You are on page 1of 291

HITACHI INVERTER-DRIVEN

MULTI-SPLIT SYSTEM
HEAT PUMP AIR CONDITIONERS
HI-MULTI SET-FREE FS SERIES
AND
HI-MULTI SET-FREE FX SERIES

Models:
Indoor Units Outdoor Units
In-the-Ceiling Type FSSERIES
RPI-O.8FS RAS-5FS
RPI-1 FS RAS-8FS
RPI-1.5FS RAS-1OFS
RPI-2FS
RPI-2.5FS FXSERIES
4-Way Cassette Type RAS-5FX
RCI-1FS RAS-8FX
RCI-1.5FS RAS-10FX
RCI-2FS
RCI-2.5FS
2-Way Cassette Type
RCD-1 FS
RCD-1.5FS
RCD-2FS
RCD-2.5FS
Wall Type
RPK-1.5FS
Floor Type
RPF-1.5FS
Floor Concealed Type
RPFI-1.5FS
Ceiling Type
RPC-2.5FS

This service manual provides the technical information for the HITACHI
Inverter-driven Multi-Split System Heat Pump Air Conditioners,"Hf-MULTI
SET-FREE, FS and FX Series".
Read this manual carefully before service activities are started.

'. HITACHI
I P5412493P I
-INDEX -

No. CONTENTS Page

1. TROUBLESHOOTING.............................................................. 1-1
1.1 Initial Troubleshooting 1-1
1.2 Troubleshooting Procedure........................................................ 1-13
1.3 Procedure of Checking Each Main Parts 1-78
1.4 Test Run 1-98

2. SERVICING. . . .. . .... . . . . .. . .. . . .. . .. . . . . ... . . . . . .. . . .. . .... .. . . .. . . .. . . .... . . . . . . 2-1


2.1 Outdoor Unit. .. . .. . . .. . .. . . . . . .. . . .. . .. . . .. .. .. . . . . . .. .. . . .. .. .. . . . . . .. . . .. . . .. . . 2-1
2.2 In-the-Ceiling Type (Models: RPI-0.8FS, RPI-1FS and RPI-l.5FS).................... 2-23

-. 2.3 In-the-Ceiling Type (Models: RPI-2FS and RPI-2.5FS)


2.4 4-Way Cassette Type. .. . .. . . .. . . . . .. . . .. . . . . . . . . .. . . . . . .. . . .. . . . . . .
2.5 2-Way Cassette Type.. . .. . .. .. . . . .. . . .. . .. . . .. . . . .. . .. . .. . . .. . . . . . . . . . . . . .. . . . . . .
2-28
2-31
2-43
2.6 Wall Type 2-56

2.7 Floor Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-65

2.8 Floor Concealed Type 2-73


2.9 Ceiling Type. .. . .. . . .. . .. . . . . . . . . . . . . .. . . .. .. . .. . . .. . . .. . ......... 2-76
2.10 Cleaning Indoor Unit's Heat Exchanger............................................. 2-85
2.11 Removing Remote Controller 2-105
2.12 Collecting Refrigerant for Replacing Indoor Unit 2-107

3. MAIN PARTS. . .. . .. . . .. . .. . . .. .. . . .. . . .. . . . . .. . . . .. . . .. . . . . . .. . . . .. . .. . . . 3-1


_ 3.1 Inverter-IGBT Inverter. . . . . . .. . .. . . .. . . . . . .. . . .. . . . . . .. . . .. . ......... 3-1
.'3,2 Thermistor 3-8

3.3 Electronic Expansion Valve........................................................ 3-12


3.4 Pressure Sensor................................................................. 3-14
3.5 Noise Filter (NF) ,............................ 3-15
3.6 Capacitor (CB1, CB2) 3-16
3.7 Reactor (DCl) 3-16
3.8 Circuit Diagram for Printed Circuit Board of Outdoor Unit.............................. 3-17
3.9 Circuit Diagram for Printed Circuit Board of Indoor Unit and CH Unit 3-24
3.10 Circuit Diagram for Printed Circuit Board of Remote Control Switch..................... 3-27

HITACHI
r

-INDEX -

No. CONTENTS Page )

4. OPTIONAL FUNCTION . 4-1

4.1 Indoor Unit . 4-1


4.2 Outdoor Unit .. 4-8

4.3 Remote Control Switches, PC-2H and PC-2C . 4-13


4.4 7-Day Timer, PSC-3T . 4-19
4.5 Central Station, PSC-3S1 . 4-21

5. FIELD WORK INSTRUCTION . 5-1


5.1 Abnormal Flickering of "RUN" Lamp on Remote Control Switch during Automatic Setting of
Unit Address . 5-1

5.2 Intake Air Temperature and Setting Temperature by Remote Control Switch . 5-2. 4
5.3 Discharge Air Temperature by Check Mode "b3" . 5-3
5.4 Power Monitor on Remote Control Switch . 5-4
5.5 What is the relation between Compressor Frequency and Other Factors? . 5-5
5.6 How are the discharge and suction pressure checked? . 5-6
5.7 Select Guide of Drain Pipe for Indoor Unit . 5-8
5.8 Caution for Installation Height of CH Unit (FX System) . 5-9
5.9 Attention for SET-FREE FX Series . 5-10
5.10Caution on Refrigerant Leakage . 5-12
5.11 Maintenance Work . 5-14
5.12Service & Maintenance Record by 7-Segment Display . 5-15
5.13Service & Maintenance Record by Remote Control Switch
5.14Service & Maintenance Record
.
. 5-1.
5-16
~

HITACHI
2 SERVICING 2-1-2-107
3 MAIN PARTS 3-1-3-27
4 OPTIONAL FUNCTIONS 4-1-4-26
5 FIELD WORK INSTRUCTIONS 5-1-5-18

1. TROUBLESHOOTING . 1-1
1.1 Initial Troubleshooting . 1-1

.
1.1.1 Dip Switch Setting . 1-1
1.1.2 Checking of Electrical Wiring . 1-4
~ 1.1.3 Failure of Power Supply to Indoor Un~ and Remote Control Switch' . 1-6
1.1.4 Abnormal Transmission of Remote Control Switch . 1-7
1.1.5 Abnormalities of Devices . 1-8
1.2 Troubleshooting Procedure .. 1-13
1.2.1 Alarm Code Table . 1-13
1.2.2 Troubleshooting by Alarm Code . 1-14
1.2.3 Troubleshooting in Check Mode by Remote Control Switch . 1-57
1.2.4 Troubleshooting by 7-Segment Display . 1-63
1.2.5 Function of DSW's and LED's . 1-68
1.2,6 Protection Control Code on 7~Segment Display . 1-77
1.3 Procedure of Checking Each Main Parts . 1-78
1.3.1 Self-Checking of PCB's using Remote Control Switch . 1-78
. " 1.3.2 Self-Checking of Remote c.~ntrol Switch . 1-80
1.3.3 Self-Checking of Indoor Unit s PCB . 1-81
1.3.4 Self-Checking of CH Unit's PCB . 1-83
1.3.5 Self-Checking of 7-Day Timer (PSC-3T) . 1-85
1.3.6 Self-Checking of Central Station (PSC-3S1) . 1-86
1.3.7 Procedure of Checking Other Main Parts , . 1-87
1.4 Test Run . 1-98
1.4.1 Test Run Mode by Remote Control Switch . 1-98
1.4.2 Test Run Mode by Outdoor Unit ' . 1-99
1.4.3 Checking List . 1-100

HITACHI
1. TROUBLESHOOTING
1.1 Initial Troubleshooting
PCB(M)
--
S=--'.-.=:=
1 . 1 . 1 Dip Switch Selting
(1) Indoor Unit

The PCB in the indoor unit is equipped with 4 dip switches. Before testing unit, set these dip
switches according to the following instructions. Unless these dip switches are set in the field, the
unit can not be operated.
a. Unit No. Selting (DSW1)
Selting is required. Set the unit No. of all indoor units respectively and serially, by following
selting position shown in the table below. Numbering must start from "0" for every outdoor unit
except the case using the central station.

Remote
Control ON NOTES:
1!l1'l1!l1!l

Unit Switch
No. 1 234 OFF
(PC-2H)
1. Automatic Address
/ j \ \
PC-2C
Display (Dip switch setting is not required.)
0 R[] ON ON ON ON--. Selling
. -R : - . before The unit number for all indoor units in the
1
------ qFf .0.N. .qN. Q~ Shipment same refrigerant cycle will be addressed
2 R2 Q~ Q~F. . qJl!. Q~
3 --Rj" qFf OFF ON ON automatically, when the remote control
4
5
::RS~~ :: Qt-:!qFf
ON
.0.N.
.0f~
.Off Q~
Q~ switch or the cemral station is used to the
indoor units in same refrigerant cycle and
6 ::~C: Qt-:! Q~F. Off Q~ the dip switches of all indoor units are set at
7 _.'J.1. _ qFf 9~F. .0f~ Q~
"No.O"position .
8 ..'!8. .. Qt-:! ON OFF
ON
.L R9 qFf ON ON OFF
10 "fIR-- Q~ 9~F. qt-!. qFf 2. For Other Cases
11
... -- Rb" qFf 9~F . qJl!. qFf
12
- -Rt - - .Off QFf
See the chapter 4 for other cases of selting
..Rd' . QFf .0!'l.
Qt-:! using the remote control switch or the
13 .0.N. .0f~ OFF
14 ::~C: Q~ 9~F .0f~ OFF central station.
15 RF OFF OFF OFF OFF

b. Optional Function Selting (DSW2)


When selting the switch for optional function, refer to the chapter 3 for each optional functions.

