DESCRIPTION
SECTION - A
iJ-PjglgljBUTION BOARD
Wlain Distributuion board designated MDB and distribution boards (DB) shall be made from 16 SWG sheet steel. The DB shall be
designed, fabricated & manufactured recessed type The sheet metal work shall be cleaned down to bare shining rnetal degreased,
derusted & painted with TWO base coats of .antirust RED paint.
The sheet metal work shall be finished in TWO coats of powder paint. The color and shade shall be as approved by the Engineer.
The distribution Board shall be complete with all internal wiring, tags, identification labels, SPN & E copper busbars, accessories etc.
DR should be provided with the armored glands.
The insulation shall be heat shrinkable type or as directed by the Engineer.
DB 4+PDS
DB GF __ ^
INCOMING __ ______ -
C1 No. 40 Amps DP MCB RC-10kA
01 No. 2 Amp fuse
01 No. Phase Indication Lamp.
MASONRY 4+ODS,
UGWT 200QGAL.
JCiL. EC _[ R1CAL WOR!
UNI
DESCRIPTION
SECTION - A ___________
LT DISTRIBUTION BOARD
Wlain Distribution board designated MDB and distribution boards (DB) shall be made from 16 SWG sheet steel. The DB shall be
designed, fabricated & manufactured recessed type The sheet metal work shall be cleaned down to bare shining rnetal degreased,
derusted & painted with TWO base coats of .antirust RED paint.
The sheet metal work shall be finished in TWO coats of powder paint. The color and shade shall be as approved by the Engineer.
The distribution Board shall be complete with all internal wiring, tags, identification labels, SPN & E copper busbars, accessories etc.
DB should be provided with the armored glands.
The insulation shall be heat shrinkable type or as directed by the Engineer.
DB 4+PDS
DB GF __ ^
INCOMING __ ______ -
C1 No. 40 Amps DP MCB RC-10kA
01 No. 2 Amp fuse
01 No. Phase Indication Lamp.
approvea uy me i iiyiiiw ...................... .......... ... ,s anew
be complete with oil internal wiring, tags, identification labels, SPN & E copper busbars, accessories etc. on should be ptovided with
the armored glands.
The insulation shall he heat shrinkable type or as directed by the Engineer.
DB 4+PDS ______________________________________ '
DB GF ________________________________
INCOMING _____________ '
C1 No 40 Amps DP MCB RC-10kA
1 No. 2 Amp fuse
01 No. Phase Indication Lamp.
OUTGOINGS
1 No. 20 Amps DP MCB RC-10KA
03 No. 6 Amps SP MCB RC-10RA (01 Spare)
2 Nos. 10 Amps SP MCB RC-10KA (01 Spare)
DB FF __ __ ________
INCOMING
01 No.20 Amps DP MCB RC-10kA 01 No. 2 Amp fuse 01 No. Indication Lamp.
OUTGOINGS
3 No. 6 Amps SP MCB RC-10kA.
0? Nos 10 Amps SP MCB RC-10KA (01 Spare)
approvea uy me i iiyiiiw ...................... .......... ... ,s anew
be complete with oil internal wiring, tags, identification labels, SPN & E copper busbars, accessories etc. on should be ptovided with
the armored glands.
The insulation shall he heat shrinkable type or as directed by the Engineer.
DB 4+PDS ______________________________________ '
DB GF ________________________________
INCOMING _____________ '
C1 No 40 Amps DP MCB RC-10kA
01 No. 2 Amp fuse
01 No. Phase Indication Lamp.
OUTGOINGS
1 No. 20 Amps DP MCB RC-10KA
3 No. 6 Amps SP MCB RC-10RA (01 Spare)
2 Nos. 10 Amps SP MCB RC-10KA (01 Spare)
DB FF __ __ ________
INCOMING
01 No.20 Amps DP MCB RC-10kA 01 No. 2 Amp fuse 01 No. Indication Lamp.
OUTGOINGS
3 No. 6 Amps SP MCB RC-10kA.
0? Nos 10 Amps SP MCB RC-10KA (01 Spare)
OB 4-i-ORDS
OB-GF
INCOMING
31 - 40 Amps DP MCB RC-'iOkA. 3 1 - 2 Amps Protection fuses.
01- Phase Indication Lamp OUTGOING
04-10 Amps SP MCB RC-10KA 01-20 Amps DP MCB RC-10KA
DB-FF
INCOMING
01 - 20 Amps DP MCB RC-1 OkA. 01 - 2 Amps Protection fuses 01- Phase Indication Lamp OUTGOING
04-10 Amps SP MCB RC-1 OKA
SECTION - B ___________________
OB 4-i-ORDS
OB-GF
INCOMING
31 - 40 Amps DP MCB RC-'iOkA. 3 1 - 2 Amps Protection fuses.
01- Phase Indication Lamp OUTGOING
04-10 Amps SP MCB RC-10KA 01-20 Amps DP MCB RC-10KA
DB-FF
INCOMING
01 - 20 Amps DP MCB RC-1 OkA. 01 - 2 Amps Protection fuses 01- Phase Indication Lamp OUTGOING
04-10 Amps SP MCB RC-1 OKA
SECTION - B ___________________

