Professional Documents
Culture Documents
About Nexans 4
Symbols 5
Accessories 7
Straight joints 29
Busbars 36
Underground 41
EAXeCVB 42
EAXeCWB-EAXeCeWB 45
EIAVB 48
EVAVB-F2 3,6 / 6 kV 51
EXeCVB 54
With energy at the basis of its development, Nexans, worldwide expert in the cable industry, offers an extensive range of
cables and cabling solutions.
The Group is a global player in the energy transmission and distribution, industry and building markets. Nexans addresses a
wide series of market segments: from energy and telecom networks to energy resources (wind turbines, photovoltaic, oil
and gas, and mining) to transportation (shipbuilding, aerospace, automotive and automation, and railways).
Nexans is a responsible industrial company that regards sustainable development as integral to its global and operational
strategy. Continuous innovation in products, solutions and services, employee development and commitment, customer
orientation and the introduction of safe industrial processes with limited environmental impact are among the key initiatives
that place Nexans at the core of a sustainable future.
With an industrial presence in 40 countries and commercial activities worldwide, Nexans employs 25,000 people and had
sales in 2012 of nearly 7.2 billion euros. Nexans is listed on NYSE Euronext Paris, compartment A.
Weather resistance
Interface
Longitudinally watertight
Water proof
Fire retardant
Chemical resistance
Accessories
A complete range of terminations, joints, separable connectors and
equipment bushings up to 42 kV. Terminations and joints are available in heat or
cold-shrinkable technologies as well as slip-on. For paper insulated cables, a full
range of terminations and joints (including transition joints) is also available.
Separable connectors are produced EPDM while equipment bushings are made
in epoxy.
Medium voltage heat-shrinkable terminations and joints
Suitable for single or 3-cores, paper or polymeric insulated cables up to 36 kV.
The high quality heat-shrinkable non-tracking tubes and stress control tubes of
the terminations provide long-term performance and the highest reliability for
indoor as well as for outdoor applications. The heat-shrinkable joints offer an
easy to install and reliable connection. If required, a galvanized steel case
can be supplied to protect the joint from external impact and ground pressure.
Medium voltage cold-shrinkable terminations and joints
Suitable for single core, paper or polymeric insulated cables up to 36 kV, these
cold-shrinkable accessories set new standards in installation technique. All
functions are integrated in single piece which is factory installed on plastic
supporting tubes. After standard cable preparation, the pre-expanded
accessory is positioned over the cable and shrunk by extracting the supporting
tubes. Installation is considerably simpler and faster than with any other system
presently available.
Medium voltage slip-on terminations
Suitable for single core polymeric insulated cables up to 42 kV, this range of
pre-molded slip-on terminations is made of silicone rubber. Terminations in
silicone-rubber are single pieces and can be used for indoor and outdoor
applications.
Medium voltage slip-on premolded separable connectors
A range of pre-molded separable connectors are available in EPDM rubber for
plug-in or bolted connections up to 36 kV and 1250 A. Available in straight,
elbow or "T" versions, these connectors offer a safe to touch connection to
switch gear and transformers. Jumpers can be supplied with a combination of
connectors and terminations at each end. An EPDM surge arrestor is available.
Medium voltage epoxy resin equipment bushings
A large range of equipment bushings for in-oil, in-air or in-gas and for plug-in or
bolted versions up to 36 kV and 1250 A. A variety of fixing flanges for different
clamping (or welding) systems is available as well as plug-in type epoxy
termination.
Description
To connect polymeric insulated cable to equipment. For use indoors in controlled
environmental conditions and subject to light condensation.
Standards
International HD 629.1 S2
Product List
Nexans Name Cond. section, range Diameter over insulation, Max. ope. volt.
ref. (mm) range (mm) (kV)
ITK - Indoor cold-shrinkable
ITK 300 .. 800 15.0 .. 33.0
termination
= Make to order, = In stock
Description
To connect polymeric insulated cable to equipment. For use indoors in controlled
environmental conditions and subject to light condensation.
Standards
International HD 629.1 S2
Description
To connect 3-core polymeric insulated cable to equipment. For use indoors in
controlled environmental conditions and subject to light condensation.
Standards
International HD 629.1 S2
Description
Provides a simple and quick methos of stress relieving on screened polymeric
cables.
This product is also part of our Windlink offer dedicated to wind turbines.
Standards
International HD 629.1 S2
Description
To connect polymeric insulated cable to equipment. For use outdoors and
exposed to prolonged sunshine and other weather conditions.
Standards
International HD 629.1 S2
Description
To connect polymeric insulated cable to equipment. For use outdoors and
exposed to prolonged sunshine and other weather conditions.