Selting before Shipmem

DSW2 Indoor Unit Model

ON RPC-2.5FS
~~~~~~~~ RPF-1.5FS
12345678 OFF RPFI-1.5FS
ON RPI 0.8FS, RPI-1FS, RPI-1.5FS, RPI-2.5FS, RPI-2.5FS
~ I!ll!ll!ll!ll!l ~ I!l RCI-1FS, RCI-1.5FS, RCI-2FS, RCI-2.5FS
12345678 OFF RCD-1FS, RCD-1.5FS, RCD-2FS, RCD-2.5FS
ON RPK 1.5FS
~I!ll!ll!ll!l~~~
12345678 OFF

NOTE:
The "." mark indicates position of dip switches. Figures show the setting before shipmem.

HITACHI
-
-- c. Capacity Code Setting (DSW3)
No setting is required, due to setting before shipment. This switch is used for setting the
capacity code which corresponds to the Horse-Power of the indoor unit.

Horse-Power 0.8 1 1.3 1.5 1.8 2

Setting
Pattern I 11111 I 11111 I1111 I
IIIi ON
1234 OFF
IiIi ON
1234 OFF
Ii II
ON
12340FF
1Illililli
ON
1lilililli
12340FF 1 234 OFF
ON I1111 IIIiI
ON
1234 OFF

Horse-Power 2.2 2.5 3 4 5

Setting
Pattern
1lillllliiON
1234 OFF
I I llili I
II1234
Ii IIIi ON
OFF
II
Ii ON
1234 OFF
1lillliliiON
12340FF
I I
II1 Ii234
IiIi ON
OFF

d. Capacity Adjustment Setting (DSW4) Horse-Power 0.8-5


No setting is required, due to setting before shipment.
Setting (m0N
This switch is used for setting the capacity adjustment. Pattern 1 2 OFF

CAUTION:
1. Before setting dip switches, firstly turn OFF power source and set the position of the dip switches.
If the switches are set without turning OFF the power source, the switches can not function.
2. Check to ensure that the connector from transformer is correctly connected to the PCN? on PCB,

corresponding with the power supply voltage .
. CN29 (brown line) for 220V . CN30 (red line) for 240V

II
f'
(2) CH Unit
a. Position of Dip Switches
The PCB2 in the electrical box of CH unit is equipped with 2 types of dip switches (DSW1,
DSW2), as figure below.
PCB2
"
DSWI

~
SW2
r==

I
:~
I
b. Setting of Dip Switches
fI No setting is required, due to setting before shipment as figure below. These are utilized for the
self-diagnosis of PCB. (Refer to chapter 1.3.4.)
-= --,
I~~~~ I
DSWI

1234
ON
OFF
,..;D:..S:..W...:2:....-

~~!!I~~~!!I!!I
12345678
ON
OFF

NOTE:
The "." mark indicates position of dip switches. Figures show the setting before shipment.

CAUTION:
1. Before setting dip switches, firstly turn OFF power source and set the position of the dip switches.
If the switches are set without turning OFF the power source, the switches can not function.
2. Check to ensure that the connector from transformer is correctly connected to the PCN? on PCB,
corresponding with the power supply voltage .
. CN21 (brown line) for 220V . CN22 (red line) for 240V

1-2 HITACHI
(3) Outdoor Unit
TURN OFF all power sources before setting. W~houtturning OFF, the switches do not work and
the contents of the setting are invalid. Mark of "." indicates the posmon of dip switcnes. Set the
dip switches according to the figure below.
For RAS-5FSand RAS-5FX (Refer to page 1-73.)
Check switch #2 of dip switch DS21 on PCB3.
ON: For 380V Power Supply
DS2Q 0521 RAS.5FS, RAS-5FX Setting Voltage
OFF: For 415V Power Supply
0521 DS~
For RAS-8FS, RAS-8FX, RAS-1 OFS and
RAS-10FX (Refer to page 1-75.) lQ"oool::o 1Q"~oo '" AAS-SFS
Check attached wiring on PCBS.
For 380Y FOt 4t5V I '\... RA~5FX Only
lSening before Shipment)

Attached: For 380V Power Supply OS2O


r.U'.U sen'ng be'''. Shfpm""
Removed: For 415V Power Supply
I UU
'1'40FF
ON
lNo need to set)

NOTES .
1. By using switch DSW4, the unit is started or OSW4 I TeSI Operation Setting
Setting is reQuired tOf test Qpefalion
stopped 10 to 20 seconds after the switch is and operating the compressor. see NOTE.

operated. Test ee
2. Make the outdoor unit No. clear to distinguish
~nlng
belore Cooling Heating Com"",,,.,,,
Forced Slop
Shipment Operation Operation

from other outdoor units for service and


maintenance.
OSW5 I Optional FunctIon Settmg

I Setting is reQuired when oPlinai tuncbons are required,


Senmg in the field Setting before Shipment
Defrosting RAS-5FS RAS-5FX
Optional COllditl(ll"l Change Model AAS-8F5 RAS-8FX
Function lor Cold Alea RA$-lQFS ~10FX

5et'llng
ON
OFF
~
~
, r, .. .,
., ~ "'
L..l.....
.
.... Setting
Position Position
1 2 3 4 5 6

OSW2 I Capacity Setting


I No setting change is reQuired. I
RAS-5FS RAS-8FS RA$-lQFS
Model RAS-5FX RAS-8FX RAS-l0FX

DSWl Outdoor Unit No settIng

No seni"'J C/'larN;l8 is reQuired.


I in lhis system.
Confirm lhal settir'IQ POSItion IS
'0 as set beto-e shIpment.

Settlr'IQ scmt

Sol by insertIng
- screw :i!'IVcr
Into the groove

OSW6 1 Aefflgeranl Plplm~ Length Sottu'lQ Thfl outdoor un,l


ThO OUlrtOOl' unIt 's iocatoc
hlghur lhom lho Indoor unll tocalod lower tho-m
"IL,.:se=n::,ng'C.::"'::'",,"~':::'ed=-----l1 Sol Ihft rel"Ollr:)nt plplno H,lml II'Q indoor unl'
I' . lenglh betwoon tho IndO(')l' ll .. lml
umt nnd the outdoor Unit as renews
H,~' ZO 2O:.H,.35 J5:.H,:.5Q .1..,20 2O:.WJ:.40
ACtU.1t p,pmg Lenglh 0 (ml

0<25 25:;0<50 50:..0 15 15:...0:..100


g~,~~ g~F~~ g:,-~~ g~f~~ g~FM
, 2 .:? I 2 1 2

Selling before
Sh,pmenl

HITACHI 1-3
- 1 . 1 . 2 Checking of Electrical Wiring

Check to ensure that the terminal for power source wiring (terminals "L1" to "L1" and "N" to "N" of
each terminal board: AC380-415V) and intermediate wiring (Operating Line: terminals "1" to "1" and
"2" to "2" of each terminal board: DC12V) between the indoor unit and the outdoor unit coincide
correctly, as figure below.

Check to ensure that the shielded wires are used for intermediate wiring to protect noise obstacle at
length of less than 300m and size complied with local code.

Check to ensure that the wirings and the breakers are chosen correctly, as shown in Table 1.1.

All the field wiring and equipment must comply with local code.

a. Example for Electrical Wiring Connection of FS System

Max.4 OU:dOOl' Units

NOl System
OutdocK Unit

.. :- ,

ELB,Fuse-Free .--_..~llLj
Bleaker or
Main Fuse

Main Switch

I
.II 3-/N
380V/50Hz
'1:,
~II; 415V/SOHz

.~
,',I
:Ii ,-
~20V/50Hz
1 240V/50Hz NO.1 System
IndOQt Units

T8 : Tenninal Board
PCB : Printed Circuit Board
ElG : Earth leakage Breaker
FFB : Fuse Free Breaker
*Remote--
Control
'-----'., r ::'
Control Cable
,
L.

Cable
- - : Field Wiring
...... : FieldWiring
: Field-5upplied
No.O System Indoor Units
11 : OptionaJ Accessat}' . (Max.B Indoor Unitsl

1-4 HITACHI
b. Example for Electrical Wiring Connection of FX System
FX Type Outdoor Un I t

.
Ilax 4 Outdoor tf n t t s
(MOdelS' RAS-SFX )
RAS-BFX NO.D Sy,tem
Outdoor Unit
No.1 Syuem No~ 2-sy; te~mj
RAS-IDFX o~or Unit Outdoor Un
ELB. Fu..-Fre. -~' FFB
~
ifF&'
Breaker o r "
1I.ln Fuse :L I~'I~'I~'I~I
TBl

1illJ
I ,
TBI
Llll\21~:1 ~ I 1illJ
I ,
~
r. e,--"L
c, .... =.J
..IT
.l1rLtiLlIl N I
TB
r,I

l L..
L~.\'l '/.L?J
3-/N _ n \ \\ r\ .-,,-r--
3BDV/50Hz
415V/50Hz
S! 1 \
'l_ 'r' I

l . L LJ
I I I

.11.1 n Switch
J.b!.
No.1 Syste m
1-
220V/SOH,
No.O Group
CH Un I t
TB, TB2
No.1 Group
CH Un I t
TBI TB2
.
CH Units
. .
HOV/50Hz
~~ I~'~~ "1'1 Ii ~~1~~~ I~'I
I I , I

,
ElB. Fus e-f ree
,
Breake." or
~y
Ualn Fuse Yj,,\ .. L __ -"
1'----1 JI 'yl
~ Oper.tlngLln. lOCI 2 Y,Shlelded WI re" - -

I-
,
~ d'r.0 ,"II
220V/50H,
HOY/50Hz
II~, ,1
NO.D
0

TB

( I '~
0
LI ~21e ~I~I
No.1
II N 1
TB No.2
1

TB No.3 TB
Indoor Unit Indoor Unit Indoor Unit Indoor Unit
J..'rS
II~, L'1 "
0
OI~1
I
~ (')

II~I~,I~I~I~I (1 (
PCB (Ill PCB (Ml PCB (Ml PCB (Ml
..... In Switch
E513Cp ' l [1~13Cp' I 1~'3Cp' I E5'3Cp 'l ,
No.1 System
* Remote
J~i*
Indoor Units
Controf- ~
'.* PC-2H ~ -I< PC-2C
.~
S'~C
C.ble Control C,ble CJ Dther CJ
* PC-2H \ c::J
I Unite In ooc.,,,o:E] Cooling
\
Ope:r"'lon Uode 1\

.
No.O System Indoor Units (M ex, B Un t t s }
\.lode J\ Only I
I

c. Table for Terminal Connection


o U ... Outdoor Unit, I U ... Indoor Unit , CH' CH Unit
Wiring System [Connection (Connection of Terminals)]
[O.U.-O.U. (L1-L1, L2-L2. I.3-L3, N-N)J
FS, FX

Power
[I.U.-I.U. (L1-L1, N-N)]
Supply
FX [CH-CH (LI2-Lll, N2-Nl)J, [CH-LU. (LI2-L1. N2-N)J
FS [O.U.-LU., I.U.-LU. (1-1, 2-2)J
[O.U.-CH, CH-CH (1-1, 2-2)J
Operating
FX [CH-LU. (3-1, 4-2)J, [CH-I.U. (1-1,2-2: Cooling Only)]
[LU.-I.U. (1-1,2-2: Between Same Operation Mode Units)J

Table 1.1 Electrical Data and Recommended Wiring, Breaker Size/1 Outdoor Un~

Max. Power FFB ELB Fuse


Running Supply Nominal Nominal Nominal
Model Current Line Current Current . Sensitive
Current
(A) (mm) (A) (Al (rnA) (A)
RAS-SFS,
17 MLFC2.0SQ 20 20 30 20
RAS-SFX
RAS-8FS,
32
RAS-8FX
MLFC3.SSQ 2X20 40 30 40
RAS-'OFS,
36
RAS-l0FX
FFB: Fuse Free Breaker, ELB: Earthleakage Breaker, MLFC: Flame Retardant Poly/lex Wire

NOTE: Regarding the wiring or breakers. follow to the local code.

HITACHI 1-5
1 .1 .3 Failure of Power Supply to Indoor Unit and Remote Control Switch



Lights and LCD is not Indicated
Not Operated
If fuses are melted or a breaker is activated, investigate
the cause of over current and take necessary action.

Action (Turn OFF
Phenomenon Cause Check Item
Main Switch)

Measure voltage Supply power.


Power Failure or Power is Not ON
by volt-meter.

ee or any amove t e cause


Short Circuit Supplied
uncovered of short-circuit and
between Wiring
art of wirin . re lace the fuse.
Melted Fuse or
Activation of Short Circuit of Measure insulation
Breaker at Wiring to Earth I--~ resistance.
Power Source

Failure of Indoor
Unit Fan Motor
Measure resistance
I-_~ between wiring and
insulation resistance.
Replace the fan
motor and fuse.
. f:
ec or any emove the cause
Short Circuit Supplied 1--001 of short-circuit and
uncovered
between Wiring
art of wirin . re lace the fuse.

Melted Fuse Remove t e cause


Short Circuit of Measure insulation of short-circuit and
at Control
Circuit
1-+-<00I Control Circuit to Earth I----<~ resistance. re lace the fuse.

Measure resistance
Failure of Indoor Replace the fan
Unit Fan Motor
1----<001 between wiring and
motor andfuse.
insulation resistance.

I; Failure of Transformer at Indoor Unit Side


Measure voltage at Replace the
" secondary side. transformer.

Replace cable or
Disconnected Cable of Remote Control Switch Connect the cable.
repair It.

Insufficient Connection
Co
Insufficient or IncorrectConnection I----<~
Contacting at of Indoor Unit PCB
Connectors of Check connectors. Correctly connect It.
Insufficient Connection
Remote Control
or IncorrectConnection t----<~
Switch of PCB in Remote
Controlswitch

Check it by self- Replace remote


Failure of Remote Control Switch checking mode *1). I--"control switch if failed.

Unconnected Wiring Correctly connect


Check connectors. wires.
to PCB
Failure of PCB
Check it by self- Replace PCB
Failure of PCB if failed.
checking mode *2).

Take action according to the procedure


Incorrect Wiring Connection indicated in "TEST RUN". ~ 1

*1): Refer to Item 1.3.2.
*2): Refer to Item 1.3.1.
1-6 HITACHI
r
,

1 , 1 ,4 Abnormal Transmission of Remote Control Switch

"RUN" Lamp on Remote Control Switch:


Flickering every 2 seconds

Action (Turn OFF


Phenomenon Cause Check Item
Main Switch)

Disconnection or Insufficient Contacting of Check cable and Repair cable or


Remote Control Cable connections. connect it.

Incorrect Wiring Connection Check wiring and


Repairing
(Incorrect Polarity) connections.

Replace it if remote
. Check it by self-
Failure of Remote Control Switch control switch is
check mode *1).
faultv.

Disconnected Wire Correctly connect


Failure of PCB ..... to PCB
Check connections.
wires.

(in Indoor Unit


and Remote
Control Switch)
-
...... Failure of PCB
Check ~ by self-
check mode *2),
Replace PCB if
failed,

Restart the system after


Immediate Starting within 5 minutes completion of automatic
after Power Supply setting of unit No,

*1): Refer to Item 1.3.2.


*2): Refer to Item 1.3.1.
*3): This phenomenon occurs when the system is newly installed and is started within 5 minutes
after power supply, since automatic setting of unit No. is performed during this period.

HITACHI 1-7
, . , . 5 Abnormalities of Devices

In the case that no abnormality (Alarm Code) is indicated on the remote control switch, and normal
operation is not available, take necessary action according to the procedures mentioned below.

Action (Turn OFF


Phenomenon Cause Check Item
f- f- Main Switch)

Disconnected Measure coil


Failure of Coil f- resistance by tester. f-
Indoor Unit Replaceilndoor
r- Fan Motor unitfan motor.
Burnt-Out Measure insulation
Coil f- resistance. I--

Disconnected ,.... Measure coil


......
.. Failure of
Outdoor Unit
Fan Motor
Coil

Burnt-Out
Coil
,....
resistance by tester.

Measure insulation
resistance. ......
Replace outdoor
unit fan motor.

"RUN" lights is

..
ON and LCD Failure of
is indicated. Magnetic Measure voltage
However, the Switch tor
Insufficient
Contacting
,.... between contacting ...... Replace PCB
system does for outdoor unit.
Outdoor Unit parts.
not operated.
- Fan Motor

(ex.
Measure resistance
The indoor,
outdoor fans
r- Failure of Camp. Motor
f- between two wires. f-
or compressor Replace compressor.
does not
operate.) "- Failure of Camp. ,.... Check for abnormal
sound from camp.
,....

.. Failure of
Magnetic
Switch
for Como.
Insufficient
Contacting
,....
Check magnetic
switch activates
correctly or not.
...... Replace
magnetic switch.

Failure of
UlSconnecteo
Wiring to
PCB
,.... Check connections.
- Correctly connect
wiring.

-
-e One or PCBs
Failure of
,.... Check PCB by Replace PCB
PCB self-checking "1). if failed.
c
.. Failure of
Failure of
Thermistor
-
-
Air Inlet
The Camp.
does not Stop
or Start even
Thermistor Disconnection
of Thermistor
Check it by
self-checking "2).
- Replace or correctly
connect wires if
abnormality exists.
if the Setting
temperature
on LCD
is Changed
- .. Abnormality of Remote
Control Switch Cord ~

~
Failure of Indoor Unit
PCB
"1): Refer to Item 1.3.1 -1.3.4.
Check it by
self-checking "1).
Replace PCB if
failed. I
"2): Refer to Item 1.3.1.
*3): Even if controllers are normal, the compressor does not operate under the following conditions.
CD Indoor Air Temp. is lower than 21"c or Outdoor Air Temp. is lower than -1 a"e for FS and _S"C for FX
during cooling operation.
Indoor Air Temp. is higher than 30"e or Outdoor Air Temp. is higher than 23"e during heating operation.
@ When a cooling (or heating) operation signal is given to the outdoor unit and a different mode as heating ~):~
(or cooling) operation signal is given to indoor units for FS.
@ When a emergency stop signal is given to outdoor unit.
@ When the dip switch, DSW4 on the outdoor unit PCB is set at the "ON" side and the compressor is stopped.

1-8 HITACHI

, (1.1.5 Abnormalities of Devices)

Phenomenon Cause Check Item Action (Turn OFF


Main SWitch)

Failure 01
Failure 01 Thermistor Check thermistor Replace or correctly
Discharge
by self-checking '2). connect wiring when
Air Temp.
it is abnormal.
Thermistor
Indoor Fan
Speed is
Not Changed Failure of Remote
Replace if failed.
Control Switch
Checknby
self-checking '1).
Failure of PCB for Replace if PCB
Indoor Unit is failed.

Failure 01 Failure of
Thermistor I-

Thermistor Replace or correctly


tor Outdoor Check it by
.... Evaporating Disconnected
f- self-checking '1). f-- connect when it is
abnormal.
Temp. during Wire of I-
Heating Thermistor

No Defrosting
f-e
Failure of
4-Way
Valve
Disconnected
4-Way
ValveCoil
Incorrect
Activation of
-
I-
Measure resistance
of coil.

Enforced power
supply.
~

1--0
Replace 4-way
valve.

Operation 4-WavValve

-
Mode is
Available Disconnected Control Wire Correctly connect
during Heating between Indoor Unit, Check connectors. f-- wiring.
Operation or CH Unit and Outdoor Unn
Defrosting
Operation is
Disconnected Correctly connect
Check connectors.
Wire to PCB f--
Continued f--
Failure of wiring.
f-e Outdoor Unit
PCB Replace it when
Failure of Check it by
I- self-checking '1 I. f--- check mode is

PCB
not available.

Disconnected Correctly connect


Wire to PCB
L. Check connectors. I-
Failure of wiring.
~ Indoor Unit
PCB Failure of I-
PCB
Check PCB by
f- 1--0 . Replace if PCB
Light and self-checking
is failed.
LCD Indication Failure of PCB in '1).
on Remote Indoor Unit or
Control Switch Remote Control Switch
are kept ON

'1): Refer to Item 1.3.1 -1.3.4.


'2): Refer to Item 1.3.1.

HITACHI 1-9
(1.1.5 Abnormalities 01 Devices)

Action (Turn OFF


Phenomenon Cause Check Item
I- f- Main SWitch)

,.. Indoor Heat Load is Greater


than Cooling Capacity I-
Calculate heat
load. f-
Use a bigger
unit

Gas Leakage Check refrigerant Correctly charge


or Shortage of
Refnnerant
I- quantity "1). r- refrigerant after
reoairina cas leakaos.
,
, ., Excessively
Small Diameter Measure and check
Tube or
Long Piping
I- field-supplied pipes. r- Use correct pipes.

,
,
i~
Incorrect
Activation of
Check Valve of
Outdoor Unit - Check whether or not
temp. difference
exists before/after
check valva.
Check Whetheror not
I-
Replace check
valve for outdoor
unit

-
SlightOpening Check connections
or Clogging of frost exists just after
at indoor unit ex.
ex. valve orthe temp.
Ex.Valve in
Outdoor Unit is almost same with f- valve in indoor unit
room temo. or replace it
Excessively
Clogged
:.. Low
Suction
Strainer in Check temp.
Replace strainer in
Indoor Unit difference at inlet
Pressure Clogging at Low I- and outlet of strainer. f- indoor unit.
Pressure Pioina
Clogging at
Check temp.
Low Pressure
Piping
I- difference. r- Remove clogging.

Insufficient
Cooling I- Insufficient I-
Check lor clogged
alrlmer.
,..... Clean air filter.
Operation Airto Indoor
UnitHeat
Exchanger Check for obstacle at
I-- Remove obstacles.
inlet or outlet f-

Excessively
Low AirTemp. --I Insufficient revolution
01 indoor unij Fan
motor?
I- Replace fan motor.

to Indoor
Unit Heat
Exchanger
Short-circuited
indoor unit air?
Remove cause of
short-circuited air.

Insufficient
- Clogging 01 Outdoor
Unit Heat Exchanger?

Obstacles at Inlet or
Remove Dusts

Remove clogging.
Air Flow to
!o- outlet 01 outdoor unit f-
heat exchanaer.
Outdoor
Unit Heat Is service spacefor Secure service
Excessively
High
Exchanger
~ outdoor unitsufficient? space.
Lot. Discharge
Pressure
LI Correct Fan Speed? ~ Replace fan motor.

Excessively
Low Air Temp.
to Outdoor
.... Short-Circuited
Air to Outdoor Unit? H Remove cause of
shortcCircuijed air.

Unit Heat
Exchanger LI Any Other Heat Load
near Outdoor Unit?
Remove heat
SOurce.

"1): Refer to item 9.1 oITC II.

1-10
HITACHI
(1.1.5 Abnormalities of Devices)

Phenomenon Cause
- Check Item :...... Action (Turn OFF
Main Switch)

Excessively
Excessively
Charged
Refrigerant

Non-Condensed
f- Check each Temp.

Check each Temp.


- Correctly Charge
Refrigerant.

r- High
Discharge Gas in Cycle r- and Pressure. r- Charge Refrigerant
after Vacuum Pumping.

-
Pressure
Insufficient
Clogging of
Cooling
Operation
- Discharge Piping
Check for Clogging. r- Remove Clogging.

Excessively
~ Low Suction
Failure of
Bypass
Solenoid Valve - Check for Leakage
of Solenoid Valve.
~
Replace Solenoid
Valve.

Pressure Malfunction or
r-
Check Temp. Difference

- Replace 4-Way

-.
IntemalLeakage between Inlet and Valve.
of 4-Way Valve Outlet of 4-Wav Valve.

Indoor Heat Load is Greater Replace the Unit


r"' than Heating Capacity r- Calculate Heat Load. f---- with a Bigger Unit.

Gas Leakage
or Insufficient
Refrigerant
Charge - Measure Superheat. f---
Correctly Charge
Refrigerant after Gas
Leakage Check and
Repairing.
Excessivefy
Small Diameter
or Long Piping

SlightOpening
or Cloggingof
- Measure
Field-Suppling Piping. r- Use Specified Pipes.

CheckConnections of
Connec1ors for Ex. Valve
I--
IndoorUnit r- Measure Superheat.
r- in Outdoor Unitand
Ex. Valve IndoorUnit or Reolaeeit.
Cloggingof Replace Strainer for
Check Temp. Difference
IndoorUniV
OutdoorUnit
Strainer
~ between Inlet and
Outlet of Strainer.
r- Outdoor Unit Dr
Indoor Unit.

-. Insufficient
Heating
Operation
"-
Excessively
Low
Suction
Pressure
Cloggingof
Suction Piping
- r-
Check Temp.
Difference of each Pari. ~

Is Outdoor Unit Heat


Exchanger Clogged? .....
Remove Clogging.

Remove Dust.

Is there Only
Insufficient Air 1-+ Obstacle at Inlet or ~ Remove Obstacle.
Flowthrough Outlet of Outdoor Unit?
Outdoor Unit
HeatExchanger
- Is service tipace
for Outdoor Unit
Sufficient? - Secure Sufficient
Service Space.

- Check for Speed of


Outdoor Unit Fan. r- Replace Fan Motor.

-
Excessively
Low AirTemp. Check for any
Remove Cause of
through Outdoor
Unit Heat
f---- Short-Circuited Air
Short-Circuited Air.
to Outdoor Unit.
Exchanoer
Defrosting is
Check Thermistor Replace Thenmistor
Insufficiently
Completed
:...... for Defrosting. f---- for Defrosting.

HITACHI 1-11

-
(1.1.5 Abnormalities of Devices)

t Phenomenon I
I
Cause
- Check Item

Check for filter


f-
Action (Turn OFF
Main Switch)
r- clogging. r- Remove dusts.

Insufficient Air cneex TOr any


Flow to Outdoor obstacles at inlet or Remove obstacle.
Unit Heat
I- outlet of indoor unit.
f-
Exchanger
Check indoor fan
Excessively
C. speed. r- Replace fan motor.

-
High
. ;to
Discharge
Excessively High Check whether or
~

Pressure
Air Temp. to
IndoorUnnHeal r- not shortcCircuited
air exists.
Remove cause of
short circuited air.
Exchanger

.
Insufficient Excesswely Check refrigerant Correctly charge
Heating
Operation
Charged
Refriaeranl
f- quantity "1). r- refrigerant.

I--
Non-Condensate
Gas in Ref.
Cycle
Clogging of
r-
Check refrigerant
quantity "1).
- Recharge refrigerant
after vacuum pumping.
~

Discharge
Pioina r- Check for clogging.
r- Remove clogging.

.. Excessively
High
Failure of
Bypass
Solenoid Valve - Check for leakage
of solenoid valve. f--
Replace solenoid
valve.

Suction
Pressure
Mallunction
or Internal
Le_geof
4-WavValve - Check temp. difference
at inlet and outlet of
4-way valve.
"-
Replace 4-way
valve.

.. Foreign Particles Inside


of Fan Casing
- Check it by viewing.
f-
Remove loreignp-
Particles.

"

, I'
I .. Indoor Unit Fan Running
is Hilling Casing -, Check it by viewing.
f-
Adjusl position of
fan runner.

,i
,
I
.. Outdoor Unn Propeller
Fan is Hilling Shroud r- Check it by Viewing f-
Adjust Position of
Propeller Fan

~I
Cooling or Faulty Check each Part is
! Heating Installation Tightly Fixed
Tightly Fix it

-
I Operation
I--

..
with Abnormal Liquid Ref. Check refrigerant Correctly Charge
Sound Abnormal Compression quantity "1). f- Refrigerant
Sound from
Compressor vvear or
, Breakage of Replace Compressor
Internal
:1 Como. Parts
:1 Replace Oil Heater
No Heating
d by Oil Heater
Check Resistance or Fuse
I
.. Hamming Sound from
Magnetic Conductor r-
Check Surface of
Contacts
., Replace Magnetic
Switch

"-
Abnormal Vibration by
Cabinets
., Check each Fixing
Screws
Tightly Fix it

"1): Refer to item 9.1 of TC II .


1-12 HITACHI
w it .. ~

Code No.
01
Cateqory
Indoor Unit
Content 01Abnormality
Tripping of Protection Device
Leading Cause
Failure of Fan Motor, Drain Discharge. PCB, Relay.
'"
ec

02 Outdoor Unit Tripping 01 Protection Device Failure of Compressor, Refrigerant Quantity, Inverse Phase.
~
03 Transmission Abnormality between Indoor and Outdoor (or Indoor) Incorrect Wiring. Faiture ot PCB. Tnpping ot Fuse. 0
~ c:
iii
3 ~
04 Inverter Inverter Trip of Ouldoor Unit Failure in Transmission 01PCB lor lnverter.
(Jl
06 Vollage Drop Voltage Drop in Outdoor Unit Voltage Drop. Incorrecl Wiring.
07 Decrease in Discharge Gas Superheat Excessive Refrigerant Charge. Failure of Thermistor, Wiring.
oo g-
0
Ref. Cycle c. g.
08 Increase in Discharge Gas Temperature Insufficient Refrigerant. Failure 01 Thermistor, Wiring. CD

09 Outdoor Unit Tripping of Protection Device Failure 01 Fan Motor PCB. p;I co
."
11 Inlet Air Thermistor
Q:
CD ao
12 Outlet Air Thermistor CD
C.
13 Sensor on c:
Freeze Protection Thermistor Failure 01 Thermistor, Sensor, Connection. @
Indoor Unit
14 Gas Piping Thermistor
10,15-19 Other Thermistor. Sensor
21 High Pressure Sensor
22
:J: 23
Outdoor Air Thermistor
Discharge Gas Thermistor

~o
Sensor on
Failure of Thermistor, Sensor, Connection.
24 Outdoor Unit Evaporating Thermistor
29 Low Pressure Sensor
20,25-28 Other Thermistor, Sensor

-
:J: 31
32
35 System
Incorrect Setting ot Outdoor and Indoor Unit Dip Switches
Abnormal Transmission of Other Indoor Unil
Incorrect Sening in Indoor Unit No.
Incorrect Setting ot Capacity Code.
Failure of Power Supply, PCB in Other Indoor Unit.
Existence of the same Indoor Unit No.
38 Abnormality of Protective Circuit in Outdoor Unit Incorrect Connection to PCB in Outdoor Unit.
30,33,34,36,37,39 Other Abnormality in System -
43 Pressure Ratio Decrease Protection Activating Failure of Compressor, Inverter, Power Supply.
44 Low Pressure Increase Protection Activatinq Overload to 'fndoor on Cooling. High Temperature 01Outdoor Air.
45 High Pressure Increase Protection Activating Overload Operation. Excessive Refrigerant.
Pressure
46 High Pressure Decrease Protection Activating Insufficient Relrigerant.
47 Low Pressure Decrease Protection Activating Vacuum Condition in Cycle Failure of Expansion Valve.
40-42, 48, 49 Other Pressure Abnormality --
51 Thermal Protection Activating Overload Operation.
52 Overcurrent Protection Activating (1) Overload, Overcunent, Locking to Compressor.
53 Inverter Overcurrent Protection Activating (2) Overload, Overcurrent to Inverter.
54 Fin Thermistor Protection Activating Overheating of Inverter. Cooling Fan Stoppage.
50,55-59 Other Abnormality --
~

~
,
co

lOIL----::: '-======-:--= .-. ~.~-----' ............


1 .2.2 Troubleshooting by Alarm Code

Alarm nf Activation of Safety Device in Indoor Unit


Code u f
"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.
,
! * This alarm code is indicated when AC220V or 240V is not given between PCNl (FS) on PCB and
I L2(N) phase during the cooling, fan or heating operation.

! No Activation of Safety Device (such


1
I
Is 220VAC or 240VAC applied between
PCN1 (FS) on PCB(P) and L2 phase? ~
as Float Switch FS and Internal
Thermostat ITI) or Incorrect
Wirino

r\ No
Check for loosenessbetween CN16 Check connections
of PCB(M} and CN20 of PCB(P}. ~ of connector. .t}

"~I__-
No
Check for wire continuitybetween CN16
I of PCB(M) and CN20 of PCB(P}. Disconnected Cable

I
I,

..
s
Is the voltage between 2# and 3# of
CN20 on PCB(P) OV?
No
Faulty PCB(P)

\ ,
Faulty PCB(M)
o
PCB(P)(High Voltage)
peN)
f,
I

I
~
rs 49FE
o
CD
ll, l2, N I ~ I
,'I
I:
"

,I

NOTE:
Above figure shows a separated-board
BBBB I. pc:.,I:CN~ II :CN~ ,
type PCB, some unit has a one-board type
PCB which has the same functions and Ms H2 52H Mo SHi 5 It
devices with the separated-board type.

1-14 HITACHI
Phenomenon Action (Turn OFF
Cause Check Item
f- f- Main Switch)

Faulty Indoor Unit Measure coil


Replace indoor unit
r- Fan Motor
I- resistance and I- fan motor if faulty.
insulation resistance.

Tripping of Check continuity


Internal alter indoor unit fan Indoor Unit Fan Motor
Fault
Thermostat motor decreases to it Faulty
I-- f- normal temp. f-
for Indoor Faulty
Unit Fan Internal
Motor Faulty Measure resistance Repair looseness and
c., Thermostat Contacting l- I-
by tester. replace connector.

Faulty
Connection
- Check connections. r- Repair connection.

High Drain Clogging of Remove clogged


r- f- Check drain pan. f-
Level Drainage foreign particles.

Fault
I--
Check continuity when
dra'in level is low. I--
Replace float switch
if faulty.

Faulty Faulty Measure resistance Repair looseness and


Activation of
Float Contacting by tester. I- replace connector.
Switch

-
Float Switch
Faulty
Check connections. Repair connection.
Connection I--
Check whether or not If cool air discharged,

.. Opening of Indoor Unit


Ex. Valve is Locked Open -
cool air discharged by
selting at "FAN" when
other indoor units are
pperated under cooling
-
CD Repair wiring of ex.


valve. connector or
connector.
Replace ex. valve,
ooeration. if faultv.

Check PCB by
Faulty Indoor Unit PCB :.- self-checking 1). f- Replace it it faulty.

-. 1): Refer to Item 1.3.1 and 1.3.3.

I,
., ;I
!

HITACHI 1-15

-
Alarm Abnormality of Picking up Phase Signal
Code (RAS-8FS, RAS-8FX, RAS-10FS and RAS-10FX)
ii
I "RUN" light flickers and "ALARM" is indicated on the remote control switch.
I' The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.
I * This alarm is indicated when the main power source phase is reversely connected or one phase is
not connected during running of the constant speed compressor.

Yes
Single Phase or Incorrect Connection
of Power Source Phase? '2) > Correctly connect each
phase of power source.

Yes
Is there any excessively voltage
decrease at power source? > Abnormality with
Power Source.

r Faulty PCBl and PCB2


or other cause.
Refer to next page.

Phenomenon

Activation of
r-
Cause

Reverse or Single Phase


-
r-
Check Item

Check it according to
electrical wiring in
r-
f-
Action (Turn OFF
Main Swach)

Replacing Wires, Repair,


Tightening SCrews or
Reverse

--
Paae 1-4, 1-5. Correct Winna
Phase
Sensor in
Outdoor Una ~ Faulty Outdoor Una PCB
r-
Check it by
self-checking '1). -i Replace PCB if
faulty.

NOTES:
*1): Refer to itsrn 1.3.1 - 1.3.4.

II *2): The neon lamp on PCB6 turns ON. However, some units are not equipped with this lamp.

I
"

,
I,
i'

HITACHI
L 1-16
r
Alarm
Activation of Safety Device for Outdoor Unit
Code
j
"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.
This alarm is indicated when one of safety devices is activated during compressor running (CMC1: ON).

DoesCMC10N
when starting?

Yes
..
No Is LED309 of
PCB2 ON durtng
stan-up and is
LED310 ON for
0.6 seconds?

Yes
..
No Check for any
looseness at CN108
of PCBl and
CN301 of PCB2.

No Looseness
Yes

c:::>
Restart after insening
CN108 or CN301
correctly.

Check for any Yes


looseness at CN401 Restart after insening
of PCB4 and CN121 CN401 or CNI21.
of PCB1.

In the voltage
I.,-.~I'-_~~---J
No Loosenessr-_-::-..,.....,...=_ _..,
Faulty PCBl

No Voltage
between PCN308
#5 and PCN301 #5 FaUlty PCB2
380V during LED
309 ON? No Looseness Check for wirtng
connections outside of

..
PCB2.
Is one ot safety
No Check for any Yes Restan after insening
devices still ON?
(No continuity
between Bl and
looseness at
PCN301 and c:::> PCN301 or PCN308
correctly.
B3 of CMC1) PCN308 of PCB2.

Yes
Is the voltage
between #3 of No Voltage Check the wirtng
PCN303 and #5 of ,. ~ connections outside
PCN301 on PC82 outdoor unit PCB.
220V or 240V? L-==:';";;===_--'
YesD

Normal PCB2

Check activation of the following safety devices. Remove the cause after checking.
CD High Pressure Switch (PSH: 30 kg/cm 2G)

HITACHI 1-17

--
In case of RAS-8FS, RAS-8FX, RAS-10FS and RAS-10FX, this alarm is indicated when one of safety
devices is activated during CMC2 is ON in addition to compressor's running.

< > I
No
Is heat load big? 1CMC2 OFF is normal.

.0 Yas
Is LED307 of PCB2


No No Yas Correctly connect
Does CMC2 ON ON and LED30B Checkforlooseness
at starting? ON for 0.6 sec. at
at CNIOB of PCBI
andCN301 of PCB2. 0 CNI 08 and CN301
and restart operation.
starting?
Yes
Yes ~ No Looseness

Check for
looseness at Yes Correctly connect
CN401 of PCB4
and CNI21 of
0 CNI08 and CN301
and restart operation.

,-
PCBt.
No Looseness
t)
Faulty PCBl
Is 220V or 240V applied
between #1 of PCN307' No
and #5 of PCN301 on
PCB2 when LE0307 &
Faulty PCB2
I
LED30B is ON?
U Yes
I No
~
Check wiring
other than PCB2.

Is one of safety


No Yes Correctiy connect
device still ON?(No Checkfor looseness
continuity between
terminals 81 and 83
at PCN301 of PCBI
and CN301 of PCB2. 0 CN301 and CN307
and restart operation.
oICMeI? )

No Yes
Is 380V applied
between #1 of PCN303 Voltage
Check wiring
and #5 of PCN301 on

.
other than PCB2.
PCB2when CMC2 is
ON?
.0 Yes
-,
PCB2 is nonmal.

Check activation of the following safety devices. PCB1: O.U. PCB (Low Voltage)
Remove the cause after checking. PCB2: O.U. PCB (High Voltage)
I <D High Pressure Switch PSH: 30kg/cm 2G PCB4: Power Supply PCB
I
Setting of ORC: 12.1 A for RAS-8FS and RAS-8FX
i 15A for RAS-10FS and RAS-l0FX

il O.U.: Outdoor Unit

1-18 HITACHI
I.
Action (Turn OFF
Phenomenon Cause f- Check Item f- Main Sw~ch)

Excessively Highor low Operate within range


r- Voltageof Power Source r- from 10%.

Excessively Large
Imbalance Among Adjust voltage
r" Compressor Motor
Running Current
f-- Phase at Power Source r- between each phasa.

Excessively High
L. Discharge Pressure r- Check for causes.

... Meted Fuse for Power


Source I- Replace the fuses.

Activation of
Overcurrent ... Single Phase Operation f--
Looseness of Screws
for Power Source I- lightly fix screws.
Relay for
Compressor Deterioration of
Replace magnetic
Motor
-
L.. Contact of Magnetic
Switch for Compo
r- contactor.

~. [RAS-SFS]
RAS-SFX
RAS-10FS
f-- Seizure of Compo Bearing Replace compressor.

RAS-10FX
Insulation Failure of Measure insulation
f-o
Compo Motor r--- resistance. I--'- Replace compressor.

Measure current ot
Fault I- comp, motor and f--o Replace overcurrent
check continuity relay when faulty
during stoppage.
L-o FaUlty
Overcurrent Faulty Measure resistance Repair looseness and
Relay Contacting I- by tester. f--o replace connector.

Faulty
Connection I-
Check connections.
r- Repair connections.

... Check for dust on


heat exchanger. r--- Remove dust.

Check for dust on


~. f- Remove dust.
-I air filter
Insufficient Air Flow to
Heat Exchanger Check for any obstacle a
(Outdoor Heat Exchanger I- inlet or outlet of outlet of f- Remove obstacles.
Activation of r"' during Cooling Operation heatexchanger.
High Pressure or Indoor Heat Exchanger
Switch due to
Excessively
High Discharge
during Heating Operation)
... Check the service
space. r- Secure service
space.
Pressure I--
Check for speed.
L. (Outdoor Fan: Cooling )
Indoor Fan: Heating
r- Replace from
motor if faulty.

L-o MaJlunction of Electronic


.. Check for looseness
of connectors. f--o Repair looseness.

Ex. Valve
y Check opening of
ex. Valve. I- Replace Ex. Valve.

-
HITACHI 1-19
i
__ ,.'.--- --c-,- -.,,,- ,-,' --,'x\"
...

Phenomenon Cause
- Check Item
- Action (Tum OFF
Main Switch)

... Calculate heat load.

Check for hot air in


- Reduce heat load or
use a bigger unit.

Make good
Excessively High Temp. ~ the ceiling (Heating). f---. circulation.
,.. Air to Indoor Unit Heat
Exchanger Check for short Remove short
f.- circuited air (Heating). f---. circuited air.

Check for other Remove heat


L.. heat source. f---. source.

Measure diSCharge
Faulty
pressure.
Pressure ~ Check continuity after f---oo Replace it if faulty.
Swijch
decreasinn of nressure.
f.- Faulty High
Pressure Insufficient Measure resistor Repair looseness.
Switch Contacling f---. by tester. f---oo Replace connector.

e I):
Activation of
High Pressure
Switch due to
'"'-
Incorrect
Connection

FaUlty Bypass
- Measure connections. f--o. Repair connections.

Replace gas bypass


Excessively f.- Solenoid Valve f---. Check for clogging. f--o. solenoid valve.
High Discharge
Pressure
Check refrigerant Charge refrigerant
f.- Overcharged Refrigerant f- quantity "I}. f--o. correctly.

Mixture of Non-Condensable Check ambient Recharge refrigerant


f.- Gas in Refrigeration Cycle f- temp. and pressure. f--o. after vacuum pumping.

Clogging of Discharge
f.- Piping f---. Check for clogging. f---. Remove clogging.

f.- Clogging of Check Valve I- Check for clogging. f---. Replace check valve.

Faulty
Solenoid
Valve
f---. Check Activation
of SVD1.
I- Replace solenoid
coil or CH unit. e t
[FX System]
Le Faulty Insufficient
Contacting f---. Check for connection
at PCNS of PCBl and
I--l Repair looseness.
CH Unij

Incorrect
PCNS of PCB3.
Check for connection
l-I Replace connector.

I-
Connection at connector 20D 1.
H Repair connections.

"I}: Refer to Item 9.1 oITCIi.

f,

1-20 HITACHI
I FS SYSTEM I
:(1 Alarm
Abnormal Transmitting between Indoor Units and Outdoor Unit
Code

"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.
* This alarm is indicated when abnormality is maintained for 3 minutes after normal transmnting
between indoor units and outdoor unit, and also abnormality is maintained for 30 seconds after the
micro-computer is automatically reset, or the alarm is indicated when the abnormal transmitting is
maintained for 30 seconds from starting of the outdoor unit.
* Investigate the cause of overcurrent and take necessary action when fuses are melted or the
breaker for the outdoor unit are activated.

tte Is LED2 (green) on


PCB1 flickering?
~ Remove PCN102
of PCBl.

Dyes

D
Yes
Is LED2 (green) on Check indoor/outdoor
Faulty PCBl
10 Is LED2 (yellow) on
PCB(M) flickering? PCB 1 flickering? unit wiring or PCB(M).

I No I No

No
Is LED2 (yellow) on Is LED2 (green) on Faulty PCB I
Faulty PCB(M)
l- PCB(M) OFF? PCBION?

Dyes I
..
No

No
Is LEDI (red) or
Check the indoor unit Is LED4 (green) on Faulty PCB I
LEDIOI (red)
transformer. PCB(M) ON?

I
flickering on PCBI?

:-t. Dyes No

Check the wiring between Check the outdoor unit


indoor andoutdoor units. power supply and PCB4.

PCB1: Outdoor Unit PCB (Low Voltage)


PCB2: Outdoor Unit PCB (High Voltage)
PCB4: Outdoor Unit PCB (Power Supply)
PCB(M): Indoor Unit PCB (Low Voltage)

HITACHI 1-21
.,

I FSSYSTEM I
Action (Tum OFF
Phenomenon Cause Check Item f-
f- Main Switch)

Measure voltage
Power Failure or No Power Supply f- f- Supply power.
by tester.

Check for breakage Remove short circuit


e"' Short Circuit between Wires f- f-
of insulation. and replace fuse.

Melted Fuse
for Power
Source or
-
.. Short Circuited Wire
to Ground
- Measure insulation
resistance.
- Remove snort circuit
to ground and replace
fuse.
Activation of
Outdoor Unit
Breaker
:... Faulty Camp. Motor
- Measure resistance
between wires and
insulation resistance - Replace camp. and
fuse.

.. Faulty Outdoor Unit


Fan Motor
- Measure resistance
belweenwiresand
insulation resistance. - Replace outdoor unit
fan motor and fuse.

Melted Fuse
for Control
Circuit or
Activation of
r-- Short Circuit between Wires

Short Circuit of Control


Circuit
-
I-
Check for breakage
01 insulation.

Measure insulation
resistance.
f-

f-
Remove short circuit
and replace fuse.

Remove short circuit


and replace fuse.
Outdoor Unit
Breaker FaullySolenoid Coil for Measure resistance Replace magnetic
~ Magnelic Switchfor Camp. I- I-
of coil. switch and fuse.
Motor

Measure output voltage


Faulty PCB4 (Outdoor Unit) f- f- Replace PCB.
of CN401 on PCB4 *2).

Disconnected Between Outdoor Unit Check continuity of


Wires r-- f- Replacing wires,
and Indoor Unit wires.
Insulticient repairing tightening
Contacting or ~
Check for looseness r--- screws, correct
Power Source Wiring of Connection screws.
Incorrect ~ wiring.
Connection for Outdoor Unit f- Check terminal Nos.

Faulty PCB
(Outdoor Unit, ~
r-
Disconnected Wires
to PCB f- Check connections.
- Correctly connect
wires.

~
Indoor Unit) Check it by
~ Faulty PCB I- self-checking *1)
Replace it if faulty.
,
II
,I

Incorrect
r-
Disconnected Wire
InsufficientContacting
- Check continuity
and looseness of
connection screws
f-
Replacing Wires,
Repairing Tightening
SCrews
Ii
I
Wiring *t) ~

"- Incorrect Wiring


- Check terminal Nos. I-
Correctly Connect
Wires

Incorrect Indoor Unit Address Setting

*1): Refer to Item 1.3.1 - 1.3.4.


- Check dip switch, DSWt
on indoor unit PCB.
-
Correctly set unil No.
on indoorunil PCB(M).
Correctly set dip switch,
DSWI.

*2): Output Voltage at CN401 on PCB4.


(5VDC between #3 and #4, 12VDC between #2 and #4, 24VDC between #1 and #4)

,
1
,.r. 1-22 HITACHI
"
1
I FX SYSTEM I
(J Alarm Abnormal Transmitting between Indoor Units,
Code CH Units and Outdoor Unit
"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.
* This alarm is indicated when abnormality is maintained for 3 minutes after normal transmitting
between indoor units and outdoor unit, and also abnormality is maintained for 30 seconds after the
micro-computer is automatically reset, or the alarm is indicated when the abnormal transmitting is
maintained for 30 seconds from starting of the outdoor unit.
* Investigate the cause of overcurrent and take necessary action when fuses are melted or the
breaker for the outdoor unit are activated.

~
Is LED2 (green) on Remove PCNt02
PCBl flickering? of PCBl.

.~. DYes
D
Is LED2 (yellow) Check indoor/CHI
Is LED2 (green) on
on PCB2 (CH) J'L.__' I outdoor unit wiring or
PCB1 flickering?
flickering? PCB(M).

No
No
No
Is LED2 (yellow) on Is LED2 (green) on
Faulty PCB2 (CH)
l- PCB2 (CH) OFF? PCBt ON?
Faulty PCBt

DYes
No

Check Ihe CH unil


powersource and
transformer.
- No
Is LED4 (green) on
PCB2 (CH) ON?

DYes

Check the wiring between


Is LEDt (red) or
LED10l (red)
flickering on PCBt?

No
Check the outdoor unil
Faulty PCBt

CH andoutdoor units. power supply and PCB4.

:".
Is LED2 (yellow) on Check PCB(M)
PCB 1: Outdoor Unit PCB (Low Voltage) PCB(M) flickering?
PCB2: Outdoor Unit PCB (High Voltage)
PCB4: Outdoor Unit PCB (Power Supply)
PCB2(CH): CH Unit PCB (Low Voltage)
Is LED2 (yellow) on FaUlty PCB(M)
PCB(M) OFF?

DYes

Is LED4 (green) on
PCB(M) ON?

DYes
..
No
Check the indoor
power supply and
transformer.

Check the wiring between


indoor and CH unit.

HITACHI 1-23
I FX SYSTEM I
Action (Turn OFF
Phenomenon Cause
r--- Check Item f-e Main Switch)

Measure voltage
Power Failure or No Power Supply I- f-e Supply power.
by tester.

Check for breakage Remove short circuit


;e Short Circuit between Wires I- of insulation. f-e and replace fuse.

Melted Fuse
for Power
-
.. Short Circuited Wire
to Ground
,..-.
Measure insulation
resistance.
- Remove short circuit
to ground and replace

..
Source or fuse.
Activation of
Outdoor Unit
Breaker
Faulty Compo Motor ,..-.
Measure resistance
between wires and
insulation resistance - Replace comp. and
fuse.

.. Faulty Outdoor Unit


Fan Motor
,..-.
Measure resistance
between wires and
insulation resistance. - Replace outdoor unit
fan motor and fuse.

\1
Melted Fuse
for Control
.. Short Circuit between Wires ,..-.
Check for breakage
of insulation.
- Remove short circuit
and replace fuse.

Circuit or
Activation of
Short Circuit of Control
Circuit
,..-.
Measure insulation
resistance.
- Remove short circuit
and replace fuse.
Outdoor Unit
Breaker
.. Faulty Solenoid Coil for
Magnetic Switch for Compo
Motor - Measure resistance
of coil. I-
Replace magnetic
switch and fuse.

Measure output voltage


Faulty PCB4 (Outdoor Unit) I- of CN401 on PCB4 '2). I- Replace PCB.

Faulty Transformer of CH Unit


Measureinput voltage of
I - CN1 on PCB2 (CH) '3).
- Replace transformer.

Disconnected
Wires
Insufficient
r-
Between Outdoor Unit,
CH Unit and Indoor Unit
- Check continuity of
wires.

-
Replacing wires,
repairing tightening
r-

-
Check for looseness
Contacting or
Incorrect
Connection
... Power Source Wiring
for Outdoor Unit
of Connection screws.
Check terminal Nos.
screws, correct
wiring.

Faulty PCB .. Disconnected Wires


to PCB
- Check connections.
- Correctly connect
wires.
ell'

..
(Outdoor Unit,
Indoor Unit '--
Check it by
and CH Unit) Faulty PCB f-I Replace it if faulty.
self-checking 'I)

-- - -
Check continuity Replacing Wires,
Disconnected Wire
and looseness of Repairing lightening
Insufficient Contacting
Incorrect connection screws Screws
\ Wiring 'I)
... Incorrect Wiring Check terminal Nos.
H Correctly Connect
Wires

-
Correctly set unit No.
Incorrect Indoor Unit Address Setting
- Check dip switch, DSW1
on indoor unit PCB.
on indoor unit PCB(M).
Correctly set dip switch,
DSWI.

'1): Refer to Item 1.3.1 - 1.3.4 in Service Manual.


'2): Output Voltage at CN401 on PCB4.
(5VDC between #3 and #4, 12VDC between #2 and #4, 24VDC between #1 and #4)
'3): Input Voltage at CN1 on PCB2 (CH).
(22.2VAC between #1 and #2, 14.5VAC between #3 and #4)

1-24 HITACHI
I
i Alarm
Abnormal Transmitting between Inverter and Outdoor Unit
Code
(J
I "RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB1.
*This alarm code is indicated when abnormal transmitting between the outdoor unit PCBl and inverter
PCB3 is maintained for 4 minutes.

No
IsLE010l (red) on Disconnect PCN10l
PCB1flickering? of PCB1.

DYes
D
Yes Yes
Check PCB3 and

tt.
IsLE04 (yellow) on IsLE010l (red) on
Check PCB3 10 PCB3 flickering? PCBl flickering? outdoor unit inverter

I No
I No t No

Yes
wirin .

I, Is LE04 (yellow) on IsLE0101 (red) on


Faulty PCB3 I. PCB30FF? PCB10N? 01_----'-_---'
Faulty PCBl

Dyes I No

No


Check the inverter's Is LEOI (red) or
IsLED6 (red) on LED2 (green) Faulty PCBl
power supply and PCB30N? flickering onPCB1?

I
transformer.

Dyes No

Check the Check PCB4.


outdoor inverter wiring.

PCB1: Control PCB (Low Voltage)


PCB3: Inverter PCB (High Voltage)
PCB4: Power Supply PCB

HITACHI 1-25
,
Action (Turn OFF
Check Item

~I
Phenomenon Cause f---- f---- Main Switch)

Measure secondary side


Faulty Transformer Coil for Inverter Replace transformer.
voltage ot transformer.

Disconnected
Wires,
Insufficient
Contacting
~
ro-
From Outdoor Unit to
PCB for Inverter I-- Check continuity of
wires.
Check for looseness of
connection screws.
-. Replacing Wires,
Repairing, Tightening
Screws, Incorrect
I
I~ Incorrect t.- Power Source Wiring
f---- I- Wiring.
'ii for Outdoor Unit Check connection No.
,
Connection
~:

Disconnected Wires Repair wiring


Faulty PCB Check connections.
to PCB connections.
(Indoor Unit
PCB, PCB3
For Inverter) Check it by
:;,1 Faulty PCB Replace PCB if faulty.
self-checking '1).
(
1'1
Ii;
Check continuity. Replacing Wires,
Disconnected Wires
reo Insufficient Contacting I-- Check for looseness f---- Repairing, Toghtening
Incorrect ofconnection screws. SCrews
wiring '1) f--
,

t.. Check connection Correct connect


I Incorrect Wiring r--- Nos. I-- Wires.
II
Disconnected Wires Repair wiring
I: Faulty PCB
r"' to PCB I-- Check connections. I--- connections.
(Outdoor Unit
I PCB, PCB for ~
Check it by
Inverter t.- Faulty PCB l- I-- Replace PCB if faulty.
I self-checking '1 ).

1): Refer to Item 1.3.1 - 1.3.4.

j
1

,Ii
'I:1
"

1-26 HITACHI
I
J....
r
,I
Alarm
Excessively Low or High Voltage to Outdoor Unit
Code

This alarm codes is indicated when voltage to the inverter circuit and CB capacitor is insufficient and its
occurrence is three limes in 30 minutes. In the case that the occurrence is smalier than 2 times, retry is
performed.

I Restan operation. I
D
Is the supplyvollege No
220V10% or Check wiring and cable
240V10%. between capacity.
L1 end N phase?

D Ves

;",
:i',
,I
I
-
Isthevoltage over
127V and under
296V. between L1
andN phasedUring
operation?
D Ves
No

Restaned normally
or
Stoppage by high frequency.
Does the voltage Ves
fait during operation
by operation 01
other apparatus?
, No
Frequency can
increase higher
Does LE06 on than 60Hz.
PCB3 ON alter Ves
compressor's
electromagnetic
switch CMCI turns
c:::>
Compressor Faulty PCB3 for Inverter.
on?
, No
stops immediately.
(lower than 20Hz) > Replace it.

,
".~::te
Are CN13 on PCB3
and its wiring
correctly connected
or conductive?
Ves
D
I
I No
~
Correct the connection
and wiring of CN13.

HITACHI 1-27
" Alarm
Decrease of Discharge Gas Superheat
Code

"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.
*In the case that the discharge gas superheat less than 10 deg. at the top of the compressor is
maintained for 1 hours, retry operation is performed. However, the alarm occurs again within two
hours, this alarm code is indicated.

No Position of Thermistor
Is the thermistor on
i top of compressor
good (1-6KQ)?
_I Faulty Thermistor I
'0
j Yes
Is the thermistor
installed correctly
No
}I I Install it correctly. I
on the compressor?
'0 Yes
RAS-5FS RAS-8FS
Heating RAS-5FX RAS-l0FS
Is it in cooling or ....,..,.....,....~_..."._
heating mode when the
alarm has occurred?
)(:=::>1 Heating Operation RAS-8FX
RAS-l0FX

Cooling '0
I Cooling OperaUon
'0 Yes
,I

Perform self No No Perform self-


checking of the checking lor the
outdoor unit PCB outdoorunit
(PCB1). PCB (PCB1).
Is superheat value
under 10 degrees t?

Removesudden '0 Yes Remove sudden


changes of load
changes of indoor No Is the opening 01 lhe
No like short path 01
" load (short path, . . outdoor unit bypass outgoing air to the
I' etc) or short path ex. valve under 1%? air intake of the
of air between outdoor unit,or the

..
outdoor units. cause of frequent
thermo-ON/OFF.
Is the connector Are the connectors
No (CN103of PCB1)of (CN10l and CN102
Plug the No
connector CN103 the outdoor unit of PCB1) of the Plug the connectors
01 PCBl correcUy. bypass ex. valve outdoor unit heat CNIOI and CNl02
connectedproperly? exchanger's electric of PCBl properly.
expansion valve
connected properly?

..
Dyes
Yes
No Charge correct
Match the Are the refrigerant No refrigerant volume.
refrigerant piping piping and electric Is refrigerant Refer to item 9.1
and electric wiring. wiring matching? correct' char ed? of TC II.
'0 '0
<
Yes Yes
No Perform 5e11-

Plug the
connector properly.
_
No Is the connector on
indoor unit PCB for
ex. valve connected
Is gas leaking?

'0 Yes
>.. checking of the
outdoorunit PCB
(PCB1). Check
properly? the ex. valve.
Repair leaks of gas.
fir! refrigerant.
.,
-'
\

1-28 HITACHI
'I
rf(j
I
Phenomenon I-_~ Cause Check Item
Action (Turn OFF
Main Switch)

\
I
,.. Ref. Cycle is Different from
the Electrical System l-
Check ref. cycle and
electrical system. I- Repair wiring.

I
I
I Overcharged Refrigerant
Correctly charge
I. foe I- Measure pressure. I--- refrigerant.

,
Replace ex. valve
l I-- Faulty Ex. Valve ~ Refer to 1-86. I- if faulty.
f
Decrease of Replace PCB and