LIGHT FIXTURES
Wiring of light circuit from Distribution Board
light point or fan point, on
including circuit
W 'UM riiee^nm switches the same circuit . r,rtie nob- single core /..o oqrnrn rvu
insulated 600/1000 Volts grade solid/stranded
copper conductor cables in concealed PVC
conduits ( conduits partly shared ) including F:VC conduit, conduit accessories etc.
Wring from switch to light or fan point with 3 nos. single core 1.5 Sqmm PVC insulated 600/1000 Volts grade solid or stranded
copper conductor cables in concealed PVC conduit including PVC conduit, Conduit accessories, etc. complete. ( conduit partly
shared )
Wiring of circuit from Distribution Board to 5A, 230Volts, 2&3 pin switched socket outlet with 3 nos. one core 2.5 Sqmm PVC
insulated 600/1000 Volts grade solid or stranded copper conductor cables in concealed PVC conduit including PVC conduit, Conduit
accessories etc. complete. ( conduit partly shared )
Wiring from 5Amps, 2&3 pin socket to socket with 3 nos. one core 2.5 Sqmm PVC insulated 600/1000 Volts grade solid or
stranded coppei conductor cables in concealed PVC conduit including PVC conduit, Conduit accessories etc complete. ( conduit
SECTION -c partly shared )
Wiring of light circuit from Distribution Board
light point or fan point, on
including circuit
W 'UM riiee^nm switches the same circuit . r,rtie nob- single core /..o oqrnrn rvu
insulated 600/1000 Volts grade solid/stranded
copper conductor cables in concealed PVC
conduits ( conduits partly shared ) including F:VC conduit, conduit accessories etc.
Wring from switch to light or fan point with 3 nos. single core 1.5 Sqmm PVC insulated 600/1000 Volts grade solid or stranded
copper conductor cables in concealed PVC conduit including PVC conduit, Conduit accessories, etc. complete. ( conduit partly
shared )
Wiring of circuit from Distribution Board to 5A, 230Volts, 2&3 pin switched socket outlet with 3 nos. one core 2.5 Sqmm PVC
insulated 600/1000 Volts grade solid or stranded copper conductor cables in concealed PVC conduit including PVC conduit, Conduit
accessories etc. complete. ( conduit partly shared )
Wiring from 5Amps, 2&3 pin socket to socket with 3 nos. one core 2.5 Sqmm PVC insulated 600/1000 Volts grade solid or
stranded coppei conductor cables in concealed PVC conduit including PVC conduit, Conduit accessories etc complete. ( conduit
partly shared )

SECTION - D
LIGHT FIXTURES

p-01
"1x36 watt flourescent light complete with lamp philips type TMS-015/136 or equivalent.
2x36 watt flourescent light fixture complete with lamp philips type TMS-015/236 or equivalent.

or Phase Indication Lamp OUTGOING

04-10 Amps SP MOB RC-10KA SECTION - B


Supply, installation, testing & commissioning of the following types of light fixtures including electronic ballast .Color 84 TL
lamp,internal wiring complete with all mounting accessories as per architectural arrangements/requirements. as acceptibly supplied
and installed and as approved by the Engineer.
1x36 watt flourescent light fixture complete with lamp philips type TMS-015/136 with GDL Reflector or equivalenL
4x18 Watt flourescent lighting fixture complete with lamp Philips type TBS-300/418 or equivalent.
1x18 watt flourescent light complete with lamp philips type TMS-015/118 or equivalent.
1x25 Watts Philips made DecoTwist complete with energy saver or equivalent.
LIGHT FIXTURES

p-01
"1x36 watt flourescent light complete with lamp philips type TMS-015/136 or equivalent.
2x36 watt flourescent light fixture complete with lamp philips type TMS-015/236 or equivalent.

