You are on page 1of 9

ARC FLASH HAZARD ANALYSIS AND ITS IMPORTANCE

Pradeep Kumar Singh (Sr. Engineer-Electrical)


GAIL (India) Ltd- PATA Petrochemical Complex
Email: - Pradeep.singh@gail.co.in

1.0 Abstract

Recent changes in workplace safety Hazard/Risk Category (HRC) task tables for
regulations have heightened the awareness personal protective equipment (PPE)
of hazards associated with electrical arcs. selection. These tables provide pre-defined
Two types of electrical hazards now well levels of PPE, which are based on the
recognized are electrical shock and available short circuit current and the speed
electrical arc/flash burn. Electrical shock of the over current protective device.
requires that a person have contact with the Therefore, in order to properly apply the
exposed energized electrical conductor or tables, some degree of electrical calculations
circuit part or be within the air flashover must be performed.
(breakdown) distance of the conductor or
circuit p art. Electrical arc/flash burn can 2.0 Causes of Arcs and Effects of
occur when the expose d body is yet several Arcing And Flashing
feet away from the exposed energized
We all are aware of electricitys hazards to
electrical conductor or circuit part.
life, but few of us are aware of the possibility
The hazard level must be quantified and
of radiation burn from the fierce fire of
workers properly protected before entering
electric arcs and flashovers. Electric arc burns
proximity of exposed energized conductors.
account for a substantial portion of the
National Fire Protection Associations
injuries from electrical malfunctions and
(NFPA) standard 70E provides the
incidents. When electric current flows
guidelines for work involving electrical
between two or more separated energized
hazards and the selection of arc flash
conducting surfaces, an arc occurs. Some arcs
protective equipment. In order to properly
may be intentional such as arc welding or
select the protective gear one must have
they may be accidental caused by a tool
knowledge of the potential thermal energy of
slipping or by touching a test probe to the
the electric arc. Institute of Electrical and
wrong surface. A common cause of an arc is
Electronics Engineers (IEEE) standard 1584
insulation failure. The fault currents
has been the standard for calculating the arc
magnetic effects cause conductors to separ ate
energy levels at different points in the
producing an arc.
electrical power system. However, NFPA
The results of such arcs are often devastating.
70E also provides the option of using the
Temperatures at the arc terminals can reach or or human error.
exceed 35,000 degrees Fahrenheit (F) or four Electrical arc flash and shock hazards have
times the temperature of the suns surface. been recognized as particularly dangerous and
The heat energy and intense light at the point fairly frequent occurrences that put the lives
of the arc is termed ARC FLASH. Air and health of electrical workers at significant
surrounding the arc is instantly heated and risk. Statistics indicate that based on
conductors are vaporized causing a pressure hospitalization records, arc flash accidents
wave termed ARC BLAST. System voltage, that involve a fatality or serious injury to an
arc resistance (impedance) and available employee occur frequently in India. Those
short-circuit current determine instantaneous incidents most often occur when personnel
arc energy. Total arc energy (incident energy) are required (or choose) to work on electrical
is the instantaneous arc energy times the arc equipment while it is in an electrically
duration. Conductive vapors help sustain the energized condition. So, there is a greater
arc and the duration of the arc is primarily importance for arc flash auditing. An arc flash
determined by the time it takes for over audit is done by considering electrical
current protective devices to open the circuit. equipment parameters. Through an arc flash
Current-limiting fuses for example may open safety analysis, one can offer alternatives to
the circuit in 8.3 ms (1/2 cycle) or less while help our organization become more aware of
other devices may take 100 ms (6 cycles) or possibilities to reduce our employee's
more to open. exposure to arc flash energy