Standards
International HD 629.1 S2
Description
To connect 3-core polymeric insulated cable to equipment. For use outdoors and
exposed to prolonged sunshine and other weather conditions.
Standards
International HD 629.1 S2
Description
Use
This range of separable connectors and bushings enables the connection of a
synthetic insulated MV cable to a MV equipment such as transformers, motors,
switchboards, switches.
Standards
International CENELEC EN 50180;
CENELEC HD 629.1; IEC 60137
Characteristics
Usage characteristics
Interface A (250 A)
Interface
A (250 A)
Description
Use
This range of separable connectors and bushings enables the connection of a
synthetic insulated MV cable to a MV equipment such as transformers, motors,
switchboards, switches.
Description
Use
This range of separable connectors and bushings with an interface C enables the
connection of a synthetic insulated MV cable to a MV equipment such as
transformers, motors, switchboards, switches.
These products are part of our rollingstock offer and also part of our windlink
offer dedicated to windturbines.
Standards
International CENELEC EN 50180;
CENELEC HD 629.1; IEC 60137
Description
Use
This range of separable connectors enables the connection of a synthetic
insulated MV cable to a MV equipment such as transformers, motors,
switchboards, switches.
The products that are presented are designed for EDF cables. For any other
standard, contact us.
Lexicon
CS = Separable connector
E = Square
D = Straight
M = Male
T = in T
2T = in double T Standards
International HD 629.1 S2
Product List
Nexans ref. Name Interface Connector shape Connector type
944TB 944TB - Interface F - Asymmetrical tee connector A (250 A) T-shaped Female
= Make to order, = In stock
Straight joints
The Nexans joints are built for modern cable installations. They control the electrical field and prevent humidity to get in the
conductors and in the insulating layers.
Cold-shrinkable joint
for synthetic insulated cables
Description
For jointing polymeric cable to be laid in air or directly buried. The product is fully
screened and fully submersible.
Standards
International HD 629.1 S2
Description
For jointing copper wire screened polymeric cable to be laid in air or directly
buried. The product is fully screened and fully submersible.
This product can be installed where installation space is limited (minimum 1
meter).
Standards
International HD 629.1 S2
Characteristics
Construction characteristics
Technology Cold shrink
Conductor material Copper or Aluminium
Kit contents
Description
For jointing copper wire screened polymeric cable to be laid in air or directly
buried. The product is fully screened and fully submersible.
Standards
International HD 629.1 S2
Characteristics
Construction characteristics
Technology Cold shrink
Conductor material Copper or Aluminium
Kit contents
Busbars
Description
Busbars Type 'IMT' for 3 up to 36 kV and up to 5000 A.
First insulation: heat-shrinkable medium voltage tube.
Second insulation: polymerised resin (polyester or epoxy) reinforced with mineral
charges.
Third layer: resin blocks - fixing the fases together; short-circuits withstanding;
limit the spread of fire.
Fourth layer: metal encloser according standard IEC 60271-200 (5.102).
Standards
Type tested according standards IEC 60271-200 and IEC 62271-1.
International IEC 60271-200;
Fire resistant according standard IEC 60439-1 & -2: resistance to abnormal heat IEC 60439-1-2
and fire, verification to flame-propagation and verification of fire resistance.
This product is part of the Keylios offer to connect photovoltaic projects.
Heat-shrinkable joint
for synthetic insulated cables
Description
For jointing polymeric cable to be laid in air or directly buried. The product is fully
screened and fully submersible.
Standards
International HD 629.1 S2
Heat-shrinkable joint
for synthetic insulated cables
Description
For jointing 3-core polymeric cable to be laid in air or directly buried. The product
is fully screened and fully submersible.
Standards
International HD 629.1 S2
Underground
From humble beginnings, power distribution systems have grown increasingly complex: Edison's 1882 station in New York
City served six square miles, while today's networks cover entire cities and regions, providing the tools and conveniences of
modern life.
Medium and low-voltage cables (1kV to 60kV) are used in the basic distribution network that brings power from high-
voltage substations to cities and remote areas. To provide this needed power for change, Nexans has been leading the way
in new materials and designs for distribution cables and networks. We also master installation techniques in some of the
toughest environments imaginable, including submarine, aerial and dense urban conditions.
EAXeCVB
Description
Application
Power distribution cable, aluminium conductor, XLPE insulated.