I-- Fault ~ check operation. I- Replace PCB illaulty.
Discharge
Gas Faulty PCB
Disconnected
Superheat Repair wiring
1-0 Wires for Ex. I- Check connections. I- connection.
Valve Control

Replace thermistor
Fault I- Measure resistance. I- if faulty.
Faulty
Discharge Incorrect Check mounting Correctly mount
~ Mounting I- state. I- thermistor.
Gas
Thermistor
Remove looseness.
Incorrect
Connection I--- Check connections. I--- replace connector or
repaircConneclions.

HITACHI 1-29
- Alarm
Code
Excessively High Discharge Gas Temperature
at Top of Compressor Chamber

"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.
* This alarm is indicated when the following conditions occurs three times within one hour;
DThe temperature of the thermistor on the top of the compressor is maintained higher than 127"C
for 10 minutes.
or
DThe temperature of the thermistor on the top of the compressor is maintained higher than 140C
for 5 seconds.

Is the thermistor on No
top of compressor
good (l-SKQ)? . .I FaUlty Thermistor Position of Thermistor
See page 3-9
'i \1 Yes forthe thermistor

I
resistance.
.~:
II
Is the thermistor
installed correctly
on the compressor?
No
Installation bad.
~ o
THM5.~"==-~THM7
r
\1
I Yes
Is it in cooling or
heating mode when the
Heating
)(=::>1 . -_ _--=_---,_
Heating Operation
RAS-5FS RAS-8FS
RAS-l0FS
RAS-5FX
I alarm has occurred? RA5-8FX
I, Cooling \1 RAS-l0FX

I Cooling Operation
\1 Yes

No Check the outdoor unit Check the outdoor unit No Perform oolf-
Perform self-
PCB if the compressor PCB to see if the checking of the
checking of the
outdoor unit PCB discharge gas temperature compressor discharge gas . . outdoor unit PCB
(PCB1). is over 127"C. temperature is over 127t. (PCBll.
'I

Remove sudden
Yes .JJ Yes Remove sudden
changes of load
changes of indoor No No like short path of
Is the opening of the Is the opening of the
load (short path, .. outdoor unit bypass discharge air to the
outdoor unit bypass
etc) or short path ex. valve 100%? air intake of the
ex. valve 100%?
of air between outdoor unit, or the

.. \1 Yes

..
outdoor units. Yes cause of frequent
thermo-ON/OFF.
Are the connectors
No (CN101 and CN102 No
Plug the Plugthe connectors
connector CN103 of PCB1) of the CN10l and CN102
of PCBl correctly. outdoor unit heat of PCBl properly.
exchanger's ex. valve
connected properly?

..
Yes
Charge correct
No refrigerant volume.
Is the amount of Refer to item 9.1
refri erant correct? ofTCIi.
\1 Yes Penorm sen-
checking of the
outdoor unit PCB
\1 Yes (PCB1). Check
theex. valve.
Repair leaks of gas.
Recharge refrigerant.

1-30 HITACHI
L
Phenomenon Cause
- Check Item f-
Action (Tum OFF
Main Switch)

r-
Ref. Cycle is Different from
the Electrical System I-
Check ref. cycle and
the electrical system.
- Repair wiring.

- Shortage of Refrigerant f- Check pressures.


- CorrectlycCharge
refrigerant.
,',

.. Faulty Ex. Valve


- Refer to 1-86. f-
Replace ex. valve
if faulty.
i..
"

Excessively
High
Discharge f.-. Faulty PCB
Fault

Disconnected
f-
Replace PCB and
check operation.
- Replace PCB if
faulty.

Gas - Wires for Ex. f- Check connections. f-


Repair wiring
connections.
Temperature Valve
(atTop of
Compressor) Faulty Gas bypass Replace solenoid

r- f- I-
Ref. Leakage
Solenoid Valve valve of faulty.

Fault
- Check resistance
of thermistor. I---
Replace thermistor
if faulty.

.. Faulty
Discharge
Gas
Thermistor
Incorrect
Mounting of
Thermistor - Check mounting
state.
- Correctly mount
thermistor.

Incorrect
Wiring f- Check connections.
- Remove looseness.
replace connectors or
repair connections.

I
I
ii'
I
I:, ,
I,
I

f I
II
I,
, I

I I.!
HITACHI 1-31
I

- ;I'
Alarm
Code
Activation of Protection Device for Outdoor Fan Motor

"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.
" * This alarm code is indicated when the temperature of the internal thermostat for the outdoor fan
motor is higher than 130"C
, ,I

Doesthe outdoor
fan run?

Yes
..
No
Is continuity present atter
temperature has dropped to
under 83"(; at the intemal
thermostat of the outdoor
fan motor?
No
. .'1 Replace the motor.

.~"
Yes
Is connection bad at the connector
Correct connection.
PCN304 of the outdoor unit PC82
Replace the connector.
or fan motor connector?

Is 220V or 240V applied across


#R and #S ot the connector
PCN304 of the outdoor unit
PCB2?
..No
If the voltage is over
264V or under 198V.
check the power source.
If the voltage is over
200V.check the wiring
around theoutdoor unit
PCB.

Replace the outdoor fan motor if


faulty. Or check outdoor
temperature. If it isunusual, take
suitable action to reduce it.

.ti l
Phenomenon Cause
- Check Item H Action (Turn OFF
Main SWitch)

r- Faulty Outdoor Unit


Fan Motor - Measure coil
resistance and
insulation resistance.
f--oo
Replace motor if
faUlty.

Activation of
Internal
Thermostat for I--
Outdoor Unit
Fan Motor ~
FaUlty
Internal I
Fault

Insufficient
-H Check continuity atterfFan
motor temperature
decreases to room temp.

Measure resistance
~
Replace fan motor
if no continuity.

CorrectlLooseness.
Thermostat Contacting by tester. replace connectors.

Incorrect
Connection - Check connections. ~ Repair connections.

1-32 HITACHI
l
Alarm f f Abnormality of Thermistor for Indoor Unit Air Inlet Temperature
Code f f (Air Inlet Thermistor)
"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.
*This alarm code is indicated when the thermistor is short-circuited (less than 0.24 kQ) or cut (greater
than 246 kQ) during the cooling or heating operation.

-,---
No
Is it connected to THM3
Connect it.
(intake) of PCB(M).

No
IS resistance of THM3
between 0.241<Q and _I Faulty Thermistor I
246kQ?

~: IndoorUnit

Faulty PCB(M)
"----J Inlet Thermistor

In Case of 4-Way Caselle

Action (Turn OFF


Phenomenon Cause j....... Check Item ~ Main Switch)

Faulty
Intake Air 1-
r.f Fault Check resistance.
Replace thermistor
if faulty.

Thermistor
4 IncorrectConnection Check connection.
Repair wiring and
connections.
Replace PCB ,f
Faulty PCB Replace PCB.
faulty.

90
82
80
70
1\
'\ 61
60

Thermistor 50
1\
46
Resistance 40
-,
(KQ) ~5
30
20
K 2Q5

~ ~5 10
<;

10 ~ 53 3.6
2.5
a-15 -10 -5 a 5 1: 15 20 25 30 35 40 45 50 55 60
Ambient Temperature (t)

NOTE: This data is applicable to the following thermistors;


1. Discharge Air Temperature, 2. Indoor Unit Liquid Refrigerant Temperature, 3. Indoor Unit Intake
~, -' Air Temperature 4. Outdoor Air Temperature 5. Outdoor Unit Evaporating Temperature

HITACHI 1-33

L
Alarm
Code
Abnormality of Thermistor for Indoor Unit
Discharge Air Temperature (Air Outlet Thermistor)
1
I

"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.

* This alarm code is indicated when the thermistor is short-circuited (less than 0.24 kQ) or cut (greater
than 246 k Q) during the heating operation.

Is thethermistor connected No
10THM4 of PCB(M)? . ., Correctly Connecl it. 1
\1 Ves
Is resistance between No
0.24 and 246KQ?
. .r Faulty Thermistor
\1 Ves Refer topage 1-33. Indoor Unit
Air Outlet
I Foully PCB(M) I Thermistor
(THM4)
In Case of
4-Way Cassette

Phenomenon Cause Check Item Action (Turn OFF


f- f- Main SWitch)

, I Faulty r-l Fault Check resistance.


Replace thermistor
if faulty.
" l
,I
I
AirOutlet
Thermistor -y Incorrect Connection Check wiring to PCB. Repair wiring and
connections.
Replace PCB and Replace PCB if
Faulty PCB
check operation. faulty.
I
i
II!ij Alarm
Code
f ;f
f _,
Abnormality of Thermistor for Indoor Unit Heat Exchanger Liquid
Refrigerant Pipe Temperature (Freeze Protection Thermistor)
Il
,! ~
"RUN" light flickers and "ALARM" is indicated on the remote control switch.
,j The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.
Ii
~( *This alarm code is indicated when the thermistor is short-circuited (less than 0.24 kQ) or cut (greater
II
II,J than 246 kQ) during the cooling operation(or heating operation at start-up only) and this state is
"I maintained for 10 minutes.

~i Is thethermistor connected
to THM5 of PCB(M)? "I
No
Correctly Connect it. I
"I
I
I,
[i \1 ves
No
Is resistance between
I' " FaultyThermistor
and 246K Q?
II 0.24
\1 Yes Refer topage 1-33. Freeze Protection
I Faulty PCB(M) I Thermistor
(THM5) In Case of 4-Way Cassette

Action (Turn OFF


I Phenomenon Cause f- Check Item f- Main Switch)
I
II""
,I'
Faulty
Freeze
Protection C-
il Fault Check resistance.
Replace thermistor
if faulty. I
:11

'\ Thermistor y Incorrect Connection Check wiring to PCB.


Repair wiring and
connections. I
Replace PCB and Replace PCB if
Faulty PCB check operation. faulty. I
1-34 HITACHI
I
f
I
us Abnormality of Thermistor for Indoor Unit Heat Exchanger
I Alarm
Code t l Gas Refrigerant Pipe Temperature (Gas Piping Thermistor)
~...J
J "RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.

*This alarm code is indicated when the thermistor is short-circuited (less than 0.24 kQ) or cut (greater
than 246 kQ) during the cooling or heating operation. The system is automatically restarted when
,t
the fault is removed.
\
I
I Is it connected to THM7
of PCB(M)?
Connect it.

I No
Is resistance of THM7
between 0.24k Q and _I Faulty Thermistor I
246kQ?
Refer to page 1-33.

Faulty PCB(M)

Action (Turn OFF


Phenomenon 1---eI Cause Check Item
Main Switch)

FaUlty Replace thermistor


Fault Check resistance.
Thermistor for if faulty.
Indoor Unit Heat
Exchanger Gas Repair wiring and
Incorrect Connection Check wiring to PCB.
Pi Tem. connections.
Replace PCB and Replace PCB if
Faulty PCB
check operation. faulty.

()

HITACHI 1-35
I
~
Alarm
Abnormality of High Pressure Sensor for Outdoor Unit
Code

"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.

*This alarm is indicated when the pressure sensor decreases lower than 0.1 V or increases higher
than 4.9V during running

No
Is the connection CN117
of the outdoor unit PCB2
>1 Connect correctly.

I
bad?

...
No

Is 12 VDC applied across No Is 12 VDC applied across Yes


1/1 and 113 of the connector 1/2 and 1/4of the connector
>1 1

PWB2 defective.
CN117 of the outdoor unit CN121 olthe outdoor
PCB2? circuit board PCB2?

I
No
Dyes

Is voltage under 0.1 VDC Is the connector N121 of


or over 4.9 VDC across 112 the outdoor unit PCB2 or Yes
and #3 of the connector
CN117of the outdoor unit
the connector CN401 of the
power supply C;leu;1 board
I
>1 . Connect it correctly.

PCB2? PCB4100se?

Dyes No

Yes
Clogged Check Joint? Replace check joint.

I No

Abnormality of High
Pressure Sensor. I Faulty PCB21 I Check PCB41

"I
Phenomenon Cause
- Check Item
- Action (Turn OFF
Main SWitch)

Check output ReplacepPressure
FaUlty High
Pressure f-
rJ Fault
voltaae is correct. sensor if faulty

Sensor y Incorrect Connection Check connections.


Repair wiring and
connections.
Replace PCB and Replace PCB ;t
Faulty PCB check operation. faulty.

Indicated
Pressure Value
is Excessively
High or Low
Malfunction of Pressure
Sensor due to Faulty
Check Joint - Check for clogging
of check joint.
- Replace
check joint.

HITACHI
r Alarm Abnormality of Thermistor for Outdoor Air Temperature
Code (Outdoor Unit Ambient Thermistor)
'} "RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is aaernately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.

* This alarm code is indicated when the thermistor is short-circuited (less than 0.2 kQ) or cut (greater
than 500 kQ) during running. However, this alarm occurs during test running mode only. In the
case that the thermistor is abnormal during running, operation continues based on the assumption
that the outdoor temperature, is 6 "C.

No
Is it connected to
CN120 (Ta) of PCB1?
_I Correctly connect it. I

No
Is resiStance of THM2
between O.2kQ and _I FaUlty Thermistor'
500kQ? Reter to page 1-33.

Outdoor Unit Ambient


Thermistor (THM6)
Faulty PCB1M

Regarding the thermistor characteristics, refer to page 1-38.

Action (Turn OFF


Phenomenon Check Item
Cause I- f- Main Switch)

Faulty
Thermistor for
I--
r1 Fault Check resistance.
Replace thermistor
if faulty. I
Outdoor Unit
Ambient y Incorrect Connection Check wiring to PCB.
Repair wiring and
connections.
Replace PCB and Replace PCB if
Faulty PCB
check operation. faulty.

HITACHI 1-37
t
Alarm Abnormality of Thermistor for Discharge Gas
Code Temperature on Top of Compressor Chamber
"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm cede is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.

* This alarm code is indicated when the thermistor is short-circuited (less than 4 kQ) or cut (greater
than 8,300 kQ) during running.
If abnormality with the thermistor is found, check all the thermistors as shown below.

No
Is the setting of DSW2
on PCBt right. _I Set DSW20n pCBt1

Yes Characteristics of Thermistor

No
,
_I Connect correctly. I ,
:[11
'i.':
Resistance .'1,., ,
ofThermistor
(KQ)
100
1\1 r
iI
Is resistance of THM5
& THM7 between 4K Q
and 8300KQ?
Faulty Thermistor. I
o .. .
so
K ~2S 32
100 IZJ 150
I
r
,I
AmbientTemperature eC)
~
Faulty PCBl

Position of Thermistor

:0 ~ 0
THMS
I
=
r
1HM7

eti l
RAS-5FS RAS-BFS ,I
RAS-5FX RAS-tOFS I
RAS-BFX
.il RAS-tOFX
I
;1
I

Action (Turn OFF


. Phenomenon Cause ~ Check Item f--e Main Switch)

Faulty
Discharge Gas I--
rl Fault Check resistance.
Replace thermistor
if faulty.

Repair wiring and


Thermistor
L1 Incorrect Connection Check wiring to PCB.
connections.
Replace PCB and Replace PCB if
Faulty PCB check operation. faulty.

Incorrect Setting of Check setting of Correctly set


DSW2 on peBl DSW2 on PCB1. DSW2 on PCB1.
ell,
,
1-38 HITACHI f
1;
Alarm Abnormality of Thermistor for Evaporating Temperature
Code during Heating Operation (Outdoor Unit)
"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.

Two evaporating thermistors during the heating operation are attached to the upper heat
exchanger (for liquid) and the lower heat exchanger (for liquid). If one of the two is faulty, this alarm
is indicated. Therefore, if this alarm occurs check two thermistors at the same time. The position
is indicated below.
*This alarm code is indicated when the thermistor is short-circuited (less than 0.2 kQ) or cut (greater
than 500 kQ) during running.

= . ; = ~THMl
THMl
-==..r~

THM3 I "'"" THM3

o 00
( ;
roo
./
.

RAS-5FS and RAS-5FX RAS-8FS, RAS-l0FS,


RAS-8FX and RAS-l0FX

Are THM1 and THM3 No


connected toCN112
(Te2) and CN118 (Te1)
.1 Connect them.
of PCB1?

No
Ismsistance ofTHM 1
or THM3 between O.2k 0 . , Fau!ty Thermistor I
and saOkO?
Regarding the thermistor characteristics, refer to page 1-33.

Faulty PCB1

Phenomenon

Faulty
Thermistor for r-I
Cause

Fault
- Check Item

Check resistance.
r--- Action (Turn OFF
Main SWitch)

Replace thermistor
if faulty:
Evaporating
Temperature
duJino Heatino
-y Incorrect Connection Check wiring to PCB. Repair wiring and
connections.

Replace PCB and Replace PCB if


Faulty PCB
check operation. faulty.

HITACHI 1-39
.-
I
Alarm Abnormality of Low Pressure Sensor
Code (Outdoor Unit)
"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.

* This alarm is indicated when the pressure sensor voltage decreases lower than 0.1 V or increases
higher than 4.9V during running.

No
Is the connection CN111
of the outdoor unit PCB2
>1 Connect it correctly.

I
~i
mated loose?

No

...
Ii
:1 Is 5 VDC applied across No Is 12 VDC applied across Ves
#1 and #3 of the connector #3 and #4 of the connector
CN111 of the outdoor circuit CN121 of the outdoor unit >1 Faulty PCB2
board PCB2?

D Ves
PCB2?

I
No .~
Is voltage under 0.1 VDC Is the connector CN121 of
or over 4.9 VDC across #2 the outdoor unlt PCB2 or Ves
and #3 of the connector
CN111 of the outdoor circuit
board PCB2?
the connector CN401 of the
power supply circuit board
PCB4 mated loose?
I
>1 Connect it correctly.

No

Yes
I Replace the check joint. I

Abnormality with High


Pressure Sensor. I Faulty PCB21 I Check PCB41

Action (Turn OFF


Phenomenon Cause I- Check Item ~ Main Switch)

Faulty High
Pressure
r1 Fault
Check output
voltaoe is correct.
Replace pressure
sensor if faUlty.

Sensor "-I..[ Incorrect Connection Check connections.


Repair wiring and
connections.
Replace PCB and Replace PCB if
Faulty PCB check operation. faUlty.

IndIcated
Pressure Value Malfunction of Pressure Check for clogging ReplacecCh
is Excessively Sensor due to Faulty ~ of check joint. f---oo eck joint.
Hinh or Low Check Joint

1-40 HITACHI ,I
.....
I
r
,
I FX SYSTEM I
} Alarm
Incorrect Wiring Connection
Code

';RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoorunit PCB.

* This alarm is indicated when two or more CH units exist between outdoorunit and indoor unit in the
operating line, caused by incorrect wiring.
*This alarm is indicated when PCB1 for FS series outdoorunit is mountedby mistake.

No
Is the operating line Correct the wiring.
wiring correct?

Dyes

No
Is the PCBl for FX Replace the PCB1.
system?

Dyes

No
Is the PCB1 normal?

ryes
>1 Check the PCB of CH unit.
I

<Example of Operating Line Wiring>

(CORRECT) (INCORRECT)

Outdoor Unit Outdoor Unit

To No.1, 2 To No.1, 2
0ITB2 ofTB2

To No.3, 4 To No.3, 4 To No.3, 4


ofTB2 ofTB2 ofTB2

,
HITACHI 1-41
L ..
r

Alarm
Code
='
_, ff
Incorrect Capacity Setting or Combined Capacity
between Indoor Units and Outdoor Unit
"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.

*This alarm is indicated when the capacity setting dip switch, DSW2 on the outdoor unit PCB, PCB1
is not set(all the settings from #1 to #3 are ON or OFF) .
. * This alarm is indicated when the capacity setting dip switch, DSW3 on the outdoor unit PCB, PCB(M)
is not set(all the settings from #1 to #4 are ON or OFF).
* This alarm is indicated when the total indoor unit capacity is smaller than 50% or greater than 130%
of the combined outdoor unit capacity.

Are #1-#3 of DSW2on No


the outdoorunit PCBl Set the capacityfor PCB1.
set correctly?

,
Are #1-#4 of DSW3 No Set the capacityfor PCB(M). (If even
, on the indoor unit one unit is undefined in the system,
"
~! PCB(M) set correctly? the alarm code will be indicated.)

j'" Total capacity01 the


indoor units wrong.
i.
~

'.~
j
,",

,
I
,(
Phenomenon Cause

Incorrect Capacity Selling of Indoor Unit


-
f-
Check Item

Checkcombination of
indoor units and
f-

f-
Action (Turn OFF
Main SWitch)

Correctly set dip


switch, DSW3.
" .caoacitv setlino on PCB.

Checkcapacity setting Correctly set dip


Incorrect Capacity Setting of Outdoor Unit
on outdoorunit PCB. switch, DSW2.
Checkoutdoorunit
Total Indoor Unit Capacity Connected to the f- modelby calculating f- Ensure that total
indoor unit capacity is
Outdoor Unit is Beyond Working Range totll;t indoor units
from 50% to 130%.
capacity.

Combination
Combined Indoor Unit
Outdoor Unit Model
Total Q'ty Total Capacity (HP)
RAS-5FS, RAS-5FX 2.5 6.5
RAS-8FS, RAS-8FX 2-8 sets 4-10
RAS-l0FS,RAS-l0FX 5-13

1-42 HITACHI
,,'
r
Alarm
Abnormality in Transmitting of Other Indoor Units
Code

"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.

* This alarm code is indicated on the remote control switch of an other indoor unit when no
transmitting data is issued from a malfunctioning indoor unit or CH unit for more than 60 minutes after
receiving transmitting data from that indoor unit.

Yes Ves
Is there any indoor Is the connectorCN2 on Plugthe connectorproperly
unit with indication
of alarmcode 03?
PCB(M) of indoor unit or
PCB2 of CH unit loose? c=> '--_---'-__--'
and restartoperation.

Yes
Is there any indoor Is LED2 (yellow) Check the wires between
unitwhose lamp is not flickering on the PCBof the indoor unit, CH unitand
lit or whoseLCD is indoorunit or CH unit? outdoorunit.
indicating nothing?
Yes
Yes
Check connections of the
PCB of indoor unit or CH
Checkthe powersource,
unit. or connectorCNI.
fuse and transformer of
the indoor unil or CH unit.

Is still LED2 lighting?


Yes

Faullyindoorunit PCB
or CH unit PCB.

Phenomenon Cause
r- Check Item
- Action (Turn OFF
Main Switch)

- Abnormal Transmitting
Indoor Unit-Outdoor Unit
OutdoorUnit-+lndoor Unit - Check indoor unit
showing alarm code
"03".
r- Take action according
to Pages 1-21 to 1-24.

Abnormal
Transmitting
lrom Other
Incorrect Power Supply
(to Indoor Unit or CH Unit "I)
- Check indoorunit
showingno light ON on
remote control switch.
f----
Take action according
10 Page 1-6.

-
Units If all indoor unit show
alarm code 32. check
Replace PCB il
L.e Faulty Indoor Unit PCB
or CH Unit PCB
r- PCB by self-checking
mode for all indoor unit
faulty.
or CH unit.

Operation is started within 1 minute after turning ON .


of indoor unit while outdoor unit is live. "2)
- Start the operation 2 minutes or more after
turning ON.

"I): This abnormality is indicated on an indoor unit which is normal, since this is due to abnormality
of transmitting of the indoor units or power source abnormality in the same refrigeration cycle
and electrical system. If the power source is abnormal, abnormality can not be indicated by its
indoor unit. so, this alarm is indicated on the remote control switch of other indoor unit.
"2): The alarm code "32" would be indicated when the operation is started within 1 minute after
turning ON of indoor unit or CH unit while outdoor unit is live.

I HITACHI 1-43
l ,
!.Ioo
r
Alarm
Incorrect Indoor Unit No. Setting
Code
~I
"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.
*This alarm code is indicated 10 minutes after power is supplied to the outdoor unit when the indoor
unit No. connected to the outdoor unit is duplicated by setting of DSW1.

Indication of 7-Segment in Outdoor Unit when Unit Nos. are Duplicated

(1)The following are indicated for 10 minutes after power supply to the outdoor unit.
1) The following is repeatedly indicated when NO.1 indoor unit setting is duplicated

om~m-Om~0
2) The following is repeatedly indicated when NO.2 indoor unit setting is duplicated

om~m OQ]~Q]

3) The following is repeatedly indicated when NO.3 indoor unit setting is duplicated

. om~m OQ]~G

13) The following is repeatedly indicated when NO.D indoor unit setting is duplicated

OeD ~eD OQ] ~IT1


14) The following is repeatedly indicated when NO.E indoor unit setting is duplicated

OeD ~eD OeD ~0


e;

,r

I
15) The following is repeatedly indicated when NO.F indoor unit setting is duplicated
. OQ] ~Q] OQ] Q]~
(2)After 10 minutes, r35J flickers. This r35J is also flickered on the remote control switch.
.1
i Outdoor Unit PCB----- Jr:~~~~~~~~
,. (PCB1: Control) ':ott I!!II
0_ _ ,
c'ir~SJClD
~ _ 0

,= 5"."""" =" ~ I
EilWlE!JBC3 c::J =
-E::::::::J c:::J CJ
-0 c::::::Jc::Jc:::1

1c:=.
==~ ~dD ""'""1--_ _---7-Segment
-~ = III
~
o I~OO~o(
_ _-lO'ho tH r=,
000 ~
(PCB2: Power Supply) O~ L-J:
oUlllJ
c::Ji
( I., I _~DCJ
I

1-44 HITACHI
Alarm Abnormality of Picking up Circuit for Protection
Code (Outdoor Unit)
"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.

*This alarm is indicated when AC 220V or 240V is supplied to voltage between PCN303 (ARM1 or
ARM2) and terminal 5# of PCN301 on PCB2 in the outdoor unit during stoppage.

Is 220VAC or 240VAC applied batwaan No


ARM1 or ARM2 of PCN303 on outdoor unit
Printed Circuit Board, PCB2 andterminal #5
of PCN301 during stopping?

~ Yes
PCB2is normal
============:::> Checkwiring
connection of other
than PCB2. '2)

EI.
I
I Phenomenon Cause ~ Check Item ~
Action (Turn OFF
Main Switch)

I Abnormality of Check voltage supplied Repair wiring


I Picking up Circuit
for Protection
Incorrect Connection 1--00 to connectors. f---<o connections.

Perform self-checking
Faulty PCB Replace PCB.
for outdoor unitPCB.
I *1): Refer to Item 1.3.1.
*2): Check wiring system connecting to PCN303 on PCB2.

I
,
..
~;'

HITACHI 1-45

L
Alarm
Activation to Protect System from Low Compression Ratio
Code

"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.

*This alarm code is indicated when a compression ralio, e = /Pd /(Ps + 1.03) is calculated from a
discharge pressure(kglcm 2G) and suction pressure(kglcm 2G) and the condition lower than
e = 1.8 occurs more than 3 times including 3 in one hour.

No

< Does the inverter operate?

DYes
> ~I Check the inverter.

.'
No

< Does the compressor operate?

Dyes
> ~I
Check the compressor and
power cable.
";''''

>1
Yes

< Is the four-way valve set halfway?

I No
> Replace the four-way valve if
defective.

No

< Is the high-pressure sensor good?


> ~
Replace the high-pressure sensor
if defective.

il Dyes

Check if the intake air temperature is


too low at the indoor or outdoor units.

I
I
(
Phenomenon

-
Cause

Inverter is not Functioning


-
-
Check Item

Check inverter.
- Action (Turn OFF
Main Switch)

Repair faulty part.


.1
,. j

- Compressor is not
Operating

Valve Stoppage at Medium


J-

r--
Check compressor.

Measure suction pipe


H
r---
Replace comp. if
faulty.

Replace 4-way
Excessively
fo- Position of 4-Way Valve temp. of 4-way valve. valve if faulty.
Low - Checkconnector for
Replace sensor if
Compression
Ratio
fo-
Abnormality of High or
Low Pressure Sensor r--- PCB, power source and
pressure indication.
"- faulty.

f0-
Excessively Low Indoor
Intake Air Temperature
r---
Check indoor unitand
outdoor unitair temp.
thermistor. - Replace thermistor
if faUlty.

~
Leakage from Solenoid
Valve: SVA Outdoor Unit or
SVD1, SVD2 of CH Unrt
r--- Check refrigerant
leakage.
- Replace SVA or CH
unit if leaking.

1-46 HITACHI
r
I

Alarm
Code
1-'f uf Activation to Protect System from Excessively
High Suction Pressure
II ,
"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoorunit PCB.

*This alarm code is indicated when the compressor is operated underthe conditions higher than
9 kg/cm2G of suction pressure and its occurrence is more than 3 times including 3 in one hour.

Yes
Is there a leak in the solenoid
valve SVA? I
> Replace the solenoid vaive SVA
if defective.

<
r ),
Yes

> Replace the four-way vaive If

t
Is the four-way vaive set halfway?

11:_
defective.

No
I
No

< Is the low-pressure sensor good?

Dyes
) ~
Replace the low-pressure sensor
if defective.

Check if the indoor/outdoor intake


air temperature is too high.

Action (Tum OFF


Phenomenon Cause f--- Check Item
f--- Main Switch)

,... Leakage of Solenoid


ValveSVA f---
Check outlet pipe temp.
01 solenoid valve, SVA. r--
Check connecting wires.
Replace solenoid vaive,
SVA if faultv.

tit. Valve Stoppageat Medium


Measure suction gas
Replace 4-way
,r l-o Position of 4-Way Vaive f--- pipe lemp. of 4-way
vaive.
r- valve if faulty.

Excessively
High Suction
Abnormal Suction
Pressure Sensor f---
Check connectors of
PCB and power source. r- Replace sensor if
faulty.
Pressure
Excessively High Indoor Check indoor unit and Replace thermistor
I-- Unit and OutdoorUnit f--- outdoor unit airtemp. f- if faulty.
Air Temoerature thermistor.

Leakage from Solenoid


L.. Valve: SVD1, SVD2 of
CH Unit
f- Check refrigerant
leakage. r- Replace CH unit if
leaking.

f:)

HITACHI
L 1-47
Alarm Activation to Protect System from Excessively
Code High Discharge Pressure
"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.

*This alarm code is indicated when the compressor is operated under the conditions higher than
27 kg/cm2G of discharge pressure (in case of frequency 20 to 30Hz, Pd is higher than
24 kg/cm2G) and its occurrence is more than 3 times including 3 in one hour.
Yes
Is there a leak in the solenoid
valves SVA or S:.:.V;B?;.-'
No
/ I
> Replacethe solenoid valve SVA
or SVB if faulty.

Is the outdoor unit stop valve


closed? Open the stop valve.

< Is the high-pressure sensor good?


Yes
No

Are ex. valves fully closed and locked? I


Yes
> Check the circuit board and connection
of the circuit board connector. Replace

N~heck
I
Are electric wiring and refrigerant
piping between the indoor and
the outdoor electronic expansion va:'::::::::n:xpansion valves illaully.

.,-~--:_..,...--:,...;._.;:and:.::,.t:;:h::e.:ind=oo;::r:..:e~lectronic expansion valvedUring heating.

I
Yes
>I -=
Correctly connect it.
_
outdoor unit incorrectly connected?

Check if indoor or outdoor intake air


femperature is 100 high.

Phenomenon Check Item Action (Turn OFF


Cause J- f- Main SWitch)
i
...
I
Check outlet temp. Check connection.
Leakage 01 Solenoid
Valve SVA, SVB
l- of solenoid valve, I- Replace solenoid
SVA & SVB. valve SVA or SVB il
(Outdoor Untt) tauhv,

~ Closed Stop Valve


H Check stop vaive.
H Open stop vaive.

Abnormal High Pressure Check connectors for Replace pressure


H. Sensor I- PCB. f--o sensor if faulty.
Excessively
High ExcessivelyHigh Indoor Check thermistorfor Replace thermistor il
Discharge Unit and Outdoor Unit I- indoor unitand outdoor f--o faulty.
Inlet Air remo. unitinlet air terno.
Pressure
Incorrect Connection Check electrical system
I-- between Indoor Unit I- and ref. cycle.
f-o Correctly Connect.
and Outdoor Unit
,..
Check connector Repair connector for
~ Locked Ex. Valve I- for PCB. I- PCB or ex. valve.
Beolace it if taultv,

,
I
'I
~
Full Open of Solenoid Valve
SVD1 (CH Unit for FX)
- Check solenoidvalve
SVD1 open in heating.
- Replace coil or
CH unit if faulty.

HITACHI
,I,i'I
"~I.
1-48

J
r
Alarm Activation to Protect System from Excessively Low Discharge
Code Pressure (for Protection of Refrigerant Shortage)

"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.
*This alarm is indicated when the discharge pressure is decreased due to insufficient refrigerant
charge. Refer to the figure below.
* This alarm is indicated when the discharge gas superheat at the top of the compressor is higher than
80 deg. during running and outdoor unit expansion valve: MV1 or bypass expansion valve: MVB is
fully opened and its state is maintained for more 25 minutes.

(kg/cnfG) (V)

3 0.9
Voltage between
Discharge #2 and#3ofCN117
0.6

o 26
Outdoor AirTemperature ('C)

No
Is the discharge pressure
Is the amount of refrigerant Correctlycharge
indicated on outdoorunit
correct? refrigerant.
PCB in the alarmregion? - L......:.=::'::"-_.....J

Connecta pressure gauge


Is the condition that the at the checkjoint of the
superheat valueof discharge compressor discharge pipe.
gas of the compressor is
over about 80 degrees
Celsiusand the outdoor unit Ves
n
\1
Ves
ex. valveMV1 or outdoor Ves
unil bypassex. valve MVB
isfully opencontinuing for
25 minutes?
Is the high-pressure in the
alarm region? c::::::> Checkfor leakage of
refrigerant.

No

Is the connectorCN117of
outdoorunit PCB1 loose?
Ves

c::::::> Plugthe connector


CN117 correctly.

Ves
Is the high-pressuresensor
pipeclogged? c::::::> I Remove clogging.

Is voltagebetween #1 and
#3 of the connector CN117 Replace the
of outdoorunit PCB1 12V. high-pressure sensor.
and voltage between#2 and
#3 in the alarm fa ion?
No
Check the outdoor unit
PCB1 by self-checking.
Replace it if faulty.

HITACHI 1-49
L
Alarm Activation to Protect System from Excessively Low Suction
Code Pressure (Protection from Vacuum Operation)
"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.

* This alarm is indicated when a suction pressure is lower than 0.2 kg/cm2G for over 10 minutes and
its state occurs more than 3 times including 3 in one hour.

No

< Is the amount of refrigerantcorrectly?)

DYes
~I Correctly charge refrigerant.

No

< Is the outdoor stop valve open?

DYes
) ~I Open the stop valve.

< Is refrigerantleaking? )1
Yes

>1 Repair leaks. et ,

t No
Yes Check connection of the connectors
Are the electronicex. valves fully
closed and locked? > and the circuit board. Replace the
electronic ex. valves if faUlty.
No

,.
I Checkthe indoor ex.valveduring cooling
and theoutdoor ex.valve during heating.

Check if connectionsof electric


wiring and refrigerantpiping between
the indoor and outdoor unit are wrong.
I
,.,,
';,

I.
l: Phenomenon Cause r- Check Item
H Action (Turn OFF
Main Switch)

(; r- Shortage of Ref. .... Check ref. charged


volume or check for
leakaae.
.... Repair leakage and
correctly charge.

r- Closed Valve r- Check stop valve. r- Open stop valve.


II
,, , . Excessively
Low Suction
Pressure
Abnormal Low
Pressure Sensor - Check connector
for PCB.
.... Replace pressure
sensor if faulty.

-
(in Vacuum)

r-
IncorrectConnection
betweenIndoor Unitand
Outdoor Unit - Check electrical
system end ref. cycle.
Correctly connect
between indoor unit
and outdoorunit.

~ Locked Ex. Vaive


- Check connector
for PCB. - Repair or replace
connector of PCB or
ex. valve.

I
I
I

I HITACHI
,I 1-50

w.
r Alarm
Code
Protection Activation by Electronic Thermal Relay for Inverter

"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.
* This alarm is indicated when the electronic thermal relay for the inverter is activated 3 times including
3 in 30 minutes. Retry operation is performed up to the occurrence of 2 times.
conditions: Inverter current is 105% of the rated current (14A), <D continuously for,30 seconds
or@the accumulated time reaches 3.5 minutes in 10 minutes.
In this case, LEDI and LED3 on the inverter control PCB flicker.

I Restart operation (see Note 4')1


Yes
Is the compressor current (The circuit board is normal)
larger than activation

~
current? Is discharge pressure
high?
No
Smallerthan Check pressure and
activationcurrent. refrigeration cycle.

t
Check for clogging of
the heat exchanger.

Check the fan motor.

Check the current No Replace the current


transformerdetecting transformer detecting
current (see Note 1'). current.

.(J Yes

No
Check the diode module Replace the diode module.
(see Note 2').

DYes

No
Check the inverter The inverter circuit board
circuit board (see Note 3'). is faulty. Replace it.

L.:=======:J Yes

NOTE:
'1): As for the checking method for the transmeter for picking up current, refer to page 1-94.
*2): As for the checking method for diode module, refer to page 1-93.
*3): As for the checking of inverter components, refer to page 1-91 regarding electrical discharge.
) *4): Operate the unit by connecting connectors, CN1? and CN18 on PCB for inverter, PCB3. If not,
the power transistor will be damaged. Refer to page 1-54.

HITACHI 1-51
r
Alarm Protection Activation Against Instantaneous
Code Overcurrent of Inverter (i)
(
"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.
* This alarm is indicated when the instantaneous overcurrent tripping occurs 3 times in 30 minutes
including 3. Retry operation is performed up to the occurrence of 2 times.
conditions: CD Inverter current is 150% of the rated current (14A).
Inverter current is OA when the compressor is running.
In this case, LED3 on the inverter control PCB flickers.

Tum off power,


disconnect U, V, W from No
Restart operation. compressor terminals.
Does it trip soon? Replace the inverter
NO.1 on 0821 (PCB3) circuit board.

ij
(see Note 4') to OFF and restart.
Does it trip?
/l trips after Ittrips in (see Note 5')


10 sec. from Isthere any cause of Check the
compressor 10 sec. from .Yes Ittrips. instantaneous voltage compressor.
compressor
start. start. decrease? ' '''
,
[1 es Check the power
~'

> source capacity.


Check the power No
1 Replace the
transistor (see
Note 2'). > ~ power transistor.

Yes
L'::==============:>I Replace the inverter
circuit board.
Is the compressor Il is larger than aetlvation current. Check the
running current right?
compressor.
No No.
It is smaller than activation current.

No

No Check the capacity


and wiring ofthe
powersource.

No
r;:====~....> Replace the inverter
circuit board.

II
NOTE:
'i 1): As for the checking method for the diode module, refer to page 1-93.
"
;~ 2): As for the checking method for power transistor, refer to page 1-92.
,"

3): As for the checking of inverter components, refer to page 1-91 regarding electrical discharge.
4*): Operate the unit by connecting connectors, CN1? and CN18 on PCB for inverter, PCB3. If not,
the power transistor will be damaged. Refer to page 1-54.
5): Turn OFF the No.1 switch of the dip switch DS21 on PCB3 when restarting with disconnecting the
terminals of the compressor. Refer to Technical Bulletin No. SG-94011A for detail.

1-52 HITACHI
Alarm Protection Activation Against Instantaneous
Code Overcurrent of Inverter (2)
II' J
"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.
* This alarm is indicated when the instantaneous overcurrent tripping occurs 3 times in 30 minutes
including 3. Retry operation is performed up to the occurrence of 2 times.
Conditions: Abnormal Current to the Power Transistor such Short Circuited or Grounded
In this case, LED2 on the inverter control PCB flickers.

Tum off power, disconneclU, V,


It does not trtp. Checkthe compressor.
W from compressor terminals.
(If there is a short-circuil
NO.1 on OS21 (PCB3) to OFF
and restart, Doesitlrtp? between phase lines,
replace the compressor.)
(see Note 3", Note 4")

D
...
Yes II tripes.

Faulty Good
Checkthe inverter Replacethe power
Checkthe powertransistor
(see Note 1").
circuit board
~ transistor.

I
(see Note 2").
Good
Faulty
Replace the power
~ transistor andinverter
circuit board.

Replace the invener


circuit board.

NOTE:

~:
I
.. 1"): As for the checking method for the power transistor, refer to page 1-92.
2*): As for the checking of inverter components, refer to page 1-91 regarding electrical discharge.
3*): Operate the unit by connecting connectors, CN17 and CN18 on PCB for inverter, PCB3. If not,
the power transistor will be damaged. Refer to page 1-54.
4*): Turn OFF the No.1 switch of the dip switch DS21 on PCB3 when restarting with disconnecting the
I terminals of the compressor. Refer to Technical Bulletin No. SG-94011A for detail.
I
I
r

I
I
I

I
I
~:, }

HITACHI 1-53
Additional Checking Method for Alarms 51, 52 and 53

In case of the RAS-5HEM SET-FREE, checking the instantaneous overcurrent protection


activation for inverter is performed by removing connector CN19 on PCB for the inverter,

However, do not disconnect the connectors, CN17 and CN 18.


If disconnected, the power transistor will be damaged, in the case
of FS and FX SET-FREE.

CTU CTV

,I
'I
:,'

(1) Checking Method 1: Checking Wiring Connections


Check to ensure that wires from terminals, U and V of IGBT are connected to the current sensor,
CTu and CTv as shown below. The arrow mark on the CTu and CTv indicates that wires from the
IGBT power transistor are connected to the terminals of the compressor.

+0
CTu

To Terminal U of
Compressor

+
'To Terminal Vof
Compressor

To Terminal W of
Compressor /
\
IGBT Power Transistor

CTv

1-54 HITACHI
1111'11...
(2) Checking Method 2: Checking Voltage of Current Sensor
Measure the voltage between two pins of connector CN8 on PCB 3 connected to the current
sensors, CTu and CTv, as shown below.
Note
Measure the voltage by connecting cord into connector, CN8 when the power to the outdoor unit is
ON and the compressor is stopping.

Table 1.1 Checking Voltage of Current Sensor (1)


Pin No, in CN8 Result
Item Black Terminal Red Terminal after Judgement
(-) of Tester (+) of Tester Measurement

CD No.8 Pin No.1 Pin 151V If the result is not good, check
the item in Table 1.2.
NO.8 Pin NO.3 Pin -151V If the result is not good. check
the item in Table 1.2.
@ No.8 Pin NO.5 Pin -O.5-+0.5V If the result is not good.
replace CTu.
@ NO.8 Pin NO.6 Pin -O.5-+0.5V If the result is not good.'
replace CTv.

Measure the voltage at the connector pins of the PCB3 after removing rod of CN8 as shown in Table 1.2
after the power to the outdoor unit is ON and the compressor is stopping.

Table 1.2 Checking Voltage of Current Sensor (2)


Pin No. in CN8 Result
Item Black Terminal Red Terminal after Judgement
(-) of Tester (+) of Tester Measurement
@ NO.8 Pin NO.1 Pin 151V If the result is not good,
replace PCB3.
If good, replace CTu.
@ NO.8 Pin No.3 Pin -151V If the result is not good,
replace PCB3.
If good, replace CTv.

Measuring Position
--~ Red Terminal (+) of Tester
PC83

CN9

R~DggeD4 D
- [i]+-'~-<:==C=:J
DCNI7 LED3 .LEDI IQJ
IQI
DCNIS ~ -, a> IQJ
:z:
DCNIS [ D J U IQI
~/ IQJ
LEDG IQI
0
a> rg I I
~
DCNI3 CN3 CN I
Dc=J Black Terminal (-) of Tester
~; )

HITACHI 1-55
r

Ctf
Alarm
Code -' ., Abnormality or Protection Activation
of Fin Thermistor for Inverter (
"RUN" light flickers and "ALARM" is indicated on the remote control switch.
The unit No. and alarm code is alternately indicated on the set temperature section, or the unit No.
and alarm code are indicated on the display of the outdoor unit PCB.
* This alarm is indicated when abnormality with the fin thermistor occurs 3 times in 30 minutes
including 3. Retry operation is performed up to the occurrence of 2 times.
Conditions: Activates at the radiation fin temperature of approximately 85"C
* This alarm code is indicated when the thermistor is short-circuited (less than 20 k Q) or cut (greater
than 2MQ) during the cooling or heating operation. In this case, LED1 on the inverter control PCB
flickers.

Cut off power and


Wait until temperature falls under
wait for a while
before checking.
..... eoc at the radiation fin.

n
Disconnect the connector CN9
on the inverter circuit board and
Connector
CN9
Black
Black

/
.~::
measure resistance across the
lines of the plug. Is it between 1-.......-1 Measuring
20 kQ and 2 MQ"'?'-- J
-----..J Range

No
\ /

The thermistor
o
is defective. Measuring
Replace it. Range
see below for fhermistor
resistance vs. temperature.

Is resistance over 1 k Q
across the lines of the
The thermistor
is normal. > socket of theconnector
CN9 on the inverter
circuit board?
Yes

The inverter circuit


board is defective.
Re lace it.

I I
l Check for clogging of the heat exchanger.

n
100
i 100
.1

\
Resistance
of Thermistor
(KO) 100
I Check the fan motor. I

..K-
1'.2 8. 31
I,
o 2S::N 100 120 150

Ambient Temperature eel


NOTE: As for checking inverter components. refer to page 1-91 before electrical discharge.
, ,
1-56 HITACHI
1 ,2,3 Troubleshooting in Check Mode by Remote Control Switch

- Use the remote control CHECK switch in the following cases.


( 1 ) When the RUN lamp is flashing,
(2! To trace back the cause of
trouble after restarting from
-
rrTIl
"I"""
:;~'I
~
,.,. =
bTI] [ill]

"1:'._
c:::.:J
~''.!I: >In.
>toO'l

\ :' = I
:l'r.!'
~ .,. JI",O!',

stoppage with the RUN lamp flashing. '"l'O'''


88, 88' . ,II r
(3) To check during normal operation or stoppage.
(4) To monitor the temperatures of intake and discharge air. - -".no' V fly' /\

'"~, MO~~Check Mode , i Current da ta wi" . . displaved.

Check Mode 2 : Data held immediately before


G[QIFJ .1....

!]JWlv'~ AlB
.... .

/8
failure occurs will be displayed.

I0 I
Check Mode
EC9 Indication will delay as transmission between the remote control
switch and indoor unit takes about 10 seconds.
1
Press for more
_ All data may be displayed as "FF" or "-I", These transient
data produced temporarily by software do not affect device
than 3 seconds.
functions at all. (The alarm code may also be indicated as "FF;.)
, ..
Unit Number and Alarm
., ---- - [Allarm code identifying the last fault that has occured in the
Code Displayed indicated unit.
On
IIU 0'2
._. __ . __ .. __ .
r Unit number of connected unit or unit number for which check-
"-- ing mode was selected previously.
Within 7 seconds 1
After
(A) to check another

7 seconds
unit r- Forward : Press the A switch to rise
from Al to A2 to A3 ,,'

[ilill l-
Check Mode 1 Backward : Press the v switch to descend
(See 1-58 for details.) from AF to AE to Ad .. ,
To view the previous indication
. I V TEMP Q
I I ~ TEMP /\
I
Will I
Press
I
Press

t. ..
Unit Number and Alarm
8] CHECK
Press for more
than 3 seconds.

Press 1\ to view the next data.


Code Displayed
~,See (A) lo~ln~
"'.' '.'L
Press v to view the previous data.

After
7 seconds
..

Will
Check Mode 2
(See 1-61 for details.)
I ' '

.In Check Mode 2. Data of the first


V TEMP?
11 I three units connected serially to a

[ilill I remote control switch are available.


Pless
.You can press the CHECK switch to

, .. .J'

Press
u release Check Mode 2.
Check Mode 1 cannot be released
Check Mode Released even if you press the CHECK switch.
) C,OCK

HITACHI 1-57
(1) Contents of Check Mode 1

The next indication is shown by pressing 1\ the part of "TEMP" switch. If the v part of "TEMP" switch is pressed the previous ( 1
indication is shown.

( Temperature Indication)
r----------- Indication of Category Code
Indication of Temperuture, etc
I -,

1
Indoor Unit Temp.
Selting IC)
I aL :I I CC
" I -1 Normal .. Temperature displayed

2

Indoor Unit
Intake Air Temp.
em I :0' I
DC L '-f
-1 Abnormal
(Thermistor Open-circuited or
L-_-' PCB Defected)

(Thermistor Short-circuited or
l
Jl
~_


at Thermistor (C) L-_-' PCB Defected)

J
See Nt.3.1 Self-Checking of
PCB's using Remote Control
fndoor Unit Switch" in pages 1-78-79.
O:t [TI]
[TIJ

3 Discharge Air Temp.
:t:t


at Thermistor (' C) (NOTE 1) During transient period such as starting time. etc.,
...... may be indicated for a limited time.
(NOTE 2) The setting " bl " indicates cooling or heating "

Indoor Unit Heat capacity required when checking is performed during


'"
4 Exchanger liquid I LfL Lff I I L:m
l.' I test run.


Pipe Temp. eC)
I

Temperature at This is indicated only when a remote sensor


5 Remote Sensor
rei
I oLC
_f I I C:t
"-: is connected.


The indication of ..... is normally indicated.

6
Outdoor Unit Ambient
Air Temp. eC) !"-I[JQJ
DO us


..
Indoor Unit Heat

" , 7 Exchanger Gas Pipe :, f


f xc.s
L


Temp. eC) ::
".,

Outdoor Unit
8 Evaporating Temp.
[M]
DO I '-f'-
":r I


during Heating eC)

This indicates the internal information for the remote

O:t I - -
I
g Control Information
eli] I
control switch. This does not have any specific


meaning.

Discharge Gas Temp. In case that temperature is higher than lOO'C,


10 at the Top of
eM]
on I lo: f i
f i I
two digits flicker.


Camp. Chamber eC)
)
(During two compressors
(ex.) 123'C - II
to next page
C :, operation, average temperature
Flickering of two compressors
is indicated.)

I'
1-58 HITACHI
1
( Indication on Micro-Computer Input/Output ) Oarl<
li:JJl lCIl l!iIJ em , lD:!l
I Micro Computer
~UW;Ti ~;, :~~

.. IT]] I
11 ! Input/Output in
jlndoor Unit
!.. I I ~ I VMS

Micro-Computer
12 Input/Output in
Outdoor Unit
[ll]
!..!.. I -- I
I
Oarl<

J
Symbols w~h a I.tt.r Y are r.lays on PCB

00 Operation OFF, Power OFF


01 Th.nno-oFF
02 Alann
( Indication of Unit Stoppage Cause)
03 Freeze Protection, Overheating Protection
04 Frosting Protection
,..,
[d : II I I 05 Instantaneous Power Failure at Outdoor Unit
131 Cause of Stoppage
!..I I I 06 Instantaneous Power Failure at Indoor Unit, Reset
07 Stoppage of Cooling Op.'ation due to Low Outdeor Air

J
Temperature, Stoppage of H.ating Operation due to High
Outdocr Air Temperature (NOTE 4)
08 Compressor Quantity Changeover, Stoppage
09 Demand of 4-Way Valv. Chang.ov., Stoppage
10 D.mand, Enforced Stoppage

,.
( Abnormality Occurrence Counter ) 11 Retry due to Compressor Ratio Decrease
12 A.try due to Low P,.ss-u-'. ...,-In-c-'.-o-s-.--------I

..
13 Aetry due to High Pressure Increase
14
Abnormality
Occurrence Times IT] I
!.. I
I
!..I I t-- 15 Aetry due to AbnonnaJ Low Pressure of High Discharg.
Gas Temperature
16 Retrydue to Decreaseof Discharg. Gas Superheat
17 Retrydue to Inverter Tripping
Instantaneus Power 18 Retry due to Voltage 0 acrease
ru

.. [ll]
Failure Occurrence
15
Times in Indoor
Unit
CC I !..I !..I f-- 19 Other A.try (Expansio n Valv. Op.ning Chang. Protection,
Abnormal Transmitting betwn Invert.r end Outdoor Unit)
20 Operaticn Mod. Chon g.ov., of Indoor Unit (NOTE 3)

(NOTE 1) Even if stoppage is caused by "Alarm", 02" is not


Transmission Error always indicated.
Occurrence Times (NOTE 2) Explanation of Term,

[fl] I !..I!../j
,-", I f - Thermo-ON: A condition that an indoor unit is

..
18 between Remote
Control Switch and C :' requesting compressor to operate.
Indoor Unit Thermc-Off": A condition that an indoor unit is not
requesting compressor to operate.
(NOTE 3) In the FX system, "20 will be indicated at the
indoor unit operat ion changeover, and the unit will
automatically restart by the Th.,mo-oN.
17
Abnormality
Occurrence Times
on Inverter
I C I uis
,..,"t -
!.. !..II
I
In the FS system "20" will be indicated at the
difference mode between indoor units.
(NOTE 4) jn the automatic CoollH.at operation of FX system,
20" will be indicated at the stoppage of cooling
operation due to Iow outdoor air temp. or of heat
operation due to high outdoor air temp.
(A.f.r to chapter 4.2.5)

' - - Countable up to 99.


Over 99 times, "99" is always indicated.

(
- ~

Indication of Automatic Louver Condition


(NOTE 1) If 0 transmitting er ror continues for 3 minutes, one is
added to the accu rrence times.
(NOTE 2) The memorized d ala can be cancened by the method
indicated in 1.3.1 "Self-ehecking of PCB's using
Remote Contro' S witch" in pag.s 1-78-79.
[J] I !..I!..I
,-,,, I
..
18 Louver Sensor I 00: Normal I
, I
W FF : Abnormal I
to next page

HITACHI 1-59
( Compressor Pressure/Frequency Indication )
(
Discharge
19 Pressure (High)
(kg/cm'G)
[]i]]
/II I ":II
11...1

Suction
20 Pressure (low)
I
", II I to','to', I
I ;;C
(kg/cm'G)

This is an indication for internal information for the


21 Control Information Ito':l1
/I _I I to'I to', 1 remote control switch. This does not have any
specific meaning.

22
Operation
Frequency (Hz) I /to'Ito'' I I to', to'I The total frequency
compressors are running.
is indicated when two

.~
( Indoor Unit Capacity Indication )

23
Indoor Unit
Capacity I
" ,-, I
d : 11 ,-,D
Indication
