 (should be highlighted)
Press Edit Device [F1].
38.Press Device Address [F1].
39.Press the Backspace key and enter in the correct IP address for this PV+
192.168.1.121 for Boiler 1
192.168.1.122 for Boiler 2
192.168.1.123 for Boiler 3
192.168.1.124 for Boiler 4
192.168.1.125 for Boiler 5
192.168.1.126 for Boiler 6
192.168.1.127 for Boiler 7
192.168.1.128 for Boiler 8
40.Press OK [F7]
41.Press Close [F8]
42.From Networks and Communications Press Close [F8]
43.From Terminal Settings Menu, Select Startup Options.Press the Enter arrow.
44.Select FactoryTalk View ME Station Startup. Press the Enter arrow.
45.Using the On Startup [F1] button, put the green bullet to Run Current Application.
46.Press Run Options [F3]
47.Press Replace RSLinx Enterprise Communication [F1] until the green dot is on NO
a. Press Delete Log Files [F2] on every power cycle until green dot is on NO
48.From Run Options Press OK [F7]
49.Press OK [F7]
50.You should now be on the Terminal Settings screen. Press Close [F8].
51.Press Reset [F7]
52.Do you want to reset the terminal? .Yes [F7]. This takes a moment!
53.Terminal should reboot and run the application
54.Once application is running and communicating properly remove the SD card from the PanelView Plus
terminal. When all devices on the network are configured with a unique IP address the interconnecting
Ethernet cables between the configured devices may be plugged into the Ethernet switch and communications
verified.
55.END OF PROCEDURE
www.cleaverbrooks.com
Section 5 Commissioning Hawk 4000
Main Screen
Warning
Note: If a VFD is present, the VFD purge value must be set above 80%.
will sequence through pilot trial and main flame and the burner will ignite. The actuators can now be
positioned for the first point.
10 points minimum must be stored for a valid curve (20 maximum allowed)
Points can not be skipped
Values for Air and Fuel Actuator 1 must be greater than previous values for a valid point to be stored.
Pressing <New Profile> at any time will erase the current curve.
When the combustion curve is complete (10 valid points are stored) the <Setup Complete> button will
appear; pressing this will go to the Combustion Control screen.
Pressing <Pt Adv Enable> will allow stepping through the combustion curve using <Next Point> and
<Prev Point>. With Points Advance disabled, the actuators will not move when <Next Point> or <Prev
Point> is pushed.
In the event of a bad remote signal, an alarm message will appear on the
screen and the control will revert to Local/Auto mode.
A help screens is available for Remote Modulation / Remote Setpoint
functions.
Alarms with configurable parameters and firing rate/setpoint limits can be edited from these screens. The
second Alarms and Limits screen is only available if the O2 analyzer, Mix O2, or FGR options have been
configured.Configurable items include the following:
5.8 Setpoints
<Set Points> allows adjustment of Setpoint 1 (and Setpoint 2 if Dual Setpoint is configured).
5.8.1 Operating Setpoint
205
200
195
190 Setpoint
185
180
Outdoor 175
Temperature
-60 -40 -20 0 20 40 60 80
proof of pilot the main gas valve de-energizes and the boiler remains on pilot. When demand returns or digital
input I2/7 is ON the main gas valve is energized.
When RTP is on a Rev to Pilot indicator will appear on the Boiler Overview and Firing Rate screens.
Initiated by process variable
If Initiate by process variable is selected, Revert to Pilot is initiated when steam pressure is greater than or
equal to Revert to Pilot Pressure and de-activated when steam pressure is below the boiler On Point.
Revert to Pilot Pressure = Off Point - (Revert to Pilot dP% x Off Point) [ensures that the RTP setting is always
less than or equal to the boiler off point]
Revert to Pilot Pressure must be greater than the boiler operating Setpoint or boiler On Point, whichever is
greater.
5.10 O2 Trim
If O2 Trim was selected and an analyzer specified during system configuration, the <Flue Gas O2 Control>
button will appear on the Main screen.
O2 Trim is accomplished by means of the air actuator, or by the VFD if present (if VFD is in Bypass, the air
actuator is used). A manual operating mode is provided for diagnostic or testing purposes.
The CB O2 analyzer requires calibration on power up, if one week has elapsed since the last calibration, or if
initiated manually from the HMI. If using the Yokogawa analyzer, the PLC will expect a Sensor OK input from
the analyzer at input I2/2.