(with longitudinal watertighness at the screen level)
Design
1. Aluminium conductor
2. Semi-conducting XLPE extruded conductor screen
3. XLPE extruded insulation
4. Semi-conducting XLPE extruded conductor screen
5. Semi-conduting swelling tape
6. Copper wires screen + counter helix copper tape
7. Swelling tape
8. Red PVC oversheath
Standards
Installation National NBN HD 620
In cable channel
In tube
with or without protection
In industry
In open air
Longitudinally watertight Mechanical resistance to impacts Max.conductor temp.in service Weather resistance
Yes Good 90 C Good
EAXeCVB
Characteristics
Construction characteristics
Conductor material Aluminium
Conductor shape Round, stranded
Material of the inner semi-conductor Semi-conducting compound
Insulation Extruded XLPE
Material of the external semi-conductor Semi-conducting compound
Screen Copper wires + copper tape
Longitudinally watertight Yes
Outer sheath PVC
Dimensional characteristics
Number of cores 1
Mechanical characteristics
Mechanical resistance to impacts Good
Usage characteristics
Short-circuit max. conductor temperature 250 C
Max. conductor temperature in service 90 C
Weather resistance Good
EAXeCVB
Av. insul. Screen Average sheath Max. outer Approx. Max. ope.
Name thickness section thickness diam. weight volt.
[mm] [mm] [mm] [mm] [kg/km] [kV]
EAXeCVB 8,7/15 kV 1 x
4.5 16 2.6 33.0 940 17.5
50/16 np
EAXeCVB 8,7/15 kV 1 x
4.5 25 2.6 36.0 1290 17.5
95/25 np
EAXeCVB 8,7/15 kV 1 x
4.5 25 2.9 40.0 1580 17.5
150/25 np
EAXeCVB 8,7/15 kV 1 x
4.5 25 3.1 44.0 2010 17.5
240/25 np
EAXeCVB 8,7/15 kV 1 x
4.5 35 3.3 50.0 2760 17.5
400/35 np
EAXeCVB 8,7/15 kV 1 x
4.5 35 3.5 56.0 3710 17.5
630/35 np
EAXeCVB 8,7/15 kV 1 x
4.5 35 3.7 68.0 5370 17.5
1000/35 np
EAXeCVB 12/20 kV 1 x
5.5 16 2.6 35.0 1030 24
50/16 np
EAXeCVB 12/20 kV 1 x
5.5 25 2.7 39.0 1410 24
95/25 np
EAXeCVB 12/20 kV 1 x
5.5 25 3.0 42.0 1710 24
150/25 np
EAXeCVB 12/20 kV 1 x
5.5 25 3.1 46.0 2140 24
240/25 np
Longitudinally watertight Mechanical resistance to impacts Max.conductor temp.in service Weather resistance
Yes Good 90 C Good
EAXeCVB
Av. insul. Screen Average sheath Max. outer Approx. Max. ope.
Name thickness section thickness diam. weight volt.
[mm] [mm] [mm] [mm] [kg/km] [kV]
EAXeCVB 12/20 kV 1 x
5.5 35 3.3 52.0 2900 24
400/35 np
EAXeCVB 12/20 kV 1 x
5.5 35 3.5 58.0 3880 24
630/35 np
EAXeCVB 12/20 kV 1 x
5.5 35 3.8 71.0 5600 24
1000/35 np
EAXeCVB 18/30 kV 1 x
8.0 16 2.8 41.0 1330 36
50/16 np
EAXeCVB 18/30 kV 1 x
8.0 25 2.9 44.0 1730 36
95/25 np
EAXeCVB 18/30 kV 1 x
8.0 25 3.2 47.0 2080 36
150/25 np
EAXeCVB 18/30 kV 1 x
8.0 25 3.3 51.0 2540 36
240/25 np
EAXeCVB 18/30 kV 1 x
8.0 35 3.5 57.0 3350 36
400/35 np
EAXeCVB 18/30 kV 1 x
8.0 35 3.7 63.0 4380 36
630/35 np
EAXeCVB 18/30 kV 1 x
8.0 35 4.0 76.0 6190 36
1000/35 np
EAXeCVB 20,8/36 kV 1 x
8.8 25 3.2 49.0 2190 41.5
150/25 np
EAXeCVB 20,8/36 kV 1 x
8.8 25 3.4 53.0 2680 41.5
240/25 np
EAXeCVB 20,8/36 kV 1 x
8.8 35 3.6 59.0 3510 41.5
400/35 np
EAXeCVB 20,8/36 kV 1 x
8.8 35 3.8 65.0 4550 41.5
630/35 np
EAXeCVB 20,8/36 kV 1 x
8.8 35 4.0 78.0 6360 41.5
1000/35 np
Selling information
All our cables are longitudinally watertight at the metallic screen level (swelling tapes)
Longitudinally watertight Mechanical resistance to impacts Max.conductor temp.in service Weather resistance
Yes Good 90 C Good
EAXeCWB-EAXeCeWB
Description
Application
Power distribution cable, aluminium conductor, XLPE insulated.