,-, 1-' ,
Factor Indoor Unit Capacity

,-,,~ x 8 Iff'

Except, the capacity code for O.SH? unit and 1.5


( Expansion Opening Indication ) H? unit are respectively 6 and i3.

Indoor Unit
24 Expansion Valve
Opening ('!o)
IT] I to:I"u I
'- I

Outdoor Unit
25 Expansion Valve MVI
Opening (%)
[Ill
L.I... I sDDI

Outdoor Unit
26 Expansion Valve MV2
Opening (%) L" I .sDDI.s
[TIJ
Outdoor Unit
27 Expansion Valve MVB []]]
'- I I '-,,,"u I
Opening ('!o)

( Estimated Electric Current Indication )


<

[fJJ
I.
28
Compressor Running
Current (A) I I
I '-_'T
sc: I The total current is indicated when
compressors are running .
t\"IO

,----~--
.f.. Returns to Temperature Indication
,I
( Temperature Indication)

1-60 HITACHI
"11 \
l!l. J
(2) Contents of Check Mode 2

The latest data of the first three indoor units only connected serially are indicated when more than three indoor units are
J connected to one remote control switch.
By pressing the 1\ part of "TEMP" switch, the next display is indicated. If the v part of "TEMP- switch is pressed, the previous
display is indicated.

- - - - - - - - - - - Indication of category Code


( Temperature Indicator )
,
Indication of Tern perature. etc

Indoor Unit
1 Intake Air Temp. [i]1:l:l1
f' .s '-
-1 Normal , ......Tempera ture displayed


at Thermistor rC)
_. I (Themistor
Open-circuited or PCB Defected)
Indoor Unit
-1 Abnormal

LG
.. 1;111'-='"'11
f'- _, u
2 Discharge Air Temp, (Themistor Short-circuited
at Thermistor ee} or PCB Defected)

I See "I. 3.1 Self-Checking of PCB's using


Remote Control Switch" in pages 1-78-79.

em
Indoor Unit Heat


3 Exchanger Liquid
Pipe Temp. (Freeze
Protection) rC)
I ,,;
"'1;1 I L _, -
(NOTE 1) During transient period such as starting time, etc.,
-
_. may be indicated for a limited time.
(NOTE 2) All the data during the check mode 2 will be
changed to "00" if a power failure occurs during
4 Outdoor Air Temp.
rC)
, , I em
lOLl ''-
alarm indicatlon.

Indoor Heat
1';'-11 ;'-t -
5

6
..
Exchanger Gas Pipe
Temo. ('C)

Evaporating Temp.
at Heating ('C) I
-;:, C:,

'-"-1
-;0 [Q]]
u _I

7

Control Information.
I '1': II - - I
I
This is an indicatio n for internal information 'for the remote
control switch.


This does not have any specific meaning.

Discharge Gas Temp.


r
I noll 1/ I The average tempe rature is indicated when two compressors
8 at the Top of -, u -,:' I are running.
Como. Chamber CC)

to next page

HITACHI 1-61


......
( Compressor Pressure/Frequency Indication

.. 11
Discharge Pressure
9
(High) (kg/cm'G) ,-' I '0 I
fI_'

I""1 ~
..
Suction Pressure
10
(Low) (kg/cm'G) fll Llf

This is an indication for internal information for the

~I
11

12
..
Control Information

Operating Frequency
(Hz)
fO

[ill
''- 1
'-'"
, f 1I

, f,
'-"
remote control switch. This does not have any
specific meaning.

The total frequency is


compressor are running.
indicated when two

( Expansion Opening Indication )

Indoor Unit
I 0_'
' a I I t.:I"
13

14
..
Expansion Valve
Opening ('!o)

Outdoor Unit
Expansion Valve MVl I
u I

Del -'0 -9\


fl... 1
Opening ('!o)

( Estimated Electric Current Indication I

15
Compressor Running
Current (AI I "'-I
f'- r C,,,l
t.f1
The total value is indicated when two compressors
are running.

..f.. Returns to Temperature Indication

( Temperature Indication )
I

i,
I
,I

1-62 HITACHI
T,
C'I ,
1 ,2.4 Troubleshooting by 7-Segment Display

(1) Simple Checking by 7-Segment Display

I [1] '*
.. Turn on All Indoor Units I * All the Indoor Units Connected to the Outdoor Unit

I
I
I
o
~
..
Turn on the Outdoor Unit

Auto-addressing Starts
Outdoor Unit Circuit Board
PCB 1
During auto-addressing, the following items can be checked using the outdoor
unit's on-board 7Segment LEO display.
i ( 1) Disconnection of power supply to the indoor unit.
(2) Reverse connection of the operating line between the outdoor and indoor units
c POD (3) Duplication of indoor unit number
"',=3"e;'f
I ,'
=I
c:::::
r---c'= ,
~
I

R .-) == 1=1
g ==...::.
==
I
c::::= ::-'.'II
7-segment display
._-}1}4}
.-, c:::::l j
- I
, ..
(1) The outdoor unit's on-board 7-segment LED display indicates as follows normally.

CD
ffi]m"""'-'ffi][Zti] will be indicated.

Normal
rr.lr;:;r;l,......, rr.lrnra
~~ ~L:lCJ
I will be indicated a few
During this time, 2-5 minutes will
Case 1G1rnT7l,......,IG1rnra J times repeatedly.
pass (it depends on the number of
UJ~ UJ~
indoor units).
1lUlrnT71
Ll2J~ may or may not be
1TOlrnT7l indicated momententarily.
~~
LED's off.

~I)l. (2) The outdoor unit's on-board 7-segment LED display indicates as follows if there is something wrong.

(A) The indoor units are not


supplied with power.
~ CDlliIlQIIJ"""-lliI[2J] will be indicated continuously.

(81 Disconnection of the

Abnormal
operating line between
the outdoor and indoor units.
~ CD[]D[QI] <; [illf2IEJ will be indicated continuously.

Case I
(el Reverse connection of the
continues to appear for 60 seconds.
operating line between
the outdoor and indoor units. continues to flash after then, for 60 seconds.

f 0) Duplicated settings of the indoor unit number Drp switch OSWl (Refer to the description of alarm
code 35, in item ~1. 2. 2 Troubleshooting by Alarm Code".)

HITACHI 1-63
'r

(2) Checking Method by 7-Segment Display

By using the 7-segments and check switch (PSW) on the PCB 1 in the outdoor unit, total quantity of combined indoor ,,
unit, 7-segments operation conditions, each part of refrigeration cycle, can be checked.

PSW r--------------------------------~
: eTa start checking, press the -PSW2" :
I switch for more than 3 seconds. I
: PSW3 PSW2 eTa proceed press the "PSW2- switch:
I [>--
"llIIIIIII for less than 2 seconds.
: eTo proceed reversely press the "PSW3"
I switch for less than 2 seconds.
:: eTo cancel this checking, press the
7-Segments I Backward Forward "PSW2" switch for more than 3
I
I seconds. The display will be changed
: to the indication one step before.
I Then, press the -PSW2- switch once
I , 1 I
I again or more than 3 seconds. I
~--------------------------------~

,.- .,r
Checking Item PSW3 PSW2
~ [>
,-n ,..,
Checking Contents (Unit)

-.
Total 01 Thermo-ON
1
o
L' --
Indoor Units Capacity PSW2 PSW3 .t
CCC-c'1C ~
~
(x
<I W)

"

Running Frequency
I1 I,
'-'I ,
... PSW3 PSW2
~ [>
, ,.., n
"I
2 of Inverter Compressor
PSW2 PSW3 nnn-",'3 n

'-' u
MC1 (Hz)
<I ~
uuu , u
f
PSW3 PSW2
11- ~ [>

,-
Running Frequency
3 of Constant Speed
Compressor MC2 -'11-'
If I L PSW2 PSW3
<I ~
,.., r n ON: RAS-8FS, RAS-8FX
(50Hz)
RAS-10FS, RAS-lOFX
L' L' (62Hz)
, ...
, PSW3 PSW2
<llII [>
4
Outdoor Unit Expansion
Valve MV1 Opening
oilE f PSW2 PSW3
<I ~ "
'-' "
u "
u 000-"':00 ('!oj

5
Outdoor Expansion
,
, ...
11,-
olle c-
PSW3 PSW2
<llII [>
, n
u" u
Valve MV2 Opening PSW2 PSW3
~
OOO-"':OG (%)
<I f
. ...
r ,., PSW3 PSW2
~ [> ..
,-, ,- , ceo-me
"- - -
Outdoor Expansion
6
t:
- -"
Valve MIJB Opening PSW2 PSW3
<I ~ u I.f
('!o)

, ...
, PSW3 PSW2

,, o-" ceo-css
~ [>.
n ,-,
r 1.1 -
Discharge Pressure
7 PSW2 PSW3
(High)
<J ~ u (kg/cm'G)

I-

1-64 HITACHI
from Previous Page

( J
Checking Item

Suction Pressure (LOW)


".
I'-i
~ ...
,-
,-
PSW3 PSW2
<llII
PSW2 PSW3
!> Checking Contents

I.'f
,-, -_ 9-9_ 9
I
<J ~
- '-' (kg/cm'G)

,~
, PSW3 PSW2

,,- , ,, u" u"


I <llII !>
ie:
Discharge Gas Temperature
on the Tap of Compressor
PSW2 PSW3
MC1 rron I <J ~
nn ,.......
uu f ,''-{c Cq

,
GaG: Open-circuited

, ... PSW3 PSW2


!>
C' 55 : Short-circuited

"-, u"
<llII
Discharge Gas Temperature
on the Top of Compressor
MC2 (r02)
I
I
I
1'- o c
I'
.

-- PSW2 PSW3
<J ~

n nn,r-: ,''fC'
uu
(Right Side Compo in
Cq
I.' RAS-8FS. RAS-8FX.
RASl0FS. RAS-l0FX)
,
I I,- '"r ,, PSW3 PSW2

,
aOD: Open-circuited

,
,,
I
<llII [> ~
C' 55: Short-circuited
Control Information , r:
I..
u" - -
PSW2 PSW3
,
i' <J ~
No Specific Meaning

"
Control lnformation
:
1'-1 r -
,
,.
PSW3 PSW2
<llII [>.
n r:
"-
PSW2 PSW3
! , 11'- I.'f
<J ~ u No Specific Meaning

I'-Ie ,,
, PSW3 PSW2
Evaporating Temperature
of Lower Heat Exchanger
I

II I'
'"
li'-
<llII
PSW2 PSW3
[>
,., I' "
at Heating (rEl)
<J ~ uJu -'fe-GBG Cq
er: :
1'- 1,-c c,
of Open-circuited
, ... PSW3 PSW2 1i''1 : Short-circuited
Evaporating Temperature
of Upper Heat Exchanger
at Heating (TE2)
I' - -
<llII
PSW2 PSW3
<J
!> .....
~
nr r
u0 ,- -'fe-GBO

-{C' r: : Opan-circuited
Cq

,
, PSW3 PSW2 li''1 : Short-circuited
,
,r 0 r.,
Ambient Air Temperature
<llII !>
u" J -
PSW2 PSW3
(rO)
I <J ~
-'f2-GBG Cq
-{2'1 : Open-circuited

n ,,
, PSW3 PSW2 :(''1 : Short-circuited
Estimated Running Current
of Compressor MCl
<llII
PSW2 PSW3
[>.
,
,
u" u" GGG-eSS
"
(AI
<J ~
, ... PSW3 PSW2
,-, [>

,, Jr:
Estimated Running
~
<llII

" -
Current of Compressor
MC2
,- PSW2 PSW3 ,-, OOG-eSS (A)
<J ~
u (Right Side Comp, in
RAS-8FS. RAS-8FX.
RAS-lOFS. RAS-lOFX)
, ...

HITACHI 1-65

-------- ------
f

from Previous Page


Checking Item , PSW3 PSW2

(No.O Unit)
, -t: 'f 1- Lf
<llI
n ,, c teo-me
C> Checking Contents
f (No.O Unit)
(

u -
PSW2 PSW3 --,.
Indoor Unit <I ~ (%)
Expansion ( ( ....
, -t: rc
Valve Opening
PSW3 PSW2
(No.F Unit) 1- <llI C>.
PSW2 PSW3
<I ~ u u
,
'f , n oco-m: (No.F Unit)
(%)

,r '-, u'f
, ... PSW3 PSW2

(No.O Unit) <llI C>


(No.O Unit)
Indoor Unit Heat PSW2 PSW3 --,.
'f jf t:
Exchanger
<I ~ j -62- :2'1
( ( '-' (C)

,r , rt:
Liquid Pipe
Temperature.
(Freeze Protection) PSW3 PSW2

u ,,
(No.F Unit) <llI C>
'- PSW2 PSW3 n f t: (No.F Unit)

<I ~ .- .- -62- :2"1 (Cl

, ~

,r
PSW3 PSW2
<llI C>
(No.O Unit)
n
, ILf ,-, f n, (No.O Unit)

-
PSW2 PSW3
Indoor Unit
Intake Air ( ( <I ~ u c -62- :2'1 (Cl

,r , lrr
Temperature
PSW3 PSW2
(No.F Unit) <llI C>
'f f 'f I (No.F Unit)
u c ,I
PSW2 PSW3

I'
, ...
<I ~
PSW3 PSW2
- (C;

(No.O Unit) r 'f n <llI C>


,-, ,-,
'- u (No.O Unit)
'f
-
PSW2 PSW3
Indoor Unit
Capacity
Setting
( " ( <I ~ u '-' "
Except, the capacity code for
(x ~ w)

o.aw unit and 1.51-P unit


,1
I ' (No.F Unit)
r '11 r PSW3 PSW2
<llI C>
are respectively 6 and 13.

'- " r PSW2 PSW3 --,. ,-, f n (No.F Unit)

-
I
~
,I
I <I ~ u t: '-' (x w)

Except, the capacity code for O.81-P unit and 1.51--P unit
, ~ PSW3 PSW2 are respectively 6 and 13.

u -, ,--
r <llI C>
'f
Total Capacity Setting
of Indoor Unit
'- r PSW2 PSW3
<l ~
'f r f uuu
"""-2'{"
u (x ~ w)

I'
Total Quantity of ,-,
'f
nn
..I
.
PSW3 PSW2
C>
Except, the capacity code for a.8f-? unit and 1.SI-P unit
are respectively 6 and 13.

n If
-
PSW2 PSW3
u u "''f 000-0:6
Combined Indoor Unit
<I ~
(sets)

..I ...
Returns to START" OP'

1-66 HITACHI
(3) Running Current of Compressor
Inverter Primary Current
-
::
The inverter primary current is estimated from the running current of the compressor MC 1
indicated on 7-segments, as chart below.

g
E 20
i!!
~

0"
1:'
til
E 15
'C
ll.
~
Q)
rQ)
> 10


.5

II
5

o 5 10 15

Running Current of Compressor MCl


indicated on 7-segment

Indicated Running Current of Compressor MC2


The running current of the compressor MC2 indicated on 7-segment is calculated by the
equation below.

H2
A2=A1x-
H1

A1: Running Current of Compressor MC1 indicated on 7-segment (A)


A2: Running Current of Compressor MC2 indicated on 7-segment (A)
H1: Running Frequency of Compressor MC1 indicated on 7-segment (Hz)
H2: Running Frequency of Compressor MC2 indicated on 7-segment (Hz)

HITACHI 1-67
T
1 .2.5 Function of DSW's and LED's

(1) Printed Circuit Board in Indoor Unit


(. Following figure shows a separated-board type PCB.)
PCB(M): Controlling Board PCB(P): Power Supply Board
8
PC8(P)

iCJ~I::
I,-++-r- YM
n[]
L'..) YSHI

o
-,~,~r

Some unit has an one-board type PCB which has the same functions and devices with the
separated-board type.

Dip Switch and LED Functions on Indoor Unit Printed Circuit Board

Name of Printed
Part Name Contents of Functions
Circuit Board
Controlling Board: CD DSW1 Selting of Indoor Unit Number
PCB(M) Selting of Optional Functions
DSW2
A. Self-Diagenosis
B. Remote ON/OFF Control
C. Automatic Restart after Short Power Failure
D. Remote Sensor Control
E. Selting of Filter Indication Interval
@DSW3 Selting of Indoor Unit Capacity Code
@DSW4 Selling of Capacity Adjustment
@LED1 This LED1 indicates the transmission state between the indoor unit
(Red) and remote control switch.
Normal Condition: Flickering
Abnormal Condition: Activated or Deactivated
@LED2 This LED2 indicates the transmission state between the indoor unit
.(Yellow) and outdoor unil.
Normal Condition: Flickering
Abnormal Condition: Activated or Deactivated
(LJ LED3 This LED3 indicates the transmission state between the indoor unit
(Green) and central station.
When Disconnected:
Normal Condition: Deactivated
Abnormal Condition: Activated
When Connected:
Normai Condition: Flickering
Abnormal Condition: Activated or Deactivated
@LED4 This LED4 indicates the power supply (5V) for micro-computer.
(Green) Normal Condition: Activated
Abnormal Condition: Deactivated
Power Supply @LDI Relay YSHi ON: Activated
Board: PCB(P)
J LD2 Relay YMe ON: Activated
@LD3 Relay YLo ON: Activated
@LD4 Reiay YSo ON: Activated
@LD5 Relay VMs ON: Activated
@LD6 Relay Y52H ON: Activated
I@LD7 Relay YH2 ON: Activated

1-68 HITACHI
(2) Printed Circuit Board in Outdoor Unit
.Arrangement Inside of Main Electrical Box
Inside of Sub-Box I I

/
P CB6
1 G
08 PCBS

V
Y 1

For Only
I
*
PCB2
IB
1)PCBS and hinged board A are
RAS-8FS, RAS-8FX only for FS series unit.
RAS-10FS,RAS-10FX
i).
.Purpose

Symbol PCB Purpose


PCB1 for Control 1. Transmitting between Indoor Unit and Outdoor Unit
(Low Voltage) 2. Processing for Sensor Input
3. Processing for Dip Switch Input
4. Operation Control for Above items 1 to 3.
Compressor Operation Control, 4-Way Valve Control, Bypass Valve
Control, Fan Control and Ex. Valve Control
5. 7-Segmentlndication
PCB2 for Control 1. Processing of Safely Device Input
(High Voltage) 2. Processing of Relay Output by PCB1
PCB3 for Inverter 1. Inverter power part is driven by instruction of PCB1 and compressor
is driven.
2. Overcurrent Control
3. Protection Control for Inverter Part
PCB4 for Power Supply 1. DC Power is supplied to PCB 1
DC5V: for Micro-computer Power Source
DC 12V: for Electronic Expansion Valve Drive and Transmitting
DC24 V: for Relay Drive Power
2. AC Power is supplied to Transformer
PCBS for Fan Control 1. Detecting Condensing Temperature
2. Fan Speed Control during Cooling Operation
PCB6 for Reverse 1. Reverse Phase Detection for Power Source
Phase Protection

HITACHI 1-69
r

a. PCB1 and PCB2

\9

PCBl:
Controlling
Board

0
CJ
<>
0 -=- 00-
-0-

0 (

0 (
0 0 <
(

0 -0
C3
0
= .~
0 I (

0 C::::3< =
!
, 'I,
II 0
o
I
r:
, I

j:
III
" I~
,I'
I Ii

'r', i: PCB2:
I!
,I Power Supply
Board

; "

'"
I;'

! I

'III
1'j
I

<.:

1-70 HITACHI
II'"
ill
Dip Switches and LED Functions on Outdoor Unit Printed Circuit Boards

Name of Internal
V' , Circuit Board
Part Name Contents of Functions
I Controlling Board: CD DSW1 Setting of Outdoor Unit Number
I PCB1
DSW2 Setting of Capacity Code
I Outdoor unit capacity is set according to nominal capacity (HP).
@DSW3 Setting of Height Difference
The height difference between outdoor unit and indoor unit is set.

II @DSW4 A. Test Running for Cooling or Heating


Outdoor unit can be run for testing. When testing has been
finished, reset the function.
B. Forced Stoppage of Compressor
When performing test running or inspection. compressors can be
forcefully stopped to ensure safety.
@DSW5 A. Setting of Outdoor Un~ System (FS or FX)
(Optional B. Setting of All the Year Cooling or Heating
Function) C. Changeover of Defrosting Condition
The defrosting operation for normal areas or cold areas can be
changed over.
@DSW6 Setting of Piping Length
The total piping length between the outdoor unit and indoor unit is
set.
\l) PSW1 Manual Defrosting Switch
The defrosting operation is manually available under the forced
defrosting area.
@PSW2 Check Switches
@PSW3 When checking units. Checking items can be selected by these
switches.
l LED1 Circuit Connected to CN25:
(Red) Normal Condition: Deactivated
Abnormal Condition: Activated
@LED2 This LED2 indicates the transmission state between the indoor unit
(Green) and outdoor unit.
Normal Condition: Flickering
Abnormal Condition: Activated or Deactivated
@LED3 ---
(Red)
@LED4 This LED4 indicates operation of defrosting.
(Green)
@LED5 This LED5 indicates operation when checking with PSW2 and
(Red) PSW3.
<@LED6 This LED6 indicates operation when operation is being controlled
(Green) with protective devices.
@LED7 This LED7 indicates when a unit is performing heating operation.
(Red)
@LED8 ---
(Red)
@LED9 This LED9 indicates when a unit is performing cooling operation.
(Red)
@LED101 This LED101 indicates the transmission state between PCB1 and
(Red) inverter-PCB.
Normal Condition: Flickering
Abnormal Condition: Activated or Deactivated
@SGE1 These indicate the following: "alarm", "protective safety device has
SGE2 tripped" or "checking items".

HITACHI 1-71
Dip Switches and LED Functions on Outdoor Unit Printed Circuit Boards(continued)

Name of Internal FS FX For r


Part Name Functions I
Circuit Board 1 2 3 4 Service

Power Supply @> LED302 Hi20U1put


X 0 x 0 0
Board: PCB2 (Red) Relay YHi2 ON: Activated
@ LED303 L02 Output
(Red) Relay YL02 ON: Activated
x 0 x 0 0
@ LED304 Hi OU1put
(Red) Relay YHi ON: Activated
0 0 0 0 0
LED305 Me Output
(Red) RelayYMe ON: Activated
0 X 0 X 0
@> LED306 Lo Output
(Red) Relay YLo ON: Activated 0 0 0 0 0
@> LED307 52C2 Output (CMC2)
x 0 x 0 0
(Red) Relay Y52C2 ON: Activated
@> LED308 52CS2 Output (Start CMC2)
(Red) Relay Y52CS2 ON: Activated
x 0 x 0 0
LED309 52C10U1put (CMC1)
(Red) Relay Y52C1 ON: Activated 0 0 0 0 0
@> LED310 52CS 1 Output (Start CMC1)
(Red) Relay Y52CS 1 ON: Activated 0 0 0 0 0
@) LED311 21 1 Output (RVR1)
x x 0 0 0
(Red) Relay Y211 ON: Activated
@> LED312 212 Output (RVR(2
(Red) Relay Y21 2 ON: Activated 0 0 0 0 0
LED313 20AOutput (SVA)
(Red) Relay Y20A ON: Activated
0 0 0 0 0
LED314 20BOutput (SVB)
(Red) Relay Y20e ON: Activated 0 0 0 0 0
@J LED315 20C Output (Not Use)
x x x x 0
(Red) Relay Y20c ON: Activated
LED316 ARM Output
(Red) ON: Activated
0 0 0 0 0
@ LED317 "Compressor On" Output
(Red) ON: Activated
X X X X 0
@ LED318 Defrosting Output
(Red) ON: Activated
X X X X 0
LED319 Operation Output
x x x x 0
(Red) ON: Activated

(Refer to NOTE2)
NOTES:
1. Some models are not equipped with LEOs. relays and connectors of power supply boards.
2. The meanings of the marks are as follows:
1: RAS-5FS
2: RAS-8FS and RAS-10FS
3: RAS-5FX
4: RAS-8FX and RAS-10FX
0: Equipped
x: Not Equ ipped

1-72 HITACHI
iI
r:
b. Inverter Printed Circuit Board: PCB3

,-----,10
b r----,"

o ==
=

, Dip Switch and LED Functions on Outdoor Unit Inverter Printed Circuit Board

Switch Name
Function
(j) DS20 DS21
1 2 3 4 1 2 3 4 Normal Operation Mode (This is set at the factory.)

ON
OFF
I~~~~ I I~M~ I
1 2 3 4
ON
OFF 1234
For RAS-SFS and RAS-SFX Switch No.2 of DS21
ON: 3S0V Power Supply
OFF: 415V Power Supply

Name of Printed
Function
Circuit Board
@LED1 (Red) The LEDs are activated or deactivated according to the state of compressor
@) LED2 (Green) operation.
LED3 (Yellow)
Compressor is Compressor is
LED1 LED2 LED3 StoPPed CAbnormal)C') Ooaratlno (Normal)

- - -
Tripping due to Stoppage due to
- o - Short-Circuit StooSional
Tripping due to Acceleration due to
- X 0 Instantaneous Overcurrent Oneration Sinnal
Tripping due to Declaration due to
() X - Overheatino of Fins Ooeration Sional
Tripping of Constant Frequency
0 x 0 Electric Thermostat Durine OPeration
Stoppage due to
- 0 0 Insufficient Voltaoe
stoppage due to
-
0 0 - Overvoltaoe -
Stoppage due to
0 0 0 Abnormal Transmission -
NOTES: ': When the compressor stops because
Deactivated of abnormality, the LED fiickers every
0: Flickering 0.5 sec.
x: Activated or Deactivated
@ LED4 (Yellow) This indicates the state of transmission.
Flickering: Normal Transmission
Activated or Deactivated: Abnormality in Transmission Circuit
,I
(J) LED6 (Red) This indicates the voltage between both terminal of capacitor CB in the inverter
I part.
I Activated: The voitage between both terminal of capacitor CB is

~I l SOV 20V or greater.


Deactivated: The voltage between both terminals of capacitor CB is
SOV 20V or smaller.

L HITACHI 1-73
- c. Power Supply Board: PCB4
T

PCN401 CN401

PCN402 CN402

Connector No. Purpose


PCN401 AC Power Supply Input (AC200-240Vor 220-260V)
PCN402 AC Power Supply to Transformer (AC200-240V or 220-260V)
CN401 DC Power Supply to PCB1 (J)+ 24V + 12V@+5V@GND)
CN402 DC Power Supply to PCB1 (J)+ 12VGND)

d. Fan Controller Board (FS Series Unit Only): PCBS


PCBS for fan controller changes the output voltage by the thyristor control and adjust the
rotation of the outdoor unit fan motor in cooling operation. The output voltage is changed
according to the detection of the condensing temperature by the TC thermistor (THM8) attached
to the outdoor heat exchanger.

CN1:
To Thermistor
(THM8)
.(Ii

, '
I

PCN2: Output Side PCN 1: Input Side


(To Fan Motor) (Power Supply)

, .,

1-74 HITACHI
--
e. Reverse Phase Protection Relay Board (RAS-BFS, BFX, 10FS and 10FX Only): PCB6

7 8

~
Neon Lamp

-@- 11 098090-8
lID

RY

~~t ;0
N

( (1 )( CZ I e
( (5 1
RJ.c>. ~I (l
) ;0
~
(>
(Vii) ( VAl ) For 3aQV
PCB
For 41SV
PCB

T s
-4- I ~ ~
\~------------_-./

Some unit does not have the neon lamp.

<D PCB6 protects the constant speed compressor from inverse phases of Ll-R, L2-S, L3-T for
the unit RAS-BFS, RAS-8FX, RAS-l0FS and RAS-l0FX.

In case of inverse phases, the neon lamp is activated and the alarm code "02" is displayed
on the remote control switch and the 7-segment display.

@ In case that the power source is 415V (nominal voltage), remove the connecting wiring (A),
and put on cap (B) on both tabs as shown figure above.

HITACHI 1-75
T
(3) Printed Circuit Board in CH Untt
PCB2: Controlling Board PCB1: Power Supply Board

m
!rn~
rtD[[D

D.b\oo= y

.Dip Switches and LED Functions on CH Untt Printed Circuit Boards


i
Name 01 Printed
Part Name Contents of Functions
Circuit Board
Controlling Board: <D DSW1 Performing 01 Self-checking Function
PCB2 Selling 01 Sell-checking Mode
DSW2
(Low Voltage) When switch #1 is only OFF, Self-checking 01 PCB is available.

~~F I ~~~~~HI~~ I
12345678
@LED1 This LED1 indicates the transmission state between the indoor unit
(Red) and CH uni!.
Normal Condition: Flickering
I, Abnormal Condition: Activated or Deactivated
@LED2 This LED2 indicates the transmission state between the outdoor unit
(Yellow) and CH unit.
Normal Condition: Flickering
Abnormal Condition: Activated or Deactivated
@LED3 This LED3 is not applied.
(Green) Normal Condition: Deactivated
Abnormal Condition: Activated
@LED4 This LED4 indicates the power supply (5V) for micro-computer.
(Green) Normal Condition: Activated
Abnormal Condition: Deactivated
Power Supply crJ LD1 Solenoid Valve SVS2 ON (Relay YSHi): Activated
Board: PCB1 @LD2 Solenoid Valve Changeover Operation ON: Deactivated
(High Voltage) Abnormality of Power Supply to PCB: Deactivated (Aiarm Code "03")
@LD3 Transmission State Between Indoor Unit and CH Unit
II,
Abnormal: Deactivated (Alarm Code "03")
,,'
i LD4 Transmission State Between Outdoor Unit and CH Unit
Abnormal: Deactivated (Alarm Code "03")
LD5 Solenoid Vaive SVSl ON (Relay VMS): Activated
@LD6 Solenoid Valve SVD2 ON (Relay Y52H): Activated
I@LD7 Solenoid Valve SVD1 ON (Relay YH2): Activated

1-76 HITACHI
1 .2.6 Protection Control Code on 7-Segment Display

(1) During the protection control except abnormal stoppage, LED 6 (Green) on the outdoor unit PCB1
~l' t lights ON and indication code for protection control is shown on the 7-segment display.

i (2) During the protection control, the light is kept ON and the light is Off when the protection control is
terminated.
f
i (3) If protection control is duplicated, priority is given to the following priority.
I a. Priority is given to Frequency Control
High Priority
~ @Compression Ratio Control
.L @Excessively High Discharge Pressure Protection Control
~ @Cu"ent Protection Control
L @Inverter FinTemperature Protection Control
L Excessively High Discharge Gas Temperature Protection Control
L @Excessively low Suction Pressure Protection Control
~ @Oil Retum Control
Low Priority
b. As for retry control, the latest retry data is indicated. However, priority is given to item "a" during
the frequency control.

Code Protection Control Activation Condition Remarks


P01 Compression Ratio Control Compression Ratio ii::9-Frequency Decrease Ps: Suction
(Pd/(PS+1.3:ii2-Frequency Increase Pressure
P02 High Pressure Protection control Pd<::24.0kg/cnlG-Frequency Decrease Pd: Discharge
Pressure
P03 Current Protection Control more than 14A(lnverter)-+Frequency Decrease
P04 Inverter Fin Overheating Fin Temp.i;:; 94"C-+Frequency Decrease
Protection Control
POS Discharge Gas Overheating HighDischarge Gas Temp. on Top of Compo -Frequency
Protection Control Decrease (Temp. isdifferent depending on frequency.)
POG Suction Pressure Protection LowSuction Pressure-sfrequency Decrease(Pressure is
Control different depending on outdoor temp.)
PO? 4-Way Valve Changeover .6P{when valve is changed)<Sks/cnl-+Frequency .6P = Pd-Ps
Control Increase
POB Oil Return Control Frequency<40Hz for more than 1 hour-s
Frequency~40Hz

P11 Compression Ratio Decrease Compression Ratio(PdI(Ps+1.3)<1.B) 1#)


Retry Control ..

P12 Suction Pressure Increase Retry PS>9ks/cnlG 1#)


Control
P13 Discharge Pressure Increase Pd>2?ks/cnlG(20-30Hz: Pd>24ks/cnlG) 1#)
Retry Control
P1S Vacuum/Discharge Gas Pd =1-3kg/cnlG, PS<O.2ks/cnlG 1#)
Temperature Increase Retry
Control against
P16 Discharge Gas Superheet 1 hour continuously at Discharge Gas Superheat 1#)
Decrease Retry Control lower than 10 deg C
P1? Inverter Trip Retry Control Inverter Instantaneous Overcurrent, Electronic 1#)
Thermal Relay or Fin Thermostat Tripping
, P1B Voltage Decrease Retry Control Power Supply Voltage Decrease 1#)
I
I P19 Other Retry Control Inverter Reset, Initial Setting of Ex. Valve

I. 1) During protection control except alarm stopping, indication code for protection control is shown.
2) During protection control, the light is kept ON and is OFF when protection control is terminated.
3) Monitoring for 30 minutes after retry control is maintained.
4) 1#): Retry: Temp. or Pressure--2 Times/h, Current--2 Times/D.S h. Alarm: At the 3rd Retry

l HITACHI 1-77
-_... 1 .3 Procedure of Checking Each Main Parts
T
I

1 .3.1 Self-Checking of PCB's using Remote Control Switch

Following troubleshooting procedure is utilized for function test of PCS's in the indoor unit and outdoor unit.

1-
I~.
( RUN/STOP)
Stop Operation

1\

PCB Check Mode


[ VTEMPC:; I .
181 ~
p,ess lwO
Switches for
3 Seconds.

Jl tex.j lno'canon of Unit No. Me

Indication of
Unit Number
r ,-, " n
,_ ,_, U ,_,

l
7
After
7 Seconds

~
Indi
canoe Contents
Operating Automatic nn Normal
uu

~
PCB Check
Abnormality (Open-circuit, Short-circuit. etc.) in circuillor
n.
I After Approx. 1 min. u Intake Air Temp. Thermislor -

Result 7 Max 3 Types of Abnoomalities Indicated. 02 Discharge Ai, Temp. Thermistor

03 LiQuid Pipe Temp. Thermistor

UJ:ill o'i Remote Thermistor Abnormality


Abnormaiity (1) 05 Gas Pipe rene. Thermistor
- Indoor Unit PCB
'-1'- UJ 06 Remote Sensct
nn Transmission OfOutdQOl Unit
u
After
'\ 7 1 Seconds 08 Tr81\$lTlission 01 Central S:alion

09 Louver Sen$Ol'

DR EEPROM -
Abnormality (2)
,=. " I
EE Transmission 01 Indoor UmI dUring
I_':J ,_" ThisChecking OperaliOtl

, l After
7 1 Seconds
F6
cn

,e8
Protection Sigr.al Detochen CirCUIt
Phase netectce
Transmission ollnvertcr
-

.e,q HighP'rcssufe Sensor


Abnormality (31
", , ,-,..
L' -, U ,_,
.C6
cr
Comp Oischar;e GJ.S Temp. Thermir.lOl
- Ol.::coor UM PeS

C lew PressureSensor

After ,cb Heal E.Chan..e EvaP?t3::cn Temp,


Contents
'\ 71 Seconds ThermlSfor
V
FE Preaasatory Thermistor ConnectIon
fF -

1-78 HITACHI
L
~,
I
, o
Return to Indication of Unit Number

Return to Indication of Unit Number

I Indication of
Unit Number rn "n
VTEMPQi)
I
l.U uu Operation of PCB check v
I mode for the next unit

'<..'7-
(ex.)
Indication of
Repetition Unit No.,. r nn
l. , uu

After
7 Seconds
, -s-
V
f"
Result

T
[ujJJ:============LLJ:ill After
Approx. 1 min.

, 7-
After 1 seeon d

Repetition <u,,. 'L'-. '-L'


s r u r n.: '-'L
f:i_

,I~
Release PCB
Check Mode [8
'I"
~'

~ress
Will
NOTE:

"~I
If this indication is continued and -J:FF- is not shown, this indicates that each one
of indoor units is not connected to the remote control switch. Check the wiring
rn nn between the remote control switch and indoor unit.
l.U UU

(2) rn this troubleshooting procedure, checking of the following part of the PCS's is not available.
PCB in Indoor Unit: Relay Circuit, Dip Switch, Option Circuit
PCB in Outdoor Unit: Relay Circuit. Dip Switch, Option Circuit
(3) If no result is given using this troubleshooting procedure (J/FF), there is a possibility of abnormal transmission of
the central station (short-clrcult : TL- TG).
(4) In the case that this troubleshooting is performed in the system using the central station, indication of the central
station may change during this procedure. However, this is not abnormal.
(5) After this troubleshooting, the memory of abnormality occurrance times described on page 1-59 will be deleted.

HITACHI 1-79
1 .3.2 Self-Checking of Remote Control Switch

Cases where CHECK switch is utilized. NOTES:


(1) If the remote control switch readouts malfunction. 1. AUTO COOUHEAT Switch is available for FX
(2) For regular maintenance check system only.
2. SWING LOUVER Switch is available for indoor
unit with swing louver only.

1 Turn ON the power source.


Checking of LCD, LEOs and Indicating Circ u i t
r-.,..-
.0 Normal: All the LCD indications
and LEOs are
activated. for 5 seconds.
(LEDI)
.:=- ... RUNiSTO p
....,1\\\'

Simultaneously depress the following 4 switches. (2 times) (LED 2)


2 ,U/I

~ IP:o
(During Operation. they can be depressed.)
II

~/\~ :::'1'== =1=


:;;'1 ~'.,~;"1 ; :;: ~,-;;~ [@;] ,.
.'ID
>
It''.~~
~ llTIJ
-,/ .. I ~,
~ .~
[E!!IJ
IJI"O".
88s 88 0 ....
.,.
,f

~~p 8 ! -,
!2l :. E:3[J 1
I
< 7
Checking of touch type switch function.
3
Depress the all touch type switches one by one.
Anyone of the switches can be depressed.
:(> By depressing a particular touch type switch, the
corresponding segment is activated.
Temperature Indicator

Normal
e-eoc ",N'''",

'\ 7
After 15 seconds

::J uu
'~,~
,~ """
,,=,
r~ ,-,~"!f"~y,
,..,.
~~
ecce
,~
"EA,

Normal Abnormal

4 The transmission circuit is checked automatically.


=t> Main Remote
Control Switch
Sub Remole
Control Switch

~ ~~
,, .. to

'7

5
Depress the Reset switch for initialization.

>[ ]
The indications return after 15 seconds. when the
unit is operating.

Example 1
~]
[
(

1-80 HITACHI
1.3.3 Self-Checking of Indoor Unit's PCB

(1) Self-Checking by Relays and LED on IndoorUnit PCB

eTo CheckAbnormality on IndoorUnit PCB due to Malfunction

eTo check Abnormality on Indoor Unit PCB Based on Results of Checking by CHECKswitch on the
remote control switch and Self-Checking Function

Procedure
Referto page 1-68 for location and function of DSW and LED.

CD Turn OFF the mainpower switch.

@ Disconnect connectors CN12 and CN2, and set dip switch DSW2 as shown below.
Set #1 and #2 at OFF side.

fl. ~~Frri~~ ~~~~ I


12345678

Dip Switch DSW2

NOTE: Before turning ON the power, see checking procedure mentioned in next page.

@ Turn ON the main power switch,


Check Mode starts. (See next page.)
Analog Test
Relay Test
LED Test

@ After completion of self-checking, turn OFF the powerand resetthe dip switch as before.

Ii) ..

,I )
I
HITACHI 1-81
- (2) Self-Checking Procedures in Check Mode

Check Item State of Mode Confirmation Method


r

Analog Test If each thermistor for intake air, discharge air If FAN operation is available, it
~ and freeze protection is normal, proceed to is normal.
~ the next step.
YSo ON S( sec) Check ON/OFF sound of
Each Relay Test
L04 ON
OFF
relays and LED lamp.
~
YLo 5(S8<) U 15( ..<)
~
L03 ON
~
YMe
~ L02 ON
~ YHi LOl ON
~
~l(sec)
~ VMS L05 ON
~ Repeatedly
Usee) ~
~ Y52H LOG ON
~ Perform.
~ YH2 L07 ON
~
~
COOL


~
RUN
~
~ ALARM
~
~ COOL
~ Thermo-ON
~
~ HEAT
~
~ HEAT ENO
LED Test Thermo-ON
Transmitting (I.U.-O.U.) LED2-lnstantaneous ON
~
Transmitting (1.U.-R.C.Sw.) LED1-lnstantaneous ON
~
Transmitting (I.U.-Central Station) LED3-lnstantaneous ON
Termination Turn OFF and reset all dip switches as they
were.

1-82 HITACHI
.,....-
I
,
,
\'
1.3. 4 Self-Checking of CH Unit's PCB

Troubleshoot CH unit's PCB if abnormalities are found.

(1) Self-Checking Procedures


Referto page 1-76 for location and function of DSWand LED.
<DTurn OFF the main power switch.
@ Set switch only #1 of DSW2 at OFF position.
@ Turn ON the main power switch. Check to ensure that LED4 is ON.
@) Start the test according to next item (2).
@ Endthe test.
Turn OFF the main power switch.
(/) Reset the dip switches as before.

(2) Contents of Test

Test Name PSW1 Setting Contents of Test

<D DSW rHJ I ~~~~ I


Test ON
Checking on ON State of DSW
OFF
1 2 3 4

@RelayTest ON
OFF
I 1iI~~~ I Checking on ON/OFF Function of Relays
on PCB1
1 234

@ Transmission Test ON
OFF
I ~1iI~~ I Checking on Transmission Circuit to
Outdoor Unit and to IndoorUnit
1 234
@) DSW rLJ Test ON
OFF
I 1iiI1iiI1iiI1iiI I Checking on OFF State of DSW

1 234
@ Reset Test ON I ~1iiI1il1iiI Resetting of Micro computer
OFF
1 2 3 4
I
<D DSW rHJ Test

DSW Setting Checking Item


!;
DSW1
~~F I ~~~~
1 234
I Switch #1 to #4 ON Siale
Normal: LD4 on PCB1 Activated

~~F I ~ I!H! ~ 1iil1iiI1il1iiI1


DSW2 Swilch #1 10 #4 ON Slate
Normal: LD3 on PCB1 Activated
12345678

~~F I iii iiiiii iii ~ ~~ ~ I


DSW2 Switch #5 10 #8 ON State
Normal: LD2 on PCB1 Activated
12345678

HITACHI 1-83
-- Relay Test
Check ON/OFF sound of relay and LED lamp.

Relay LED 0 1 2 3 4 5 S 7 8 (sec)


I I I I I I I I I

YTG - No Checking

YSHI LDI
OFF ~
Y52H LDS
OFF
ON I!
YH2 LD7
OFF
ON I!
VMS LD5 ONn
OFF

YSo LD4 ONfI


OFF

YLo LD3
OFF
ON II
YMe LD2 ONI'"L-
OFF
,

I"
'iI, @ Transmission Test
Check on LD4 activation and LD5 flicker with 1 second interval.
,
Transmission Circuit Normal Abnormal
i
i To Indoor Unit (LEDI on PCB2) LD40N LD40FF
I To Outdoor Unit (LED2 on PCB2) LD50N LD50FF
!

I @ DSW rLJ Test

I,, DSW Setting Checking Item

~~F I Iillillillil I
DSWI Switch #1 to #4 OFF State
Normal: LD4 on PCB1 Activated
1 2 3 4

~~F I Iillillillil ~ ~~ ~ I
DSW2 Switch #1 to #4 OFF State
Normal: LD3 on PCBl Activated
12345678
DSW2 ON
OFF
I ~ I!IIH!I iii iiiiii iii I Switch #5 to #8 OFF State
Normal: LD2 on PCBl Activated
.
12345678

@ Reset Test'
All LDI to LD7 are activated, and after one second they are deactivated by resetting of
micro-computer.

, '" 1-84 HITACHI


h
1 .3.5 Self-Checking of 7-Day Timer (PSC-3T)

This procedure is utilized for regular maintenance check, and if the 7-day timer is malfunction.

<D Turn ON the main power switch.


~
Checking of LCD and Indicating Circuit:
Simultaneously depress the following 4 switches, (HOUR) of "PRESENT TIME"
(PRESENT DAY) of "DAY OF WEEK" (ON TIME) (OFF TIME) of" MONITOR".
During operation, they can be depressed.

All the LCD indications activated, for 5 seconds.


CONTROL TIMER HrrACHI

J ... 'BBB= <''''',

:,r~
PM I
All the LCD indications deactivated, for 1 second. .._ .". p,,_fo
... .,..,..,. 't" ......
.\.
NORMAL: I 1"'_!of'Ul",,'tIUI

..
-: .,.~ ;~~~~
~~,
.
All the LCD indications activated, for 5 seconds.
iM"' ' ,,~- ~""'" "~I~
IHOURI [\jJ~'EIIHoURllvlMlrEI ~Cl!
I D01 C, "'H-:-
All the LCD indications deactivated, for 1 second. I
Pll~~~NI !~lEcrl 01 01111(1
il:;'~ OAY \ll,.Hl( "';Nlrat

IRElUllN] -'ESE' lCAsmllcrr 1l~1


I;J,;;;;!

@ Checking of Touch Type Switch Function:


Depress all the touch type switches one by one. By depressing a particular touch type switch,
the corresponding segment is activated.
Anyone of the switches can be depressed.
Indication
MINUTE

(p~R;~nME) ~S;~SETPRESENT

n -
NORMAL: HOUR RETURN
(ONIOFFTIME) OFF TIME DAY

After 15 Seconds
MINUTE
(ON1OFF TIME) , f CANCEL
ssr
T V_ f SETI
MONITOR

HOUR
(PRESENT TIME) SELECT
~ME
f) @ Completion of self-checking, '77" is indicated, for
3 seconds.

-='
.n.;
@ Return to the indication before the self-checking.

AM Wtnn
ILJ . LJLJ
\
,
'Y
SUN MQN TUE WED THU FRI SAT
J 1 ,
,
~ 11 10
,

HITACHI 1-85
- 1 .3.6 Self-Checking of Central Station (PSC-3S1)

This procedure is utilized for regular maintenance check, and if the central station is malfunction.
T

<D Turn ON the main power switch.

~ Checking of LCD and IndicatingCircuit:


Simultaneouslydepress the following 4 switches, (FAN) (COOL) and ('17) (t.) of "UNIT".
During operation, they can be depressed.

CENTRAL STATION
All the LCD indications activated, for 5 seconds. [Ell!] Il;'llI!J I!!E!IJ = I!!ll!!J

~
a:mEBl Iro!Bll UNI T SET ne,

~D'" BB BB"~
~11~~~iiiiii;~;~~;~ I!B!KJ
All the LCD indications deactivated, for 1 second.
NORMAL: ~
All the LCD indications activated, for 5 seconds.
CJ @UN/STOP) CO UNIT
~ 8(:r;II:f~~;Lrl~~:~II~;~ ~F
!SET T[t.lER ..
All the LCD indications deactivated, for 1 second.
\:OVL! ru~ Iv TEMP AID;
TR
/,.,-:;
"""
///
/ . ///;

@ Checking of Touch Type Switch Function: By depressing a particular touch type switch,
Depress all the touch type switches one by one. the corresponding segment is activated.
Anyone of the switches can be depressed. Temp. Indication Part
V (UNIT) [blank)

NORMAL:

After 15 Seconds
A (UNIT)

V (TEMP.)

INDVL
- -
~"'f MNTR
t::::.f
!~EMP.)
RMT HEAT
DRY

!~N
PRGMTIMER
~- , RUN!STOP
t::::.f COOL

@ Checking of TransmissionCircuit:
NORMAL ABNORMAL
Automatically checked, and the result will be
indicated as figure right, for 3 seconds.

@ Return to the indication before the self-checking.

i. UN IT SET TEMP.
IAVL I} RMT. SW
RR c
IMNTRI

UNIT 1 ~ 1 \ ; 1 I 1 1011 11 I) II '1 1~


,L
"1 1-86 HITACHI
1'.!1
:L
1 .3.7 Procedure of Checking Other Main Parts
....:.'._
~ -"'0 -TN"_ --. -, '. _ . """"''0. . '
,,_>~ ..A ,".,
.

(1) High Voltage Discharge Work for Replacing Parts

(Perform this high voltage discharge work to avoid an electric shock.]


Procedure

(a) Check to ensure that no high voltage exists. If LED6 is ON after start-up and LED6 is OFF
after turning OFF power source, the voltage will decrease lower than DC50V.

(b) Connect connecting wires to an electrical brazer.

(c) Connect the wires to terminals. + and - on power transistor. --+Discharging is started, resulting
in hot brazer. Pay attention not to short-circuit between terminal + and - .

fIt.

Brazer ~ Connecting
\
P ower
Wires Transistor

(d) Wait for 2 or 3 minutes and measure the voltage once again. Check to ensure that no voltage is
charged.

HITACHI 1-87
T
(2) Checking Procedures Power Transistor
Outer Appearance and Internal Circuit of Power Transistor

1 r@ 6

!~~[!'J~I
- u v w -
1---1-'
u

~ ~ ~ ~ ~
@I @ e
Remove all the terminals of the power transistor before check.
If lterns (a) to (e) are performed and the results are satisfactory. the power transistor is normal.
Measure it under 1 kO range of a tester. Do not use a digital tester.

(a) By touching the + side of the tester to the + terminal \


of power transistor and the - side of tester to U. V and
W of power transistor, measure the resistance. If all the
resistances are from 1 to 5 kO, it is normal.

(b) By touching the - side of the tester to the + terminal


of power transistor and the + side of tester to U, V and
\
W of power transistor, measure the resistance. If all the
resistances are greater than 100 kO. it is normal.

(c) By touching the - side of the tester to the - terminal of


power transistor and the + side of tester to U, V and W \
of power transistor, measure the resistance. If all the
resistances are from 1 to 5 kO, it is normal.

(d) By touching the + side of the tester to the - terminal of


power transistor and the - side of tester to U. V and W
\
of power transistor. measure the resistance. If all the
resistances are greater than 100 kO, it is normal.
.~
(e) If more detailed check is required. check it by the following table.

Tester Ell Tesler 8 Tesler Ell Tesler e Tesler Ell Tesler e


IGBT Ell G1 G1 E1 U G2
IGBT Ell G3 G2 E2 V G4
IGBT Ell GS G3 E3 W 06
IGBT8 G2 04 E4 G2 U
IGBT8 G4 GS ES G4 V
IGBT8 G6 G6 E6 G6 W
G1 IGBT Ell E1 G1
G3 IGBT Ell E2 G2
GS IGST Ell E3 G3
G2 IGSTS E4 G4
04 IGSTS ES 05
06 IGBTS E6 G6

It is normal if allihe resistance is infinity (00).

1-88 HITACHI
, (3) Checking Procedures on Diode Module
Outer Appearance and Internal Circuit of Diode Module

,--,--,-"0 +

'V o----t
'V 0o>----I--~
'V 1

If items (a) to (d) are performed and the results are satisfactory, the diode module is normal.
Measure it under 1 kn range of a tester. Do not use a digital tester.

(a) By touching the + side of the tester to the + terminal


of the diode module and the - side of tester to the
- terminals (3 NOs.) of the diode module, measure
the resistance. Ifall the resistances are from 5 to
50 kn, ~ is normal.

(b) By touching the - side of the tester to the + terminal


of the diode module and the + side of tester to the
- terminals(3 Nos.) of the diode module, measure the
resistance. If all the resistances are greater than
500 k n, it is normal.

tte
(c) By touching the - side of the tester to the - terminal of
the diode module and the + side of tester to the
- terminals(3 Nos.) of the diode module, measure
the resistance. If all the resistances are from 5 to 50 kn,
~ is normal.

(d) By touching the + side of the tester to the -terminal of


the diode module and the - side of tester to the
- terminals(3 Nos.) of the diode module, measure
the resistance. If all the resistances are greater than
500 k n, it is normal.

HITACHI 1-89
T
. . . . . ... ...""1
_.~~
--,----- .-.---,-.

(4) Checking Procedures on Transmeter for Picking up Current

Outer Appearance

-.
Arrow Mark

from U pf Power Transistor


J

Arrow Mark
to U ofComp. from Vof
j Power
Transistor

I
\
Wires
I
\
to Vol Compo

If the results are satisfactory after checking items mentioned below, it is


normal. .~
a. Check to ensure that the arrown mark and wire direction are correct.
I
b. Check to ensure that the wires to the trans meter are correctly i
inserted.
C. Check for any abnormal breakage on the surface.

1-90 HITACHI
(5) Checking Method of Electronic Expansion Valve
a. Electronic Expansion Valve
I
<D Outdoor Unit Electronic Expansion Valve MV1 (For Lower Heat Exchange). MV2 (For Upper
Heat Exchanger). These expansion valves control a refrigerant flow during heating
operation.

Operation Conditions: Operate all the indoor units during heating operation.

Checking Method: When operation is stabilized. check to ensure that compressor


upper part temperature Td is in the appropriate range indicated
in the figure below by activation of electronic expansion valve MV1
or MV2. The opening (0~100%) of electronic expansion valve
MV1 and MV2 can be checked by outdoor unit check mode items
oE1 and oE2.
Outdoor Units Electronic Expansion Valve MVB (For Bypass)
This electronic expansion valve controls the refrigerant flow during cooling operation.

Operation Conditions: Operate all the indoor units during cooling operation.

Checking Method: When operation is stabilized. check to ensure that compressor


upper part temperature Td is in the appropriate range indicated
in the chart below by activation of electronic expansion valve MVB.
The opening (0~1 00%) of electronic expansion valve MVB can
be checked by outdoor unit check mode item oE1b.
When performing heating. the electronic valve is closed.
@ Indoor Unit Electronic Expansion Valve MV
This electronic expansion valve controls the indoor unit capacity.

Operation Conditions: Operate all the indoor units in cooling operation.

Checking Method: When operation is stabilized. check to ensure that the temperature
of the indoor unit heat exchanger gas pipe ;s higher by 2'C to 20'C
than of the liquid pipe. The temperatures of the indoor unit heat
exchanger gas pipe and liquid pipe can be checked by remote


control switch check mode items b7 and b4.

~
(t)
100
90 High Temperature
Range
80
1:: 75
'~"
n. 70
60
8:~
:::>., 50
5a
Ill",
.,~ 40
~.,
0.0. 35
EE 30 saturated Temperature
8~ 20 ofRefrigerant

10

10 12 14 16 18 20 22 24 (kgJadG)
~I t Discharge Pressure Pd

Appropriate Range of Compressor UpperPartTemperature According to High Pressure

HITACHI 1-91
T

(6) Checking Method of Outdoor Fan Motor


The outdoor air flow is controlled by changing over the taps of the fan motor according to outdoor
temperature during heating operation.

Operating Conditions: Operate all the indoor units during heating operation.

Checking Method: When the operation is stabilized, check to confirm the taps of the
outdoor unit fan motor with LEDs on the outdoor unit printed circuit
board PCB2, according to outdoor temperature.

a. RAS-5FS and RAS-5FX Hi


One outdoor fan motor is controlled.
Me
Fan Motor Name MOF1
,

~Tap Hi Me Lo
Lo


Air
Flow LED 304 305 306
Hi 0 x x
Me x 0 x
Lo x x 0 11
!

14 15
,

18
0: Activated x: Deactivated Air Flow Control by
Outdoor Unit Ambient Temperature eCl

b. RAS-8FS, RAS-8FX, RAS-10FS and RAS-10FX Hi


Two outdoor fan motor are controlled separately.
I
Fan Motor Name

.~Tap
Air
Flow LED
Hi
302
MOF1
Lo
303
MOF2
Hi
304
Lo
306
h1 Me

Lo

Hi
Me
Lo

0: Activated
0
x
x
x
0
0
x: Deactivated
0
0
x
x
x
0 1
't
14 15
Air Flow Control by
I

18

Outdoor Unit Ambient Temperature eC)


.i

:\

1-92 HITACHI
(7) Checking of Electrical Coil Parts
....-
Resist-
Wiring
Name of Parts Model Electrical Wiring Diagram ance
No.
(0)
Fan Motor for Indoor Unit wcr-,. CD-~ 44.8
; t>i\ ~-@ 41.1
<Do...:~
,~-
ENO-KPPA @-@ 21.0
55W ill ~o \ 'r" @-@ 4.3
<V~-.!.> @-@ 2.9
for RPI-0.8FS, 1FS,
1.5FS
[~
u, ~ at 25"C

Fan Motor for Indoor Unit CD-~ 12.7


-f?',::::==:= ENO-KPPA
~-@
@-@
12.8
4.4
\\ ~\\.;J 160W @-@ 6.6
we>-,., ) @-@ 3.7
for RP/-2FS o-s \ at 25'C
@ 0-1o ~,

Fan Motor for Indoor Unit :J) ~o


" '~ CD-~ 23.7
(j)~0 ~-@ 10.4
:>
:>
5!!f-~
~'~~I
ENO-KPPA
180W
~~
.j, -J @-
@-
4.1
4.7
@-@ 4.2
for RPI-2.5FS at 25'C
@-CD 397.5

e
Fan Motor for Indoor Unit <De>;.
(i)~ CD-~ 66.91
CL2361 CD1 0 ~~ "J':."~~0 ~-@ 52.93
w~-~I- CD-(l) 389.3

~~
12W at 25'C
for RPI-l FS ~
Fan Motor for Indoor Unit @-CD 139.8
CD-~ 31.94

~
H CL3060

23W
"i'~
aJO"" ,0
~-@
@-@
CD-@
31.94
42.62
115.1
for RCI-1.5FS (V~ at 25"C

0
CD 0 '; JJ~..;~..o:])
Fan Motor for Indoor Unit ( o-l~-\\'" @-CD 102.2
CD-~ 16.27

f!1 CP3030 ~~ Cill=J ~-@


@-@
47.80
51.78
~ 30W CD-(l) 154.9
for RCI-2FS, 2.5FS at 25"C

Fan Motor for Indoor Unit @-CD 156.18


CD-~ 46.9
~-@ 25.5
eO It , '
', '-'
-==, ENO-KPPA
~~
<DO"" @-@
CD-(l)
67.4
20W CV~ 111.8
for RCD-IFS , CD~XJ at 25"C
oJ..-~\--
Fan Motor for Indoor Unit '1'. @-CD 113.4
i~ @OJ' CD-~ 31.29

effi ', '-'


=, CP2559
20W
~-@
@-@
CD-(l)
27.68
74.58
133.9
for RCD-1.5FS at 25"C

HITACHI 1-93
......

Resist-
Wiring
Name of Parts Model Electrical Wiring Diagram ance
No.
(0)
Fan Motor for Indoor Unit or (j)-@ 64.5
$ Oi\ @-@ 22.2
ENO-KPPA 0~l'<. @-@ 16.1
Q) ..." ,,
c{] " I.:;
==, 65W J ~
J)~~
'r.-. @-@ 6.6
@-@ 13.2
for RCD-2FS ~~
c1J
~ at 25"C

Fan Motor for Indoor Unit @-(j) 88.85


0<>:J (j)- 34.25
CP3045 ale-:;
@-@
c{] " '-'
==,
85W
al~
CD~<D @-@
37.02
109.2
oJ:-~\--- (j)-() 107.8
for RCD-2.5FS
~~ 0'AP at 25'C
Fan Motor for Indoor Unit (j)-@ 316.5
or, @-@ 54.3

~
(J) ~,
ENO-KPPA @-@ 37.8 I
15W
@~~ " ,,
@ 0-.; @-@ 41.1
"
(i) ~Q;
'", @-@ 117.5 I
~~ @=J at 25"C
for RPK-1.5FS
Fan Motor for Indoor Unit o-,..J , @-(j) 161.4
(j)-

~
Oil' 61.1
TNO-KP 0~l'<.
" , -@ 26.3
e o-i
~'1'
\ (j)-() 51.7
20W cD ..... l,; ~ 73.8
for RPF-1.5F8,
RPFI 1.5FS. ~~
L!J ~ at 25'C

Fan Motor for Indoor Unit ...,~o--;.. @-@ 5.4


(;, Ci\ @-@ 8.8
CH3531 @o-::~ @-@ 4.5
~.. '
~:\\v
= " , -@ 10.8
65W @ o-i "
.::t ~(D (j)- 32.5

~~ ~ at 25"C -


for RPC-2.5FS

Fan Motor for Indoor Unit @-(j) 30.75


(j)-
r!.~
18.72
..... '-"', CX8001 -@ 44.36
~ ale-, @-(j) 21.13
100W 1:V~ at 25'C
for RAS-5FS. RAS-5FX
CD "
I~@
~ oJ,.,..I,\""-
Fan Motor for Indoor Unit @-(j) 30.75
~~ [fuJ (j)- 18.72
ri~
..... '-"',
CX8002 -@
@-@
81.29
22.82
\::::::J 50W at 25'C
for RAS-8FS. RAS-8FX

,
Fan Motor for Indoor Unit (j)e-,
CD~(j)
@-(j)
CD-
23.77
73.41
[!0J
..... '-"', CX8005 ill. 0-1---\\" @-CD 17.13
.1) ~ at 25'C
\::::::J 150W .:l) 0'AP
forRAS-10FS.RAS-10FX

I
1-94 HITACHI
i
Resistance
Name of Parts Model
(0)
U J Drain-up Motor

~ 135
~ PCD-4N230HS-3 at 20"C
""
for RCI-1 FS, 1.5FS, 2FS, 2.5FS
Drain-up Motor

@ 135
~ PCD-4N230HS-2 at 20"C
""
for RCD-1 FS, 1.5FS, 2FS, 2.5FS
Solenoid Valve for Gas Bypass

It
1,900
ST10P at 20"C

for RAS-5FS, BFS, 10FS,


RAS-5FX,BFX,10FX
4-WayValve

~
1,740
V25760B at 20"C

for RAS-5FS, BFS, 10FS,


RAS-5FX,8FX,10FX
Compressor Motor
~
J.'="' 1.71

~.v 500AHV at 20"C


-1

~:~ ;<,il
~,F

D.
rorRAS-5FS,RAS-5FX
Compressor Motor

triP
. Cti G) B03TLV
for Inverter: 1.68
for Constant Speed:
3.93
at 20"C

for RAS-BFS, RAS-BFX


Compressor Motor

~
F
tri
.~euu~~.
rorRAS-1DFS,RAS-10FX
1003TLV
tor Inverter: 1.68
for Constant Speed:
2.90
at 20"C

tj.
Contactor for Compressor Motor

520
A25 at 20"C
~ '/<
) ) for RAS-5FS, BFS, 10FS,
RAS-5FX,BFX,10FX
I
i HITACHI 1-95
L
-- (8) Checking of Compressor

CHECK LIST ON COMPRESSOR


T

CLIENT: MODEL: DATE:


Serial No.: Production Dale: Checker