Once the O2 sensor is calibrated or Sensor OK input is on, the O2 setpoint is captured when setting
combustion curves.
PID control of O2 Trim is provided. Values can be adjusted by pressing <Tuning & Trend>. Defaults are P=3,
I=5, and D=0.
5.11 Mix O2
The Mix O2 feature is designed to improve combustion control for Ultra Low NOx (<9 ppm) systems. Requires
an 8 channel analog input module in Slot 8. If Mix O2 is selected during configuration, Input I8/2 will be
automatically configured with C-B default settings.
Using an O2 probe mounted in the boiler head, the FGR valve is modulated (more FGR for lower Mix O2 levels
and less FGR for higher Mix O2) to maintain optimum O2 levels throughout the firing range. A Mix O2 control
screen provides features similar to standard O2 Trim control:
In order to configure the Ethernet port, the PLC switch must be in REM and the RUN LED must be GREEN.
If 2 Boiler Lead Lag Master is enabled in the Configuration section, two additional screens (for Lead Lag Setup
and Lead Lag Control) will be available.
Select Modulation
Select Lead Lag (steam boilers only) or Unison modulation.
Start Delay
This time delay is activated when Lead boiler control output is greater than Start Point setting. After the time
delay has expired the Lag boiler is commanded to start. Valid values are from 0 to 600 seconds.
Stop Point
Control output percentage of the Lead boiler at which the Stop Delay timer is activated. Valid values are
from 0 to Start Point.
Stop Delay
This time delay relay is activated when the Lead's boiler control output is less then Stop Point setting. After
the time delay has expired, the Lag boiler is commanded to stop. Valid values are from 0 to 600 seconds.
Shutdown Delay
This is the length of time that the Lag boiler is allowed to run after the Stop Delay has expired. Valid values
are from 0 to 600 seconds.
Modulation Start
Control output to the Lead boiler at which the Lag boiler starts modulation. This parameter is only applicable
to Lead/Lag modulation. Valid values are from 0 to 100%.
Sequencing
If enabled, will automatically rotate the Lead and Lag boilers after Number of Days.
The Lead Lag control screen has Auto/Manual controls and graphic displays showing operational data for each
boiler and for the Lead Lag System.
Note: In order for either boiler to be part of the lead lag sequence, <Remote> must be selected under
Control Mode on the boilers firing rate screen.
Lead Lag Modulation - The lag boiler starts when the lead boilers firing rate signal reaches the Start Point
(and the Start Delay has expired). The lag boiler starts modulating after the lead boiler reaches the configured
Modulation Start point. The lag boiler is commanded to stop when the lead boilers firing rate signal reaches
the Stop Point (and the Stop Delay has expired).
In the event of a header sensor failure, master and slave boilers will revert to local firing rate control.
Output Split Range is only applicable if BOTH the condensate return and makeup bypass valves are enabled.
This is the value that determines how the control output is split between the two valves. At 0% the condensate
return valve will be disabled and only the makeup bypass valve will modulate. At 100% the makeup bypass
valve will be disabled and only the condensate return valve will modulate.
Output Force on PV Failure is the value that the control output is set to when the 2nd stage water out
temperature analog signal fails.
Manual/Auto controls and graphic/numeric displays for monitoring economizer operation are on the
economizer control screen:
www.cleaverbrooks.com
Section 6 Diagnostics and Troubleshooting Hawk 4000
CB780E CB120E
Figure 6-2. Burner Control screen
The status of the Flame Safety control is shown as well as the status of the inputs that allow the boiler to start.
The following flame safety status and boiler inputs are shown on the Burner Control screen:
Burner Switch - Indicates position of the burner switch.
Load Demand - When starting the boiler, there is a load demand if the system pressure (steam) or temperature
(hot water) is below the On Point. When system Pressure/Temperature exceeds the OFF point, No Demand
is indicated. When the system Pressure/Temperature drops below the On Point, load demand will again be
displayed.
Limits -This is an indication of the status of the running interlocks on the boiler.
External Interlock - Feedback input from external interlock. When there is a load demand, and the burner
switch and limits are closed, the HAWK 4000 has isolated contacts (2.5A @ 125VAC) for output to an
external interlock device (e.g. fresh air damper, circulating pump). The boiler will start once the external
interlock is proven.
Note: The external interlock must be jumped if not used
ALFCO - Assured Low Fire Cut-Off. An external isolated start-stop contact can be provided to shut down the
boiler. This contact will drive the boiler to low fire prior to shut down.
Note: The ALFCO must be jumped if not used.
