You are on page 1of 11

75 STUB ANGLE

x
COPING
G.L GL 225 GL
EXCAVATION LINE

FxF
C

J
W1
SECTION
G
A W2
D1
G

D W3 250
D2
EXCAVATION LINE

D3 C.C. 1:2:4
100 P.C.C. 1:4:8
C
L OF TOWER
B/2 B/2
J
K
B

G
NOTE-2 : For locations of cut point / angle towers, the classification of tower
foundations shall be at next higher type for ensuring safety of the Transmission
line which is likely to be subjected to seasonal changes / climatic conditions
G from time to time.
NOTE-3 : In case of highly collapsible & loose soils and river crossings, special
PLAN design for foundations are to be made by Civil Engineering wing for adoption on
case to case basis.
NOTE-4 : All locations subjected to water logging, particularly in paddy fields,
NOTE-1 : While classifying foundations of Wet, Partially submerged /
ponds, marshy areas etc., the chimney of all stubs are to be raised to 600 mm
Partially black cotton, Fully submerged / Black cotton foundations
over the normal chimney being adopted in other cases. This shall be done after
mentioned above, the worst conditions should be considered and not
completion of erection of towers as a separate item for identified locations.
necessarily the conditions prevailing at the time of inspection. For
instance there are areas where subsoil water raised when canal water is
let out in the field raising subsoil water to a considerable degree. TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED
Similarly the effect of monsoon or when the nearby reservoirs are full
should be considered and not the conditions prevailing in open season or FOUNDATION DETAILS OF 220 K.V. TYPE TOWER -
summer when work is carried out normally. (L&T)
Drg. No. 220KV-TL-G.A. Scale 1:50
Page

26
FOUNDATION DETAILS FOR 220 KV A-TYPE TOWER
Basic W1 D1 Vol. Of Vol. Of
Soil A B C D F X PCC Sand G J K
Tower W2 D2 Excavation PCC M-15
Type (mm) (mm) (mm) (mm) (mm) (mm) 1:4:8 filling (mm) (mm) (mm)
Extension W3 D3 M3 M3
175 200
0.00 M 3000 1400 2500 500 300 6251 375 300 6872 12405
0 0

1.02
Dry 3.00 M 3000 1400 2500 500 300 6964 44.76 Cum 1900 7585 13414 3.70 Cum
Cum

6.00 M 3000 1400 2500 500 300 7676 8297 14421

325 350
0.00 M 3000 2000 2250 750 450 6251 450 400 6815 13173
0 0

1.94
Wet 3.00 M 3000 2000 2250 750 450 6964 77.50 Cum 2500 7528 14182 10.16 Cum
Cum

6.00 M 3000 2000 2250 750 450 7676 8240 15189

375 350
0.00 M 3000 2550 1950 1050 450 6251 375 400 6750 13859
300 300

3.03 5.58
P.S. 3.00 M 3000 2550 1950 1050 450 6964 120.93 Cum 3050 7463 14868 17.73 Cum
Cum Cum

6.00 M 3000 2550 1950 1050 450 7676 8175 15875

325 350
0.00 M 3000 3000 1800 1200 450 6251 450 400 6679 14395
500 450

4.10 7.35
F.S. 3.00 M 3000 3000 1800 1200 450 6964 159.25 Cum 3500 7392 15404 26.00 Cum
Cum Cum

6.00 M 3000 3000 1800 1200 450 7676 8104 16411


275 1200
0.00 M 1200 1000 0 1200 450 6251 6304 10329

HardRock 3.00 M 1200 1000 0 1200 450 6964 4.80 Cum 1000 7017 11338 5.04 Cum

6.00 M 1200 1000 0 1200 450 7676 7729 12345

625 650
0.00 M 3000 1700 2350 650 450 6251 6815 12042

Soft
3.00 M 3000 1700 2350 650 450 6964 34.68 Cum 1700 7528 13050 9.66 Cum
Rock

6.00 M 3000 1700 2350 650 450 7676 8240 14057


T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004

x
Scale 1:50
COPING
75 STUB ANGLE
100X100X10

G.L GL 225 GL
EXCAVATION LINE

300X300

2500
J
3100
SECTION
G

175
G
200 375 250

EXCAVATION LINE 300 C.C. 1:2:4


100 P.C.C. 1:4:8
700 700
1400
C
L OF TOWER 1600
1900
J
K
SOIL CLASSIFICATION
G Where normal dry cohesive or non-cohesive soils are met.

