ColumnBase

Demo v4.0.0 Envelope Design Report License ID: DemoVersion4.0.0

Job No.
Company:
Current Time: 2017/08/22 15:33:45

Design Preferences
Steel Design Code: AISC360-10 [LRFD] Foong/Grout Design Provision AISC360-10 ,J8 [LRFD]
Consider Tension-Shear Interacon for Bolts? Yes Foong/Grout Design Criteria Normal Stress
Anchor Threads Excluded From Shear Plane? No Bearing Strength Capacity Based on Design Code
Plate Design Criteria Von-Mises Stress
Plate Strength Reducon Factor 0.9

Embedded Anchors Design Provision ACI318-14


Seismic Category C,D,E,F
Concrete Cracked Under Service Loads? Yes
Anchor reinf. and Supplementary reinf. is present? No

Demand/Capacity Rao Limit: 0.99

Envelope Design Summery

Check Point Controlling Load Combo Demand/Capacity Rao Check


Plate Stress Check LRFD03 0.45 Pass
Foong Bearing Stress Check LRFD02 1.03 Fail
Anchor Steel Failure In Tension and Shear LRFD03 0.37 Pass
Pullout Strength of Anchors LRFD03 0.79 Pass
Concrete Breakout in Tension LRFD03 1 Fail
Concrete Side-face Blowout Failure LRFD01 0 Pass

Plate Stress Check Demand/Capacity Ratio: 0.45 Check: Pass

General Data
Design Provisions AISC360-10 [LRFD]
Controlling Load Combo LRFD03 136
Design Criteria Von-Mises Stress 126
116
Design Formulation 106
96
(Demand/Capacity Rao) 86

a (Allowable stress) 76
Fy = 344.738 MPa (Plate yield stress) 66
= 0.9 (Strength reducon factor) 56
vm,max (Max. von-Mises stress under current load combo) 46
36
Plate Check 26
vm,max [MPa] a [MPa] DCR Check 16
6
139.423 310.264 0.45 Pass
Plate Bottom Face Von-Mises Stress [LRFD03]
Min Value: 3.3786 , Max Value: 139.4234 MPa

ColumnBase Demo v4.0.0 Design Report (www.PCEESoft.com) Page 1 of 5


Footing Bearing Stress Check Demand/Capacity Ratio: 1.03 Check: Fail

General Data
Design Provisions AISC360-10 ,J8 [LRFD]
Controlling Load Combo LRFD02
0.1
Foong Bearing Capacity Based on Design Code
-1.9
Foong Design Criteria Normal Stress
-3.9
-5.9
Design Formulation
-7.9
-9.9
(Demand/Capacity Rao)
-11.9
f'c = 27.579 MPa (Foong Concrete f'c) -13.9
A1 = 126451.404 mm <AISC360-10 J.8> -15.9
A2 = 360000 mm <AISC360-10 J.8> -17.9
c = 0.65 (Strenght reducon factor) -19.9
fp,max (Max. bearing stress under current load combo)
-21.9
-23.9
Footing Check
-25.9
fp,max [MPa] c.fp [MPa] DCR Check
Footing Bearing Stress For LoadCombo: LRFD02
26.424 25.71 1.03 Fail Min Value: -26.4236 , Max Value: 0.5063 MPa

Anchor Steel Check In Tension and Shear Demand/Capacity Ratio: 0.37 Check: Pass

General Data
Design Provisions AISC360-10 [LRFD] J3.6-J3.7
Consider Interacon? Yes (Consider Tension-Shear Interacon?)
Threads Excluded? No (Threads are Excluded From Shear Plane?)
Load Combo Controlling LoadCombo
Anchors Fu 689.476 MPa (Minimum Tensile Strength of Anchor Bolts)
Anchors Fnt 517.107 MPa <Nominal Tensile Strength ,AISC360-10 Table J3.2>
Steel Failure Mode
Anchors Fnv 310.264 MPa <Nominal Shear Strength ,AISC360-10 Table J3.2>

Design Formulations
<AISC360-10 Secon J3.6 ,J3.7>
<AISC360-10 Secon J3.7>
(Calculaon of ulmate shear force and stress)
(Demand/Capacity Rao)
Ab (Nominal unthreaded body area of bolt)
F'nt (Nominal tensile stress modied to include the eects of shear stress)
Tu (Anchor bolt tension force under current load combo)
Vu (Anchor bolt shear force under current load combo)
frv (Shear stress under current load combo)
= 0.75 (Strength Reducon Factor)

Anchors Check
No. ID Ab [mm] Crical LC T [kN] Vx [kN] Vy [kN] Vr [kN] F'nt [MPa] Rnt [kN] Rnv [kN] DCR Check
1 20 314.16 LRFD03 0 6.41 25.374 26.171 487.118 114.774 73.104 0.36 Pass
2 20 314.16 LRFD03 0 -6.41 25.374 26.171 487.118 114.774 73.104 0.36 Pass
3 20 314.16 LRFD03 43.035 2.762 24.626 24.781 496.95 117.091 73.104 0.37 Pass
4 20 314.16 LRFD03 43.035 -2.762 24.626 24.781 496.95 117.091 73.104 0.37 Pass