6.2 Alarms
If an alarm is active the alarm bell will be visible on all screens:
Press the alarm bell or <Alarms> from the Main Screen to access the Alarm screen.
This screen can be toggled between <Active Alarms> and <Alarm History>. The Alarm History will store up
to 200 alarms. The history can be cleared (password required) by pressing <Clear Alarm History>.
<Alarm Silence> will turn the alarm bell off until another alarm becomes active.
NS (Ethernet Net- Off The port is not initialized; it does not have an IP address and is operating in BOOTP or DHCP
work Status0 mode.
Green The port has an IP address and CIP connections are established.
Flashing green The port has an IP address, but no CIP connections are established.
Red The port has detected that the assigned IP address is already in use.
Flashing red The SD card does not have a valid file system.
Remote Modulation Signal Remote Mod Signal Failed With remote mod by analog, Check analog input wiring.
Failure CB Master LLag, or 2 Boiler View analog input Raw value
LLag Slave option selected, on the HMI PLC I/O status
Analog input I:4/3 is outside of screen.
range. Measure analog input.
Range> 3.3 ma Verify System Configuration
Range< 20.5ma settings on HMI
Remote Set Point Signal Failure Remote Set point Signal Failed With remote set point by Check analog input wiring.
analog option selected, Analog View analog input Raw value
input I:4/3 is outside of range. on the HMI PLC I/O status
Range> 3.3 ma screen.
Range< 20.5ma Measure analog input.
Verify System Configuration
settings on HMI
Header Sensor Failure Header Sensor Signal Failed With 2 Boiler Lead Lag Master Check analog input wiring.
option selected, Analog input Measure analog input.
I:4/3 is outside of range. View analog input Raw value
Range> 3.3 ma on the HMI PLC I/O status
Range< 20.5ma screen.
Verify System Configuration
settings on HMI
Low Oxygen in Flue Gas Low Oxygen level in flue gas O2 level below alarm set point Check combustion.
or below 0.5% From system config screen
check if correct O2 analyzer is
selected.
Check analyzer wiring.
Verify O2 Calibration voltage if
CB analyzer is selected
Low Oxygen in Flue Gas Low Low Oxygen level in flue O2 level below Shutdown set Check combustion.
Shutdown gas point. From system config screen
check if correct O2 analyzer is
selected.
Check analyzer wiring.
Verify O2 Calibration voltage if
CB analyzer is selected
Stack O2 Sensor Calibration O2 analyzer calibration failed O2 signal (input I:4/2) must be Check wiring.
Failed (Only applicable to CB O2 between 4 and 6.5 VDC Repeat calibration.
analyzer) during calibration
Fuel 1, Fuel 2, Fuel 3 Gas Low fuel gas pressure/oil PLC Input I:7/5 is energized Check gas pressure regulator.
Pressure/Oil Temperature Low temperature Verify Oil Temperature for
specific Fuel Selected
Air/xxx Actuator Feedback Low Air actuator position feedback Actuator feedback signal is Check air damper for binding.
is low lower than -2.0% Check alignment.
Check wiring connections.
Re-commission actuator (Fuel
curve will be lost).
Replace actuator
Air/xxx Actuator Feedback High Air actuator position feedback Actuator feedback signal is Check air damper for binding.
is High greater than 102.0% Check alignment.
Check wiring connections.
Re-commission actuator (Fuel
curve will be lost).
Replace actuator.
Stack Temperature Sensor Sensor analog signal is either Analog input I:6.0 is outside of 1. Check sensor.
Failure too low or too high. range. 2. Check wiring.
Range> 3.3 ma 3. Measure analog signal 4-
Range< 20.5ma 20ma is valid.
4. View analog input Raw
value on the HMI PLC I/O
status screen.
Water Shell Temperature Sensor analog signal is either Analog input I:6.2 is outside of 1. Check sensor.
Sensor Failure (Steam Boiler) too low or too high. range. 2. Check wiring.
Range> 3.3 ma 3. Measure analog signal 4-
Range< 20.5ma 20ma is valid.
4. View analog input Raw
value on the HMI PLC I/O
status screen.
Master PIDe Instruction Fault PIDe instruction fault. Call Cleaver-Brooks, Inc.
Technical Services
Outdoor Temperature Sensor Sensor analog signal is either Analog input I:6.2 is outside of 1. Check sensor.
Failure (Hot Water Boiler) too low or too high. range. 2. Check wiring.