3.0 Impact of Electric Arcs


Definitely the impacts of arc flash accidents
are very severe. We generally see the impacts
like serious injuries and medical costs, serious
burns or even death, equipment damage and
repair cost, switchgear replacement,
production loss. Three key factors determine
the intensity of an arc flash on personnel.
These factors are the quantity of fault current
available in a system, the time taken for
Fig 1. Effect of Arcing & Flashing
successful short circuit interruption, and the
distance an individual is from a fault arc.
Various design and equipment configuration
Therefore the persons working on or near choices can be made to affect these factors
energized electrical equipments should wear and in turn reduce the arc flash hazard. To
personal protective clothing equipment to prevent arc flash hazards, there are certain
prevent injuries to the eyes, head, face, body, equipment called Arc Fault Circuit
limbs, and extremities from electrical arcs and Interrupters which are designed to prevent
flash due to equipment failure, malfunction, fires by detecting an unintended electric arc
and disconnecting the power before the arc flash protective equipment. The materials are
starts a fire. Conventional circuit breakers tested for their arc rating. The arc rating is the
only respond to overloads and short circuits. maximum incident energy resistance
So they do not protect against arcing demonstrated by a material prior to break
conditions that produce erratic, and often open (a hole in the material) or necessary to
reduced current. An Arc Flash Circuit pass through and cause with 50% probability
Interrupter is selective so that normal arcs do a second or third degree burn.
not cause it to trip. The Arc Flash Circuit
Interrupter circuitry continuously monitors 5.0 Use of NFPA 70E Tables
the current and discriminates between normal
and unwanted arcing conditions. Once an NFPA 70E provides Hazard/Risk Category
unwanted arcing condition is detected, the tables, which highlight specific personnel
Arc Flash Circuit Interrupter opens its internal protective equipment to be used on various
contacts, thus de-energizing the circuit and electrical distribution equipment. However,
reducing the potential for a fire to occur. An these tables are based on fundamental
Arc Flash Circuit Interrupter should not trip assumptions about the available fault current
during normal arcing conditions, which can and the over current device clearing time.
occur when a switch is opened or a plug is In order to use the tables, the person in charge
pulled from a receptacle, or a device with a must verify that the available fault current and
brush-type motor is in operation. the over current protective device (OCPD)
tripping time are both equal to or lower than
4.0 What is Arc Flash Analysis? the values assumed for developing the tables.
This essentially requires performing the
An Arc Flash Hazard Analysis starts with majority of the calculations that are necessary
gathering up-to-date equipment information, for determining the arc flash energy.
then performing a detailed analysis comprised However, a common but incorrect approach
of a load-flow study, short circuit study, and to using the tables is to select the PPE based
protective device coordination study as well on the equipment and voltage levels only and
as an equipment evaluation to determine that ignore the limitations imposed by the fault
the current withstand rating is acceptable. An current and over current protective device
arc flash analysis is crucial for personnel operating time.
safety in an industrial plant