EAXeCWB cables are provided with longitudinal watertighness at the screen level
EAXeCeWB : idem EAXeCWB cables + transversal watertighness over the
screen
Design
1. Aluminium conductor
2. Semi-conducting XLPE extruded conductor screen
3. XLPE extruded insulation
4. Semi-conducting XLPE extruded conductor screen
5. Semi-conduting swelling tape
6. Copper wires screen + counter helix copper tape
7. Swelling tape Standards
8. Aluminium tape bonded to the PE sheath (only for EAXeCeWB cables) National NBN HD 620
9. Red PE oversheath
Installation
In cable channel
In tube
with or without protection
In industry
In open air
Longitudinally watertight Mechanical resistance to impacts Max.conductor temp.in service Weather resistance
Yes Good 90 C Good
EAXeCWB-EAXeCeWB
Characteristics
Construction characteristics
Conductor material Aluminium
Conductor shape Round, stranded
Material of the inner semi-conductor Semi-conducting compound
Insulation Extruded XLPE
Material of the external semi-conductor Semi-conducting compound
Screen Copper wires + copper tape
Longitudinally watertight Yes
Outer sheath PE
Dimensional characteristics
Number of cores 1
Mechanical characteristics
Mechanical resistance to impacts Good
Usage characteristics
Max. conductor temperature in service 90 C
Short-circuit max. conductor temperature 250 C
Weather resistance Good
EAXeCWB-EAXeCeWB
Av. insul. Screen Average sheath Max. outer Approx. Max. ope.
Name thickness section thickness diam. weight volt.
[mm] [mm] [mm] [mm] [kg/km] [kV]
EAXeCWB 8,7/15 kV 1 x
4.5 16 2.6 33.0 940 17.5
50/16 np
EAXeCWB 8,7/15 kV 1 x
4.5 25 2.6 36.0 1290 17.5
95/25 np
EAXeCWB 8,7/15 kV 1 x
4.5 25 2.9 40.0 1580 17.5
150/25 np
EAXeCeWB 8,7/15 kV 1 x
4.5 25 2.9 40.0 1580 17.5
150/25 np
EAXeCeWB 8,7/15 kV 1 x
4.5 25 3.1 44.0 2010 17.5
240/25 np
EAXeCWB 8,7/15 kV 1 x
4.5 25 3.1 44.0 2010 17.5
240/25 np
EAXeCWB 8,7/15 kV 1 x
4.5 35 3.3 50.0 2760 17.5
400/35 np
EAXeCWB 8,7/15 kV 1 x
4.5 35 3.5 56.0 3710 17.5
630/35 np
EAXeCWB 8,7/15 kV 1 x
4.5 35 3.7 68.0 5370 17.5
1000/35 np
EAXeCWB 12/20 kV 1 x
5.5 16 2.6 35.0 1030 24
50/16 np
EAXeCWB 12/20 kV 1 x
5.5 25 2.7 39.0 1410 24
95/25 np
Longitudinally watertight Mechanical resistance to impacts Max.conductor temp.in service Weather resistance
Yes Good 90 C Good
EAXeCWB-EAXeCeWB
Av. insul. Screen Average sheath Max. outer Approx. Max. ope.
Name thickness section thickness diam. weight volt.