No. Check Item Check Method Result Remarks


1 Are THM5(CN119) and THM7(CN113) <DAre wires between THM5 and CN119,
correctly connected? and THM7 and CN113 correctly
THM5. THM7: Discharge Gas connected by viewing?
Thermistor ~ Check to ensure that7-segment
(THM7 is only for RAS-8FS, 8FX, 10FS indication of Td1 is higher Td2 when
and 10FX) No.1 comp. is operating.
Td1: Temperature of THM5
Td2: Temperature of THM7
2 Are thermistors, THM5 and THM7 <D Check to ensure that thermistor on the
disconnected? top of cornp, is correctly mounted by
viewing?
Check to ensure that actually measured
temp. are greatly different from the


indication(Td1, Td2) during check mode.
3 Are connectors for current sensor(CN8 (j)Checkto ensure that indication A1 and
and current sensor connector)? A2 are 0 during compressor stopping.
@ChecktoensurethatindicationA1 and
4 Is current sensor faulty? A2 are not 0 during compressor
running.(However. A2 is 0 during
5 Is current sensing part on PCB3 faulty?
stopping of No.2 comp.)
6 Is the direction of current sensor(CTU. Check the direction. by viewing.
CTV) reverse?
7 Are power source wires, U and V Check to ensure that wires are correctly
inserted correctly into current sensor? inserted.
8 Are ex. valves(MV1 , MV2 and MVB) Check to ensure that MV1-CN1 01, MV2-
correctly connected? CN102 and MVB-CN103 are correctly
connected.
9 Are ex. valve coils(MV1. MV2 and MVB) Check to ensure that each coil is correctly
correctly mounted? mounted on the valve.
10 Are the refrigeration cycle and electrical Check to ensure that refrigerant is flowing
wiring system incorrectly connected? into indoor units by operating one
refrigerating cycle only from the outdoor
unit.
11 Is opening of ex. valve completely Check the following by the check mode of
closed(locked)? outdoor unit.
(j)Liquid Pipe Temp.(TL)<Air Intake
Temp.(li) during Cooling Operation
@Liquid Pipe Temp.(TLAir Intake
Temp.(li) during Heating Operation
12 Is opening of ex. valve fully opened Check to ensure that liquid pipe temp. is
(locked)? lower than air intake temp of stopping
indoor unit whenother indoor units are
operating under cooling operation.
13 Are the contacts for comp. magnetic Check the surface of each contact(R. S and
switch CMC faUlty? T) by viewing.
14 Is there any voltage abnormality among Check to ensure that voltage imbalance is
L1-L2. L2-L3 and L3-L1? smaller than 3%.
Please note that power source voltage must
be within 380V or 415V 10%.
15 Is the cornp, oil acidified during Check to ensure that the oil color is not
compressor motorburning? black.

1-96 HITACHI
1
Additional Information for "CHECK LIST ON COMPRESSOR"

Check
Additionallnformation(Mechanism of Compressor Failure)
Item
1& 2 The liquid refrigerant return volume to the compressor is controlled by the discharge gas
temperature Tdl when NO.1 compressor only is operating. I' Tdl and Td2 are reversely
connected, the liquid refrigerant return volume will become small by detecting the temperatures
even even if the actual discharge gas temperature is high. Therefore, this abnormal
overheating operation will result in insulation failure of the motor winding.
3,4&5 Overcurrent control(operating frequency control) is performed by detectingcurrent by the
current sensor.
In this case, winding insulation failure will occur, since control is not available in spite of actually
high current.
6,7 The Current sensor checks phaseand adjusts outputelectrical wave in addition to the above
mentioned items. If fault occurs, the output electrical wave becomes unstable giving stress to
the motor winding, resulting in winding insulation failure.
8,9 During a cooling operation, Pd is controlled by MVl and MV2, and Td and SH are controlled by

MVB.
During a heating operation, Td and SH are controlled by MVl and MV2, and MVB is fully
closed.
If expansion valves are incorrectly connected, correctcontrol is not available, resulting in
compressor seizure depending on liquid refrigerant returning conditions or motor winding
insulation failure depending on overheating conditions.
10 If the refrigeration cycle and electrical system are incorrectly connected, abnormally low suction
pressure operation is maintained or abnormally high discharge pressureoperation is
maintained, resultinq in giving stress to the compressor, since their correct control is not
available.
11 ditto
12 The compressor may be locked due to the liquid return operation during the, cooling operation.
13 In the case that the contacting resistance becomes big, voltage imbalance among each phase
will cause abnormal overcurrent.
14 In this case, overcurrent will occur, efficiency will decrease or the motor winding will be
excessively heated.

15 In the case, it will result in motor burningor compressor seizure.

,
, ,,

I
\ HITACHI 1-97
L
"
'.4 Test Run
, .4. 1 Test Run Mode by Remote Control Switch

- I Turn ON the power source of the units.


II Procedure for MTEST RUN" mode of remote control switch. I
Depress the MODE and the CHECK switches

~
together for more than 3 second.

,..-11 "TEST RUN" and the counting number of the


connected units to the remote control switch
~
(for example "01") are indicated on the remote Counting Number

control switch, the connection of remote control of Connected Units .,... O


cable is correct.
This indication will last for approximately
Operation
Piq,I
.
."
"'~
:"!r _.(

1 minute.
Lamp '<,
r--- ",,,,.,~ I V :~ ...= /\

l.-. If no indication appears or the number of the !] b.:: -

..
units indicated is smaller than the actual num- D~ IV''''A,.Q
........
Remote Control Switch
ber of the units. some abnormalities eXist
III
Remote
l
Control Switch Fault Inspection Points after the Power Source OFF
Indication
The power source is not turned ON. 1. Connection between the connector and the wires:

No Indication
The connection of the remote control
cable is incorrect.

The connecting wires of power supply


line are incorrect or loosed.
I{
2.
3.
4.
5.
Red wire-No.t. Black wire-No.2, White wire -No.3
Connecting points of Remote Control Cable
Contact of Connectors of Remote Control Cable
Connection Order of each Terminal Boards
Screw Fastening of each Terminal Boards
The setting of unit number is incorrect. - -- - 6. Dip Switch Setting on Printed Circuit Board
Counting 7. Wire Connecting Order of Bridge Cable
The connection of control cables be-
number of
connected units
tween each indoor units are incorrect.
(When one remote control switch
{ 8. Connecting Points of Bridge Cable
9. Contact of Connectors of Bridge Cable
is incorrect.
controls multiple units.)

IV Select TEST RUN MODE by depresslna MODE Switch. (COOL or HEAT)

t
V Depress RUN/STOP switch.


The "TEST RUN" operation will be started. (The"TEST RUN" opeation will be finished after 2 hours unit
operation or by depressing the RUN STOP switch again.)
If the units do not start or the operation lamp on the remote control switch is flickered. some abnormalities
exist.
VI
Remote Control Switch
I Inspection Points aher the Power
Unit Condition Fault
Indication Source OFF
The operation lamp flickers. Connecting Order of each Terminal
(lTime/1Sec.) And the Unit The unit does not The connecting wires of operating Boards.
No. and Alarm Code "03" start. line are incorrect or loosed. Screw Fastening of each Terminal
flicker. Boards
The operation lamp flickers. The unit does not The connection of remote control
This is the same as item 1Il 1,2. and 3.
(lTime/2Sec.) start. cable is incorrect.
The unit does not The connection of the thermistors
Check by the alarm code table in
Indication or Flicker different start, or starts or other connectors are incorrect.
the service manual.
to above. once and then Tripping of protector exists. or (Do it by service peoprej
stops. etses.
The outdoor fans The connecting order of power Connecting Order of the Terminal
Normal supplly line is incorrect. Board: Tal in the Outdoor Unit.
rotate reversely.
Connecting Point of Power Supply
The outdoor fans Some wires of power" supply line
Normal Line. Contact Outdoor Fan Motor
do not start. is disconnected.
Connector.

1-98 HITACHI
-- t

1 . 4 . 2 Test Run Mode by Outdoor Unit

(1) Purpose: This function is used to check operation conditions of components by test operation from
the outdoor unit by a service engineer.

(2) Operation Method: After setting the dip switch, DSW4 on on the outdoor unit PCB, turn ON the
main switch. After power supply, wait for more than 5 minutes due to automatic address setting by
the micro-computer, and then, start the test operation.

Cooling Operation Heating Operation

ON ON
!!I iii iii iii !!I !!I iii iii
1 2 3 4 1 234

a. All the indoor units connected to the outdoor unit are automatically started under the same
operation mode such as cooling or heating.

b. During this test running, the remote control switch indicates "TESr on the display. If
temperature setting is not performed, the following setting is given.
Cooling Operation Heating Operation
Fan Speed: Setting Speed before Test Run Fan Speed: Setting Speed before Test Run
Temperature: 19 Temperature: 34

c In the case that the operation mode such as operation controlled by remote control switches or
central station, the normal test operation is not available.
@Remote Control Switch: Switch OFF the "RUN/STOP switch.
@Central Station: Stop the central control and give instruction for individual operation.
After the test operation by the outdoor unit is started, If the above mentioned controller are
used, operation mode may be changed or this test operation may be automatically stopped.
Therefore, do not touch any controllers.

d. If the system is stopped due to an alarm during this test operation, turn OFF the main power
sw~ch and remove the cause of the alarm and then, supply power to the system so that the test
operation can be re-started.

(3) Cause of Stoppage


a. Turning OFF Main switch to Outdoor Unit (Power OFF to Outdoor Unit PCB)
b. Alarm
c. Sw~ching RUN/STOP Switch OFF
d. Resetting the dip switch, DSW4 DSW4
Check to ensure that the dip switch, DSW4 is reset ~
as it was after this test operation. ~

i
I

I HITACHI 1-99

L
I"

-
::.,:===
-, ' .'. ~ ::. -: .~-- - ::- - -,

1 . 4 . 3 Checking List
..
, ' ,;,

CHECK LIST ON TEST OPERATION


CLIENT: INSTALLER: DATE:
O.U. MODEL: O.U. Serial No.: Checker

(l)General

No. Check Item Result

4
1
2
3
Was the dip switch, DSW6 for piping length in O.U. set?
WaJ3 the dip switch, DSW3 for piping lift in O.U. set?
Is the transmitting wire contacting to power lines?
Was an earth wire connected?

5 Check for any short circuit?
6 Is there any voltage abnormality among each phase(L1-L2, L2-L3, L3-L1)?

(2)Refrigeration Cycle NOTE: Perform checking after all the indoor units are operated at the "HIGH" speed
and the system becomes stable.

a. Common

No. Check Item Result


1 Is A 1 (compressor running current) is greater than r1j when compressor is

3
running?
Is Td1 (discharge gas temp.) higher than Td2 when only No.1 comp. is
operating?
Is there any abnormal sound or vibration?
-
.' I

b. Cooling Operation (It is applicable when outdoor temperature is higher than 15C.)

I No. Check Item Result


1 Is oEb (O.U. Ex. Valve Opening) within "7" to "40''when Td - SH is 15 to 30
degG."?
.
2 Is Ps r3j to r5j when solenoid valve, SVA is OFF?
3 Is the H1 + H2 (compressor frequency) abnormally low or high? If outdoor
temp. or indoor temp. is high, H1 + H2 becomes high.
4 Is Pd r14j to r22j ?
5 Is solenoid valve SVA OFF?(check LED on PCB2.)

1-100 HITACHI
,
.......
No. Check Item Result
6 Is indoor unit heat exchanger SH 2 to 10 deg. when iE (I.U. ex valve) is less
I than r7J or r100J ?
Indoor unit heat exchanger SH indicates the following;
b7 (I.U. Heat Exchanger Gas Temp.) - b4 (I.U. Heat Exchanger Liquid
Temp.) which are indicated on the remotecontrol switch
However, The above is applicable only when the data can meet the following.
b2 (Intake Air Temp.) - b1 (Setting Temp.) >3 deg
7 Are TL (I.U. heat exchanger liquid ternp.) and Ti (I.U. Intake Air Temp.) almost
same when iE (I.U. ex. valve) is r2J (at stoppage or thermostat OFF)?

c. Heating Operation (It is applicable when outdoor temperature is higher than O"C.)

No. Check Item Result


1 Is oE1 + oE2 (O.U. Ex. Valves (No.1 & 2) Opening) abnormally low of high
when Td - SH is 15to 30 degC. ?(If operating frequency is high, oEl + oE2
will become high.)
2 Is Pd r16J to r22J ?
3 Is the Hl + H2 (compressor frequency) abnormally low or high? If outdoor
temp. or indoor temp. is low, H1 + H2 becomes high.
4 Is Ps rlJ to r5J when solenoid valve SVA is OFF?
5 Check for leakage on liquid bypass ex. valve(oEb) by touching.
6 Is the temperature difference between I.U. more than15 deg when iE (I.U. ex.
valve) is r100J ?
The temperature difference between I.U. means the following;
b3 (Discharge Gas Temp.) - b2 (Intake Air Temp.) indicated on the remote
control switch by check mode:-However, this is applicable only when
>
b2 (Intake Air Temp.) - bl (Setting Temp.) 3 deg.

NOTE: The symbol with an underline indicates checking item and the mark r J indicates checked
data.
(3) Others

HITACHI 1-101
--
\I' } No. Contents Page
l
1 TROUBLESHOOTING 1-1-1-101
I
. .g.~*1o,1!i1t!
3 MAIN PARTS 3-1-3-27
4 OPTIONAL FUNCTIONS 4-1-4-26
5 FIELD WORK INSTRUCTIONS 5-1-5-18

2. SERVICING '" . . 2-1


2.1 Outdoor Unit..................................................................... 2-1
2.1.1 Removing Air Intake Grille Nets ...... :......................................... 2-1

~
I 2.1.2 Removing Front Service Panel.. . .. . . . . . . . .. . . . . . . . . . .. . . .. . .. . . . . . . . . . . . . .. . . .
2.1.3 Removing Fan Guard Nets
2.1.4 Removing Compressor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.5 Removing High Pressure Switch, High Pressure Sensor and Low Pressure Sensor .. .
2-2
2-3
2-4
2-8
2.1.6 Removing Fusible Plug
(only for Models. RAS-8FS, RAS-8FX. RAS-10FS and RAS-10FX) 2-11
2.1.7 Removing Electrical Parts..................................................... 2-12
2.1.8 Removing Electrical Box...................................................... 2-16
2.1.9 Removing Outdoor Fan....................................................... 2-18
2.1.10 Removing Coil for Reversing Valve and Solenoid Valve 2-20
2.1.11 Removing Thermistor for Liquid Pipe ,.............. 2-21
2.2 In-the-Ceiling Type (Models: RPI-0.8FS, RPI-1FS and RPI-1.5FS) . 2-23

I 2.2.1 Removing Indoor Fan Motor


2.2.2 Removing Thermistors for Liquid Piping and Gas Piping
: ..
.
2-23
2-24
I~:
2.2.3 Removing Printed Circuit Board (PCB) . 2-24
f 2.2.4 Removing Drain-Up Mechanism . 2-25
I
2.2.5 Removing Float Switch . 2-26
Ii 2.2.6 Removing Drain Pan : . 2-27
\
2.3 In-the-Ceiling Type (Models: RPI-2FS and RPI-2.5FS) . 2-28
2.3.1 Removing Indoor Fan Motor . 2-28
2.3.2 Removing Thermistors for Liquid Piping and Gas Piping . 2-28
2.3.3 Removing Printed Circuit Board (PCB) . 2-29
2.3.4 Removing Float Switch . 2-29
2.3.5 Removing Drain Pan . 2-30

i
HITACHI
L
_...........
-'P"., ",
7 ..
--
."

.
,_,',",~__

2.4 4-Way Cassette Type . 2-31


2.4.1 Removing Long Life Air Filter . 2-31
2.4.2 Removing Intake Air Grille . 2-32
2.4.3 Removing Electrical Box Cover . 2-32
2.4.4 Removing Optional Air Panel . 2-33
2.4.5 Removing Fan Runner and Fan Motor . 2-34
2.4.6 Removing Printed Circuit Board (PCB) . 2-36
2.4.7 Removing Float Switch . 2-37
2.4.8 Removing Drain-Up Mechanism . 2-38
2.4.9 Removing Drain Pan . 2-39
2.4.10 Removing Thermistors for Liquid Pipe and Gas Pipe . 2-40

.'
2.4.11 Removing Automatic Louver Motor : ' . 2-41
2.5 2-Way Cassette Type : . 2-43
2.5.1 Removing Long Life Filter . 2-43
2.5.2 Removing Optional Air Panel . 2-44
2.5.3 Removing Fan Motor . 2-45
2.5.4 Removing Bearing (not required for Model RCD-1 FS) . 2-47
2.5.5 Removing Coupling (not required for Model RCD-1 FS) . 2-47
2.5.6 Removing Printed Circuit Board (PCB) . 2-48
2.5.7 Removing Drain Pan . 2-49
2.5.8 Removing Drain-Up Mechanism .' . 2-50
2.5.9 Removing Float Swnch . 2-52
2.5.10 Removing Thermistors for Liquid and Gas Pipes . 2-53
2.5.11 Removing Motor for Automatic Louver . 2-54
2.6 Wall Type
2.6.1 Removing Air Filter
2.6.2 Removing Right Side Cover
2.6.3 Removing Front Panel
.
.
.
.
2-56
2-56
2-56
2-57
.'
2.6.4 Removing Motor for Automatic Louver . 2-58
2.6.5 Removing Thermistors for Liquid Pipe and Gas Pipe .' . 2-59
2.6.6 Removing Electrical Box Cover and PCB . 2-60
2.6.7 Removing Drain Pan . 2-61
2.6.8 Removing Heat Exchanger and Fan Motor . 2-62

()

HITACHI
ij , J 2.7 Floor Type . 2-65
2.7.1 Removing Intake Air Grille . 2-65
I 2.7.2 Removing Air Filtsr . 2-65
2.7.3 Removing Discharge Air Grille . 2-66
2.7.4 Removing Front Cover . 2-66
2.7.5 Removing Fan Motor . 2-67
2.7.6 Removing Printed Circuit Board (PCB) . 2-69
2.7.7 Removing Thermistors for Uquid Pipe and Gas Pipe . 2-71
2.8 Floor Concealed Type . 2-73
2.8.1 Removing Air Fitter . 2-73
2.8.2 Removing Front Covers . 2-73
2.8.3 Removing Fan Motor . 2-75
2.8.4 Removing Printed Circuit Board (PCB) . 2-75
2.8.5 Removing Thermistors for Liquid Pipe and Gas Pipe . 2-75
2.9 Ceiling Type . 2-76
2.9.1 Removing Air Filter . 2-76
. 2.9.2 Removing Side Cover . 2-76
2.9.3 Removing Discharge Air Grille . 2-77
2.9.4 Removing Fan Motor . 2-78
2.9.5 Removing Bearing . 2-80
2.9.6 Removing Coupling . 2-80
2.9.7 Removing Automatic Louver Motor .'. 2-81
2.9.8 Troubleshooting on Automatic Louver . 2-82
2.9.9 Removing Thermistors for Ucjuid Pipe and Gas Pipe . 2-83

ie 2.9.10 Removing Printed Circuit Board (PCB)


2.10 Cleaning Indoor Unit's Heat Exchanger
.
.
2-84
2-85
2.10.1 Required Tools for Cleaning (for All Indoor Units) . 2-85
2.10.2 In-the-Ceiling Type . 2-87
2.10.3 Cleaning 4-Way Cassette type Indoor Unit .. 2-90
2.10.4 Cleaning 2-Way Cassette Type Indoor Unit . 2-95
2.10.5 Cleaning Wall Type Indoor Unit .. 2-98
2.10.6 Cleaning Floor Type and Floor Concealed Type Indoor Unit . 2-100
2.10.7 Cleaning Ceiling Type Indoor Unit . 2-103
2.11 Removing Remote Controller . 2-105
2.11.1 Removing Remote Controller . 2-105
2.11.2 Removing Remote Control Switch (Revised) . 2-106
2.12 Collecting Refrigerant for Replacing Indoor Unit . 2-107

HITACHI
2. SERVICING
2. 1 Outdoor Unit
- (2.1 Outdoor Unit)

it. WARNING
TURN OFF all power source switches.

2 . 1. 1 Removing Air Intake Grille Nets

(1) The intake air grille nets provided on the


back of the unit consist of two or four parts.
Remove the screws (12 pieces for
RAS-5FS and RAS-5FX, 12 x 2 pieces for
RAS-8FS, RAS-8FX, RAS-10FS and
RAS-10FX), then remove the nets by Phillips Screwdriver
pulling them up slightly.

~I
NOTE:
At first, remove screws fixing the motor clamp
holding the fan motor.
. Two Screws for RAS-5FS and RAS-5FX
. Four Screws for RAS-8FS, RAS-8FX,
RAS-10FS and RAS-10FX
Check to ensure that all screws are fixed
back correctly.

.-r----Screws to Fix Motor


Clamp

O[

HITACHI 2-1

L
r,
-'j-
(2.1 Outdoor Unit)
2.1 .2 Removing Front Service Panel
T

&. WARNING
TURN OFF all power source switches.

(1) Remove two screws attaching the valve


cover and remove the valve cover. The
front service cover is attached by three
screws. The left side front panel for
RAS-8FS, RAS-8FX, RAS-10FS and
RAS-1 0FX is attached by two screws as
shown below. Slightly lift the panels Phillips Screwdriver
upwards and remove them.

Upper Panel

.",

.,1


e L ~-t~ \

valvec~
~
e.
~ Screw for Left Side (I
Panel only

2-2 HITACHI
2.1.3 Removing Fan Guard Nets
_ y

c. -._----------- --

(2.1 Outdoor Unit)


", . - - -,. - -.-.-.'".-.,
.

& WARNING
TURN OFF all power source switches.

(1) This fan guard can be removed after dismantling the intake air grille nets and front service
panels. Remove the intake air grille nets according to the item, 2.1.1, "Removing Intake Air
Grille Nets".

(2) Remove the front service panel according to item 2.1.1 "Removing Front Service Panel".

(3) The fan guard is not attached by screws. The fan guard can be removed by lifting the front side
upwards and pulling it towards the front. .

Not Required

Quantity of Fan Guards:


1 No.: RAS-5FS and RAS-5FX
2 Nos.: RAS-8FS. RAS-8FX, RAS-10FS and RAS-10FX

Air Intake
Grille Net

I
.11'.
Fan Guard
.Net

HITACHI 2-3
-(2.1 Outdoor Unit)
2 . 1.4 Removing Compressor
r

& WARNING
TURN OFF all power source switches.

Do not expose the refrigeration cycle open to the atmosphere for a long period of time when
replacing a compressor to protect the cycle from mixing water or foreign particles. If exposed for a
long time. seal pipe ends using caps or tape.
Remove the caps for the compressor just before replacing the compressor.
Check to ensure each terminal No. when connecting compressor power wires. If incorrectly
connected, the compressor will fail due to reverse rotation.
(1) Remove the front service panel according item 2.1.2. Please note that removing the upper
panel is not required.
(2) Collect all the refrigerant by connecting a hose to the check joint at the suction side.

eRAS-5FS and RAS-5FX eRAS-8FX and RAS-10FX


Tool
Charge-Hose. Adjustable
Wrench or Spanner
.'
Check Joint
at Suction Side

Charge-Hose
Charge-Hose

Accumulator

eRAS-8FS and RAS-10FS

Check Joint Charge-Hose


at Suction Side

I
,

2-4 HITACHI
r, I (3) Removing Compressor and Wires
Disconnect the wires from the compressor after dismantling the terminal cover. Check
.....
(2.1 Outdoor Unit)

I the terminal Nos. and mark bands.


In case of models, RAS-8FS, RAS-8FX, RAS-10FS and RAS-10FX, terminals of MC1
I for the inverter driven compressor is located at rear side and terminals of MC2 for the
constant speed compressor at the front side respectively.
I
eRAS-5FS and RAS-5FX

I Terminal
Nos.

Mark
Band
e RAS-8FS, RAS-8FX,
RAS-10FS and RAS-10FX

" .(

Pull upper part


of the cover.
leonina!
Wires
Terminal Box for
Inverter-driven
compressor

Cover

NOTES: RearSide

1. Check to ensure that the faston terminal are


correctly connected. (A pulling"force of 2 kg
is required, If abnormality with faston Front
tenninals is detected, replace them with new Side
ones. Terminal Boxfor
Constant Speed
2. Fix the wirestightly. Compressor

,
HITACHI 2-5
I
A ...
T
"~l
(2.1 Outdoor Unit)

(4) Removing Oil Heater


Dismantle the sound-proof cover around the compressor. Disconnect the hook of the
spring for the oil heater located at the lower side of the compressor.

eRAS-5FS and RAS-5FX eRAS-8FS, RAS-8FX, RAS-l0FS and RAS-10FX

Inner Side of Sound-


Proof Cover

Spring

.~
Oil Heater
Remove the spring by
lengthening the spring.

(5) Removing Suction Gas Pipe


Remove the suction gas pipe using two spanners as Adjustable Wrench or
shown below. Tool
Spanner

eRAS-5FS and RAS-5FX eRAS-8FS. RAS-8FX, RAS-l0FS and RAS-l0FX


Two suction gas pipes are
located at the right and left.
Suction Gas
Pipe

Two
Spanners

2-6 HITACHI
. '
(6) Removing Discharge Gas Pipe
Remove the suction gas pipe
using two spanners as shown Tool
--
(2.1 Outdoor Unit)

Adjustable Wrench or
Spanner
below.

eRAS-5FS and RAS-5FX eRAS-BFS, RAS-BFX. RAS-10FS and RAS-10FX

Discharge --....
Suction Gas Gas Pipe
Pipe

Two
Spanners

(7) Removing Fixing Nuts for Compressor Adjustable Wrench


Remove the compressor after removing Tool or Spanner, Phillips
fixing nuts. Screwdriver

eRAS-5FS and RAS-5FX eRAS-BFS, RAS-8FX. RAS-10FS and RAS-10FX


Two suction gas pipes are
located at the right and left.
<DUft upwards
t @Pull toward Remove two fixing screws ------....
front side. for base frame 'U'

without Nut Special

\ ~Nut
I
Vibration
Absorbing.
Rubber

Front Side
~
I =-

~~ (v )
~~
, ~
./' ()
- C)C)
/
I
I
I)' ~ Pull outthecompressor toward the front side, and remove the
'! i]
vibration absorbing rubbers.

L HITACHI 2-7
_,'.'-
........ "."..~

(2.1 Outdoor Unit)


2.1 .5
=E"','_'~"

Removing High Pressure Switch, High Pressure Sensor and Low Pressure Sensor

(1) Dismantle the front service panel according to item 2.1.2. It is not required to dismantle the upper
panel.

(2) Collect all refrigerant from the low pressure side check joint when the high pressure switch is
removed. Use two spanners when the pressure sensors are removed.

Adjustable Wrench or
Tool Spanner and Charge Hose

eRAS-5FS eRAS-5FX
Low Pressure Low Pressure
Check Joint Check Joint

Check Jointlor Check Jointfor


Low Pressure Sensor Low Pressure
Sensor

High Pressure
Switch
High Pressure
Switch

Check Joint lor Check Jointlor


High Pressure Sensor High Pressure Sensor

eRAS-8FS and RAS-10FS eRAS-8FX and RAS-10FX

Check Joint for @ Check Jointlor


High Pressure Sensor Low Pressure Sensor
High Pressure Switch Low Pressure Check Joint

Check Joint for


Low Pressure Sensor Check Joint for
i High Pressure Sensor
. I
I
High Pressure
Switch

Low Pressure
Check Joint

2-8 HITACHI
II
.'
rI .r4811111
(2.1 Outdoor Unit)
a. Removing High Pressure Switch
CD Disconnect the faston terminals.
@ Remove the high pressure switch pipe connected to the discharge pipe by using a gas burner.

Gas Burner

NOTE: ~tonTerminal
Do not expose the refrigeration
cycle to the atmosphere for a
long period to avoid mixing of
water and foreign particles into
the refrigeration cycle.
If exposed for a long period, seal
the hole.
High Pressure
Switch ~,
,' ,
e"
e"
t
Discharge Gas


Brazing Part Pipe

b. Removing High Pressure Sensor (See the mark@on page 2-8.)


CD Remove the pipe of the high pressure sensor using two spanners. Firstly, remove it at the mark@.
@ Remove the connector for the high pressure sensor.
@ Remove the high pressure sensor after removing two fixing screws for the high pressure sensor.

Spanner or Adjustable Wrench


Tool Phillips Screwdriver

Electrical Wire
Box Connector
'J

High Pressure
----'lirr---;::==:::::::llrr---r.@~ Sensor

Two Spanners

Remove it from
the checkJ.!?int at
the mark@. If
the sensor side
is removed,
refrigerant will be
discharged.

HITACHI 2-9
_ .. ':.10\1.'.
__.,__ - ,_;x-m-/",M!t!-.-_~;;
(2.1 Outdoor Unit)

c. Removing Low Pressure Sensor (See the mark@ on page 2-8.)


(j)Remove the pipe of the low pressure sensor using two spanners. Firstly, remove it at the mark@ .
Remove the connector for low pressure sensor and earth wire.
@Remove the low pressure sensor after removing two fixing screws for the sensor fixing plate.

Spanner or Adjustable Wrench


Tool Phillips Screwdriver

Electrical
Box

Sensor Fixing
Plate

Low Pressure
sensor

The main refrigeration side pipe


is used with a check joint.
Remove the check joint of the
mark@firstly. If the sensor
side is removed, refrigerant will
be discharged.

2-10 HITACHI
!
I
h
2.1.6
. 1iIJjJ--
::;;;;:n=
(2.1 Outdoor Unit)
Removing Fusible Plug (only for Models, RAS-8FS, RAS-8FX, RAS-10FS and RAS-10FX)

(1) Dismantle the front service panel according to item 2.1.2. It is not required to dismantle the upper
I! .,
, panel and front-left panel.
(2) Collect all the refrigerant by connecting a hose to the check joint at the sunction side.
(3) Remove the fusible plug.

Tool Spanner or Adjustable Wrench

Fusible


Plug
~,
r

o
o

Example: for RAS-10FS

HITACHI 2-11
-(2.1 Outdoor Unit)
2 . 1 .7 Removing Electrical Parts

.& DANGER
Do not touch the electrical parts when the LEDS (red) on the inverter PCB (PCB3) is lit. since
the voltage is higher than 50V.

<D Apply silicon grease on the fin contacting surface when parts on the heat rejection fins, (such as
power transistor module, diode module, cement resistor and heat rejection fin overheating
protection thermostat) are replaced.
@ Identify each terminal No. with wire mark band symbol when reconnecting. If incorrectly
connected, malfunction or damage of electrical components will occur.
@ Insert the two wires(U &W) of the power source wires(U. V and W) through the sensor for the
current transformer, which is located on the heat rejection fin. If not correctly inserted,
overcurrent will flow or safety device may activate, resulting in damage of electrical components.
@ Pay attention that electrical wires are clamped by plates and electrical components when PCBs
are mounted.
As for the models, RAS-8FS, RAS-8FX, RAS-10FS and RAS-10FX, an electrical box for
control and the inverter(Main Box) and an electrical control box for the constant speed
compressor(Sub-Box) are used.

(1) Removing PCBs

a. Dismantle the front service panel according to item 2.1.2. It is not required to dismantle the upper
panel.

b. Remove the electrical box cover afler removing the two fixing screws. As for the sub-box cover for
the constant speed compressor, remove it after removing six fixing screws.

B Phillips Screwdriver

eRAS-5FS and RAS-5FX eRAS-8FS, RAS-8FX, RAS-10FS and RAS-10FX

Main Box Cover

i~I
.

2-12 HITACHI
c. PCBs
.1_
(2.1 Outdoor Unit)

There are S kinds of PCBs such as PCB1 for control, PCB2 for power source, PCB3 for inverter,
~I I PCB4 for DC power source and PCBS (FS only) for the fan controller.
When removing the PCB, disconnect all the connectors to the PCB and remove it by holding the
expanded part of the holder by long-nose pliers. When removing the PCB, hold it near the holder
and pull out it from the holder.

& WARNING
1. DO NOT TOUCH electrical components.
2. Pay attention not to apply a big force to PCB. If applied. the PCB will be faulty.

Other Electrical Components


Remove wires and replace electrical components accordingly. If required, open the sub-board (A)
(FS only) or remove the sub-board (B). For details, refer to the nex1 page.

Sub-Board(Al LED6(RED). Sub-Board(B)

/ I
ri . 1m
F====::"
/ I

e .~.. 5t
: 0 Em . 1"
~ pca, "'"" 0

j
~~
""
PCBS
=
~O=I
I hi
UG,-,;...,..,CI
QQ 'I eacILl:l.I@I",,,,
m ORe ~ 1

~ a: g ':;~ I...., I~ !
iii !.<JClClo '-.::, pca, I~ I
~
'I. =
e 0 e fiilliiI fiill

,r-------.,--' c =~ ~
~ I 0

!i:;jI PCB2 pca ..


r""""~II+r 1---: . 0 @

o '-

t
Example: for RAS-10FS

& WARNING
1. When reconnecting wires, identify terminal Nos. with wire mark band symbols. If incorrectly
connected, Malfunction will occur or electrical components may be damaged.
) 2. When replacing PCBs, check to ensure each setting of dip switches.

HITACHI 2-13
-(2.1 Outdoor Unit)

G) The sub-board (A) (FS only) will come out


Fixing Screws
for Sub-Board (Al
towards the front by removing the fixing
screw as shown below,
Pay attention not to scratch the wires,

The sub-boards(B) can be removed by


\ StJ b-Boa rd
181
removing the fixing screws as shown in Sub-Board
(AI
Hinges
the figure after opening the sub-board (A)
(FS only) and disconnecting wires to
"
the sub-board (B). When removing, pay
attention not to scratch the wires or components.

@ If required. remove other parts accordingly, Fixing Screws


for Sub-Board (B)

&. WARNING
1, DO NOT TOUCH electrical components.
2. Pay attention not to apply big force to PCB, If applied, the PCB will be faulty.

,"':======'",

"
t~8~
"1E.m .~ III
III
III
III
o
,.
19
.' 0

~
I

1].
J!.:

~ ~ ~
. .

tfl! .;-

CdE~
. .
= ,~ "
.. .

.. . . .
~ ..
-~---,,
,, .
e

<!lQ
-
e

e
0

-
0 " V

Example: for RAS-10FS

Figure after Opening Sub-Board (A) and Removing Sub-Board (B)

Lt. WARNING
1, When reconnecting wires. identify terminal Nos, with wire mark band symbols, If incorrectly
connected, Malfunction will occur or electrical components may be damaged.
2. When replacing PCBs, check to ensure each setting of dip switches. (

2-14 HITACHI
__ I
(2.1 Outdoor Unit)
d. Phase Protection Relay Board (PCB6)
The phase protection relay board, PCB6 is located inside of the sub-box only for models
RAS-SFS, RAS-SFX, RAS-10FS and RAS-10FX.
When removing this PCB, disconnect all the connectors to the PCB and remove it by holding the
expanded part of the holder by long-nose pliers. When removing the PCB, hold ~ near the holder
and pull out it from the holder.

Lt. WARNING
1. DO NOT TOUCH electrical components.
2. Pay attention not to apply a big force to PCB. If applied. the PCB will be fau~y.

Other Electrical Components


, Remove wires and replace electrical components accordingly.

I
I

I
~l. u 0

0


I-I!!!I
I I I I'

0
PCB6 Inl
liOl_
., I I'

! 8SA2
FFB2
CNC2

II m
OCR

i
I 0 0

~,D. . .
~ TJ\1
0

Sub-Box

Lt. WARNING
1. When reconnecting wires, identify terminal Nos. with wire mark band symbols. If incorrectly
connected, Malfunction will occur or electrical components may be damaged.

HITACHI 2-15
....
r
-(2.1 Outdoor Unit)
2 . 1 . 8 Removing Electrical Box

& DANGER
Do not touch the electrical parts when the LED6(red) on the inverter PCB(PCB3) is lit, since
the voltage is higher than 50V.

(1) Dismantle the front service panel according to item 2.1.2. It is not required to dismantle the upper
panel.

(2) Remove the electrical box cover after removing the two fixing screws.

(3) Remove the following connectors and connections.

Phillips Screwdriver &


Tool
. Long-nose Pliers

G)Main Box

Connector or
CN101 CN102 CN103
on PCB1

CN111 CN112 CN113 CN117


.'
Terminal
Device to be
Connected MV1 MV2 MVB Ps THM1 'THM7 Pd
(Symbol)

on PCB1 on PCB5 Connector for Devices


Connector or CN5
CN118 CN119 CN120 CN1 CN1 CN2
Terminal (CN4)
Device to be
RVR(2)
Connected THM3 THM5 THM6 "THM8 MOF1 'MOF2
(RVR1)


(Symbol)

Connector of Devices Terminal of Devices

Connector or Oil Heater


CN7 CN8 U,V,W C,H
Terminal DS1, DS2 DS1-4
Device to be
Connected SVA SVB CH1 'CH2 MC1 PSH
(Symbol)

NOTE:
- -
1. The mark ' indicates only for RAS-8FS, RAS-8FX, RAS-10FS and RAS-10FX.
2. The mark". indicates only for FS series.
3. Symbol in parentheses is only for FX series.

2-16 HITACHI
_~"7;',_."'.
(2.1 Outdoor Unit)
Terminal Board
Connector or Terminal L1, L2, L3, N CD,
Device to be Connected
TB1 TB2
(Symbol)

Sub-Box for RAS-8FS, RAS-8FX, RAS-10FS and RAS-10FX only

Terminal of Connector or
Terminal Board
Devices Devices
Connector or Terminal L1, L2, L3, N U,V,W CN9

Device to be Connected Main-Box


TB3 MC2
(Symbol)

(4) Removing Electrical Box


CD Put all wires (from the lower side of the electrical box) in the electrical box.
As for models, RAS-8FS, RAS-8FX, RAS-10FS and RAS-10FX, remove the sub-box after
removing six fixing screws for sub-box (for constant speed compressor).
@ Remove four fixing screws for the main-box.
@ By pushing the wires for thermistors and motors (which are inserted into the side plate hole of
the main box) little by little, and lifting the main-box to unhook the hook slowly, pull the
main-box towards the front. Pay attention not to drop the main-box since the weight is
approximately 30 kg.

eRAS-5FS and RAS-5FX eRAS-8FS, RAS-8FX, RAS-10FS and RAS-10FX

1-'
( .
& WARNING
1. When reconnecting wires, identify terminal Nos. with wire mark band symbols. If incorrectly
connected, Malfunction will occur or electrical components may be damaged.
2. When replacing PCBs, check to ensure each setting of dip switches.

I )

HITACHI 2-17
-
=:: ' '.'

(2.1 Outdoor Unit)


2.1 .9
__ -;,' __'>0'-"0-0

Removing Outdoor Fan

Lt WARNING
TURN OFF all power source switches.

(1) Remove the fan guard according to the ,item, 2.1.1, "Removing Air Intake Grille Nets".
(2) Remove the front service panel according to item 2.1.2, "Removing Front Service Panel".
(3) Remove the fan guard nets according to item 2.1.3, "Removing Fan Guard Nets".
(4) Remove the fans by removing the nuts and washers fixing the propeller fans onto the motor shafts.
If it is difficult to remove the fan, use a puller.

Tool Spanner, Adjustable

.j
Wrench or Puller

eRAS-5FS Flat Washer


and RAS-5FX

Propeller Fan

Motor Shaft

?
Nut

Flat Washer
Motor Shaft
e RAS-8FS, RAS-8FX,
RAS-10FS and RAS-10FX "<, ----.:::::"..-.-=-.1...
...
Propeller Fan

r -_ _

2-18 HITACHI
(5) Removing Wires
a. Remove the electrical box cover according to item 2.1.7, "Removing Electrical Parts".
-- (2.1 Outdoor Unit)

) b. Remove the sub-box according to the item, 2.1.8, "Removing Electrical Box".
c. Pull out wires through the wire hole at the side plate, after disconnecting the connectors for the
motors in the electrical box.
d. Cut the plastic tie fixing wires.
e. Remove the motors by removing four fixing screws for the motors.

NOTE:
When reassembling RAS-5FS or RAS-5FX, push in fan motor Phillips Screwdriver,
wiring between right side panel and right side partition by using Tool Adjustable Wrench,
a stick to insert the wiring into the hole of partition. Spanner, Cutter, Stick

When reassembling, firmly fix


RAS-5FS it by the motor clamp fixing
and RAS-5FX screws on the air intake side.

Fan Motor

Motor
Clamp

._-~
-= l
/
Pull the motor
upwards.

""''-----Connector

RAS-8FS, RAS-8FX,
RAS-10FS and RAS-l0FX

'I. Plastic
Tie
/

..."::.::.=-=.-----=-

"
\\ U
Plastic 'J Connector Plastic
Tie
looseness: 30mm Tie

NOTES:
1. Provide a looseness at the cord outlet of the motor when mounting the motor, as shown above.
2. Firmly fix the motor cord onto the motor clamp, not to touch the propeller fans.
3. Mounting Propeller Fan
Put and push the propeller fan by identifying theQ mark with the cut part of the motor shaft.
Firmly fix the propeller fan with a tightening torque of 50 to 70 kg-em after the head of the fan
shaft comes up. .
4. Connect the motor wires to the electrical connecting part at the lower part of the electrical box.
5. Firmly attach the fan guard net onto the shroud.

HITACHI 2-19
L
-(2.1 Outdoor Unit)
2 . 1 . 1 0 Removing Coil for Reversing Valve and Solenoid Valve

it. WARNING
TURN OFF all power source switches.

(1) Remove the fan guard according to the item, 2.1.1, "Removing Air Intake Grille Nets". It is not
required to dismantle the upper panel. As for models, RAS-8FS, RAS-8FX, RAS-10FS and
RAS-10FX, it is also not required to dismantle the front left side panel.
(2) Remove the cover of the electrical box (Main-Box) according to item 2.1.7, "Removing Electrical
Components".

Lt. DANGER
Do not touch the electrical parts when the LED6(red) on the inverter PCB(PCB3) is lit, since


the voltage is higher than 50V.

(3) Disconnect connector, CN5 which is connected to the reversing valve and connectors, CN7 and
CN8 connected to the solenoid valve.
(4) Remove the fixing screw for the solenoid valve.
(5) Remove the coil for the reversing valve and the solenoid valve, after removing the fixing screws.

Phillips Screwdriver
Tool Adjustable Wrench,
Spanner,


RAS-5FS and RAS-5FX RAS-8FS, RAS-8FX,

c;
F" PI I
RAS-10FSandRAS-10FX ,x,ng ae
for Solenoid
Valve
SolenoidValve Coil
tor Gas Bypass(SVA) i
~.
r
Solenoid Valve Coil I
lor Gas Bypass (SVB)
! -l; ....:,
~
/ l,,"~_~.
Solenoid Valve Coil
for Gas Bypass(SVA) for Gas Bypass(SVB)

2-20 HITACHI
2. 1 . 11 Removing Thermistor for Liquid Pipe
--(2.1 Outdoor Unit)

GI .& WARNING
TURN OFF all power source switches.

(1) Remove the fan guard according to the itsrn, 2.1.1, "Removing Air Intake Grille Nets".

(2) Remove the front service panel according to the item 2.1.2, "Removing Front Service Panel".

(3). Remove the electrical box cover according to the item, 2.1.7.

.& DANGER
Do not touch the electrical parts when the LED6(red) on the inverter PCB(PCB3) is lit, since
the voltage is higher than 50V.

(4) Remove the side cover panel, R after removing the twelve fiXing screws.

Phillips Screw
Tool
Driver

RAS-5FS and RAS-5FX

/!I~
N Side
CoverA

'I~
RAS-8FS, RAS-8FX,
RAS-1 OFS and RAS-10FX

p
/

Electrical
Box Cover
-. e
"7
I
N"~
'"'i.

I, l Side

~il
--""'--- Cover R
d
~ p

/
Electrical
Box Cover

HITACHI 2-21
- ~
(2.1 Outdoor Unit)

(5) Pull out the thermistor fixing plate from the pipe after detaching theCORK TAPE, and remove the
thermistor for the liquid pipe.

'<,


A--"'; ~
'~
---
Ii
.

I Ir,
.
h,
,
I rF"

\: I
'- I

'" ~;(J!
Thermistor
Fixing Plate Thermistor
r If.
1~ ~ ~~--~~T~''--.].>(~
t ~---bJ
CORK TAPE

-<
::::c=-\' g - -::
..

Seal around the


thermistor
using CORK TAPE.

I p,
Tc Themistor(THM8 for FS only):
l;,,,,"o',,, t~shal be '5kg-~.

(I

2-22 HITACHI
r
I
2.2 In-the-Ceiling Type (Models: RPI-O.8FS. RPI-1 FS and RPI-1.5FS)
2 . 2. 1 Removing Indoor Fan Motor
-
(2.2 In-the-Ceiling Type [O.a-1.5HP) )

&. WARNING
TURN OFF all power source switches.

Step Procedure Required Tool


1 Remove seven screws and projected lower cover. .Phillips Screwdriver
2 Remove the connector of the lead wire for the indoor fan motor.
3 Remove the lower part (j) of
the 2-division casing by T-
:::: I
pushing the four hooks.

J~
"":::

HOOk~ ~ J
Casing
.

4 Remove the holding band for .Phillips Screwdriver


motorand remove the motor
carefully.

= ~~I~8and
I
JJ
--r~~'" ~
= Fixing
Screw

I.

HITACHI 2-23
--
(2.2 In-the-Ceiling Type (O.8-1.5HP) )
2.2.2 Removing Thermistors for Liquid Piping and Gas Piping

Step Procedure Required Tool ('


1 Remove the drain pan according to item 2.2.6. "Removing Drain Pan". .Phillips Screwdriver
2 Remove the thermistors for .Phillips Screwdriver
the liquid piping and gas
piping attached to the liquid
piping and gas piping of the
heat exchanger.

2.2.3 Removing Printed Circuit Board (PCB)

Step
1
2 Remove the PCB.
The electrical box can be
removed according to the
following procedures.
Procedure
Remove the electrical box cover after removing one fixing screw.
Required Tool
. .Phillips Screwdriver
.Phillips Screwdriver
Printed Circuit Board .Long-nose Pliers
PCB(M)

(1) Remove the wiring cover PCB(P)
at the right side and
remove all the connectors
from inside.
(2) Remove the wiring cover
at the left side.
(3) Remove the connectors
from the PCBs.
(4) Remove two screws fixing
the electrical box.

2-24 HITACHI
2.2.4 Removing Drain-Up Mechanism
-
(2.2 In-the-Ceiling Type (O.8-1.5HP) )

Step Procedure Required Tool


1 Remove the screws (3 pes.) .Phillips Screwdriver
fixing the service cover and
remove the service cover.

2 Remove the screws (2 pes.)


fixing the drain-up motor and
remove the service cover.


3 Turn and draw out the
drain-up motor towards the
open space from the service
panel.

I. 4
5
Remove the hose band and remove the drain-up motor from the drain hose.
Remove the connector of the
lead wire for the drain-up
motor.

HITACHI 2-25
I
......
-====
(2.2 In-the-Ceiling Type (O.8-1.5HP) )

Step Procedure Required Tool

6 When reassembling the


(
drain-up motor, check to
ensure that the strainer is
attached to the suction hole
at the end of the drain-up
motor.

2 .2 . 5 Removing Float Switch

Step Procedure Required Tool


1 Remove the drain pan according to item "2.2.6 Removing of Drain Pan". .Phillips Screwdriver
.Bucket
2 Remove the connectors (FS) .Phillips Screwdriver
(1-Pin, 1 pc.) of the lead wire
for the float switch inside of
the wiring cover at the right
t3.
Cover .....
Connectors

~
side of the electrical box.

-,
,
~

\ I

3 Remove the service cover according to item "2.2.4 Removing of Drain-Up .Phillips Screwdriver
Mechanism".
4 Remove the screw (1 pc.) of .Phiilips Screwdriver

fJ
the plate fixing the float

Ilt~
switch and remove the float
switch.

-~~
2-26 HITACHI
2 .2 .6 Removing Drain Pan
-
(2.2 In-the-Ceiling Type (O.8-1.5HP) )

Step Procedure Required Tool


1 Remove the screws (17 pes.) fixing the lower covers and remove both of the .Phillips Screwdriver
lower covers.
2 Remove the screws (5 pes.) .Phillips Screwdriver
fixing the plate for water
protection.

~'.,

~)) . 3 Pull out the rubber bush of


the drain pan and discharge
the drain water left in the
drain pan. Check to ensure
that the drain hole is not
clogged by pricking with
.Sucket (about
5 liters content)

pencil or others.

4 Remove the screws (2 pes.) .Phillips Screwdriver


for the plates fixing the drain
pan at both sides and draw
out the drain pan downward.

HITACHI 2-27
-
(2.3 In-the-Ceiling Type (2, 2.5HPl )
2.3 In-the-Ceiling Type (Models: RPI-2FS and RPI-2.5FS)
2.3. 1 Removing Indoor Fan Motor

it. WARNING
TURN OFF all power source switches.

Step Procedure Required Tool


1 Remove the seven screws and remove the lower cover. .Phillips Screwdriver
At this time, remove the connector of the electric heater for condensate air
protection at the inside of the lower cover.
2 Remove the connector of the lead wire for the indoor fan motor.
3 Remove the lower part CD of
the 2-division casing by
pushing the four hooks. - _\
"OO.~~
. \.
Casing

4 Remove the holding band for .Phillips Screwdriver
the motor and remove the
motor carefu lIy. 0\ l. JJ
----.:f::m~ Band
-
~~v,

_ FiXing~
Screw ~
<

2 .3. 2 Removing Thermistors for Liquid Piping and Gas Piping

.'
Step Procedure Required Tool
1 Remove the drain pan according to item "2.3.5 Removing of Drain Pan". .Phillips Screwdriver
2 Remove the thermistors for .Phillips Screwdriver
the liquid piping and gas
,\~~
piping attached to the liquid
piping and gas piping of the
heat exchanger. i'
'\\~\J'N- IJ
-Cf~ .1/

2-28 HITACHI
r
i
I
2.3.3 Removing Printed Circuit Board (PCB)
-
(2.3 In-the-Ceiling Type (2, 2.5HP) )

Step Procedure Required Tool


1 Remove the screw (1 pc.) fixing the electrical box cover and remove the .Phillips Screwdriver
electrical box cover.
2 Remove the printed circuit Connectors .Long-nose Plier
board. (CN21. CN23, CN27, CN28 and CN32) .Phillips Screwdriver

The electrical box can be W'\


removed according to the
following procedures.
(1) Remove the screws
(4 pes.) fixing the wiring
cover plate and remove
ri;'
I
\[~/.

/
.'1
:
\
7
/

the connectors CN21 (for


I

\
,
I

indoor fan motor), CN23


(for float switch), CN27
(for freeze protection ~lF-
Wiring Cover Plate
thermistor), CN28 (for gas
piping thermistor) and PCB(M)
CN32 (for capacitor of PrinledCirc~P)
RPI.,.2.5FS). Board ......... .
(2) Remove the connectors
from the printed circuit
'"
i
.<f
..
.
boards. ~ Electrical Electrical

/f
Box Cover
(3) Remove the screws ~ Box
(4 pes.) fixing the electrical

~~":;;
box. 1..-' ;
(2; ;.

~
"~?,,~
~
" Screw-J
.

2 .3 . 4 Removing Float Switch

Step Procedure Required Tool


1 Remove the screws (2 pes.) fixing the wiring cover plate and remove the .Phillips Screwdriver
connector CN23 (for float switch).
2 Remove the screws (2 pes.) View from the Air Intake A~r Intake
.Phillips Screwdriver
of the plate fixing the float
switch and remove the plate . .r ,..L..~
w~h the float switch.
/ ~-

.:) 1-, 0

~
'-' rh'''-@
Electrical Box j //0\
.
W;,;ng Cov er PI':"! \
Screw Connector
PI,,, \

)'f..
<,
Float Svvitch

HITACHI 2-29
-
(2.3 In-the-Ceiling Type (2, 2.5HPJ )
2 . 3 . 5 Removing Drain Pan

(
Step Procedure Required Tool
1 Remove the screws (16 pcs.) .Phillips Screwdriver
fixing the lower covers and
remove both of the lower
;Fl. i lit
~r.fJf!JI.
--==,
7
covers. At this time. remove
the connector of the electric ~~ .n-0r.inPa"
heaterfor dew protection at
the inside of the lower cover.
y;
: }- Connector
/
ElectricHe'!er

i'::~::::V
Screw 1 \
Lower COver

2 Disconnect the drain piping and drain pan. .Bucket (about


It is necessary to remove the drain water left in the drain pan. 5 I~ers content)
3 Remove the screws (6 pes.) .Phillips Screwdriver
for fixing the drain pan and
draw out the drainpan
downward.

NOTE:
Be careful that the insulation
at the insideof the unit is not
broken. If the insulation at
the inside of the unit is
broken, remake the broken
insulation.

\
Screw
\\
Drain Pan Screw

2-30 HITACHI
I
I
2.4
2 .4. 1
4-Way Cassette Type
Removing Long Life Air Filter
--
(2.4 4-Way Cassette Type)

.&. WARNING
TURN OFF all power source switches.

(1) The long life filter is located inside of the intake air grille. Detach the filter after opening the intake
air grille. By pushing the knob in the arrow mark direction, the intake air grille can be opened.

(2) The filter can be removed from the intake air grille by supporting the lower side of the intake air
I grille and filter, and unhooking it from the extrusion part,

I
I

I!.
I
Upper Part of
Long Life Filter

Extruded
Part of Grille

Knob - _ _---,

-. Long Life!
Filter

Extruded
~partofGrille

~ Lower Part of
Long Lile Filter

HITACHI 2-31
-
( 2.4 4-Way Cassette Type)
2.4.2 Removing Intake Air Grille

(
Lt. WARNING
TURN OFF all power source switches,

1. By lifting the intake air grille at an angle of approximately 30 and releasing its chain, the intake air
grille can be removed by holding it upwards and then towards you. If the chain is released and the
angle is 90' , the intake air grille can not be removed.

Hold up by keeping
Ceiling Side the angle at 30'

Air Panel
Chain J
~ Approx. 30-40'
Intake Air
Grille

Incorrect Position

2 .4. 3 Removing Electrical Box Cover

&. WARNING
TURN OFF all power source switches.

1. By opening the intake air grille, the electrical box can be seen.
Remove two screws fixing the electrical box cover and remove the Phillips
Tool
cover. Screwdriver

~~)~l
.!~I~i
/1 i~7~
Intake Air Grille ~.. ~l
'-----il- \
Electrical Box Cover

2-32 HITACHI
-_.
2 .4 . 4 Removing Optional Air Panel
--
(2.4 4-Way Cassette Type)

& WARNING
TURN OFF all power source switches,

(1) By opening the intake air grille, the electrical box can be seen.
Remove two screws fixing the electrical box cover and remove the cover.
CD Disconnect the connector (6 Pins) for heater and louver motor.
@) Disconnect the connector (Red) for louver sensor.

Panel Terminal Board Panel Connector for


LOINer Sensor(RBd)

1";:-';;-;-\- , GEl EJ
ill GEl GEl
,,
raE~:{j
I
.,"
.
! ."
-.: ,
I .'.
,,'
"
,,
..
"
~.~''''''-_.'
~~
~~~ __t::_i---- .: 0

