SFRA Quick Start Guide

Doble SFRA Quick Start Guide


Introduction
This Quick Start Guide shows how to make a good measurement using an M5200 or M5300 test set
CAUTION

The transformer under test must be completely de-energized and isolated from the system.
Follow your own company rules, policies, and government regulations to ensure safety of personnel and
property. The transformer and the M5300 test instrument must share a common ground or earthing point.
Preparing the Transformer
All bushings and windings should be disconnected from any connecting bus and/or insulators. Terminals not under test
should be isolated and floating unless otherwise specified.

Setting up the Instrument and Software


M5300: Start the SFRA M5300 software on the M5300 test set. The M5300 software will start automatically. Double click
on the SFRA software icon if necessary.
M5200: On your PC install the software only on the C drive, not a network drive. Make sure SFRA M5200 software is
running and you have no network connections , no wireless connections active or turned on and no firewall and/or virus
software active or enabled (networks, virus software and firewalls interfere with communications with the M5200). Follow
the procedure in the table below.

1. Click on Edit and then Edit Apparatus. 2. Once you have entered the 3. Click on Start Test 4. Fill in details in the Test Details
Select each of the following editors in turn: information, click on in the middle of the window and click on Run Test.
Location Select Apparatus pane at left.
Location (on the) to select
Transformer the apparatus for test.
Test Equipment
Test Organization
Enter details for each editor.

Make sure to select a template for the


transformer.

Checking Instruments and Leads


The Doble SFRA test set and leads are configured for use as in Figure 1 color coded yellow-red-black.

Figure 1 M5300 Test Set and Test Leads

PN 500-0545 -1- 72A-2499-01 Rev.C 09/07


SFRA Quick Start Guide

Start up the Doble SFRA software. Ensure the cables are connected to the test set following the color coded BNC
connections. A test lead integrity check may be performed if required: see the Doble SFRA User Guide for details.
Connecting Leads to the Transformer and Running Tests
When running a test on a transformer winding, for example H1-H0, attach the Red Lead to the H1 bushing and the Black
Lead to the H0 bushing, as shown in Figure 4.

Note
When connecting leads to a transformer,
ensure that you attach the lead grounds to
a stud or bolt at the base of the bushing,
and that good electrical contact is
established and maintained.

Figure 4 Connecting Leads to the Transformer to Measure H1-H0


It is important to record nameplate and test arrangement data in the 'Nameplate' section of the software.
The following details are a minimum set required for each test.
Manufacturer, serial number LTC and DETC positions during test Location
HV/LV/TV, MVA, Impedance Red and black lead locations Bushings shorted
LTC and DETC ranges and nominal position Bushings grounded

Changing tap position or DETC position or removing core ground connections will give different SFRA results. This means that
where previous results are available, measurements must be made in a manner consistent with those previous results.
Care of Equipment
Follow the points below to take care of your equipment.
Keep test set and test leads in good order.
Do not pull on test leads as they may break.
Support the weight of the test leads where necessary by use of cable ties or similar.
Cables are made of co-ax and have a 2 minimum bend radius (don't bend cable too tightly.)
If a clip repair is necessary through field damage, keep the center conductor separate from the shield.

Typical Results
Correct use of the test set and test leads will result in measurements similar to those given in Figure 5. These plots give the
results for all three phases of an individual transformer.

Figure 5 Typical LV Delta and HV Wye (Star) Winding Results

PN 500-0545 -2- 72A-2499-01 Rev. C 09/07


SFRA Quick Start Guide

Test Connections

Make sure good electrical connections are made at bushing terminals and at the base of bushings; clean, file or wire brush
connection points if necessary.

When making short circuit measurements, ensure all three phases are solidly shorted: 1 to 2, 2 to 3, and 3 back to 1.
Test connections are given here for some common transformer designs; red lead is first of the two named terminals. For
further designs, refer to the Doble Test Connections Guide.
Two Winding Transformer Table
Test Type Test # 3 3 3 3 1
Delta- Wye- Delta- Wye-
Wye Delta Delta Wye
HV Open Circuit (OC) Test 1 H1-H3 H1-H0 H1-H3 H1-H0 H1-H2
All Other Terminals Floating Test 2 H2-H1 H2-H0 H2-H1 H2-H0 (H1-H0)
Test 3 H3-H2 H3-H0 H3-H2 H3-H0
LV Open Circuit (OC) Test 4 X1-X0 X1-X3 X1-X3 X1-X0 X1-X2
All Other Terminals Floating Test 5 X2-X0 X2-X1 X2-X1 X2-X0 (X1-X0)
Test 6 X3-X0 X3-X2 X3-X2 X3-X0
Short Circuit (SC) Test 7 H1-H3 H1-H0 H1-H3 H1-H0 H1-H0
High (H) to Low (L) Test 8 H2-H1 H2-H0 H2-H1 H2-H0 Short
Short [X1-X2-X3] Test 9 H3-H2 H3-H0 H3-H2 H3-H0 [X1-X2]