[mm] [mm] [mm] [mm] [kg/km] [kV]
EAXeCWB 12/20 kV 1 x
5.5 25 3.0 42.0 1710 24
150/25 np
EAXeCWB 12/20 kV 1 x
5.5 25 3.1 46.0 2140 24
240/25 np
EAXeCWB 12/20 kV 1 x
5.5 35 3.3 52.0 2900 24
400/35 np
EAXeCWB 12/20 kV 1 x
5.5 35 3.5 58.0 3880 24
630/35 np
EAXeCWB 12/20 kV 1 x
5.5 35 3.8 71.0 5600 24
1000/35 np
EAXeCWB 18/30 kV 1 x
8.0 16 2.8 41.0 1330 36
50/16 np
EAXeCWB 18/30 kV 1 x
8.0 25 2.9 44.0 1730 36
95/25 np
EAXeCWB 18/30 kV 1 x
8.0 25 3.2 47.0 2080 36
150/25 np
EAXeCWB 18/30 kV 1 x
8.0 25 3.3 51.0 2540 36
240/25 np
EAXeCWB 18/30 kV 1 x
8.0 35 3.5 57.0 3350 36
400/35 np
EAXeCWB 18/30 kV 1 x
8.0 35 3.7 63.0 4380 36
630/35 np
EAXeCWB 18/30 kV 1 x
8.0 35 4.0 76.0 6190 36
1000/35 np
EAXeCWB 20,8/36 kV 1 x
8.8 25 3.2 49.0 2190 41.5
150/25 np
EAXeCeWB 20,8/36 kV 1 x
8.8 25 3.4 53.0 2680 41.5
240/25 np
EAXeCWB 20,8/36 kV 1 x
8.8 25 3.4 53.0 2680 41.5
240/25 np
EAXeCWB 20,8/36 kV 1 x
8.8 35 3.6 59.0 3510 41.5
400/35 np
EAXeCWB 20,8/36 kV 1 x
8.8 35 3.8 65.0 4550 41.5
630/35 np
EAXeCWB 20,8/36 kV 1 x
8.8 35 4.0 78.0 6360 41.5
1000/35 np
Longitudinally watertight Mechanical resistance to impacts Max.conductor temp.in service Weather resistance
Yes Good 90 C Good
EIAVB
Description
Application
For medium voltage installations
Design
1. Copper core
2. Semi-conducting paper tape
3. Impregnated paper tape insulation
4. Belted paper tape
5. Lead sheath
6. Asphalted tape
7. Jute bedding
8. Steel tapes
9. PVC sheath
Installation
In cable channel
In tube
With or without protection
In open air
In industry
EIAVB
Characteristics
Construction characteristics
Conductor material Copper
Wire colour Ecru - blue - red
Insulation Impregnated paper tape
Inner sheath Lead
Material of bedding Jute
Armour type Two steel tapes
Outer sheath PVC
Sheath colour Red
Dimensional characteristics
Number of cores 3
Mechanical characteristics
Impact resistance (EN 187 000) 60 J
Usage characteristics
Chemical resistance Excellent
Operating temperature, range -5 .. 40 C
Water proof AD8
Resistance to vibrations Low
EIAVB Characteristics
Nom. Max. Current
Armour Approx. Perm. current
outer ope. rating,
Name Conductor shape thickness weight rating open air
diam. volt. buried
[mm] [kg/km] [A]
[mm] [kV] [A]
EIAVB 7/12 (15) kV
Round, massive 42.5 1.4 4400 15 77 82
- 3 x 16 mm
E I AV B 8,7/15
(17,5) kV - 3 x 16 Round, massive 50.0 1.4 5900 18 77 82
mm
EIAVB 7/12 (15) kV
Round, stranded 46.0 1.4 5300 15 100 105
- 3 x 25 mm
EIAVB 7/12 (15) kV
Round, stranded 48.5 1.4 6100 15 120 130
- 3 x 35 mm
E I AV B 8,7/15
(17,5) kV - 3 x 25 Round, stranded 50.5 1.4 6100 18 100 105
mm
EIAVB 7/12 (15) kV
Round, stranded 52.0 1.4 6900 15 145 150
- 3 x 50 mm
E I AV B 8,7/15
(17,5) kV - 3 x 35 Round, stranded 53.0 1.4 7000 18 120 130
mm
E I AV B 8,7/15
(17,5) kV - 3 x 50 Round, stranded 56.5 1.4 7900 18 145 150
mm
EIAVB
Nom. Max. Current
Armour Approx. Perm. current
outer ope. rating,
Name Conductor shape thickness weight rating open air
diam. volt. buried
[mm] [kg/km] [A]
[mm] [kV] [A]
E I AV B 8,7/15
(17,5) kV - 3 x 70 Round, stranded 60.5 1.4 9400 18 180 185
mm
EIAVB 7/12 (15) kV Sector-shaped
52.5 1.4 7650 15 180 185
- 3 x 70 mm stranded (SM)
EIAVB 7/12 (15) kV Sector-shaped
56.0 1.4 8900 15 225 235
- 3 x 95 mm stranded (SM)
EIAVB 7/12 (15) kV Sector-shaped
58.0 1.4 10000 15 260 265
- 3 x 120 mm stranded (SM)
E I AV B 8,7/15
Sector-shaped
(17,5) kV - 3 x 95 60.5 1.4 10000 18 225 235
stranded (SM)
mm
EIAVB 7/12 (15) kV Sector-shaped
62.0 1.4 11600 15 300 305
- 3 x 150 mm stranded (SM)
E I AV B 8,7/15
Sector-shaped
(17,5) kV - 3 x 120 63.0 1.4 11300 18 260 265
stranded (SM)
mm
EIAVB 7/12 (15) kV Sector-shaped
65.5 1.4 13400 15 340 335
- 3 x 185 mm stranded (SM)
E I AV B 8,7/15
Sector-shaped
(17,5) kV - 3 x 150 66.5 1.4 12600 18 300 305
stranded (SM)
mm
E I AV B 8,7/15
Sector-shaped
(17,5) kV - 3 x 185 69.5 1.4 14600 18 340 335
stranded (SM)
mm
EIAVB 7/12 (15) kV Sector-shaped
70.5 1.4 16100 15 390 385
- 3 x 240 mm stranded (SM)
E I AV B 8,7/15
Sector-shaped
(17,5) kV - 3 x 240 75.0 1.4 17300 18 390 385
stranded (SM)
mm
EVAVB-F2 3,6 / 6 kV
Description
Application
For underground installations or installations in areas exposed to mechanical
damage.