A study investigating a workers potential 6.0 IEEE 1584 analysis


exposure conducted for the purpose of injury procedure
prevention and the determination of safe work
practices and appropriate levels of PPE. There The IEEE 1584 analysis procedure begins
are many methods of arc flash protections. with a complete data collection from the
This includes PPE (Personnel Protective power system. Characteristics of the power
Equipment) or modifying the design and source utility or generator and the power
configuration of electrical equipment. There system components such as transformers and
have been many companies that offer arc cables, as well as the tripping characteristics
of over current protective devices are can be used to solve the equations.
identified and entered into a computer
program. The program first calculates the A detailed arc-flash hazard analysis
bolted 3-phase short circuit current at each using this method requires the
bus of concern in the system. Then the arc
following steps.
fault current is calculated at each location. For
Step1) Collect the power system and
low voltage systems, the arc fault current will
installation equipment data.
be lower than the bolted fault current because
of arc impedance. Next, under the arc-fault
Step 2) Review the system single line for each
current condition, the clearing time of the
location and determine the power systems
protective device protecting the bus is
modes of operation. If a single line does not
determined. For fuses, the manufacturers
exist, inspect the system and develop a single-
total clearing time is used. For relayed
line diagram.
medium voltage breakers, the relays curve
shows only the relay operating time and the
Step 3) Perform an analysis of the maximum
particular breakers opening time must be
and minimum available short-circuit currents
added to this time.
for each different mode of operation that
Following the clearing time determination,
applies. Determine the first cycle symmetrical
the working distance at each bus is selected.
root-mean-square bolted three phase fault
Next, incident energies are calculated for each
current and X/R ratio at all locations where
bus. Incident energy is the amount of energy
people could be working on energized
impressed on the face and body of the
electrical equipment. Equipment below 240 V
electrical worker. One of the units used to
need not be considered unless it involves at
measure incident energy is calories/cm2. The
least one 125-kVA, or larger, low-impedance
flash protection boundary based on incident
transformer in its immediate power supply.
energy of 1.2 calories/cm2 is calculated. This
is the generally accepted energy level that
Step 4) Determine the arc fault currents. The
causes the onset of a second-degree burn.
arc fault current for each location where an
Finally, the hazard risk category and the
arc-flash hazard exists and the portion of that
workers protective clothing system for each
current that flows through the protective
bus under consideration are determined. All
device that will clear this fault must be
arc flash hazard analysis results are presented
determined.
in an easy to understand format.
Step 5) from the protective device
A. Steps in calculating arc-flash energy characteristics, find the arcing duration. The
total clearing time of the fault will determine
IEEE STD 1584-2002 provides a method of
the time factor in the energy equation.
conducting an arc flash hazard analysis. This
If power in the arc remains constant, a longer
method uses equations that were developed
time will produce more energy based on the
using statistical analysis of data from arc-
following:
flash testing performed at laboratories. This
Energy = Power X time
standard includes a spreadsheet calculator that
TABLE I
Step 6) Record the system voltages and the WORKING DISTANCE BASED ON
equipment classes for each bus. For example, VOLTAGE LEVEL
record whether the equipment is switchgear or
a motor control center. Working
Distance Equipment KV
Step 7) Determine working distances. Arc-
flash protection is based on the incident Type
energy level on the persons face and chest
24 inches (610mm) Switchgear <1
area at the working distance. The degree of
injury in a burn depends on the percentage
of a persons skin that is burned. Burns to 18 inches (455mm) Panel <1
the head and/or chest area are much more
life threatening than burns on the
extremities. The working distance based on 36 inches (910mm) Switchgear > 1 & <
the voltage level and equipment type using 35
the table I.
72 inches
(1829mm) Switchgear > 35
Step 8) Determine incident energy for each
work location in the study. This is best done
18 inches (455mm) all others
using a software package. The equations in
IEEE Std 1584-2002 are available in
spreadsheet format. These equations have B. How arc-flash energy affects
been incorporated into the packages of personal protective equipment
power system software vendors.
(PPE)
Step 9) Determine the flash-protection
NFPA 70E defines five levels of arc
boundary for each work location in the
hazard. Table II shows the hazard/risk
study. Incident energy equations can be
category levels and the calculated incident
solved for the distance from the arc source at
energy at the working distance. The table
which the onset of a second-degree burn
lists typical clothing and layer counts for the
could occur. This is called the flash-
torso. In short, this is the level of clothing
protection boundary. The incident energy
that should be worn to limit incident energy
for the flash-protection boundary must be set
damage to a second-degree burn. Put another
at the minimum energy beyond which a
way, this guide is designed to protect the
second-degree burn could occur (1.2
worker from heat to prevent a second-degree
cal/cm2).
burn.
TABLE II
PERSONAL PROTECTIVE EQUIPMENT
(PPE) TO LIMIT BURNS.