or Phase Indication Lamp OUTGOING

04-10 Amps SP MOB RC-10KA SECTION - B


Supply, installation, testing & commissioning of the following types of light fixtures including electronic ballast .Color 84 TL
lamp,internal wiring complete with all mounting accessories as per architectural arrangements/requirements. as acceptibly supplied
and installed and as approved by the Engineer.
1x36 watt flourescent light fixture complete with lamp philips type TMS-015/136 with GDL Reflector or equivalenL
4x18 Watt flourescent lighting fixture complete with lamp Philips type TBS-300/418 or equivalent.
1x18 watt flourescent light complete with lamp philips type TMS-015/118 or equivalent.
1x25 Watts Philips made DecoTwist complete with energy saver or equivalent.
| Wiring from SAmps, 2&3 pin socket to socket wi;n 3 nos. one core 2.5 Sqmm PVC insulated 600/;000 Volts grade solid or stranded
copper I conductor cables in concealed PVC conduit t including PVC conduit, Conduit accessories, j etc complete. ( conduit partly
shared )
i- SECTION - D _____________________________
; WIRING ACCESSORIES
gang 1 way switches, size concealed back box.
gang 1 way switches size concealed back box.
gang t way switches size concealed back box.
= 10 Anp, 250 Volts, 1
K inducing appropriate
I 10 Amp, 250 Volts, 2
including appropriate
h 10 Amp, 250 Volts, 3
including appropriate
:
5 Anps, 250Volts, 2&3 pin switch socket
t, unit in duriing appropriate size back box
k ..
5
t.
Fan Dimmer with switch/back box along with wiring accessories.
| Wiring from SAmps, 2&3 pin socket to socket wi;n 3 nos. one core 2.5 Sqmm PVC insulated 600/;000 Volts grade solid or stranded
copper I conductor cables in concealed PVC conduit t including PVC conduit, Conduit accessories, j etc complete. ( conduit partly
shared )
i- SECTION - D _____________________________
; WIRING ACCESSORIES
gang 1 way switches, size concealed back box.
gang 1 way switches size concealed back box.
gang t way switches size concealed back box.
= 10 Anp, 250 Volts, 1
K inducing appropriate
I 10 Amp, 250 Volts, 2
including appropriate
h 10 Amp, 250 Volts, 3
including appropriate
:
5 Anps, 250Volts, 2&3 pin switch socket
t, unit in duriing appropriate size back box
k ..
5
t.
Fan Dimmer with switch/back box along with wiring accessories.
DESCRIPTION
SECTION - E l.T Cables
10 sq mm , 2 core PVC/PVC standard copper conductor cable, 300/500v grade in already installed conduit.
6 sqmm, 2 core PVC/PVC stranded copper conductor cable, 300/500 V grade in already installed conduit /or, cable tray.
4 sq mm , 2 core PVC/PVC standard copper
conductor cable, 3Q0/500v grade in already installed conduit.
SECTION - F EARTHING
10 sqmm, 1 core PVC insulated stranded copper conductor cable, 450/ 750V grade in already installed PVC conduits 6 sqmm, 1
core GREEN PVC insulated stranded
utle'450,750V 9rade
DESCRIPTION
SECTION - E l.T Cables
10 sq mm , 2 core PVC/PVC standard copper conductor cable, 300/500v grade in already installed conduit.
6 sqmm, 2 core PVC/PVC stranded copper conductor cable, 300/500 V grade in already installed conduit /or, cable tray.
4 sq mm , 2 core PVC/PVC standard copper
conductor cable, 3Q0/500v grade in already installed conduit.
SECTION - F EARTHING
10 sqmm, 1 core PVC insulated stranded copper conductor cable, 450/ 750V grade in already installed PVC conduits 6 sqmm, 1
core GREEN PVC insulated stranded
utle'450,750V 9rade