Design
1. Copper core
2. PVC insulation
3. Bedding or tapes
4. Safety circuit with copper wires
5. Steel tapes
6. PVC sheath
Colour code
Neutral
Standards
Installation National NBN C33-121
In cable channel
In tube
With or without protection
In open air
In industry or houses
EVAVB-F2 3,6 / 6 kV
Characteristics
Construction characteristics
Conductor material Copper
Insulation PVC
Armour type Two steel tapes
Outer sheath PVC
Sheath colour Red
Dimensional characteristics
Number of cores 3
Electrical characteristics
Rated Voltage Uo/U (Um) 3.6/6 kV
Usage characteristics
Chemical resistance Medium
Fire retardant Yes
Resistance to vibrations Moderate
Packaging Cut to length
EVAVB-F2 - 3,6/6 kV
Current rating, Perm. current rating Av. insul. Armour Nom. outer Approx.
Name buried open air thickness thickness diam. weight
[A] [A] [mm] [mm] [mm] [kg/km]
EVAVB-F2 6 kV 3 x
72 60 3.0 1 32.0 1690
10 mm
EVAVB-F2 6 kV 3 x
92 79 3.0 1 35.0 2070
16 mm
EVAVB-F2 6 kV 3 x
120 100 3.2 1 39.0 2700
25 mm
EVAVB-F2 6 kV 3 x
150 125 3.2 1 41.0 3170
35 mm
EVAVB-F2 6 kV 3 x
175 150 3.2 1 41.0 2970
50 mm
EVAVB-F2 6 kV 3 x
215 190 3.2 1 43.5 3640
70 mm
EVAVB-F2 6 kV 3 x
260 235 3.4 1.4 48.5 4880
95 mm
EVAVB-F2 6 kV 3 x
295 270 3.4 1.4 52.0 5850
120 mm
EVAVB-F2 6 kV 3 x
330 305 3.4 1.4 55.0 6700
150 mm
EVAVB-F2 6 kV 3 x
380 350 3.4 1.4 57.5 7910
185 mm
EVAVB-F2 6 kV 3 x
440 410 3.6 1.4 64.0 10000
240 mm
EVAVB-F2 6 kV 3 x
495 470 3.6 1.4 67.5 11930
300 mm
EVAVB-F2 3,6 / 6 kV
Current rating, Perm. current rating Av. insul. Armour Nom. outer Approx.
Name buried open air thickness thickness diam. weight
[A] [A] [mm] [mm] [mm] [kg/km]
EVAVB-F2 6 kV 3 x
555 545 3.6 1.4 73.6 14950
400 mm
EXeCVB
Description
Application
Power distribution cable, copper conductor, XLPE insulated
(and longitudinal watertighness at the metallic screen level)
Description
1. Copper conductor
2. Semi-conducting XLPE extruded conductor screen
3. XLPE extruded insulation
4. Semi-conducting XLPE extruded insulation screen
5. Semi-conducting swelling tape
6. Copper wires screen + counter helix copper tape
7. Swelling tape
8. Red PVC oversheath
Standards
Installation
National NBN HD 620
In cable channel
In tube
with or without protection
In industry
In open air
Longitudinally watertight Mechanical resistance to impacts Max.conductor temp.in service Weather resistance
Yes Good 90 C Good
EXeCVB
Characteristics
Construction characteristics
Conductor material Copper
Conductor shape Round, stranded
Material of the inner semi-conductor Semi-conducting compound
Insulation Extruded XLPE
Material of the external semi-conductor Semi-conducting compound
Screen Copper wires + copper tape
Longitudinally watertight Yes
Outer sheath PVC
Dimensional characteristics
Number of cores 1
Mechanical characteristics
Mechanical resistance to impacts Good
Usage characteristics
Max. conductor temperature in service 90 C
Short-circuit max. conductor temperature 250 C
Weather resistance Good
EXeCVB
Av. insul. Screen Average sheath Max. outer Approx. Max. ope.
