VIPER - Read Me Document

It is important that the correct version of VIPER software is used to configure the Vega control panel.

The table below outlines the Main Control Processor (MCP), Master & Slave Basic Loop Controller (MBLC & SBLC)
and Repeater Vega panel software part numbers together with the appropriate VIPER software.

Key to Kidde part number system:

Example: Vega MCP software, part number P28180-104 breaks down as follows: -
q P28 = Vega range of software.
q 181 = Main operating feature such as VegaNET graphics support.
q 1XX = Version control.
q X06 = Revision status.
e.g version 307 VIPER should be used with version P28181-107 MCP software.

MBLC/SBLC Vega
VIPER MBLC/SBLC Software Repeater Comments Issue Date
MCP Software Software Software (Appollo) (Hochiki) Software

P28100-101 D28300-106 P28200-101-103 P28210-101 P28500-105 Upgrade Recommended 8/4/1997

P28100-201 D28300-107 P28200-201 P28210-102-107 P28500-105 Standard + MARS - Upgrade Recommended 3/9/1998
P28100-202 D28300-107 P28200-202 P28210-102-107 P28500-105 Standard + MARS - Upgrade Recommended 4/14/1998
P28100-203 D28300-107 P28200-203 P28210-102-107 P28500-105 Standard + MARS - Upgrade Recommended 7/27/1999
P28100-204 D28300-107 P28200-204 P28210-102-107 P28500-105 Standard + MARS Output 8/28/1999
P28100-205 D28300-107 P28200-205 P28210-102-107 P28500-105 Standard + MARS Output
P28100-206 D28300-107 P28200-206 P28210-102-107 P28500-105 Standard + MARS Output 12/15/1999

P28100-301 D28300-303 Blank P28210-301 P28500-301 Standard + MARS - Upgrade Recommended 10/24/2001
P28150-301 D28300-303 P28200-301 Blank P28500-301 Standard + MARS - Upgrade Recommended 10/24/2001
P28100-302 D28300-303 P28200-302-305 P28210-302-304 P28500-302 Standard + MARS Output 11/6/2001
P28101-302 D28300-303 P28200-302-305 P28210-302-304 P28500-302 Standard + MARS motherboard support (loop16) 12/7/2001

P28180-101 D28300-303 P28200-302-305 P28210-302-304 P28500-302 Special release incorporating VegaNET output 5/14/2002
P28180-102 D28300-303 P28200-302-305 P28210-302-304 P28500-302 Special release incorporating VegaNET output 6/17/2002
P28180-103 D28300-303 P28200-302-305 P28210-302-304 P28500-302 Standard release incorporating VegaNET output 8/13/2002
P28180-104 D28300-305 P28200-306 P28210-305 P28500-302 Standard release incorporating VegaNET output 5/12/2003
P28180-105 D28300-305 P28200-307-308 P28210-305 P28500-302 Network Broadcasting Fixes (No Subaddressing) 12/16/2003
P28180-106 D28300-305 P28200-307-308 P28210-305 P28500-303 Repeater Fixes & HTM82 (No Subaddressing) 4/19/2004
P28180-107 D28300-305 P28200-307-308 P28210-305 P28500-303 Backlight Fix (No Subaddressing) 7/29/2004

P28181-101 D28300-305 P28200-307-308 P28210-305 P28500-302 Original Release - Subaddressing 12/16/2003


P28181-102 D28300-305 P28200-307-308 P28210-305 P28500-303 Repeater Fixes & HTM82 4/19/2004
P28181-103 D28300-305 P28200-307-308 P28210-305 P28500-303 Backlight Fix 7/29/2004
P28181-104 D28300-307 P28200-308 P28210-305 P28500-303 Cross Panel Programming 10/21/2005
P28181-105 D28300-307 P28200-308 P28210-305 P28500-303 Network Plant Alarms 1/10/2006
P28181-106 D28300-307 P28200-308 P28210-305 P28500-303 Group to Group, Cross Panel Programming 8/9/2006
P28181-107 D28300-307 P28200-308 P28210-305 P28500-303 Replaced with fix for isolation problems 2/7/2007
P28181-108 D28300-307 P28200-308 P28210-305 P28500-303 Current release VegaNET graphics version 10/1/2007

P28170-101 D28320-102 P28200-302-305 P28210-302-304 P28500-302 Original release CZN Network version 1/17/2002
P28170-102 D28320-102 P28200-302-305 P28210-302-304 P28500-302 CZN - BGU Network Overide Fix 8/13/2002
P28170-103 D28320-102 P28200-306 P28210-305 P28500-302 CZN - Network version 6/17/2003
P28170-104 D28320-102 P28200-307 P28210-305 P28500-303 CZN - Repeater Fixes & HTM82 4/19/2004
P28170-105 D28320-102 P28200-307 P28210-305 P28500-303 CZN - Backlight Fix 7/29/2004
P28170-106 D28320-102 P28200-308 P28210-305 P28500-303 Current release CZN Network version 1/10/2006
MBLC/SBLC Vega
VIPER MBLC/SBLC Software Repeater Comments Issue Date
MCP Software Software Software (Appollo) (Hochiki) Software

P28175-101 D28320-102 P28205-101 P28215-101 P28500-302 Vega LT- CZN Network version (initial release) 10/16/2003
P28175-102 D28320-102 P28205-102 P28215-101 P28500-303 Vega LT - Repeater Fixes & HTM82 4/19/2004
P28175-103 D28320-102 P28205-102 P28215-101 P28500-303 Vega LT- Backlight Fix 7/29/2004
P28175-104 D28320-102 P28205-103 P28215-101 P28500-303 Vega LT- CZN Network version (current release) 1/10/2006

P28185-101 D28300-305 P28205-101 P28215-101 P28500-302 Vega LT- without subaddressing (initial rel.) MARS 10/16/2003
P28185-102 D28300-306 P28205-102 P28215-101 P28500-303 Vega LT - Repeater Fixes & HTM82 4/19/2004
P28185-103 D28300-307 P28205-103 P28215-101 P28500-303 Vega LT- without subaddressing (current rel.) MARS 7/29/2004

P28186-101 D28300-305 P28205-101 P28215-101 P28500-302 Vega LT- with subaddressing (initial rel.) VegaNET 10/16/2003
P28186-102 D28300-306 P28205-102 P28215-101 P28500-303 Vega LT - Repeater Fixes & HTM82 4/19/2004
P28186-103 D28300-307 P28205-103 P28215-101 P28500-303 Backlight Fix 7/29/2004
P28186-104 D28300-307 P28205-103 P28215-101 P28500-303 Cross Panel Programming 10/21/2005
P28186-105 D28300-307 P28205-103 P28215-101 P28500-303 Vega LT- with subaddressing (current release) 8/9/2006
VegaNET (group to Group Modifications)

How to determine which software is installed within your control panel

MCP Enter the access level 2 code and select 'Panel Test'
The software part number will be displayed on the LCD
Alternatively,
Software Eprom is located on board number 44782-K071 at IC 9

MBLC Software Eprom is located on board number 44782-K073 at IC 16

SBLC Software Eprom is located on board number 44782-K084 at IC 10

Repeater Software Eprom is located on board number 44782-K077 at IC 1

Thermal Printer option is available from software version P28100-301 onwards.

MBLC Inputs 7 & 8 is available from software version P28180-105 onwards

To convert version 107 VIPER files to current release, a conversion programme is available.
Upgrading version P28100-101 may need hardware upgrade also.
Please contact our Technical Support department for further advice.