Range> 3.3 ma 3. Measure analog signal 4-
Range< 20.5ma 20ma is valid.
4. View analog input Raw
value on the HMI PLC I/O
status screen.
HMI
Electrical
www.cleaverbrooks.com
Section 7 Parts Hawk 4000
Ethernet
Steam Transmitters
Temperature Transmitters
Flame Safeguard
Stack Light
O2 Trim
O2 Kit CB 880-02124-000
1 ECM controller with NTK Wide Band Sensor and Cable Harness 880-01847-000
1 Combustion Air Temperature Sensor 832-02091-000
1 O2 Sampling Probe Housing Assembly 040-00735-000
Outdoor Reset
AB[6].3 Fuel3 Actuator 1 Out Of Position Alarm BI 100 DI 100 10100 nvoFl3AcPsAl_XXX SNVT_switch
AB[6].4 Fuel3 Actuator 1 Feedback Fail Low BI 101 DI 101 10101 nvoFl3AFdLoA_XXX SNVT_switch
Alarm
AB[6].5 Fuel3 Actuator 1 Feedback Fail High BI 102 DI 102 10102 nvoFl3AFdHiA_XXX SNVT_switch
Alarm
AB[6].6 Stack Pressure Input Fail BI 103 DI 103 10103 nvoStkPrInFl_XXX SNVT_switch
AB[6].7 High Stack Pressure Alarm BI 104 DI 104 10104 nvoHiStkPrAl_XXX SNVT_switch
AB[6].8 Stack Damper Not Open Alarm BI 105 DI 105 10105 nvoStDpNtOAl_XXX SNVT_switch
AB[6].9 O2 Calibration Failed BI 106 DI 106 10106 nvoO2ClRtFld_XXX SNVT_switch
AB[6].10 Low Steam Pressure/Water Temp Alarm BI 107 DI 107 10107 nvoLoStPWTAl_XXX SNVT_switch
AB[6].11 Processor Test Fail Alarm BI 108 DI 108 10108 nvoPrTstFlAl_XXX SNVT_switch
AB[6].12 O2 Trim Internal Alarm BI 109 DI 109 10109 nvoO2TrmInAl_XXX SNVT_switch
AB[6].13 Firetube or Flextube 1 = Flextube BI 110 DI 110 10110 nvoFir_FlxTb_XXX SNVT_switch
AB[6].14 Reserved for Cleaver Brooks BI 111 DI 111 10111 nvoAB_6_14_XXX SNVT_switch
AB[6].15 VSD Limits Internal Alarm BI 112 DI 112 10112 nvoVSDLmInAl_XXX SNVT_switch
AB[7].0 Gas Actuator #2 Out Of Position Alarm BI 113 DI 113 10113 nvoGsAc2PsAl_XXX SNVT_switch
AB[7].1 Gas Actuator #2 Feedback Fail Low Alarm BI 114 DI 114 10114 nvoGsAc2LoAl_XXX SNVT_switch
AB[7].2 Gas Actuator #2 Feedback Fail High BI 115 DI 115 10115 nvoGsAc2HiAl_XXX SNVT_switch
Alarm
AB[7].3 Actuator Modbus Communication Error BI 116 DI 116 10116 nvoAcModCmEr_XXX SNVT_switch
AB[7].4 Air Actuator Modbus Comm Error Node 1 BI 117 DI 117 10117 nvoAAcMdCEr1_XXX SNVT_switch
AB[7].5 Gas Actuator Modbus Comm Error Node BI 118 DI 118 10118 nvoGsAMdCEr2_XXX SNVT_switch
2
AB[7].6 Gas Act #2 Modbus Comm Error Node 3 BI 119 DI 119 10119 nvoGsA2MdCE3_XXX SNVT_switch
AB[7].7 Oil Actuator Modbus Comm Error Node 5 BI 120 DI 120 10120 nvoOAcMdCEr5_XXX SNVT_switch
AB[7].8 FGR Actuator Modbus Comm Error Node BI 121 DI 121 10121 nvoFGRAMdCE7_XXX SNVT_switch
7
AB[7].9 Reserved BI 122 DI 122 10122 nvoAB_7_9_XXX SNVT_switch
AB[7].10 Reserved BI 123 DI 123 10123 nvoAB_7_10_XXX SNVT_switch
AB[7].11 Second Stage Outlet Water Temp Sensor BI 124 DI 124 10124 nvo2SOtWTSnF_XXX SNVT_switch