PLAN Released for Construction

CHIEF ENGINEER/CIVIL

TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


FOUNDATION DETAILS OF 220 K.V. - "A" TYPE TOWER -
(L&T)
Drg. No. 220KV-TL-A-DRY DRY
Pa g e

29
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004

x Scale 1:50
COPING
75 STUB ANGLE
100X100X10

G.L GL 225 GL
EXCAVATION LINE

450X450

2250

J
3100
SECTION
G
325

G 450 250
350

EXCAVATION LINE
400 C.C. 1:2:4
100 P.C.C. 1:4:8
1000 1000
2000
C
L OF TOWER 2200
2500
J
K SOIL CLASSIFICATION
a) Where sub soil water is met at 1.5 Mtrs. or more below the ground level in
normal soil.(OR)
G b) Where surface water could stand for long period with water penetration
not exceeding 1 Mtr. Below ground level (example : Paddy fields, Sugarcane
G fields).

PLAN Released for Construction

CHIEF ENGINEER/CIVIL

TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


G J K Volume of
+0 M 6815 13173 Excavation Concrete P.C.C. FOUNDATION DETAILS OF 220 K.V. - "A" TYPE TOWER -
+3M 2500 7528 14182 (L&T)
77.50CuM 10.16CuM 1.94CuM
+6M 8240 15189 Drg. No. 220KV-TL-A-WET WET
Pa g e

30
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004

x
Scale 1:50
COPING
75 STUB ANGLE
100X100X10

G.L GL 225 GL
EXCAVATION LINE

450X450

1950

J
3250
SECTION 375
G
375
350 C.C. 1:2:4
G 300 250
400

EXCAVATION LINE 300


100 P.C.C. 1:4:8
150 Sand Filling
1275 1275
C
L OF TOWER
2550
J 2750
K
SOIL CLASSIFICATION 3050

G
a) Where sub soil water is encountered between 0.75 Mtrs. and 1.5 Mtrs. depth below
ground level.(OR)
b) Where top layer of black cotton soil extends up to 50 % of the depth with normal soil
G thereafter.
NOTE : Where soil is clayey type, not necessarily
PLAN black in colour, which shrinks when dry, swells when wet. Released for Construction

CHIEF ENGINEER/CIVIL

G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


+ 0M 6,750 13,859 Excavation Concrete P.C.C. Sand FOUNDATION DETAILS OF 220 K.V. - "A" TYPE TOWER -
+ 3M 3050 7,463 14,868 (L&T)
120.93 Cum 17.73 Cum 3.03 Cum 5.58 Cum
+ 6M 8,175 15,875 Drg. No. 220KV-TL-A-P.S. PS / PBC
Pa g e

31
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004
75 STUB ANGLE Scale 1:25
x
100X100X10
COPING
225 450X450
G.L GL GL
As per field conditions
EXCAVATION LINE
0 to 1800

J
1200
SECTION C.C. 1:2:4
G

EXCAVATION LINE

1000

C
L OF TOWER

J
K
SOIL CLASSIFICATION
a) Where hard rock is encountered at 1.5 Mtrs. or less below ground level.(OR)
b) Where hard rock is encountered from 1.5 Mtrs. to 2.5 Mtrs. below ground
G level though top layer is of normal soil.(OR)
c) Where chiseling, drilling and blasting is required for excavation.
G

PLAN Released for Construction

CHIEF ENGINEER/CIVIL

G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


+0 M 6304 10329 Excavation Concrete FOUNDATION DETAILS OF 220 K.V. - "A" TYPE TOWER -
+3M 1000 7017 11338 4.8 to 5.04 to (L&T)
+6M 7729 12345 12.00CuM 6.50 CuM Drg. No. 220KV-TL-A-H.R. HARD ROCK
Pa g e

33
T.O.O. Dir (Tr. & G.O.) M.S. No. 156 Dated 8-10-2004

x Scale 1:50
COPING
75 STUB ANGLE
100X100X10
G.L GL 225 GL
EXCAVATION LINE

450X450

2350

J
3000
SECTION
G

G
650
C.C. 1:2:4
EXCAVATION LINE

1700

C
L OF TOWER
SOIL CLASSIFICATION
J a) Where decomposed or fissured rock, hard gravel, kankar, lime stone,
K laterite or any other soil of similar nature is met.(OR)
b) Where top layer of normal dry soil extends up to 85% of the depth followed
G
by fissured rock without presence of water.

PLAN Released for Construction

CHIEF ENGINEER/CIVIL

G J K Volume of TRANSMISSION CORPORATION OF ANDHRA PRADESH LIMITED


+0 M 6815 12042 Excavation Concrete FOUNDATION DETAILS OF 220 K.V. - "A" TYPE TOWER -
+3M 1700 7528 13050 (L&T)
34.68CuM 9.66CuM
+6M 8240 14057 Drg. No. 220KV-TL-A-S.R. SOFT ROCK/ F&F ROCK