Name thickness section thickness diam. weight volt.
[mm] [mm] [mm] [mm] [kg/km] [kV]
EXeCVB 8,7/15 kV 1 x
4.5 16 2.6 30.5 960 17.5
25/16 np
EXeCVB 8,7/15 kV 1 x
4.5 16 2.6 33.0 1220 17.5
50/16 np
EXeCVB 8,7/15 kV 1 x
4.5 25 2.6 36.0 1860 17.5
95/25 np
EXeCVB 8,7/15 kV 1 x
4.5 25 2.9 40.0 2460 17.5
150/25 np
EXeCVB 8,7/15 kV 1 x
4.5 25 3.1 44.0 3470 17.5
240/25 np
EXeCVB 8,7/15 kV 1 x
4.5 35 3.3 50.0 5100 17.5
400/35 np
EXeCVB 8,7/15 kV 1 x
4.5 35 3.5 56.0 7600 17.5
630/35 np
EXeCVB 8,7/15 kV 1 x
4.5 35 3.7 68.0 11620 17.5
1000/35 np
EXeCVB 12/20 kV 1 x
5.5 16 2.6 35.0 1310 24
50/16 np
EXeCVB 12/20 kV 1 x
5.5 25 2.7 39.0 1980 24
95/25 np
EXeCVB 12/20 kV 1 x
5.5 25 3.0 42.0 2600 24
150/25 np
Longitudinally watertight Mechanical resistance to impacts Max.conductor temp.in service Weather resistance
Yes Good 90 C Good
EXeCVB
Av. insul. Screen Average sheath Max. outer Approx. Max. ope.
Name thickness section thickness diam. weight volt.
[mm] [mm] [mm] [mm] [kg/km] [kV]
EXeCVB 12/20 kV 1 x
5.5 25 3.1 46.0 3600 24
240/25 np
EXeCVB 12/20 kV 1 x
5.5 35 3.3 52.0 5250 24
400/35 np
EXeCVB 12/20 kV 1 x
5.5 35 3.5 58.0 7770 24
630/35 np
EXeCVB 12/20 kV 1 x
5.5 35 3.8 71.0 11850 24
1000/35 np
EXeCVB 18/30 kV 1 x
8.0 16 2.8 41.0 1600 36
50/16 np
EXeCVB 18/30 kV 1 x
8.0 25 2.9 44.0 2310 36
95/25 np
EXeCVB 18/30 kV 1 x
8.0 25 3.2 47.0 2960 36
150/25 np
EXeCVB 18/30 kV 1 x
8.0 25 3.3 51.0 4000 36
240/25 np
EXeCVB 18/30 kV 1 x
8.0 35 3.5 57.0 5700 36
400/35 np
EXeCVB 18/30 kV 1 x
8.0 35 3.7 63.0 8270 36
630/35 np
EXeCVB 18/30 kV 1 x
8.0 35 4.0 76.0 12450 36
1000/35 np
EXeCVB 20,8/36 kV 1 x
8.8 25 3.2 49.0 3080 41.5
150/25 np
EXeCVB 20,8/36 kV 1 x
8.8 25 3.4 53.0 4140 41.5
240/25 np
EXeCVB 20,8/36 kV 1 x
8.8 35 3.6 59.0 5860 41.5
400/35 np
EXeCVB 20,8/36 kV 1 x
8.8 35 3.8 65.0 8450 41.5
630/35 np
EXeCVB 20,8/36 kV 1 x
8.8 35 4.0 78.0 12610 41.5
1000/35 np
Selling information
All our cables are longitudinally watertight at the metallic screen level (swelling tapes)
Longitudinally watertight Mechanical resistance to impacts Max.conductor temp.in service Weather resistance
Yes Good 90 C Good
EXeCWB-EXeCeWB
Description
Application
Power distribution cable, copper conductor, XLPE insulated.