Failed
AB[7].12 Water Temperature Second Stage Out BI 125 DI 125 10125 nvoWtTp2SOtH_XXX SNVT_switch
High
AB[7].13 Air Actuator Manual Override Pushbutton BI 126 DI 126 10126 nvoAAcMnOBPr_XXX SNVT_switch
Pressed
AB[7].14 Gas Actuator #1 Manual Override BI 127 DI 127 10127 nvoGAc1MOBPr_XXX SNVT_switch
Pushbutton Pressed
AB[7].15 Gas Actuator #2 Manual Override BI 128 DI 128 10128 nvoGAc2MOBPr_XXX SNVT_switch
Pushbutton Pressed
AB[8].0 Oil Actuator Manual Override Pushbutton BI 129 DI 129 10129 nvoOAcMnOBPr_XXX SNVT_switch
Pressed
AB[8].1 FGR Actuator Manual Override BI 130 DI 130 10130 nvoFGRAMnOBP_XXX SNVT_switch
Pushbutton Pressed
AB[8].2 Fuel 3 Actuator #1 Manual Override BI 131 DI 131 10131 nvoFl3A1MOBP_XXX SNVT_switch
Pushbutton Pressed
AB[8].3 Fuel 3 Actuator #2 Manual Override BI 132 DI 132 10132 nvoFl3A2MOBP_XXX SNVT_switch
Pushbutton Pressed
AB[8].4 Communication from BMS Failed BI 133 DI 133 10133 nvoComBMSFld_XXX SNVT_switch
AB[8].5 Combustion Air Pressure High BI 134 DI 134 10134 nvoLoO2Shdn_XXX SNVT_switch
AB[8].6 Water Flow Low BI 135 DI 135 10135 nvoAB_8_6_XXX SNVT_switch
AB[8].7 Water Level Signal Failed BI 136 DI 136 10136 nvoAB_8_7_XXX SNVT_switch
AB[8].8 Remote Setpoint Signal Failed BI 137 DI 137 10137 nvoAB_8_8_XXX SNVT_switch
AB[8].9 Low O2 Shutdown BI 138 DI 138 10138 nvoAB_8_9_XXX SNVT_switch
AB[8].10 Air Actuator Fault BI 139 DI 139 10139 nvoAB_8_10_XXX SNVT_switch
AB[8].11 Fuel 1 Actuator 1 Fault BI 140 DI 140 10140 nvoAB_8_11_XXX SNVT_switch
AB[8].12 Fuel 1 Actuator 2 Fault BI 141 DI 141 10141 nvoAB_8_12_XXX SNVT_switch
AB[8].13 Fuel 2 Actuator 1 Fault BI 142 DI 142 10142 nvoAB_8_13_XXX SNVT_switch
AB[8].14 Fuel 2 Actuator 2 Fault BI 143 DI 143 10143 nvoAB_8_14_XXX SNVT_switch
AB[8].15 FGR Actuator Fault BI 144 DI 144 10144 nvoAB_8_15_XXX SNVT_switch
AB[9].0 Fuel 2 Actuator 2 Position Deviation BI 145 DI 145 10145 nvoAB_9_0_XXX SNVT_switch
AB[9].1 Fuel 2 Actuator 2 Feedback Low BI 146 DI 146 10146 nvoAB_9_1_XXX SNVT_switch
AB[9].2 Fuel 2 Actuator 2 Feedback High BI 147 DI 147 10147 nvoAB_9_2_XXX SNVT_switch
AB[9].3 Fuel 2 Actuator 2 Manual PB Pressed BI 148 DI 148 10148 nvoAB_9_3_XXX SNVT_switch
AB[9].4 VFD Feedback Low BI 149 DI 149 10149 nvoAB_9_4_XXX SNVT_switch
AB[9].5 VFD Feedback High BI 150 DI 150 10150 nvoAB_9_5_XXX SNVT_switch
AB[9].6 Master PIDE Instruction Fault BI 151 DI 151 10151 nvoAB_9_6_XXX SNVT_switch
AB[9].7 FGEN Fault BI 152 DI 152 10152 nvoAB_9_7_XXX SNVT_switch
AB[9].8 Outdoor Temp Sensor Failed BI 153 DI 153 10153 nvoAB_9_8_XXX SNVT_switch
AB[9].9 Combustion Air Temp Sensor Failed BI 154 DI 154 10154 nvoAB_9_9_XXX SNVT_switch
AB[9].10 Yokogawa O2 Sensor Fault BI 155 DI 155 10155 nvoAB_9_10_XXX SNVT_switch