ColumnBase Demo v4.0.0 Design Report (www.PCEESoft.com) Page 2 of 5


Pullout Strength of Cast-in Anchors Demand/Capacity Ratio: 0.79 Check: Pass

General Data
Design Provisions ACI318-14 Secon 17.4.3
Load Combo Controlling Load Combo
Strength Reducon Factor(Seismic) 0.75
Anchors Type Headed Bolts
Anchors Head Type Hex
Concrete Cracked? Yes
Foong Concrete f'c 27.579 MPa
Pullout Failure Mode

Design Formulation
<ACI318-14 Secon 17.4.3>
c,p = 1 <ACI318-14 Secon 17.4.3.6>
= 0.7 <ACI318-14 Secon 17.3.3>
Abrg (Net bearing area of the head of anchor)
Nua (Anchor tension force under current load combo)

Anchors Check
No. ID Crical LC da [mm] Abrg [mm] 0.75Npn [kN] Nua [kN] DCR Check
1 20 LRFD01 20 467.685 54.173 0 0 Pass
2 20 LRFD01 20 467.685 54.173 0 0 Pass
3 20 LRFD03 20 467.685 54.173 43.035 0.79 Pass
4 20 LRFD03 20 467.685 54.173 43.035 0.79 Pass

ColumnBase Demo v4.0.0 Design Report (www.PCEESoft.com) Page 3 of 5


Concrete Breakout Strength In Tension Demand/Capacity Ratio: 1 Check: Fail

General Data
Design Provisions ACI318-14 Secon 17.4.2
Controlling Load Combo Controlling LoadCombo
Anchors Type Headed Bolts
Strength Reducon Factor(Seismic) 0.75
Anchor Reinf. and Supplementary Reinf. Is Present? No
hef ,Eecve embedment depth of anchor 400 mm
Foong Concrete, f'c 27.579 MPa
Concrete Cracked? Yes Concrete Breakout Failure Mode

, Concrete lightweight factor 1

Design Formulation
<ACI318-14 Secon 17.4.2.1>
(Units: psi,in) <ACI318-14 Secon 17.4.2.2>
(Units: psi,in) <ACI318-14 Secon 17.4.2.2>
<ACI318-14 Secon 17.4.2.3>
(Demand/Capacity Rao)
ed,N <ACI318-14 Eq 17.4.2.5>
c,N = 1 <ACI318-14 Secon 17.4.2.6>
cp,N = 1 <ACI318-14 Secon 17.4.2.7>
kc = 24 <ACI318-14 Secon 17.4.2.2>
ANc <ACI318-14 Secon 17.4.2.1>
ANco <ACI318-14 Secon 17.4.2.1>
Ca,min (Minimum edge distance)
Ca,max (Maximum edge distance)
Nua (Anchor tension force under current load combo)
= 0.7 <ACI318-14 Secon 17.3.3>

Anchors Check
No. ID Crical LC Ca,min [mm] Ca,max [mm] hef [mm] ANc [mm] ed,N Nb [kN] 0.75Ncb [kN] Nua [kN] DCR Check
1 20 LRFD01 160.3 439.7 400 360000 0.78 0.157 43.206 0 0 Pass
2 20 LRFD01 160.3 439.7 400 360000 0.78 0.157 43.206 0 0 Pass
3 20 LRFD03 160.3 439.7 400 360000 0.78 0.157 43.206 43.035 1 Fail
4 20 LRFD03 160.3 439.7 400 360000 0.78 0.157 43.206 43.035 1 Fail

ColumnBase Demo v4.0.0 Design Report (www.PCEESoft.com) Page 4 of 5


Concrete Side-face Blowout Strength Demand/Capacity Ratio: 0 Check: Pass

General Data
Design Provisions ACI318-14 Secon 17.4.4
Controlling Load Combo Controlling LoadCombo
Strength Reducon Factor(Seismic) 0.75
Anchors Type Headed Bolts
Anchors Head Type Hex
hef, Eecve embedment depth of anchor 400 mm
Foong Concrete, f'c 27.579 MPa Sideface Blowout Failure Mode
, Concrete lightweight factor 1

Design Formulation
(Otherwise the side-face blowout failure is not applicable for the anchor)
<ACI318-14 Eq 17.4.4.1>
(Modicaon factor, ACI318-14 Secon 17.4.4.1)
(Demand/Capacity Rao)
Ca1 (Minimum edge distance)
Ca2 (Minimum edge distance in the direcon perpendicular to ca1)
Abrg (Net bearing area of the head of anchor)
= 0.7 <ACI318-14 Secon 17.3.3>
Nua (Anchor tension force under current load combo)

Anchors Check
No. ID Crical LC Ca1 [mm] hef >2.5Ca1 Ca2 [mm] Abrg [mm] 0.75 Nsb [kN] Nua [kN] DCR Check
1 20 LRFD01 160.3 No N.A N.A N.A N.A N.A - -
2 20 LRFD01 160.3 No N.A N.A N.A N.A N.A - -
3 20 LRFD01 160.3 No N.A N.A N.A N.A N.A - -
4 20 LRFD01 160.3 No N.A N.A N.A N.A N.A - -

ColumnBase Demo v4.0.0 Design Report (www.PCEESoft.com) Page 5 of 5