Required
Clothing description (No.
Hazard Minimun Arc
of clothing layers is given
Risk rating of
in parentheses)
PPE(cal/cm2)
Non melting,flammable
materials(i.e untreated
0 cotton,wool,rayon or silk or N/A
blends of these materials)
FR shirt and FR pants or
1 FR coverall(1) 4
Cotton underware-
conventional short sleeve
2 and brief/shorts,plus FR 8
shirt and FR pants(1 or 2)
Cotton underware plus FR
shirt and FR pants plus FR
3 overall or cotton underware 25
plus 2 FR coveralls(2 or 3)
Cotton underware plus FR
shirt and FR pants plus
4 multilayer flash suit(3 or 40
more)

7.0 Arc Flash Labels

Arc flash labels are provided. The data in the


labels will be populated based on the arc flash
calculation software output. The labels must
have the following characteristics.
1. UL 969 standard compliance for durability
and adhesion 8.0 Reduction Strategies For
2. Include shock protection data per NFPA Arc Flash Energy
70E in addition to arc flash hazard data.
An arc-flash hazard evaluation for an
industrial power system will generally
uncover locations in the power system where
the incident energy levels are high. This is
considered to be levels above 40 cal/cm2.

1) Reduce Existing Pickup Settings


In some cases, the arcing fault current
magnitude may not be large enough to
operate the over current protective device in
its short delay or instantaneous trip time. If 3) Reduce Fault Current
possible, the short delay or instantaneous Incident energy can also be reduced by
pickup should be reduced to allow for more lowering the arcing fault current. The
sensitive sensing of the calculated arcing reduction of incident energy will depend on
current that flows through the protective the trip time that results at the reduced
device. Changing the sensing element from current. A protective device with a definite
long delay to short delay or instantaneous can time characteristic is best suited for this
make a significant difference in incident incident energy reduction technique. Note that
energy levels. Care must be taken with the for most inverse time current curve
choice of the reduced pickup setting to ensure characteristic shapes, reduced arcing currents
that over current coordination is maintained will result in increased trip time and increased
and nuisance tripping on load energization incident energy. Fault levels can be reduced
inrush will not occur. by one of the following design changes, both
of which require a significant amount of cost
2) Reduce Existing Time Delay and engineering effort:
Settings
If a protective device operates in its long Installation of current limiting reactor
time region, the time curve is normally an Use of multiple transformers instead of
inverse type that has increased time delay as one large transformer.
fault current decreases. Arcing fault
magnitude is approximately 50% of the bolted 4) Remote Racking Device
fault current magnitude. Long delay trip time These devices are presently available for
greater than 2 s may occur for arcing faults. It some equipment. Awareness of the arc-flash
is generally recognized that the reaction time hazard is accelerating the development of
required to move away from an arc-flash these devices to work with an increasing
hazard is 2 s. Based on the work task, if there number of equipment types from various
is a good possibility that the worker can move manufacturers. By operating the breakers
away from the arc-flash area, then a remotely, you have increased safety.
maximum clearing time of 2 s may be used However, this idea is cost prohibitive in low
for incident energy calculations. When voltage switchboards. To make every breaker
reviewing existing coordination studies, there electrically operated would add
are usually areas found where coordination approximately $1,000 per breaker to the
between two devices can be eliminated which switchboard plus the addition of a controller
will allow the time delay setting for the station. Remote racking is a great idea for
upstream device to be reduced. Two areas draw out switchgear. However, most
where removal of the coordination interval switchboards do not have draw out
can be considered are between the main and components and thus this must be ruled out.
tie protective devices or between primary and
secondary protective devices on transformers. 5) Insulated Bus Bars
Insulating the bus bars is a positive
addition to any design. It adds protection from
inadvertent live bus bar contact. It protects the non-prohibited work.
qualified electrician from the unqualified and 3. The results must be documented.
startled rodent, snake, bird or other animal 4. Personnel must be trained, understand the
that makes phase to phase contact inside the hazards, and take appropriate action.
gear. Also it can protect the electrician from a 5. Analysis should be revaluated if the
flash due to metal parts left loose inside the standards, PPE types, or system
gear or from a falling metal tool. configuration changes.