EXeCWB cables are provided with longitudinal watertighness at the screen level
EXeCeWB : idem EXeCWB cables + transversal watertighness over the screen
Design
1. Copper conductor
2. Semi-conducting XLPE extruded conductor screen
3. XLPE extruded insulation
4. Semi-conducting XLPE extruded conductor screen
5. Semi-conduting swelling tape
6. Copper wires screen + counter helix copper tape Standards
7. Swelling tape
National NBN HD 620
8. Aluminium tape bonded to the PE sheath (only for EXeCeWB cables)
9. Red PE oversheath
Installation
In cable channel
In tube
with or without protection
In industry
In open air
Longitudinally watertight Mechanical resistance to impacts Max.conductor temp.in service Weather resistance
Yes Good 90 C Good
EXeCWB-EXeCeWB
Characteristics
Construction characteristics
Conductor material Copper
Conductor shape Round, stranded
Material of the inner semi-conductor Semi-conducting compound
Insulation Extruded XLPE
Material of the external semi-conductor Semi-conducting compound
Screen Copper wires + copper tape
Longitudinally watertight Yes
Outer sheath PE
Dimensional characteristics
Number of cores 1
Mechanical characteristics
Mechanical resistance to impacts Good
Usage characteristics
Max. conductor temperature in service 90 C
Short-circuit max. conductor temperature 250 C
Weather resistance Good
EXeCWB-EXeCeWB
Av. insul. Screen Average sheath Max. outer Approx. Max. ope.
Name thickness section thickness diam. weight volt.
[mm] [mm] [mm] [mm] [kg/km] [kV]
EXeCWB 8,7/15 kV 1 x
4.5 16 2.6 30.5 960 17.5
25/16 np
EXeCWB 8,7/15 kV 1 x
4.5 16 2.6 33.0 1220 17.5
50/16 np
EXeCWB 8,7/15 kV 1 x
4.5 25 2.6 36.0 1860 17.5
95/25 np
EXeCWB 8,7/15 kV 1 x
4.5 25 2.9 40.0 2460 17.5
150/25 np
EXeCWB 8,7/15 kV 1 x
4.5 25 3.1 44.0 3470 17.5
240/25 np
EXeCWB 8,7/15 kV 1 x
4.5 35 3.3 50.0 5100 17.5
400/35 np
EXeCWB 8,7/15 kV 1 x
4.5 35 3.5 56.0 7600 17.5
630/35 np
EXeCWB 8,7/15 kV 1 x
4.5 35 3.7 68.0 11620 17.5
1000/35 np
EXeCeWB 8,7/15 kV 1 x
4.5 35 3.7 68.0 11620 17.5
1000/35 np
EXeCWB 12/20 kV 1 x
5.5 16 2.6 35.0 1310 24
50/16 np
EXeCWB 12/20 kV 1 x
5.5 25 2.7 39.0 1980 24
95/25 np
Longitudinally watertight Mechanical resistance to impacts Max.conductor temp.in service Weather resistance
Yes Good 90 C Good
EXeCWB-EXeCeWB
Av. insul. Screen Average sheath Max. outer Approx. Max. ope.
Name thickness section thickness diam. weight volt.
[mm] [mm] [mm] [mm] [kg/km] [kV]
EXeCWB 12/20 kV 1 x
5.5 25 3.0 42.0 2600 24
150/25 np
EXeCWB 12/20 kV 1 x
5.5 25 3.1 46.0 3600 24
240/25 np
EXeCWB 12/20 kV 1 x
5.5 35 3.3 52.0 5250 24
400/35 np
EXeCWB 12/20 kV 1 x
5.5 35 3.5 58.0 7770 24
630/35 np
EXeCWB 12/20 kV 1 x
5.5 35 3.8 71.0 11850 24
1000/35 np
EXeCWB 18/30 kV 1 x
8.0 16 2.8 41.0 1600 36
50/16 np
EXeCWB 18/30 kV 1 x
8.0 25 2.9 44.0 2310 36
95/25 np
EXeCWB 18/30 kV 1 x
8.0 25 3.2 47.0 2960 36
150/25 np
EXeCWB 18/30 kV 1 x
8.0 25 3.3 51.0 4000 36
240/25 np
EXeCWB 18/30 kV 1 x
8.0 35 3.5 57.0 5700 36
400/35 np
EXeCWB 18/30 kV 1 x
8.0 35 3.7 63.0 8270 36
630/35 np
EXeCWB 18/30 kV 1 x
8.0 35 4.0 76.0 12450 36
1000/35 np
EXeCWB 20,8/36 kV 1 x
8.8 25 3.2 49.0 3080 41.5
150/25 np
EXeCWB 20,8/36 kV 1 x
8.8 25 3.4 53.0 4140 41.5
240/25 np
EXeCWB 20,8/36 kV 1 x
8.8 35 3.6 59.0 5860 41.5
400/35 np
EXeCWB 20,8/36 kV 1 x
8.8 35 3.8 65.0 8450 41.5
630/35 np
EXeCWB 20,8/36 kV 1 x
8.8 35 4.0 78.0 12610 41.5
1000/35 np
Longitudinally watertight Mechanical resistance to impacts Max.conductor temp.in service Weather resistance
Yes Good 90 C Good
Distributed by :