.---- ..... .:~.~--_.

Connector for Heater&


LOINer Motor(6Pins)

(2) Remove four screws fixing the optional air panel. ( Remove the fixing
screws by hooking on the hindge.) Remove the optional air panel after
unhooking the hindge onto the hooks at the two positions near the drain Phillips
pan. Screwdriver

i ~

I
I HITACHI 2-33
L
_.D.
(2.4 4-Way Cassette Type)
2.4.5 Removing Fan Runner and Fan Motor

(
it WARNING
TURN OFF all power source switches.

(1) Remove the intake air grille according to item 2.4.2, "Removing Intake Air Grille".

(2) Drawing Electrical Box


CD Remove the discharge air thermistor from the PCB.
Disconnect the connector of each wire.
@ Remove two fixing screws for the electrical box and pull the electrical box towards the front,
then the electrical box will turn with an angle of approximately 90'
Phillips
Tool Screwdriver

LElectrical Box

(3) Removing Bell-Mouth

CD Remove the four screws which fix the bell mouth onto Phillips
the drain pain and remove the bell-mouth. Screwdriver

2-34 HITACHI
-_.
.~
::, ::.-._.'.": \/. -.':, :
~ .. ... ' " ':"'"
..
" " -.

(2.4 4-Way Cassette Type)


(4) Removing Fan Runner and Fan Motor
The fan runner can be removed after removing the fixing screws for the fan runner, vibration
absorbing rubber, special washers and flat washers.
ill Remove the wiring connector for the fan motor and the earth wire.
Remove the motor after removing four fixing screws.

Phillips Screwdriver,
Tool Adjustable Wrench,
Spanner

Motor

, Earth
Terminal

Fan
Runner

NOTE:
Fix the fan runner with a fixing torque of approximately 30kg-cm for each
screw after mounting the vibration absorbing rubber onto the fan runner
when assembling.

HITACHI 2-35
-
(2.4 4-Way Cassette Type)
2. 4.6 Removing Printed Circuit Board (PCB)

it. WARNING (

TURN OFF all power source switches.

(1) Remove the intake air grille according to the item, 2.4.2 "Removing IntakeAir Grille".

(2) Remove the electrical box cover according to the item, 2.4.3, "Removing Electrical Box Cover".

(3) There are two printed circuit boards (PCBs) in the electrical box. Disconnect the connectors.
Each PCB is supported by four holders. Remove the PCBs by holding the expanded part of the
holders using long-nose pliers.

Tool Phillips Screwdriver,


Long-nose Plier

NOTE:
Do not touch electrical components on the PCBs.
If big force is appliedto the PCB, it will be faulty.

fI'

PCB

Electrical
Box Cover

2-36 HITACHI
2 .4. 7 Removing Float Switch
=;=.:
-
(2.4 4-Way Cassette Type)

.6 WARNING
TURN OFF all power source switches.

(1) Remove the intake air grille according to the item, 2.4.2, "Removing Intake Air Grille".
(2) Remove the bell-mouth and fan runner according to the item, 2.4.5, "Removing Fan Runner and
Fan Motor".
(3) Remove the service access cover after removing the three fixing screws near the pipes inside of
the indoor unit,

Tool Phillips Screwdriver

Service Access
Cover

(4) Removing Float Switch


Remove the float switch after removing the one fixing
screw from the fixing plate of the heat exchanger.
Tool Phillips Screwdriver

l
Float

- Switch

NOTE:
Carefully handle the floatswitch. Do not drop it on
the floor. If dropped, malfunolion may occur.
When mounting, do nol use a motor screwdriver.

HITACHI 2,..37
---
(2.4 4-Way Cassette Type)
2.4.8 Removing Drain-Up Mechanism

&. WARNING
TURN OFF all power source switches.

(1) Remove the service access cover near the pipes according to the item 2.4.7, "Removing Float
Switch".

(2) Remove the two screws(A) fixing the fixing plate for the drain-up pump after removing the wiring
connector. Loosen the fixing screw(B) remove the fixing plate from the fixing screw(B) and pull out
the drain-up mechanism.

Tool Phillips Screwdriver

Fixing Plate for


NOTE: Drain-Up Mechanism
Do not remove the screw (B).
If removed, the drain-up
mechanism will drop.
.~

,I
Fixing
Screw (B)

Fixing
___ Screw (A)
~

(3) Firstly support the drain-up mechanism by hand so as not to drop. Then remove the hose band
from the drain hose and then disconnect the drain hose and then remove.the drain-up mechanism. ('

Drain-Up Fixing Plate for


Mechanism :>--- Drain-Up Mechanism

2-38 HITACHI
r
._. ------- .
(2.4 4-Way Cassette Type)
- -... -----.-
.....
.. -

2.4.9 Removing Drain Pan

&. WARNING
TURN OFF all power source switches.

(1) Disconnect the connectors between indoorunit and outdoor unit, and in the electrical box after
opening the electrical box coveraccording to the item, 2.4.3, "Removing Electrical Box Cover".
(2) Remove the optional air panel according to the item, 2.4.4, "Removing Optional Air Panel".

(3) Remove the bell-mouth according to No.3 of item, 2.4.5, "Removing Indoor Fan and Fan Motor".

(4) Remove drain water

(5) Remove the drainpan after removing the four screws fixing
the drain pan ontothe indoorunit. Bucket
Tool (Approx. 5 liters)

Tool Phillips Screwdriver

NOTE:
Remove water on the drainpan by pulling out the
rubber plug. Checkto ensure that the water hole
is not clogged by pricking with a pencil.

l
HITACHI 2-39

L
-=:;::=;;;
,. -,""' -.' ,,"-'.-'/. ::

(2.4 4-Way Cassette Type)


2 .4. 10 Removing Thermistors for Liquid Pipe and Gas Pipe

(
it. WARNING
TURN OFF all power source switches.

(1) Remove the optional air panel according to the item, 2.4.4, "Removing Optional Air Panel".

(2) Remove the bell-mouth according to NO.3 of item, 2.4.5, "Removing Indoor Fan and Fan Motor".

(3) Remove the drain pan according to the item, 2.4.9, "Removing Drain Pan".