6) Maintain Adequate Working Documenting the results occurs in two forms.


The first is the site safety manual. The Safety
Clearances
manual should include the results of the
The safest thing to do is not to get near the
calculations, and required PPE classifications
gear. If you are not a qualified electrician,
for each location, complete descriptions of the
stay away from exposed live parts. Obviously
PPE classifications, and procedures
this is not practical for the qualified
associated with performing energized work.
electrician. In many applications it is often
The second is labelling at the locations where
not practical. Testing, troubleshooting,
energized work is to be performed. In order to
diagnostics and a continuous process segment
meet the requirements of the relevant
require that power remain on to complete the
standards, more than just a warning is
task and de-energizing would introduce an
necessary. Figures shown below are two
increased hazard or is infeasible. This is
examples of labels generated using the arc
where many accidents occur and the risks and
flash module in a power systems analysis
effects of an arc flash are the greatest.
software package.
Finally, maintaining adequate work
clearances does not minimize the hazard.
10.0 Importance of Arc Flash
9.0 Proficiency & Retraining Assessment

The employer shall provide training to Without an arc flash study you will not know
each employee who is required by this section the actual level of danger or the appropriate
to use PPE. Each such employee shall be personal protective equipment (PPE) required
trained to know at least the following: When for employees. Electrical systems are
PPE is necessary; what PPE is necessary; dynamic and change over time. Internal
How to properly don, doff, adjust, and wear changes, such as adding new equipment can
PPE; The limitations of the PPE; and, The affect the level of arc flash energy. A study
proper care, maintenance, useful life and must be updated every time the system
disposal of the PPE. Distilling the changes. External changes, such as utility
requirements from the various standards changing transformers or changes at your
yields the following requirements. utilitys closest substation can severely
impact your level of arc flash energy.
1. The arc flash hazard must be assessed. Performing this study will help you create a
2. Appropriate PPE must be selected for safer work environment.
Benefits of Performing an Arc-Flash 2) Cost associated with lost productivity.
Hazard Assessment 3) Increased equipment repair costs.
4) Medical expenses for injured workers.
1) Provides workers with the best possible 5) Legal costs.
PPE. 6) Most importantly, loss of life, there is no
price for this.
2) Insurance premiums can be reduced.
11.0 Conclusion
3) Brings electrical system documentation up
to date by providing current and accurate An arc-flash event occurs whenever a fault
one-line diagrams. occurs. The attention given to the safety of
personnel continues to increase. Conducting
4) System reliability can be enhanced with a arc-flash studies allows engineers to
proper protective device coordination determine personal protective equipment
study to insure device closest to the fault required and flash boundaries. Implementing
opens in the least amount of time. protection schemes to reduce trip increases
safety and could reduce injuries or even save
5) Over-dutied equipment can be identified lives. On new and existing systems, consider
from an accurate system wide short circuit adding controls to enable instantaneous
analysis. tripping when personnel are in close
proximity to energized equipment. The cost
6) Since the system is typically modelled on of implementation is small compared to the
software, it will be easy to make future benefits of reduced trip times and reduced
changes or upgrades with minimal arc-flash hazards.
expense or effort. This paper has described the process of
arc flash hazard assessment with an example
7) Most importantly, there will be fewer system, including the calculation of incident
injured worker when an analysis is energy levels in arc flash faults and selection
performed and recommended procedures of appropriate Personal Protective Equipment
are followed. (PPE) levels as well various strategies for
reducing this arc flash phenomena.
The IEEE 1584 method, however, is a
Costs of Not Performing an Arc- systematic approach which calculates the
Flash Hazard Assessment exact arc flash energies from the electrical
Costs due to not performing an arc flash power system parameters
hazard analysis can range from minor costs
associated with fines, to millions of dollars
for lifelong medical cost and can include any
of the following:

1) Cost of non-compliance fines.

You might also like