AB[9].11 Mix O2 Sensor Calibration Fail BI 156 DI 156 10156 nvoAB_9_11_XXX SNVT_switch
AB[9].12 Mix O2 Enable BI 157 DI 157 10157 nvoAB_9_12_XXX SNVT_switch
AB[9].13 Air Actuator Not at Purge BI 158 DI 158 10158 nvoAB_9_13_XXX SNVT_switch
AB[9].14 VFD Not at Purge BI 159 DI 159 10159 nvoAB_9_14_XXX SNVT_switch
AB[9].15 Hawk 1000 system BI 160 DI 160 10160 nvoAB_9_15_XXX SNVT_switch
AB[10].0 Hawk 4500 - Increase MSG Size of Bool BI 161 DI 161 10161
to 15
AB[10].1 Stack Temp Econ Out Sensor Failed BI 162 DI 162 10162
AB[10].2 Econ In Water Temp Sensor Failed BI 163 DI 163 10163
AB[10].3 Fuel 3 Actuator 1 Fault BI 164 DI 164 10164
AB[10].4 Fuel 3 Actuator 2 Position Deviation BI 165 DI 165 10165
AB[10].5 Fuel 3 Actuator 2 Feedback Low BI 166 DI 166 10166
AB[10].6 Fuel 3 Actuator 2 Feedback High BI 167 DI 167 10167
AB[10].7 Fuel 3 Actuator 2 Fault BI 168 DI 168 10168
AB[10].8 Fuel 3 Actuator 1 Modbus Comm Error BI 169 DI 169 10169
AB[10].9 Fuel 3 Actuator 2 Modbus Comm Error BI 170 DI 170 10170
AB[10].10 Fuel 2 Actuator 2 Modbus Comm Error BI 171 DI 171 10171
AB[10].11 Return Temp Sensor Failed BI 172 DI 172 10172
AB[10].12 Water Shell Temp Sensor Failed BI 173 DI 173 10173
AB[10].13 Feedwater/Econ Out Temp Sensor Failed BI 174 DI 174 10174
AB[10].14 Feedwater Level Control Option Selected BI 175 DI 175 10175
AB[10].15 BI 176 DI 176 10176
AB[11].0 Slot8 Ch0 Bad Quality BI 177 DI 177 10177
AB[11].1 Slot8 Ch0 Low Alarm BI 178 DI 178 10178
AB[11].2 Slot8 Ch0 High Alarm BI 179 DI 179 10179
AB[11].3 Slot8 Ch1 Bad Quality BI 180 DI 180 10180
AB[11].4 Slot8 Ch1 Low Alarm BI 181 DI 181 10181
AB[11].5 Slot8 Ch1 High Alarm BI 182 DI 182 10182
AB[11].6 Slot8 Ch2 Bad Quality/Mix O2 Signal Fail BI 183 DI 183 10183
AB[11].7 Slot8 Ch2 Low Alarm BI 184 DI 184 10184
AB[11].8 Slot8 Ch2 High Alarm BI 185 DI 185 10185
AB[11].9 Slot8 Ch3 Bad Quality BI 186 DI 186 10186
AB[11].10 Slot8 Ch3 Low Alarm BI 187 DI 187 10187
AB[11].11 Slot8 Ch3 High Alarm BI 188 DI 188 10188
AB[11].12 Slot8 Ch4 Bad Quality BI 189 DI 189 10189
AB[11].13 Slot8 Ch4 Low Alarm BI 190 DI 190 10190
AB[11].14 Slot8 Ch4 High Alarm BI 191 DI 191 10191
AB[11].15 Spare BI 192 DI 192 10192
AB[12].0 Slot8 Ch5 Bad Quality BI 193 DI 193 10193
AB[12].1 Slot8 Ch5 Low Alarm BI 194 DI 194 10194
AB[12].2 Slot8 Ch5 High Alarm BI 195 DI 195 10195
AB[12].3 Slot8 Ch6 Bad Quality BI 196 DI 196 10196
AB[12].4 Slot8 Ch6 Low Alarm BI 197 DI 197 10197
AB[12].5 Slot8 Ch6 High Alarm BI 198 DI 198 10198
6.Navigate to the location of the SD card that will be used to transfer the Logix folder to the PLC. Select
Extract.
9.Use the Remove Hardware tool to safely eject the SD card from the computer.
10. Install the SD card into the PLC SD card slot. The PLC switch should be in REM.