(4) Remove the CORK TAPE from the liquid pipe or gas pipe,
where the thermistor fixed by a fixing plate is located, and
then pull out the thermistor.
Tool Phillips Screwdriver


Liquid Pipe
Thermistor

Gas Pipe
Thermistor

Rxing Plate for


Thermistor
/ Thermistor
~ =0 /
A------n(~(r-~i~ 1,--'--- -,
, , =i=!- ~ .- :ocr --:~
L,-.-----.J \ )
1
CORK TAPE
/
_/_ Seal around the thermistor
with CORK TAPE.
NOTE
Fix the fixing plate es
shown above.

2-40 HITACHI
2 . 4. 1 1 Removing Automatic Louver Motor
'-'IM
(2.4 4-Way Cassette Type)

it. WARNING
TURN OFF all power source switches.

(1) Remove the optional air panel according to the item, 2.4.4, "Removing Optional Air Panel".

(2) Remove the motor cover after removing the two screws fixing the cover for the automatic louver
motor.

Tool Phillips Screwdriver

Motor Cover

t".

(3) Disconnect all the connectors connected to the motor. Remove the motor after removing the two
screws fixing it onto the air panel.

~. Tool Phillips Screwdriver

I
I r - - - Fixing Plate
for Motor
<i
\

V I
J
!
I, HITACHI 2-41
1
-.":~---J.,' - ,-':,_" ,,'

(2.4 4-Way Casselle Type)


'-'-d:

(4) Remove the crank after looseningthe fixing screw on the motor shaft.
1

Tool Phillips Screwdriver

r-----Fixing Screw

Crank.
(5) Remove the motor after removing the two fixing screws

Tool Phillips Screwdriver

~/
Motor

2-42 HITACHI
T ..111,-
(2.5 2-Way Cassette Type)
2 . 52-Way Casselle Type
2.5.1 Removing Long Life Filter

& WARNING
TURN OFF all power source switches.

(1) Open the service panel by supporting the hooked part upwards, and slide it towards the front
side.

CD Lift the hooked part . Slide it toward you.

Service Panel

(2) By sliding the air filter towards the fixed part and pulling downwards, remove the air filter .

Long Life Filter

Long Life Filter


"ROOM SIDE"
is indicated.

When installing, check to ensure that


the filter is correctly installed by
checking the "ROOM SIDE" mark.

HITACHI 2-43
-
(2.5 2-Way Cassette Type)
2 .5.2 Removing Optional Air Panel

(
it WARNING
TURN OFF all power source switches.

(1) Disconnect the wiring connectors after opening the service panel and service access cover.

Connector for Louver


Sensor (Red, 3 Pins)
Connector for Louver
Motor and Dew
Protection Heater (6P)

(2) Remove the four screws fixing the panel onto the indoor unit.

(3) Remove the panel by unhooking the hook of the suspension bracket.

Tool Phillips Screwdriver

Remove the panel from the


suspension bracket.

V~.!I.

Fixing Screw for Panel


(Each Two at Right and Left)

Perform this work by supporting


the panel by hand.

2-44 HITACHI
T
I
2.5.3 Removing Fan Motor
--
(2.5 2-Way Casselle Type)

I) WARNING
I TURN OFF all power source switches.

I (1) Remove the optional air panel according to the item, 2.5.2, "Removing Optional Air Panel".
(2) Remove the air distribution chamber after removing the six fixing screws.
I
Tool Phillips Screwdriver
I

I.
Air Distribution
Chamber
!\
Screw

(3) Disconnec1 the connec1or for the fan motor.

(4) Remove the fan motor mounted on the fixing plate. after removing the two fixing screws.

Tool Phillips Screwdriver

Fixing Plate for Motor

HITACHI 2-45
_I .,," '. - --~_'Z

(2.5 2-Way Cassette Type)

(5) Remove the casing by pushing the four extruded parts at the lower part of the casing, which
consists of two parts.

Extruded Part Casing

(6) Loosen the screw by a hexagon wrench. This work is not required for model RCD-l FS.

I Tool I Hexagon Wrench

Motor

Hexagon Wrench
Coupling

(7) Remove the motor, after removing the fixing band for the motor. Perform this work by supporting
the motor by hand.

Tool Phillips Screwdriver

,
\
\ Band
\
I
I
I
I
-~
i

Fixing
Screw

2-46 HITACHI
2.5.4 Removing Bearing (not required for Model RCD-1 FS)
.'....
(2.5 2-Way Cassette Type)

it WARNING
TURN OFF all power source switches.

(1) Remove the optional air panel according to the item, 2.5.2, "Removing Optional Air Panel".

(2) Remove the air distribution chamber according to NO.2 of the item, 2.5.3, "Removing Fan Motor".

(3) loosen the two fixing screws (M8 screw) fixing the bearings and shaft by a hexagon wrench.

(4) Remove the bearings.

Tool I Hexagon Wrench

,
I Tool Phillips Screwdriver

,'.
I

Fixing Screw
for Bearing
fl.
r V Fixing Screw for Shaft

lli ~Casing

\ Bearing

L
~~_&
~t
. ., '. W ~ ~.

~)Ii
I 2.5.5 Removing Coupling (not required for Model RCD-1 FS)

it WARNING
TURN OFF all power source switches.

(1) Remove the optional air panel according to the item, 2.5.2, "Removing Optional Air Panel".

(2) Remc;>ve the air distribution chamber according to No.2 of the item, 2.5.3, "Removing Fan Motor".

(3) Remove the bearing according to the item, 2.5.4, "Removing Bearing.

(4) Remove the coupling after removing the shaft and fan runner assembly.

,,
HITACHI 2-47

L
--
(2.5 2-Way Cassette Type)
2.5.6 Removing Printed Circuit Board (PCB)

& WARNING
TURN OFF all power source switches.

(1) Remove the service access cover after opening the service panel according to the item, 2.5.1,
"Removing Long Life Filter".

(2) Remove the cover after removing the one fixing screws on the electrical box in the unit.
(3) Disconnect the connector. Pull out the PCB by pinching the expanded part of the PCB holders by
long-nose plier.

Phillips Screwdriver,
Tool
Long-nose Plier

Terminal Board

Electrical
Box
/


NOTE:
Do not touch electrical components on the PCB.
Do not apply big force to the PCB. If applied, it will
be faulty.

2-48 HITACHI
2.5.7 Removing Drain Pan
.....
(2.5 2-Way Cassette Type)

& WARNING
TURN OFF all power source switches.

(1) Remove the optional air panel according to the item, 2.5.2, "Removing Optional Air Panel".
(2) Remove the air distribution chamber according to No.2 of the item, 2.5.3, "Removing Fan Motor".
(3) Remove the radiation sensor after removing the one fixing screw.

Tool Phillips Screwdriver


(4) Wipe off water on the drain pan after pulling out the rubber plug. Prick the drain hole wtth a pencil,
etc., to check whether or not water can flow.

Bucket
Tool
(Approx. 5 Itters)
:
I
I
,

!.
(5) Draw out the drain pan in a downward motion after removing the screws fixing both sides of the
drain pan.

Tool Phillips Screwdriver

1\ 'v:-.. ..
1/ .~'\ 0

~ Drain Pan

'~~
.r

""'-!
I
~
HITACHI 2-49
.....
-( 2.5 2-Way Cassette Type)
2.5.8 Removing Drain-Up Mechanism
T

(
it WARNING
TURN OFF all power source switches.

(1) Remove the optional air panel according to the item, 2.5.2, "Removing Optional Air Panel".
(2) Remove the service cover after removing three screws fixing the service cover on the unit.

Tool Phillips Screwdriver

Service Cover

(3) Remove the two screws fixing the drain-up motor.



Tool Phillips Screwdriver

(4) Pull the drain-up motor towards you from the service access hole by rotating it.
)

2-50 HITACHI
T
,
(5) Remove the drain hose from the drain-up motor after removing the hose band.

(6) Disconnect the connector for drain-up motor wiring .


--
(2.5 2-Way Cassette Type)

(7) When assembling the drain-up motor, check to ensure that a strainer is mounted at the inlet of the
drain-up motor.

HITACHI 2-51
--
(2:5 2-Way Cassette Type)
2.5.9 Removing Float Switch
r
& WARNING
TURN OFF all power source switches.

(1) Remove the optional air panel according to the item, 2.5.2, "Removing Optional Air Panel".
(2) Remove the air distribution chamber according to NO.2 of the item, 2.5.3, "Removing Fan Motor".
(3) Remove the drain pan according to the item, 2.5.7, "Removing Drain Pan".
(4) Remove the electrical box cover after removing the one fixing screw.
(5) Disconnect the connector for the wiring of the float switch.

(6) Remove Ihe service cover of the unit according 10 No.2 of the item 2.5.8, "Removing Drain-up
Mechanism".
(7) Remove the float switch after removing the one screw fixing the fixing plate to the float switch,

Tool Phillips Screwdriver

.',
Motor for
Drain-Up

o
(c
Fixing Plate for
Float Switch

~
.
'

\
Float Switch

2-52 HITACHI
2 . 5. 10 Removing Thermistors for Liquid and Gas Pipes

~l J &. WARNING
TURN OFF all power source switches.
I
(1) Remove the optional air panel according to the item, 2.5.2, "Removing Optional Air Panel".
(2) Remove the air distribution chamber according to No.2 of the item, 2.5.3, "Removing Fan Motor".

(3) Remove the drain pan according to the item, 2.5.7, "Removing Drain Pan".
(4) Remove the CORK TAPE fixing the thermistor after removing the fixing plate for the the thermistor.

Fixing Plate
for Thermistor
~ Thermistor

-ii
,---------~-, .:
(GB=~
, \ ,'
'-
7
CORK TAPE

:--~
j'__ 0,)
Seal the thermistor with
CORK TAPE.

Thermistor tor
Liquid Pipe
/

/
/
Thermistor for Gas Pipe

I .~
~', .'1
I
I HITACHI 2-53

L
-
=:.:::i:;;
: -.:, ." ': ._,_ :._ f.'-~ : ;'- - -,., ,..,!,

(2.5 2-Way Cassette Type)


--W:

2 . 5 . 1 1 Removing Motor for Automatic Louver


T

it. WARNING
TURN OFF all power source switches.

(1) Remove the optional air panel according to the item. 2.5.2, "Removing Optional Air Panel".
(2) Remove the motor cover after removing three fixing screws.
Tool Phillips Screwdriver

Motor Cover

.'
(3) Remove all the wiring connectors and terminals connected to the motor.

Motor for
Automatic Louver

Faston
Terminal

<,
Connector
for Wiring

(4) Remove the crank from the motor shaft after loosening the fixing screw.

Tool Phillips Screwdriver

Crank

NOTE: When reassembling, checkto ensure


thatthe crankis correctly positioned. If the
position is incorrect, the louver will malfunction.

2-54 HITACHI
. . . .11.
(2.5 2-Way Cassette Type)
(5) Remove the motor after removing two fixing screws.

Tool Phillips Screwdriver

- Screw

Louver Motor

VIe

)1.
I

HITACHI 2-55
L
--
(2.6 Wall Type)
2.6
2 .6 . 1
Wall Type
Removing Air Filter
(

& WARNING
TURN OFF all power source switches.

(1) Check to ensure that the horizontal deflector is positioning vertically. The deflector stops at the
vertical position when operation is stopped.

(2) Remove the air filter by pulling it downwards, as shown below.

Intake
Air Grille

e'
Air Filter ---f::~=;~1I-..

2 .6. 2 Removing Right Side Cover

& WARNING
TURN OFF all power source switches.

(1) Remove the right side cover by turning it slightly, after


removing three fixing screws as shown below.
Tool Phillips Screwdriver .~

Front Panel
RighI Side Rectangular Hole
Cover

NOTE:
Right Side
When reassembling,
Cover
check to ensure that
the stopper is
inserted into the
rectangular hole.

Stopper

The stopper is inserted into


the rectangular hole.

2-56 HITACHI
~.
(2.6 Wall Type)
2.6.3 Removing Front Panel

\
&. WARNING
TURN OFF all power source switches.

(1) Remove the right side cover according to the item, 2.6.2, "Removing Right Side Cover".
(2) Disconnect the automatic louver connector, CD and louver sensor connector, .

Tool Phillips Screwdriver

.:D z: Louver Sensor


Connector (Red) "- E3
Iiilrk B B 1iJ

j
CJ
e


ill
ill g \\
1iJ
Connector for
)) NOTE:
Automatic .....
I Louver Motor
I Refer to the item, 2.6.6 regarding
PCB
removing electrical box.

(3) Remove the caps at the air discharge side on the front panel and then remove screws from the
holes.

Tool Phillips Screwdriver

Panel Cap .

~. screw

i J,~--- ?~
~
!
:: . j
,~
,~
-~:
iii. NOTE:
Remove the cap firstly and !hen
Air Outlet . - remove the screws.

(4) Remove the front panel by pulling the lower side of the front panel slowly towards you and by
paying attention that the lower end of the drain pan does not touch the panel

Front Panel Stopper

Front Panel

Stopper

Rectangular Hole

HITACHI 2-57
.(fl.
(2.6 Wall Type)
2 .6 .4 Removing Motor for Automatic Louver

it WARNING
TURN OFF all power source switches.

(1) Remove the front panel according to the item, 2.3.2, "Removing Front Panel".
(2) Remove the AS cover after removing the one fixing screw and unhooking the extruded part.

(3) Remove the two screws fixing the mounting plate AS. Remove the shaft of the horizontal deflector
inserted into the arm by sliding the louver assembly horizontally, and then remove the louver
assembly from the front panel.

(4) Disconnect the connector connected to the motor.


(5) Loosen one screw fixing the arm AS. Remove the louver motor from the mounting plate AS after
removing the two screws fixing the louver motor.

Mounting
Plate AS
r---_
Tool Phillips Screwdriver

.'
Wiring for Automatic
Louver Motor

~.
~
\~ Screw

Automatic
Louver Motor

Hook


~Screw
AS Cover

Wiring for
Louver Sensor
Bearing 1
Arm
Automatic
' - - - - Connecting Louver
Rod Assembly

'----ArmAS

2-58 HITACHI
........
.....,....,..
I

2.6.5 Removing Thermistors for Liquid Pipe and Gas Pipe


_ ...
(2.6 Wall Type)

&. WARNING
TURN OFF all power source switches.

(1) Remove the right side cover according to the item, 2.6.2, "Removing Right Side Cover".
(2) Remove the front panel according to the item, 2.6.3, "Removing Front Panel".
(3) Remove the black connector for the liquid pipe thermistor and the yellow connector for the gas pipe
thermistor connected to the PCB(M) in the electrical box.

Connector for Liquid Indoor Unit PCB(M)


Pipe Thermistor ___
(THM5) '-~~~~::;;-::::::::::-;:::::::::;--=-::=.---1

Connector for
.>:
Gas Pipe Thermistor
(THM7)

(4) Remove the CORK TAPE and pull out the thermistors after removing the fixing plate for the
thermistor.

Fixing Plate for


Intake Air Temp. Electrical Box
Thermistor
Thennistor

Liquid Pipe
Thermistor

Gas Pipe Thennistor

Fixing
Plate lor
Thermistor

CORK TAPE

I NOTE:
seer around Thermistor
I Discharge Air with CORK TAPE.

I ~ Temp. Thermistor Mount the fixing plateas


shown above.

HITACHI 2-59
_
(2.6 Wall Type)
2.6.6 Removing Electrical Box Cover and PCB

&. WARNING
TURN OFF all power source switches.

(1) Remove the right side cover according to the item, 2.6.2, "Removing Right Side Cover".
(2) Remove the screw for the electrical box cover.

(3) The PCB (low voltage) is supported by the holder. The holder can be opened by removing the
close/open screw fixing the holder. High voltage PCB is located at the bottom side.

Tool Phillips Screwdriver

lnssrted Tj~[~7":;:--':~::::=
Close/Open Screw

Electrical
Box Cover
.,).I
. I

Slide

Screw ~

L
Electrical
Boi< ----'--'

(4) Removing the Low Voltage PCB.


Remove the low voltage PCB by pushing the
PCB to the left side and bending the holder, as
<D Push to this direction.

il

- I
Low Vonage PCB
I

\
i1Lr:J Pull up.
.1
shown in the right figure. t
Holding Plate
=
(5) Removing the High Voltage PCB.
Bend the holder (4 pieces) supporting the PCB
I[ \
~J
- ---< ELtl
towards the arrow mark direction and pull the Bend It.

PCB upwards. Removing Low Voltage PCB

NOTE: Do not touch electrical components. Do Holder

\~~
not apply big force to the PCB. If applied, the High Voltage
PCB
PCB will be faulty. -t/
lI--j)
., \'DV
<
<f

Removing High Voltage PCB

2-60 HITACHI
2 .6 . 7 Removing Drain Pan
..- (2.6 Wall Type)

G ,
, .& WARNING
TURN OFF all power source switches.

I (1) Remove the right side cover according to the item, 2.6.2, "Removing Right Side Cover".
(2) Remove the front panel according to the item, 2.6.3, "Removing Front Panel".
(3) Separate the drain pipe from the drain hose.
(4) Pull out the drain pan by drawing it towards you after removing two screws fixing the drain pan at
the right and left.

Phillips Screwdriver,
Tool Bucket
(Approx. 5 liters)

~.
Electrical Box

Heat Exchanger

II.
Screw

NOTE:
Remove drain on the drain pan by pulling out the
rubber plug. Check to ensure that water can flow
through the hole by pricking the hole w~h a pencil.

HITACHI 2-61
(
.2.
.
-~~
6 Wall Type) . Heat Exchanger ana. Fan Motor
6 8 Removing
1"'"
I

2. . & WARNING

Body Assembly

Heater
Partition u u

Bearing
Support
I Side
Panell

Partition

Dew Protection

I
Fan Runner
~OO--:t (f
Bearing

Band

Heat Exchanger ~PiPeBand

2-62 HITACHI
r Removing Heat Exchanger
_..-(2.6 Wall Type)

it. WARNING
TURN OFF all power source switches.

(1 ) Remove the right side cover according to the item, 2.6.2, "Removing Right Side Cover".
(2) Remove the front panel according to the item, 2.6.3, "Removing Front Panel".
(3) Remove the drain pan according to the item, 2.6.4, "Removing Drain Pan".
(4) Collect refrigerant from the low pressure check joint in the outdoor unit.
(5) Remove the flare-nuts of refrigerant
piping (liquid and gas side) from the Removing each Thermistor and Connector (Item?)
indoor unit. Discharge AirTemp. Thermistor

(6) Remove the fixing band for refrigerant Discharge AirTemp. Thermistor
pipes after removing the one fixing
screw.
/ c
,:
(?) Disconnect the connectors to the
discharge air temperature thermistor,
intake air temperature thermistor, freeze
protection thermistor and gas pipe
thermistor which are connected to the
:====================l
Intake Air Temp. Thermistor
Intake AirTemp. Thermistor
* THM4
PCB(M)

low voltage PCB(M) in the electrical box.


Take out wires for the discharge air
temperature thermistor, intake air
o
temperature thermistor, freeze protection
THM3
thermistor and gas pipe thermistor from
the electrical box. PCB(M)

(8) Remove each two screws at the right Freeze


Protection
and left, fixing the heat exchanger at the Thermistor

)11. both sides.


(9) Draw out the heat exchanger by pushing
Fixing
Plate for
Thermistor
it upwards.

I Tool Phillips Screwdriver gas pipe thermistor


PCB(M)

Removing Heat Exchanger


for Items 5, 6, 8 and 9

Heat
Exchanger

Screws
(each two at
Right and Left)
Pipe Band

Flare-Nut
Screw

HITACHI 2-63
-
(2.6 Wall Type)
Removing Fan and Fan Motor (after Removing Heat Exchanger)

(
&. WARNING
TURN OFF all power source switches.

Remove the heat exchanger according to the item, "Removing Heat Exchanger".

(10) Draw out the bearing support after removing the two fixing screws.
(11) Remove the female fixing screw( '" 6) fixing the fan runner on the motor shaft by a hexagon wrench.

(12) Remove the side plate L by changing the position to the left side after removing four screws fixing
t~e side plate L onto the body.
(13) Remove the fan shaft from the fan runner by pulling out it to the left side.
(14) Remove the partition after removing the four screws fixing the partition onto the body.

(15) Disconnect the motor wiring connectors (6P and 3P connectors in the electrical box).
(16) Remove the fan motor after removing the screw (each one, totally 2 pieces) fixing the motor fixing
band for the motor.

Tool
Phillips Screwdriver,

Hexagon Wrench

,
I ' - .. u u
Bearing J.
__-'-, L.-.. _
Support
Side
Panel L

~Partition
Fan Motor
Dew Protection

Bearing
Fixing Screw
...for Fan Motor
j lighlening Band
Torque: 50kg-cm

2-64 HITACHI
'
...........
x ~ ~,_,_,,',___ .
_.:.-.
'<w._;._.'_ .

(2.7 Floor Type)


2.7 Floor Type
2 .7 . 1 Removing Intake Air Grille

& WARNING
TURN OFF all power source switches.

(1) By pushing the knob at both sides of the intake air grille towards the arrow mark direction, the grille
can be opened with an angle of 30'

(2) Remove it from the hinged part.

2 .7 . 2 Removing Air Filter

& WARNING
TURN OFF all power source switches.

(1) The air filter is located at the inner side of the intake air grille. Remove all the intake air grilles.

lJe (2) Remove the air filter by pulling the knob of the air fi~er.

I} ~

HITACHI 2-65
L
. . .KG
(2.7 Floor Type)
2 .7 .3 Removing Discharge Air Grille

.& WARNING
TURN OFF all power source switches.

(1) The discharge air grilles are mounted on the top by using a guide-rail.
(2) By opening the top cover and sliding the discharge air grilles, the grilles can be removed.

Discharge
Air Grille


2 . 7 .4 Removing Front Cover

.& WARNING
TURN OFF all power source swttches.

(1) Remove the air filter according to the item, 2.7.2, "Removing Air Filter".

(2) Remove the front cover from the slit after removing four fixing screws at the lower part and pulling it
out downwards.

Tool Phillips Screwdriver



t- Front
Cover

<,
~SCr8w

2-66 HITACHI
2.7.5 Removing Fan Motor
-- (2.7 Floor Type)

it. WARNING
TURN OFF all power source switches.

(1) Remove the intake air grille according to the item, 2.7.1, "Removing Intake Air Grille".
(2) Remove the air filter according to the itsrn, 2.7.2, "Removing Air Filter".
(3) Remove the front cover according to the item, 2.7.4, "Removing Front Cover".
(4) Remove the mounting plate for the fan motor after removing four fixing screws.

Tool Phillips Screwdriver

l'I'

~ Screw

(5) Disconnect the wiring connector for the fan motor. Remove the wiring assembly and connector.

Connector
o

\
Wiring Assembly
\ \ /

~)I! )

l HITACHI 2-67
......
(2.7 Floor Type)
(6) Remove the casing CD by pushing the hook part at the four
positions towards the inner side. Tool Phillips Screwdriver

CD
I

Hook
Casing

(7) Loosen the screw by a hexagon wrench.

I ITool Hexagon Wrench I."


Motor

, ; ~

1\
To Loosen '.'.~ _
,;';? Hexagon Wrench

(8) Remove the fan motor by sliding it backwards after


removing the fixing plate. Pay attention not to drop it. Tool Phillips Screwdriver

.
;;:,

Band

==---~

2-68 HITACHI
-_.
2.7.6 Removing Printed Circuit Board (PCB)
_...(2.7 Floor Type)

&. WARNING
TURN OFF all power source switches.

(1) Remove the intake air grille according to the item, 2.7.1, "Removing Intake Air Grille".
(2) Remove the air filter according to the item, 2.7.2, "Removing Air Filter".
(3) Remove the front cover according to the item, 2.7.4, "Removing Front Cover".
(4) The side cover can be removed by removing the three fixing screws and pulling ~ downwards.

Tool Phillips Screwdriver

Side Panel --~-/..

Screw ~
q:P

(5) Remove the electrical box cover after removing the two fixing screws.

Tool Phillips Screwdriver

Electrical
BoxCover _ _

/
Screw

0'1, ~

!
HITACHI 2-69
L
811,_
(2.7 Floor Type)
(6) The electrical box can be turned up to an angle of 90 by removing the two fixing screws and
unhooking the hook at the rear side of the electrical box.
(7) The PCB is supported by the four holders. Pull out the PCB from the PCB hole by pushing the
expanded part of the holder using long-nose pliers and putting a finger near the hole of the PCB.

Phillips Screwdriver,
Tool
Long-nose Pliers

@) @
(-rr======11 G ~

0111

PCB Rear Side


of Unit
Front Side
of Unit

I
Expanded Part "
of Holder 0111

~\ ) J
PCB J
~~ (Low Voltage) l
UIO
0 I,
~~O

nn
J
0
0 ~
illJl-
View from Left Side of Unit

NOTES: I~O
1/
"
"

l-

1. Do not touch electrical components. Do not I\.
apply big force to the PCB. If applied, the PCB
will be faulty.
I~I~
2. When reassembling, check to ensure that each rzs-.
.;"
terminal is correctly connected by referring to
the wire marks and terminal codes. If incorrectly
connected, malfunction or damage of electrical
parts will occur.
View from Front Side of Unit

2-70 HITACHI
T
I
2.7.7 Removing Thermistors for Liquid Pipe and Gas Pipe
.-
;:::, ----:::z:J
(2.7 Floor Type)

& WARNING
TURN OFF all power source switches.

(1) Remove the intake air grille according to the item, 2.7.1, "Removing Intake Air Grille".
(2) Remove the air filter according to the item, 2.7.2, "Removing Air Filter".
(3) Remove the front cover according to the item, 2.7.4, "Removing Front Cover".
(4) Remove the side cover after removing three fixing screws.

Side Cover

Il

(5) Remove the piping cover after removing the two fixing screws for the partition plate and the four
fixing screws for piping cover.

//1 1: III

~
!J!!!fi!3
1 I~/ i: 111:1---+-1---_ Piping Cover
II!
~ ~/IJ!I:;
/ / I
III,','

------
~ // "
~ ':
--IZ
!---~
:
Partition / >?'
Plate
/
Screw

~II )
!
HITACHI 2-71

L
- ~
(2.7 Floor Type)
(6) Remove CORK TAPE and pull out the thermistor after removing the fixing plate for the thermistors.

Thermistor
for Gas Pipe

Fixing Plate
for Thermistor
CORK
-
~
-4--------~r-(
Thermistor

-"-r4ve ('

~
TAPE

.1
'<-----r----- ' c
/ Liquid Pipe
Cork Tape Thermistor
=~--~
Seal thsihermii: ')
with CORK TAPE.
Mount it as shown
above.

2-72 HITACHI
2.8

2 .8. 1
Floor Concealed Type

Removing Air Filter


-
(2.8 Floor Concealed Type)

Lt. WARNING
TURN OFF all power source switches.

(1) The air filter is located at the inner upper part of the inlet.
(2) Remove the air filter by pulling the center knob and bending the filter.

II
I
~"I.
Air Filter

2. 8 . 2 Removing Front Covers

Lt. WARNING
TURN OFF all power source switches.

(1) Remove the air filter according to the item, 2.8.1, "Removing Air Fitter".
(2) Remove the front lower cover after removing the ten screws at the lower part of the front cover.

Tool Phillips Screwdriver


~I

Lower Front
Cover

'i
HITACHI 2-73
-
( 2.8 Floor Concealed Type)
(3) Remove the front upper cover after removing the eleven fixing screws.

(
Tool Phillips Screwdriver

Screw

Front Upper

Cover

2-74 HITACHI
2.8.3 Removing Fan Motor
--
(2.8 Floor Concealed Type)

& WARNING
TURN OFF all power source switches.

(1) Remove the air filler according to the item, 2.8.1, "Removing Air Filter".
(2) Remove the front covers according to the item, 2.8.2, "Removing Front Covers".

(3) Remove the fan motor as same as indicated in NO.4 to


Phillips Screwdriver,
Tool
NO.8 of the item, 2.7.5. Hexagon Wrench

2 .8.4 Removing Printed Circuit Board (PCB)

& WARNING
TURN OFF all power source switches.

(1) Remove the front covers according to the item, 2.8.2, "Removing Front Covers".

(2) Remove the PCBs as same as indicated in NO.5 to NO.7 of Phillips Screwdriver,
Tool
the item, 2.7.6. Pincers

2.8.5 Removing Thermistors for Liquid Pipe and Gas Pipe

& WARNING
TURN OFF allpower source switches.
II ..
(1) Remove the air filter according to the item, 2.8.1, "Removing Air Filter".
(2) Remove the front covers according to the item, 2.8.2, "Removing Front Covers".
(3) Remove the thermistor as same as indicated in No.4 to
Tool Phillips Screwdriver
No.6 of the item, 2.7.7.

HITACHI 2-75
-(2.9 Ceiling Type)
2.9 Ceiling Type
2 .9. 1 Removing Air Filter
T

.&. WARNING
TURN OFF all power source switches.

(1) The air filter is located inside of the intake air grille. Remove the air filter after opening the intake
air grilles.

<D Push the knobs of the intake air grille


backwards.
@ Open the intake air grille downwards.
@ By lifting the knob upwards. the filter
can be removed.

2 .9. 2 Removing Side Cover

.&. WARNING
TURN OFF all power source switches.

.1
(1) Pull the side cover towards you.
(2) Unhook the hook at the lower part of the side cover.
(3) Lift it upwards.

Hook at Upper Part


Hook at Front Part of Side Cover (2 Nos.)
of Side Cover

Hook at Lower Part


Side Cover of Side Cover (2 Nos.)

2-76 HITACHI
.......
T q."18iIIIII.
. 10&1 .. .
[M.

(2.9 Ceiling Type)


I 2 .9 . 3 Removing Discharge Air Grille

I, &. WARNING
TURN OFF all power source switches.
I
I (1) Remove the side covers according to the item, 2.9.2, "Removing Side Cover".

(2) Remove the crank assembly mounted on the right side


I shaft of the air deflector.
Tool Phillips Screwdriver

Air Deflector Swing Motor

te (3) Disconnect the connector for the photo-interrupter at the left side.

Connector for Sensor Cover


Photo-Interrupter ~

o Air Deflection

Lower Cover /

(4) Remove the sensor cover.

Sensor -~'-J---C="'
Cover Air Deflector

e
Lower Cover

(5) Pull out the deflector including the bearing after removing
Tool Phillips Screwdriver
the four fixing screws at the right and left.

Fixing

T
r:: Bearing
Air
Deflection

~ l~!':."",

~
~ ~
.,All
~ t- Air
Deflection
I

HITACHI 2-77
L
- ......
=:;.;::::
.::.'. - "~ ',' -:": :~-- %
I

(2.9 Ceiling Type)


2.9.4 Removing Fan Motor

&. WARNING
TURN OFF all power source switches.

(1) Open the intake air grille according to the item, 2.9.1, "Removing Air Filler".
(2) Remove the stay at the air inlet.

Tool Phillips Screwdriver

Intake
Air Panel Stay
,,


(3) Disconnect the connector for the indoor fan motor.

Wiring Cover
-
(4) Hook the electrical box on the lower frame after removing the screws fiXing the electrical box.

Tool Phillips Screwdriver

Lower Frame

NOTE: (
During this work, support the electrical
box by handsnot to drop it.

2-78 HITACHI
T
(7) Remove the casing CD by pushing the hook part at the four
positions towards the inner side.
..-(2.9 Ceiling Type)

Tool Phillips Screwdriver

(i)

\J It=::::::
!

I
I Hook'
[
i Casing
I
(6) Loosen the screws by a hexagon wrench.

I I Tool I Hexagon Wrench

I
I
Motor

Hexagon Wrench

Coupling

(8) Remove the fan motor by sliding it backwards after


removing the fixing band. Pay attention not to drop ~.
Tool Phillips Screwdriver

Fixing Band

Fixing Screw

HITACHI 2-79
L
_ .
'c'; . ,,;," " " w
.>m: ' '.C. __'"
I
(2.9 Ceiling Type)
2 .9 .5 Removing Bearing

(
&. WARNING
TURN OFF all power source switches.

(1) Remove the side covers according to the item, 2.9,1, "Removing Side Cover".

(2) Loosen the two screws fixing the bearing and shaft by a hexagon wrench.

(3) Remove the bearing after removing two fixing screws (M8).

Hexagon Wrench,
Tool
Phillips Screwdriver

Fixing Screw
for Bearing
Fixing Screw for Shaft

------ Casing
Bearing

Air Filter

2 .9. 6 Removing Coupling

&. WARNING
TURN OFF all power source switches,

(1) Remove the side covers according to the item, 2.9,1, "Removing Air Filter".

(2) Separate the casing into two pieces according to the item, 2,9.4, "Removing Fan Motor", Loosen
the screw for the coupling by a hexagon wrench.

(3) Remove the M8 screw fixing the bearing according to the item, 2.9.5, "Removing Bearing".

(4) Remove the coupling after removing the shaft and fan runner assembly,

2-80 HITACHI
2 .9. 7 Removing Automatic Louver Motor
......
(2.9 Ceiling Type)

it. WARNING
TURN OFF all power source switches.

(1) Remove the side covers according to the item, 2.9.2, "Removing Side Cover".

(2) Remove the crank assembly after removing the two M3 screws. Pay attention not to damage
the crank assembly.
(3) Disconnect the connector for the louver motor.

(4) Remove the motor after removing the two fixing screws.
Tool Phillips Screwdriver