&>> electrode for the earthing of LT


j 4 sq mm , core PVC/PVC standard copper

j conductor cable. iOO/SQOv gtutlG In already installed ['


conduit,
SECTION - F ____________ I
EARTHING ________________________
10 sqrnm, I corn I'VClnsiilulud stranded copper conductor cable, <1 SO/ 750V grade in already installed PVC conduits !
6 sqinm, 1 core GREEN PVC insulated strands
copper conductor cable, 450/750V grade in alreac j installed PVC conduits
; Earth electrode for the earthing of LT
electrical system . The Earth {. electrode shall comprise 600 x 600 x 3mm
; Thick Copper plate with I our nos 1/2 inch > die copper nuts, bolts and washeis, 3/OSWG HDHC Copper wire as earthing leads,
TWO 1 inch dia Gl pipe (15 feet long), lime and charcoal (Ratio 1:3), inspection chamber (CC 1:4:5), light duty Cl cover, excavation
& backfilling, rill accessories as per site requirements &
; as directed by ihe Engineer, complete , A pit of dimensions 4 feet x 4 feet & 15feet I,' deep shall be excavated in the ground.
Thf! !
]- ime and charcoal shall be mixed |. throughly in the ratio of 1:3 with ONE foot lhick hard packed bed in pit. The Copper i. plate
with earthing leads shall be placed ; vert,cal|y abovf2 the lime and charcoal bed.
, The ,!nos 3/OSWG Earthing leads shall be !.. conr|cc,ed diagonally to the nuts and bolts I, tflt C0PPer Plate, brought out through he P'Pe
a
PtO the first nnrth rfinnorlinn j conductor cable. iOO/SQOv gtutlG In already installed [' conduit,
SECTION - F ____________ I
EARTHING ________________________
10 sqrnm, I corn I'VClnsiilulud stranded copper conductor cable, <1 SO/ 750V grade in already installed PVC conduits !
6 sqinm, 1 core GREEN PVC insulated strands
copper conductor cable, 450/750V grade in alreac j installed PVC conduits
; Earth electrode for the earthing of LT
electrical system . The Earth {. electrode shall comprise 600 x 600 x 3mm
; Thick Copper plate with I our nos 1/2 inch > die copper nuts, bolts and washeis, 3/OSWG HDHC Copper wire as earthing leads,
TWO 1 inch dia Gl pipe (15 feet long), lime and charcoal (Ratio 1:3), inspection chamber (CC 1:4:5), light duty Cl cover, excavation
& backfilling, rill accessories as per site requirements &
; as directed by ihe Engineer, complete , A pit of dimensions 4 feet x 4 feet & 15feet I,' deep shall be excavated in the ground.
Thf! !
]- ime and charcoal shall be mixed |. throughly in the ratio of 1:3 with ONE foot lhick hard packed bed in pit. The Copper i. plate
with earthing leads shall be placed ; vert,cal|y abovf2 the lime and charcoal bed.
, The ,!nos 3/OSWG Earthing leads shall be !.. conr|cc,ed diagonally to the nuts and bolts I, tflt C0PPer Plate, brought out through he P'Pe
a
PtO the first nnrth rfinnorlinn
SECTION - G
MgCELLANEGuantMs

Su.onlv. installation

iu yivc ail dll


displacement of minimum 11700 Cu. ft./min. i he ceiling fan shall comprise circular fan body metallic fan blades, down rod of
suitable dia & length, AC capacitor, internal wiring, terminals all installation & operational accessories as per tender specifications,
as per site requirements and as directed by the Engineer
Ceiling hook properly installed in the slab, as directed by the Engineer.
Supply, installation, testing & commissioning of 9 inch (300mm) dia exhaust fan The 9" exhaust fan shall be suitable to give an air
disolscement of minimum 875 Cu.ft./min. The exhaust fan shall comprise plastic fan blades, square plastic body with circular fan
opening, all installation & operational accessories as per tender specifications, as per site requirements and as directed by the
Engineer. The exhaust fan shall be suitable for installation in glazing/ glass of windows or ventillators as required.
Su.onlv. installation

SECTION - G
MgCELLANEGuantMs

iu yivc ail dll


displacement of minimum 11700 Cu. ft./min. i he ceiling fan shall comprise circular fan body metallic fan blades, down rod of
suitable dia & length, AC capacitor, internal wiring, terminals all installation & operational accessories as per tender specifications,
as per site requirements and as directed by the Engineer
Ceiling hook properly installed in the slab, as directed by the Engineer.
Supply, installation, testing & commissioning of 9 inch (300mm) dia exhaust fan The 9" exhaust fan shall be suitable to give an air
disolscement of minimum 875 Cu.ft./min. The exhaust fan shall comprise plastic fan blades, square plastic body with circular fan
opening, all installation & operational accessories as per tender specifications, as per site requirements and as directed by the
Engineer. The exhaust fan shall be suitable for installation in glazing/ glass of windows or ventillators as required.