Three Winding Transformer Table Part 1

Test Type Test # 3 3 3 3 1


Delta- Delta- Delta- Delta-
Delta- Delta- Wye Wye-
Delta Wye Delta Wye
HV Open Circuit (OC) Test 1 H1-H3 H1-H3 H1-H3 H1-H3 H1-H2
All Other Terminals Floating Test 2 H2-H1 H2-H1 H2-H1 H2-H1 (H1-H0)
Test 3 H3-H2 H3-H2 H3-H2 H3-H2
LV Open Circuit (OC) Test 4 X1-X3 X1-X3 X1-X0 X1-X0 X1-X2
All Other Terminals Floating Test 5 X2-X1 X2-X1 X2-X0 X2-X0 (X1-X0)
Test 6 X3-X2 X3-X2 X3-X0 X3-X0
Tert Open Circuit (OC) Test 7 Y1-Y3 Y1-Y0 Y1-Y3 Y1-Y0 Y1-Y2
All Other Terminals Floating Test 8 Y2-Y1 Y2-Y0 Y2-Y1 Y2-Y0 (Y1-Y0)
Test 9 Y3-Y2 Y3-Y0 Y3-Y2 Y3-Y0
Short Circuit (SC) Test 10 H1-H3 H1-H3 H1-H3 H1-H3 H1-H0
High (H) to Low (L) Test 11 H2-H1 H2-H1 H2-H1 H2-H1 Short
Short [X1-X2-X3]* Test 12 H3-H2 H3-H2 H3-H2 H3-H2 [X1-X2]*
Short Circuit (SC) Test 13 H1-H3 H1-H3 H1-H3 H1-H3 H1-H0
High (H) to Tertiary (T) Test 14 H2-H1 H2-H1 H2-H1 H2-H1 Short
Short [Y1-Y2-Y3]* Test 15 H3-H2 H3-H2 H3-H2 H3-H2 [Y1-Y2]*
Short Circuit (SC) Test 16 X1-X3 X1-X3 X1-X0 X1-X0 X1-X0
Low (L) to Tertiary (T) Test 17 X2-X1 X2-X1 X2-X0 X2-X0 Short
Short [Y1-Y2-Y3]* Test 18 X3-X2 X3-X2 X3-X0 X3-X0 [Y1-Y2]*

Three Winding Transformer Table Part 2

PN 500-0545 -3- 72A-2499-01 Rev. C 09/07


SFRA Quick Start Guide

Test Type Test # 3 3 3 3


Wye- Wye- Wye- Wye-
Wye- Wye- Delta- Delta-
Wye Delta Wye Delta
HV Open Circuit (OC) Test 1 H1-H0 H1-H0 H1-H0 H1-H0
All Other Terminals Floating Test 2 H2-H0 H2-H0 H2-H0 H2-H0
Test 3 H3-H0 H3-H0 H3-H0 H3-H0
LV Open Circuit (OC) Test 4 X1-X0 X1-X0 X1-X3 X1-X3
All Other Terminals Floating Test 5 X2-X0 X2-X0 X2-X1 X2-X1
Test 6 X3-X0 X3-X0 X3-X2 X3-X2
Tert Open Circuit (OC) Test 7 Y1-Y0 Y1-Y3 Y1-Y0 Y1-Y3
All Other Terminals Floating Test 8 Y2-Y0 Y2-Y1 Y2-Y0 Y2-Y1
Test 9 Y3-Y0 Y3-Y2 Y3-Y0 Y3-Y2
Short Circuit (SC) Test 10 H1-H0 H1-H0 H1-H0 H1-H0
High (H) to Low (L) Test 11 H2-H0 H2-H0 H2-H0 H2-H0
Short [X1-X2-X3]* Test 12 H3-H0 H3-H0 H3-H0 H3-H0
Short Circuit (SC) Test 13 H1-H0 H1-H0 H1-H0 H1-H0
High (H) to Tertiary (T) Test 14 H2-H0 H2-H0 H2-H0 H2-H0
Short [Y1-Y2-Y3]* Test 15 H3-H0 H3-H0 H3-H0 H3-H0
Short Circuit (SC) Test 16 X1-X0 X1-X0 X1-X3 X1-X3
Low (L) to Tertiary (T) Test 17 X2-X0 X2-X0 X2-X1 X2-X1
Short [Y1-Y2-Y3]* Test 18 X3-X0 X3-X0 X3-X2 X3-X2

Auto-Transformer Table
Test Type Test # 3 1
Series Winding (OC) Test 1 H1-X1 H1-X1
All Other Terminals Floating Test 2 H2-X2
Test 3 H3-X3
Common Winding (OC) Test 4 X1-H0X0 X1-H0X0
All Other Terminals Floating Test 5 X2-H0X0
Test 6 X3-H0X0
Tertiary Winding (OC) Test 7 Y1-Y3 Y1-Y2
All Other Terminals Floating Test 8 Y2-Y1 (Y1-Y0)
Test 9 Y3-Y2
Short Circuit (SC) Test 10 H1-H0X0 H1-H0X0
High (H) to Low (L) Test 11 H2-H0X0 Short
Short [X1-X2-X3] Test 12 H3-H0X0 [X1-H0X0]
Short Circuit (SC) Test 13 H1-H0X0 H1-H0X0
High (H) to Tertiary (Y) Test 14 H2-H0X0 Short
Short [Y1-Y2-Y3] Test 15 H3-H0X0 [Y1-Y2]
Short Circuit (SC) Test 16 X1-H0X0 X1-H0X0
Low (L) to Tertiary (Y) Test 17 X2-H0X0 Short
Short [Y1-Y2-Y3] Test 18 X3-H0X0 [Y1-Y2]

Limitation in Liability
"The limitations on liability and copyright notices contained in page ii of the Doble SFRA User Guide shall apply to the use
of this quick start guide and are hereby incorporated by reference."
Copyright 2006
By Doble Engineering Company
All Rights Reserved

PN 500-0545 -4- 72A-2499-01 Rev. C 09/07