Fixing Screw

f.. '.
M3Screw ~ Crank Assembly

~~~
~,#~.t.'

.
~
I
Louver Motor

Discharge
Air Louver
Lower

NOTE:
When assembling, tighten the two screws with a
torque of 3.5kg-cm using a torque wrench.
When the crank assembly is disassembled, the
louver will be positioned upside down due to its
weight. Therefore, when assembling, set the
louver correctly as it was.
I Tool I Torque Wrench

, HITACHI 2-81
i
........
--
(2.9 Ceiling Type)
2.9.8 Troubleshooting on Automatic Louver

Thelouver does not tum.


The louverstopsquickly. (
(;?) Check connection
ofconnector.
Checkthe following connectors are correetJy
connected.
(f) louver sensorconnector on PCB
Photo-lnternJpter Connector (Fig.1) Sensor
@ PCB Connector for Louver Motor (PCNS) Cover
@ Mediate Connector Connected to @

@ Check to ensure thatthe ex1nJded part


of the sensor cover is firmly inserted.
(Fig. 1)

@ Checkto ensure thatthe sensor flap is Lower Cover


correctly mounted on theshaft. (Fig. 2)

Fig. 1 Connector for Photo-Interrupter


Cl> Checkto ensure that the sensor flap can
cross thephoto-interrupter.

(Measure it ina KO range.)

, No
@ Check
sensor flap.

Inse~rt-===::::::;I-~_-!:==:::~_J
Replace
photo-interrupter.

,
Replace
NO

Sensor
Flap
Fig. 2 Sensor Rap

5
Shaft

,
louver motor.
No

Replace PCB.

, No

Replace PCB. I----<(])--_


Check the distance,

,
fJ) is within 22.S--27.5mm.

No Fig.. 3 Sensor Rap and Photo-Interrupter

NOTE:
Utilization of lhe automatic louver mechanism is
Replace remote checked by the PCB within one minute after power
control switch. supply.
Check the function after power supply when
END repairing work is completed.

2-82 HITACHI
~

I
I 11II'''111
(2.9 Ceiling Type)
2.9.9 Removing Thermistors for Liquid Pipe and Gas Pipe

(
& WARNING
TURN OFF all power source switches.

(1) Remove the right and left side covers according to the item, 2.9.2, "Removing Side Cover".
(2) Remove the lower cover.

Tool Phillips Screwdriver

Lower Cover

(3) Remove the drain pan after disconnecting the drain hose.

Drain Hose Drain Pan

(4) Remove the thermistors for the liquid pipe and gas pipe.

Side Cover Fixing Plate


Thermistor for Thermistor
for Gas Pipe ~"'1:-~~J[ Thermistor

'- T .' r;:;;---"l


CORK TAPE =i.. 3 ... C;
Mount the fixing plate
7--,--".1
..
\))
for the thermistor as Seal the thermistor With
I shown above. CORK TAPE.
~I !
I
I HITACHI 2-83
l
-- - '.=""-.---,.,.---'''''''
(2.9 Ceiling Type)
2 . 9. 1 a Removing Printed Circuit Board (PCB)

(
& WARNING
TURN OFF all power source switches.

(1) Openthe intake air panel according to the item, 2.9.1, "Removing Air Filter".
(2) Disconnect the wiring connector for the fan motor.
(3) Turnthe electricalbox according to No.4 of the item, 2.9.4, "Removing Fan Motor" and hook the
electrical box at the lower frame.
(4) Remove the cover after removing the two screws fixings electrical box cover.

Tool Phillips Screwdriver

- \~ ",,~
=~~
NOTE:
~~
~ \ ') Cover
During this work, support the
electrical box not to drop it.

(5) There are two PCBs. The PCB is supported by the four holders. Pinch the expanded part of the
holderwith long-nose pliers.

Tool I Long-nose Pliers

Expanded Part
PCB
of Holder

t~\JB NOTE:
Do not touch the electrical components. Do not apply
big force to the PCB. If applied, the PCB will be faulty.

2-84 HITACHI
~

I 1111.'1.
(2.10 Cleaning Indoor Unit's Heat Exchanger)
I 2 . 1 0 Cleaning Indoor Unit's Heat Exchanger

~
2. 1 0 . 1 Required Tools for Cleaning (for All Indoor Units)
I
\
No. Remark No. Tool Remark

I 1 Cleaning Water Pump 2 Water Tank Approx. 18 liters


Clean Water
A waler pump equipped
I with a lank is
3 Nozzle
recommended. 4 Brush If the heat exchanger is heavily
I

~
clogged with dust, remove it
with this brush. The length of
brush should be 25-35mm.

5 Hose for Water Select a hose according to site


Pan requirements.


6 Bucket 2 Nos. for 5.liters
,.,
7 Phillips 1 No.
Screwdriver
8 Pincers 1 No.
9 Adjustable 1 No.
Wrench
Megohm Tester 500V
Cleaning Agent Select a neutral type cleaning
agent.
12 Spray To spray cleaning water.
13 Tape with To fix the vinyl sheet to protect
Adhesive the room from cleaning water.
14 Rope 1m, 4 Pieces
15 Vinyl Sheet Select a vinyl sheet with
O.5mm thickness ..

16 Gloves

HITACHI 2-85
-
( 2.10 Cleaning Indoor Unit's Heat Exchanger)

No. Remark
17 Cleaning Water Collector
e In-the-Ceiling Type
e 2-Way Casselle Type
eWallType Bar
e Ceiling Type
Insert )
the bar.

Insert
the bar.

Inner Side of r/J 120 hole should


Hose--lJ be covered with felt sheet to
insert the spray nozzle.

18 Cleaning Water Collector K~


e 4-Way Casselle Type

No Part Material Remarks Q'ty


Tent with
1 Vinyl Chloride Sheet 1t, with Handling Cover 0.3t 1
Handling Cover
2 Support A Stainless r/J10 8
3 Sheet A Vinyl Chloride Sheet tt, with Support B and Magnet 1
4 Sheet B Vinyl Chloride Sheet 11, w~h Support B and Magnet 1
5 SheetC Vinyl Chloride Sheet 11, with Support B and Magnet 1
6 Sheet D Vinyl Chloride Sheet 11, with Support B and Magnet 1
7 Motor Cover Vinyl Chloride Sheet 11, with Magnet 1
8 Motor Band Vinyl Chloride Sheet 11, Magic Tape 1
9 Wiring Cover Vinyl Chloride Sheet 1
10 Gloves Rubber 1
11 Sling Rope 1m 4

~o

with I
Elastic SupportB
Sheet A Sheet 8 Sheet C Sheet 0
String

'Motor Cover

~";i'h Maqnets
ii
bJP Motor /r",i_ _-",
Band

2-86 HITACHI
T
2 . 10 . 2 In-the-Ceiling Type
...-
(2.10 Cleaning Indoor Unit's Heat Exchanger)

&. WARNING
TURN OFF all power source switches.

Belore cleaning, cover the floor with a vinyl sheet.

Refer to Chapter 2.10.1 about cleaning tools.

Step Procedure Required Tool


1 Remove the drain pan according to the items, 2.2.6 and 2.3.5, "Removing
Drain Pan" and clean the drain pan".
2 Remove the indoor fan motor and the fan runner assembly according to
the items 2.2.1 and 2.3.1 "Removing Indoor Fan Motor".
3 Removing Fan Fixing Plate TopPlata .Phillips Screwdriver

~'I.
I
Side Plate

I
1 Fan Fixing
Plata

Remove the screws fixing the fan


fixing plate and then pull out the
fan fixing plate downwards.

After removing the fan fixing plate, cover the


lead wire wijh a vinyl sheet to avoid cleaning
water.
4 Removing Dust Clogged in .Brush
Heat Exchanger , .Bucket or
Qr. I Paper Board Box

I
Fins of Suction Side
Heat Exchanger

,I Scratch and remove the dust clogged in the


I fins 01 the suction side exchanger with a
I brush. Collect the dust in a bucket.
I
. I ~

{j)'! 'I
I
,

, HITACHI 2-87
L
..,.....
_.. .. " . .'. ;il. . .
."'-<~-. ----,-~".",'
(2.10 Cleaning Indoor Unit's Heat Exchanger)

Step Procedure Required Tool


5 Protection from Cleaning .Vinyl Sheet
Water Heal Exchanger -Adhsslve Tape
.Cutter

Vinyl Sheet

Discharge Side Suction Side

Cover the discharge side of the heat


exchanger with a vinyl sheet to protect the
insulation materials inside the unit from
cleaning water. Seal the vinyl sheet properly
so as to make no gaps with the adhesive
tape.

NOTE:
Peiform the work by wearing gloves to


prevent any injuries from touching the fins of
the heat exchanger.
Attach the vinyl sheet to protect the
insulation materials from the cleaning water.
(A transparent board is also applicable
instead of the vinyl sheet.)
6 Attaching Cleaning Water
Pan Indoor Unit

Metal Bar
~

Cleaning Water
Collector

~Boss
~Hose

<l:- Bucket

Hang a cleaning water collector from the
indoor unit.
(1) Attach ropes to the suspension brackets.
(2) Put the metal bars through the holes of
the cleaning water collector.
(3) Attach the ropes to the four bars of the
cleaning water collector and suspend the
cleaning water collector.
(4) Attach the hose to the boss of the
cleaning water collector and set the
bucket at the end of the hose.
7 Spraying the Cleaning Water Spray the cleaning water over the fins of the .Cleaning Agent
heat exchanger. (

2-88 HITACHI
.......
Step
8 Cleaning with Clean Water
Procedure
--
(2.10 Cleaning Indoor Unit's Heat Exchanger)
Required Tool
.WaterTank
.Pump
.Washer

Hole

Cleaning
Water
Collector

Hose"':;'
Pump

CleanWater

Insert the nozzle into the hole of the


cleaning water collector. Operate the pump,
wash the dust off on the fins with clean
water thoroughly. If the cleaning agent is left
on the fins, it may cause corrosion.)

Adjust the pressure of the spray at


approximately 2.5 to 5.0 kg/ad so as not to
crush the fins and direct the nozzle in a
straight line toward the fins.
9 Make sure that there are no drops of water left after cleaning the fins and .Screwdriver
reassemble the fan assembly and the drain pan. .Hexagon Wrench
10 Measure the condition of insulation of the drain pump with a megohm-meter
tester.
(Check to ensure that the resistance is bigger than 1 MQ at 500V.)
11 Connect the electrical wiring as it was. .Screwdriver
12 Neutralization Treatment after Cleaning
The cleaning agent specified in the item, 2.10.1, is of neutral type. However,
the cleaning water after cleaning may be not neutral due to dust or other
foreign particles. Collect all cleaning water and make necessary
neutralization for the cleaning water.

HITACHI
_tll:
(2.10 Cleaning Indoor Unit's Heat Exchanger)
2.10.3 Cleaning 4-Way Cassette type Indoor Unit
T

Spread a vinyl sheet over the floor to protect furnitures, etc. from cleaning water before this work. )

& WARNING
TURN OFF all power source switches.

No. Procedure Tool


1 Remove the optional air panel according to page 2-33 and the item, 2.4.4, Phillips Screwdriver
"Removing Optional Air Panel".
2 Remove the electrical box after opening the electrical box cover and Phillips Screwdriver
disconnecting the connectors between the indoor and outdoor units and
other connectors according to page 2-32 and the item, 2.4.4, "Removing
Electrical Box Cover".
3 Remove the bell-mouth and fan according to page 2-34 and the item, 2.4.5, Phillips Screwdriver
"Removing Indoor Fan and Fan Motor". Adjustable Wrench
4 Remove the drain pan according to page 2-37 and the item, 2.4.7, Phillips Screwdriver
"Removing Drain Pan". .

5 Remove the float switch according to page 2-37 and the item, 2.4.7, Phillips Screwdriver
"Removing Float Switch".
6 Remove the drain-up mechanism according to page 2-38 and the item, Phillips Screwdriver
2.4.8, "Removing Drain-up Mechanism".

NOTES:
Remove the drain pan after removing drain water on the drain pan.
G) Remove the drain water on the drain pan after pulling out the rubber plug. Check to ensure that
water can flow smoothly through the hole by pricking it with a pencil.
Insert the rubber plug into the hole after the above checking.
Remove the drain pan after removing the four fixing screws. Carefully remove the drain pan,
since drain water may remain at the bottom of the drain pan.
@ Clean and dry the drain pan after removing. Carefully handle the drain pan not to damage it.
)

( )

2-90 HITACHI
_
(2.10 Cleaning Indoor Unit's Heat Exchanger)
'".. ; ".
..
"

& WARNING
) TURN OFF all power source switches.

(1) Attach a vinyl sheet around the heat MOlar Cover


exchanger so that cleaning water will not
be splashed over the insulation surface
and drain-up pump. Fix the vinyl sheet
on the side plate of the heat exchanger
by using tape with adhesive. Seal the
gap between vinyl sheets using tape wtth
adhesive.
Put a vinyl sheet here to
protectinsulation sheet
from the splashed
Tape with Adhesive
deaning water.
Before attaching the
water collector tothe
heal exchanger, take the
following work. Motor Band

Magnet

Magic Tapa

Magnet

Motor Cover

Magnet Magnet
/'

Inner
Side

Vinyl Sheet
5 Nos. (A.B,C,D)

NOTES:
1. Wear gloves to avoid any injury
by fins of the heat sxchanqer,
2. In addition to magnets, fix the
motor cover using tape with
Vinyl Sheet, Tape, Cutter adhesive.
Tool
and Phillips Screwdriver

HITACHI 2-91
-
(2.10 Cleaning Indoor Unit's Heat Exchanger)

(2) Scratch off the dust on the inner surface of


T
I

the heat exchanger downwards using a (


brush. Collect all dust in a bucket or carton
box.

Tool Brush, Bucket


(or Carton Box)

(3) Suspend the cleaning water collector from


the indoor un~.
a. Tie the rope on the suspension bolts for

b.

c.
the indoor unit and put it downwards.
Insert the support bars into the holes of
the water collector.
Tie the rope on the support bar of the

water collector and suspend the water
collector. Cleaning
-. Water
d. Connect a hose to the boss and put the Collector
end 01 the hose in a bucket. Support
Bar
(S Nos.)

Bucket

Jndoor Unil
Suspension Bolt

Rope
Suspension

Bracket

_ _ ~ The water
_ ...lL- 20- 30~ collector
-T should be
i
located 20
Ceiling to30mm
higher than
the bottom
of the unit.
Cleaning Water
Collector

. Cutler, Bucket (
I

2-92 HITACHI
1
l_
(2.10 Cleaning Indoor Unit's Heat Exchanger)

(4) Put approximately 15 liters of cleaning


agent for aluminum fins in a supply tank.

CleaningAgent for
Aluminum Fins

(5) Insert the spray nozzle through the hole .


of the cleaning water collector. Operate

~) the water pump and clean the dust on the


heat exchanger. After cleaning, spray
clean water to remove the cleaning water.
Adjust the pressure of the water pump so
as not to damage the fins.
Cleaning
Spray

~)
Bucket

NOTES:
1. If the cleaning water remains, fins
will be corroded.
2. Adjust the pressure of the pump at
2.5 to 5.0 kg/cm2 so as not to
damage fins.
v} Tool
Clean Water, Cleaning
Agent, Water Pump,
Cleaning Spray

HITACHI 2-93
-
( 2.10 Cleaning Indoor Unit's Heat Exchanger)

(6) After cleaning, mount the drain pan by


extending the rope downwards. (

Drain
Pan

NOTE:
In the case that the cleaning water collector
is removed. wipe off the drops from the
indoor unit.
Cleaning
Water
Collector
Tool Phillips Screwdriver

(7) Check the insulation of the drain pump with a megohm-meter. Check to ensure that the insulation
is grater than 1 M Q when 500V is applied.

(8) Connect wiring as it was.

(9) Neutralization Treatment after Cleaning


The cleaning agent specified in the item, 2.10.1 is of the neutral type. However, the cleaning water
after use may be not neutral. Collect all cleaning water and make necessary neutralization .: )
treatment for the cleaning water.

( )

2-94 HITACHI ___ir&


)
2. 1O. 4 Cleaning 2-Way Cassette Type Indoor Unit
--
(2.10 Cleaning Indoor Unit's Heat Exchanger)

Spread a vinyl sheet over the floor to protect furnitures, etc. from cleaning water before this work.

&. WARNING
TURN OFF all power source switches.

(1) Remove the drain pan according to page 2-49 and the item, 2.5.7, "Removing Drain Pan". Clean
the drain pan after removal.
(2) Remove the indoor fan motor and fan runner assembly according to page 2-45, and the item,
2.5.3, "Removing Fan Motor", and page 2-47 and the item, 2.5.4, "Removing Bearing". and also,
according to page 2-47 and the item, 2.5.5, "RemOVing Coupling".
(3) Removing Fixing Plate
Protect the wiring from cleaning water during Top
Plate
the cleaning after removing fixing plate for
the fan.

Side
Plate

Fixing
Plate Pull downthe fixing plate
tor Fan after removing three
screws fixing the fixing
plate for the fan to the top
Tool Phillips Screwdriver plate and side plate.

(4) Removing Dust on Heat Exchanger


Remove dust on the fins at the inlet side of
the heat exchangerby scratching off
downwards.
Collect all dust in a bucket or carton box.

Inlet Side of
Heat Exchanger

Brush, Bucket
Tool (or Carton Box)

HITACHI 2-95
-
(2.10 Cleaning Indoor Unit's Heat Exchanger)

(5) Put a vinyl sheet behind the heat exchanger


so that cleaning water will not be splashed (
on the insulation surface of the unit. Seal Heal
Exchanger
the gap between vinyl sheets.

Intake
Discharge Vinyl
Sheet
Side
Side

NOTES:
1. It is recommended thatgloves be usedduring this
Vinyl Sheet, Tape, work toavoid any injury.
Tool 2. Put a vinyf sheet to avoid spJashed cleaning water.
Cutter

(6) Suspend the cleaning water collector from


the indoor unit.
a. Connect a rope to the suspension
IndoorUnit
bracket of the indoor unit put is
downwards.
b. Insert the support bar into the cleaning
water collector hole.
c. .Suspend the cleaning water collector
with the rope from the indoor unit.
d. Connect a hose to the boss for the
cleaning water collector and put the
other end in a bucket.

(7) Spraying Cleaning Water


Spray the cleaning water over the fins of the
heat exchanger.

Cleaning Water

2-96 HITACHI
T (8) Cleaning with Clean Water
Insert the spray nozzle through the hole of
-
(2.10 Cleaning Indoor Unit's Heat Exchanger)

the cleaning water collector.


Operate the pump and clean the fins with
clean water. Adjust the water pump
pressure so as not to damage the fins.

Hose~

Bucket

Pump
NOTES:
1. If the cleaning water remains, fins will
be corroded.
2. Adjust the pressure of the pump at 2.5
Clean Water, Pump, to 5.0 kglcm 2 so as not to damage fins.
Tool
Spray

(9) Attach the fan assembly and drain pan after cleaning is Phillips Screwdriver,
Tool
completed and dropping of cleaning water is stopped. Hexagon Wrench

) . (10) Check the insulation of drain-up pump by megohm-meter. Check to ensure that the insulation is
greater than 1 M n when 500V is applied.

(11) Connect the wiring as it was. Mount the air distribution


chamber and optional air panel.
Tool
Phillips Screwdriver,
Megohm-meter

(12) Neutralization Treatment after Cleaning


The cleaning agent specified in the item, 2.10.1 is of the neutral type. Howeve,r the cleaning water
after use may be not neutral. Collect all cleaning water and make necessary neutralization
treatment for the cleaning water.

I) )

HITACHI 2-97
-
( 2.10 Cleaning Indoor Unit's Heat Exchanger)
2.1 0.5 Cleaning Wall Type Indoor Unit

Spread a vinyl sheet over the floor to protect furnitures, etc. from cleaning water before this work.

it. WARNING
TURN OFF all power source switches.

(1) Remove side cover R according to page 2-56 and the item, 2.6.2, "Removing Side Cover R".
(2) Remove the front panel according to page 2-57 and the item, 2.6.3, "Removing Front Panel".
(3) Standard Cleaning
a. Remove dust with a brush.
b. Cover a vinyl sheet over the electrical
components to protect them from
splashed cleaning water.
c. In the case that cleaning agent is
used, clean the heat exchanger with
clean water completely.
d. Adjust the pressure of the pump so
as not to damage fins.

Pump

NOTES:
1. If the cleaning water remains, fins will
be corroded.
2. Adjust the pressure of the pump at 2.5
to 5.0 kg/cm 2 so as not to damage fins.
Cleaning Water, Clean
Tool
Water, Pump, Spray

2-98 HITACHI
T &. WARNING
--
(2.10 Cleaning Indoor Unit's Heat Exchanger)

TURN OFF all power source switches.

(4) Extra Cleaning


a. Remove the heat exchanger
according to page 2-62 and the
item, 2.6.8, "Removing Heat
Exchanger and Indoor Fan Motor".
b. Remove the dust with a brush.
c. Spraying Cleaning Water
The higher the cleaning water Nozzle
temperature is, the more cleaning
effect is normally increased.
Follow the instruction of each
cleaning agent
d. Clean the heat exchanger
completely with clean water.
e. Adjust the pressure of the pump so Heal
Exchanger
as not to damage the fins.

NOTES:
1. "the cleaning water remains, fins will be
corroded.
2. Adjust the pressure of the pump at 2.5
Cleaning Water, Clean
Tool Water, Pump, Spray to 5.0 kglcm 2 so as not to damage fins.

(5) Reassemble the unit and connect the wiring as it was.

(6) Check insulation of the terminal board in the electrical box. "the Insulation is greater than 1M Q by
a 500 Megohm-meter, it is normal.

(7) Neutralization Treatment after Cleaning


The cleaning agent specified in the item, 2.10.1 is of the neutral type. However, the cleaning water
after use may be not neutral. Collect all cleaning water and make necessary neutralization
treatment for the cleaning water.

HITACHI 2-99
_ . '
' .. :." ' "

,-~"'"
('

...
" "..~,-,-,,'

(2.10 Cleaning Indoor Unit's Heat Exchanger)


..........

I
2.1 a .6 Cleaning Floor Type and Floor Concealed Type Indoor Unit I
Spread a vinyl sheet over the floor to protect furnitures, etc. from cleaning water before this work.
( \

I
& WARNING
TURN OFF aU 'power source switches. I
(1) Remove the front cover according to page 2-66 and the item, 2.7.4, "Removing Front Cover". I
(2) Disconnect the drain hose from the field-supplied pipe.
I
(3) Cover the rear side of the heat exchanger
wijh a vinyl sheet after removing front I
side partition and drain pan. After
covering, remount the front side partition I
and drain pan. Heat
Exchanger I
Cover ~
with Vinyl
Sheet .1
I
Front Side
Partition
I
I
Drain
Tool
Vinyl Sheet, Tape, Pan I
Culler

(4) By lifting the drain hose and pu1the end


in a bucket.

2-100 HITACHI
TI (5) Removing Dust on Heat Exchanger
(2.10 Cleaning -..-
. Indoor Unit's Heat Exchanger)

cI } Remove the dust on the heat exchanger


with a brush by scratching dust
downwards. Collect all dust in a bucket or
carton box.

Tool Brush, Bucket


(or Carton Box)

Bucket

(6) Spray cleaning water over the fins of the


heat exchanger.

I Tool I Spray

(7) Cleaning with Clean Water


Cover the wiring connectors with
insulation tape. Operate the pump and
clean the heat exchanger with clean water
completely.
Adjust the pressure of of pump so as not
to damage fins.

Clean Water,
Tool
Pump, Spray

NOTES:
1. If the cleaning water remains, fins will
be corroded.
2. Adjust the pressure of the pump at 2.5
to 5.0 kg/cm 2 so as not to damage fins.

HITACHI 2-101
--
(2.10 Cleaning Indoor Unit's Heat Exchanger)

(8) After checking that no power is supplied, connect the drain pipe and remove the insulation tape for
T

the wiring connectors and then mount the front cover correctly, (
(9) Check insulation of the terminal board in the electrical box. If the insulation is greater than 1M Q by
a 500 Megohm-meter, ~ is normal.

Megohm-meter, Voltage-Checker,
Tool
Phillips Screwdriver

(10) Neutralization Treatment after Cleaning


The cleaning agent specified in the itsrn, 2,10.1 is of the neutral type, However, the cleaning water
after use may be not neutral. Collect all cleaning water and make necessary neutralization
treatment for the cleaning water.

2-102 HITACHI
2. , 0.7 Cleaning Ceiling Type Indoor Unit

Spread a vinyl sheet over the floor to avoid cleaning water before this work .
-
(2.10 Cleaning Indoor Unit's Heat Exchanger)

.&. WARNING
TURN OFF all power source switches.

(1) Remove the left and right side covers according to page 2-76 and the item, 2.9.2, "Removing
Side Cover".

(2) Remove the discharge deflector according to page 2-77 and Tool Philips Screwdriver
the item, 2.9.3, "Removing Discharge Grille".

(3) Open the intake air grille according to page 2-76 and the item, 2.9.1, "Removing Air Filter".

(4) Remove the lower cover and drain pan according to page Tool Phillips Screwdriver
2-83 and the item 2.9.9, "Removing Thermistors for Liquid
Pipe and Gas Pipe".
Tool Philips Screwdriver
(5) Remove the indoor fan motor and fan assembly according to
page 2-78 and 2.9.4, "Removing Fan Motor".

(6) Remove the partition plate 2 after removing


the two fixing screws.

Tool Phillips Screwdriver


I

(7) Remove the fixing plate for the tan after


removing the two screws at the left and
one screw at the right side partition.

Tool Phillips Screwdriver

(8) Attach the drain pan and lower cover according to the
reverse procedures in the item, (4).
Tool I Phillips Screwdriver

HITACHI 2-103
- ~~';;'; . ..- --<

(2.10 Cleaning Indoor Unit's Heat Exchanger)

(9) Cover all components except the drain pan NOTE:


Weargloves to avoid anyinjury during this
with a vinyl sheet avoid splashed cleaning
war!< dueto sharp edge of fins.
water.

Tool Vinyl Sheet, Tape, Cutter,


Philips Screwdriver

(10) Spray the cleaning water over the fins from


the rear side of the heat exchanger. If the
heat exchanger is heavily covered with dust,
use a brush to wipe off.

Tool 1 Spray, Brush ......

(11) Cleaning with Clean Water


a. Operate the pump and clean the heat
exchanger with clean water completely.
b. Adjust pressure of the pump so as not
to damage fins.

Tool Clean Water, Pump, NOTES:


Cleaning Water 1. If the cleaning water remains, fins will be
corroded.
(12) Check insulation of the terminal board with a 2. Adjust the pressure of the pump at 2.5
megohm-meter. Check to ensure that the to 5.0 kg/cm 2 so as not to damage fins.

insulation is greater than 1 M n when 500V


is applied.

Tool 1 Megohm-Meter

(13) Check to ensure that water can flow


---'

NOTE:

Pay attention to the drain pan
smoothly after pouring water on the drain not to overflow.
pan.

(14) Neutralization Treatment after Cleaning


The cleaning agent specified in the item,
2.10.1 is of the neutral type. However, the
cleaning water after use may be not neutral.
Collect all cleaning water and make
necessary neutralization treatment for the
cleaning water.

(
I

2-104 HITACHI
1
2. 1 1 Removing Remote Controller
2 . 1 1 . 1 Removing Remote Controller
-
(2.11 Removing Remote Controller)

See next page for the revised remote control switch.

& WARNING
TURN OFF all power source switches.

(1) Remove the panel from the bracket.


~
a. For Remote Control Swftch and Central Station
(j) Snap out the bottom part of the panel from the bracket, and '"
unhook the top part. Panel Wall

Bracket

CD

b. For 7-Day limer


(j) Slide up the panel from the bracket, and -~

unhook the top part. Panel Wall


t:
(j)
,, Bracket
,
:

(2) Remove the connector wfth the cable from the panel.
a. Remote Control Swftch and Central Station b. 7-Day limer

ti) !. Pc
(3) Disassemble the panel by removing the four screws.
a. Remote Control Switch and Central Station b. 7-Day limer

Bracket Screw
Frame
:.~
Bracket
Remote
Control Case PCB

7-Daylimer

NOTES:
1. When holding the printed circuit board by hand, hold the edge and do not touch the electrical parts
especially the micro-computer part. The electrical parts may be broken by the static electricity.
2. When reassembling, pay attention to the followings.
Blow the dust of each part away and then assembly them .
When tightening screws, pay attention not to break the plastic part.

HITACHI 2-105
-
(2.11 Removing Remote Controller)
2 . 1 1 . 2 Removing Remote Control Switch (Revised)

(
&. WARNING
TURN OFF all power source switches.

(1) Remove the panel from the bracket.


<D Snap out the bottom part of the panel from the bracket, and
unhook the top part. Panel
Wall

Bracket

<D
(2) Remove the connector with the cable from the panel.

Bracket

(3) Disassemble the panel by removing the four screws. PCB
Remote
Control Case

.
-
\," Screw
Fra/
NOTES: Aane'
1. When holding the printed ctrcuit board by hand, hold the edge and do not touch the electrical parts
especially the micro-computer part. The electrical parts may be broken by the static elsctricity.
2. When reassembling, pay atlention to the followings.
Blow the dust of each part away and then assembly them.
When tightening screws, pay atlention not to break the plastic part.
3. Distinguish the revised remote control switch after from before, with HITACHI mark at the upper left
of L.C.D, as below.

Before Revised After Revised

..
rr:DJ @TIJ ([[ITJ c:3 [!J[liJ I:::::D) [ill1J EITI] c:3 [!J[liJ
,; s_
s~

,:~ ',i:
,;;;;;;;
.;.
Y':."
",,, :~, I
:~ :
:.,:.
.:': ."y. uvcn
:,":5'
_:~ .,:
,~

.:-
",,:.\0
",;,:;"l >,:.
;, : "';':
:i''''.
use-r
:,:':!"
'CR ""'!'. "'"'" .'r." ""'p.
~
CH

~
CH
8S"; It.. "' I-''-'c
:", :'I::~
mrrrn :";'C
'-' .,111111 ~ 885 CO
;: II :,!~::
"Itlill

- ?U"-i$T')Ol V tEMP 1\ - ;lll"'{!i.n~ .


I V It''AP 1\ (

2-106 HITACHI I

.......I
T 2. 1 2 Collecting Refrigerant for Replacing Indoor Unit
-
(2.12 Collecting Refrigerant)

) (1) Prepare an empty refrigerant cylinder at -760mmHg with a charging hose. Measure the empty
cylinder's weight.

(2) After shutting the stop valve on the cylinder, connect the charge hose to the liquid line stop valve.
Connect a pressure gauge to the check joint on the gas line stop valve.

(3) Air purge inside of the hose between the liquid line stop valve and cylinder by loosening connection
of the liquid line stop valve and close the connecting port of the cylinder after air purging.

(4) Operate the unit as cooling mode at a frequency of 48Hz.

Connecting

Port
NOTES:
Cylinder 1. The cylinder capacity shall be equivalent
to half of the total refrigerant capacity.
~ 2. In case of 8HP and 10HP outdoor units;
Pressure Gage
Remove the terminals of the constant
Liquid Line Gas Line speed compressor, and cover the
Stop Valve Stop Valve terminals of the cables by insulator.

Setting Method of Frequencyat 48Hz

ON 1 2 3 4 Set the Nos. 2 and 3 of DS20 on the

l~ww~1
PCB3
at the "OFF" side.
OFF OS20

(5) Open the liquid line stop valve on the cylinder to collect refrigerant into it. The cylinder capacity
shall be equivalent to half of the total refrigerant capacity. Check the refrigerant quantity by
measuring the weight.

(6) Close the liquid line stop valve on the cylinder gradually during the cooling operation.

(7) Fix the opening of the liquid line stop valve at a slightly opened position. Continue the cooling
operation.

(8) Finally close the liquid line stop valve and then gas line stop valve and stop the units at the same
time when the pressure at the liquid line stop valve reaches at -400mmHg.

NOTE:
- -
In the case that the collected refrigerant is recharged into the system, charge it by let the cylinder
up side down so that refrigerant and oil can be charged together.

HITACHI 2-107
-
~ No. Contents Page
1 TROUBLESHOOTING 1-1-1-101
2 SERVICING 2-1-2-107

4 OPTIONAL FUNCTIONS 4-1-4-26


5 FIELD WORK INSTRUCTIONS 5-1-5-18

3. MAIN PARTS. . . . . .. . . . . . . . . .. . . .. . . .. . . . . . . . . . .. . . . . . .. . . . . . . . . . .. . ..... . . . . . . . . . . 3-1


3.1 Inverter-IGBT Inverter. . .. . . . . ... . . . . . .. . . .. . . . . . .. . . . .. . . . . . . . .. . . . . . .. . . . . . . . . . . 3-1

},. 3.1.1 Calculation of Operating Frequency............................................


3.1.2 Specifications of Inverter
3.1.3 Monitoring of Frequency
3.1.4 Arrangement of Inverter Power Unit
. . . . . .. . . . . . . . . . . . . .. . . . . . .. . . .. . . . . . .
3-1
3-2
3-3
3-4
3.1.5 InverterTime Chart . .. . . .. .. . . . .. . . . . . . . . .. . . .. . . . . . .. . . . . . . . . . . . . .. . . .. . .. . . . 3-5
3.1.6 Protective Function . .. . . .. . . . . . . . . . .. . . . . . .. . .. . . . . . . . . . . 3-6
3.2 Thermistor 3-8
3.2.1 Resistance Value of Thermistor 3-9
3.3 Electronic Expansion Valve . 3-12
3.3.1 Electronic Expansion Valve for Outdoor Units . 3-12
3.3.2 Electronic Expansion Valve for Indoor Un~s . 3-13
3.4 Pressure Sensor . 3-14
3.5 Noise Filter (NF) . 3-15
3.6 Capacitor (CB1, CB2) .. 3-16

)'. 3.7 Reactor (DCl)


3.8 Circuit Diagram for Printed Circuit Boardof Outdoor Un~
.
.
3-16
3-17
3.9 Circuit Diagram for Printed Circuit Board of Indoor Unit and CH Unit . 3-24
3.10 Circuit Diagram for Printed Circuit Board of Remote Control Switch . 3-27

! ,~

HITACHI
3. MAIN PARTS
3.1 Inverter-IGBT Inverter
-
3. 1 . 1 Calculation of Operating Frequency

Indoor Unit
Intake Air Temperature

Sensing Intake Air


Temperature by Thermistor

Setting Temperature
by Remote Control
Switch
~ .Temperature
Difference
Temperature
J
Micro-Computer for Indoor Unit

Calculation
of Required
- Expansion
Trans-
mitting
Micro-Computer for
Outdoor Unit

.Suction and..... Calculation


Changing Ratio Valve Opening Discharge of
Pressure - Compressor
.Opening Operating
of Each Frequency
Expansion
Valve I

IGBT Inverter

Compressor
(Operating Frequency)
20~ 130Hz (115Hz)

The compressor is stopped


when the calculated
frequency is smaller
than 20Hz.

Control System of Refrigerant Cycle

Purpose
Control SUbject
~). Cooling Operation Heating Operation
Opening Degree of For Controlling Closed
Exp. V for Liquid Temperatureof Discharge
Bypass: MVB Super-Heat: Td SH
Opening Degree of For Controlling Pressure at Refrigerant For Controlling
Exp. V for Heat Discharge: Pd Temperatureof Discharge
Exchanger of Super-Heat: Td SH
Outdoor
Unit: MV1. MV2
Opening Degree of 1. For Controlling Temperature Difference 1. For Controlling Temperature Difference
Exp. V of Indoor between Air Inlet and Air Outlet of between Air Inlet and Air Outlet of
Unit: MV Indoor Unit Indoor Unit
2. For Controlling Temperature Difference 2. For Balancing Temperature Differences
between Gas Pipe and Liquid Pipe of between Gas Pipe and Liquid Pipe of
Indoor Unij Heat Exchanger each Indoor Unij
Inverter Frequency For Controlling Pressure of Refrigerant For Controlling Pressure of Refrigerant
of Compressor Suction: PS Discharge: Pd
Exp. V: Micro-Computer Control Expansion Valve

HITACHI 3-1
- 3. 1 . 2 Specifications of Inverter

Applicable Compressor 5HP, 8HP, 10HP


Applicable Power Source 3 Phase 380/415V 10% 50Hz 5%
Output Voltage (Maximum) 380/415V, 3 Phase
Output Current (Maximum) 14A
Time Rating Continuous
Control Method Space Vector PWM Control
Range Output Frequency 18-135Hz (Operation: 0.1-135Hz)
Accuracy of Frequency . 0.5Hz at Applicable Frequency Range
Controlled Frequency O.OlHz .

Accuracy of Output Voltage 10% at Applicable Frequency Range


Conditions:
I. Power Source Voltage AC380/415V
2. Non-Loading (Free Output)
3. Anmeter Type Vol t-Ueter (X 1.1)
415 --------------_._------------------
400 f--------------------------------- -
380 c-
300 I-
meansC3l
,, (2)
0
0
0
,
,,,
0

0
(1)

V 0

Output/Characteristics [V] c- o
0
0
0
200 f- 0
0
,,
0

c- ,
I
0
0
0
I 0
100 f- 0
0 ,
0

,
0 0
0
C- ,
o
0
0
,
0

0 I 0 I I , , : I 0 :
0 50 90 100 130
f [H zl
Refer the below notes for (1), (2) and (3).
Soft Start Stop 0.5-30HzlS (5 Steps)
Protection Function
Instantaneous Overcurrent Tripping at a Current Greater than 150% of Rating Current
or at Short-Circuiting Current
Overload Control Overload Control at a Current Greater than 100% of
Rating Current
Overload Control Release at a Current Smaller than 90% of
Rating Current
Frequency Control against Stoppage at 0-17Hz, Fixed at 135Hz when Higher than 136Hz
Abnormality
Overheating Protection of Tripped at 95'C 5'C of Transistor Temperature
Transistor
NOTES:
(1) Characteristic of RAS-8FS, RAS-8FX, RAS-l0FS and RAS-l0FX at 380V power source. And
characteristic of RAS-5FS and RAS-5FX at 380V and 415V power source. For RAS-5FS and
RAS-5FX, the characteristic at 415V is converted into the characteristic at 380V by the dip switch
D~l. (
(2) Characteristic of RAS-8FS, RAS-8FX, RAS-10FS and RAS-10FX at 415V power source.
(3) Characteristics are fluctuated by the current minimize control.

3-2 HITACHI
I
----l..
T _
Protection Function
Low Voltage Output is cut when a voltage between L1 and N is lower than
r ) 12710V.

v
210 - . - - - . - - - - . . . -
/ @
'-'I'l'l' / ~
v
U
~
/
~
V
"
.!!!. /
~(j)
"E
i= ~ v
~
Electronic Thermal Relay
~ /

30 - .. - - . . - - - . - - - /// / /
,
, , I ~
50 100 105 150

~" <D

Load Rate (%)

Instaneous trip when load is greaterthan 150%.


Trip when load greaterthan 105%condition is maintained .
longer than 30 seconds.
@ Trip when load greaterthan 105%condition is accumulated
longerthan 3.5 minutes during 10 minutes samplingtime.
Protection from Short Tripping by Sensing Short Circuit after Terminals,
Circuit to Earth U.V. and W in JGBT *1) (Secondary Side of Inverter)
Protection from Excessive Output is cut at a voltage greaterthan 296V 15V between L1
Vonage and N.

*1): Tripping is sensed at a starting currentwithin a speed of 100Al "'S.

3 . , . 3 Monitoring of Frequency

1
PCB3 T=-----
Output Frequency
CN4 CN4 DC5V
No.3 Pin NO.1 Pin
~ ~
GNO FM

Output frequency can be monitored by connecting a frequency counterbetween GND and FM.

~i )

HITACHI 3-3
- 3.1 .4 Arrangement of Inverter Power Unit

x I
LO
.1
LO
N
I
0

o o
x

o o o

------J 200

No. Parts Model Name


1 Fin (200mm x 255mm X 5Omm) -
2 Transistor Module 6MB130L-120 IGBT
3 Diode Module DF40AA160 DMl
4 Diode Module RM201-1A-20F DM2
5 Cement Resistor N15Fl0QJ RS3
6 Thermistor - THR
7 CT Sensor SB1502 CTU
8 CT5ensor 581502 CTV
9 Capacitor - CS1. CS2. CS3

3-4 HITACHI
3. 1 . 5 Inverter Time Chart -
Main Circuit
Power Source --l
'.'

~FrcQuency Frequency lOW


L
: HIGH All r=8.:..il~1_ _..,.., r-r-_ _:.:.AI:..:I~8::.:i:..:.l 1 Operat ion:

Frequency
t
Instruction

t'.
Output Voltage

1
Soft Start Stop
(Frequency) --~The
/ .
changi ns speed: :

I depends on the outer; :

H
se t t ina. ::
I
i
Failure Signal
[[J L
Activation of
Protection Device
r rens "RJ i,,,],,," :L
rn
Error 40sec.; Activation

Overload Signal
~' . '
iL
: Activation Recovery
: Overload

Tripping Signal
(LEDl-3)
-->----;-,-------!H""''''"'j
: Alarm

. : ON

Charged Indication J L
(Red LED6)

HITACHI 3-5
- 3 . 1 . 6 Protective Function

(1) Instantaneous Overcurrent (


a. Level of Detection
When the output current is increased to 150% of the rated value, abnormalities are detected.
b. Function
The output is cut and a tripping signal is issued, indicating with an LED.
c. Reset
CD When a stopping order is issued, the output of tripping signal ends. After this, the indication I
of the LED is reset according to an operation order.
@ The indication of tripping signals and LEDs are reset by the cutting power source.
I
I
(2) Insufficient Voltage
a. Level of Detection
I
Whenthe voltage between L1 and N decreases to 127 1OV abnormalities are detected.
b. Function
I
When abnormalities are detected, the output is cut, signals are issued, and these are indicated
on the LED.
.1
c. Reset
I
CD When a stopping order is issued, tripping signal output is set. After this, the indication of the
\
LED is reset according to an operation order.
@ The indicationof tripping signals and LEDs are reset by power source setting. I
(3) Overload Control \
a. Level of Detection
When the output current exceeds 100% of the rated value, abnormalitieswill be detected.
b. Function
An overload signal is issued when output exceeds 100% of the required output, and the
I
frequency decreases at a rated of 6Hz/s. The inverter is operatedwhen the output current I

.
decreases for 5 minutes from the time when the current decreases to 90% of the rated value.
However, if the frequency order is smaller than the maximum value, the operation will be
performed according to the order. :
c. Reset
The inverterwill be reset after 5 minutes indicated in previous itsrn b. I
(4) Setting against Abnormality
I
a. Detection
When a frequency of 17Hz or smaller or 136Hz or greater is inputted, an abnormality will be \
detected.
b- Function
17Hz or Smaller: The inverter is stopped.
136Hz or Greater: The inverter is operated accordingto a 136Hz order.

3-6 HITACHI
,.,..-
I
I
(5) Electronic Thermal Relay
a. Level of Detection
-
I ) When the output current exceeds 105% of the rated value, overcurrent is detected.
b. Function
I CD When the output current reaches 105% of the rated value or greater for 30 seconds
continuously, the output is cut and the abnormality is indicated with an LED.
I @ When the output current exceed 105% of the rated value intermittently for 3.5 minutes in

I total during a 10 minutes period, the output will be cut and the abnormality is indicated with
an LED.
1
c. Reset
CD The tripping signal is reset by a stopping order, and the LED indication is reset by an
operation order thereafter.
@ The tripping signal and LED indication are reset by a power source cut.

(6) Safety by Grounding


a. Level of Detection
When the output current reaches 150% of the rated value, an abnormality is indicated.
b. Function
After cutting the output, LED indication is performed by issuing a tripping signal.
c. Reset
CD The tripping signal output is reset according to a stopping order. The LED indication is reset
by an operation order thereafter.
@ The tripping signal and LED indication are reset according to a power source cut.

(7) Protection Against Excessive Voltage


a. Detection
When the voltage between L1 and N reaches 296.15V or higher, an abnormality is detected.
b. Function
After detection, the output is cut and tripping signals and LED indication are performed.
c. Reset
CD The tripping signal output is reset by a stopping order. The LED indication is reset by an
operation order thereafter.
@ The tripping signal and LED indication are reset by a power source cut.

(8) Heating of Transistor


a. Level of Detection
When the temperature of power transistor IGBT increases to 95 5C, an abnormality is
detected.
b. Function
After cutting the output, a tripping signal is issued, then an abnormality is indicated on the LED.
c. Reset
CD The tripping signal is reset by a stopping order. The LED indication is tripped by an
operation order thereafter.
The tripping signal and LED indication are reset by a power source cut.

HITACHI 3-7
- 3.2 Thermistor

Thermistors for Outdoor Unit (


Thermistor for
Discharge Gas
Temperature
(THM5) .;.:"" '" .
Thermistor for ;..:~.,?'J:'":JjJJ<:y
Condensing '~..."""'- ?""A-:;'~"'-'~:,
Temperature . ~"
(THM8 for FS only) .. ~ Thermistor for

~
Outdoor Ambient
Temperature
(THM6)
Thermistor for

I
Evaporator pipe
Temperature
(THM1)
(5HP)
,


Thermistor for
Thermistor for Discharge Gas
Discharge Gas (Front Side) Temperature
Temperature (THM7)
(THM5) (8HP s 10HP)

Thermistors for Indoor Unit

Thermistor for
Air Inlet Thermistor for
Temperature Indoor Heat

I
Thermistor for
(THM3) Exchanger Gas
Pipe Temperature
(THM7)
Air Outlat
Temperature
(THM4)

Thermistor for Indoor


Heat Exchanger Liqu~
Pipe Temperature
(for Freeze Protection)
(THM5)
(

3-8 HITACHI
3 . 2. 1 Resistance Value of Thermistor
-
(1) Discharge Gas Overheating Prevention
(Thermistor for Checking UpperPart of Compressor,THM5 and THM7)

a. A thermistor checking the temperature of the compressor upper part is installed, to prevent
discharge gas from overheating. If discharge gas temperature increases excessively lubricating
oil deterioration occurs and lubricating properties deteriorate, resulting in short compressor life.

b. If discharge gas temperature increases excessively, compressor temperature increases. Atthe


worst, compressor motorwinding will be burnt on.

c. When the compressor upper part temperature increases during heating operation, the unit is
controlled according to the following method.

e An electronic expansion valve of liquid bypass opensand high pressure refrigerant is returned to
the compressor through the accumulator, decreasing compressor temperature.

elf the compressor upper part temperature increases exceeding 127"C for 10 minutes even if an
electronic expansion valve opens, the compressor is stopped, in order to protect the
compressor. Thermistor resistance characteristics are shown in Fig. 3.1.

d. If compressor upper part temperature increases exceeding 127"C for 10 minutes during cooling
operation, the compressor is stopped. (Refer to the block diagram for details.)

Gas Bypass

200
I

-o
100
1\
-.
~
\ 72.3
>
uc
14.2 8.32

~
a 25 50 100 120 150
Te_perature (1:)
Li qu i d Bypass

Fig. 3.1 Resistance Characteristics of Thermistor Fig. 3.2 Refrigeration Cycle of Outdoor Unit
for Discharge Gas Overheating Protection

HITACHI 3-9
i1
_ ~...... ' " ~
..............
. :

(2) Thermistor for Outdoor Ambient Temperature (THM6)


When outdoor temperature decrease to -5"C or lower, the compressor is stopped, during cooling
operation in the case of FX series. Thermistor resistance characteristics are shown in Fig. 3.3.
(
90 ._-,---
o B2
1
~ 70 \
\
;=" 60 61
~

0_50 1\
~O '6
-;;; c
40 l-
> ~5
.- - f - -- - - ,-
"u
c
:l
30
ZO
IZ 205
-r?,S - - - -
~ 10
" 10 0
~. 5 3 ]5
'" o- .
1 .5
1, -10 -5 0 5 10 15 10 b 30 3, JO 015 50 55 60
A.bient Te.p. (~)

Fig. 3.3 Resistance Characteristics of Outdoor Air Temperature Thermistor

(3) Thermistor for Defrosting (THM1, THM3)


The characteristics for the thermistor is the same with the value of outdoor ambient temperature
thermistor.

(4) Thermistor for Room Temperature Control


(Indoor Unit Air Inlet Temperature Thermistor, THM3)
The room temperature control is performed by this air inlet temperature thermistor, THM3. The
setting temperatures are indicated on the remote control switch with figures. Set room temperature
so that room temperature dose not become too cool ortoo hot.
We recommend that temperature be set in the following ranges.
Economical Cooling Operation: 27"C to 29"C
Economical Heating Operation: 18"C to 20"C
The resistance characteristics of the thermistor is shown in Fig. 3.4.
---

=~~]]I
90
81 I --.- --
s 70 \
I --_.
; .
._.

\
.c
.... 60
IiI .L - _. -_ ... - --- .- --j
~

o _so \ 1 -*_. _._- ._. __.. .. . - ..-


llO 016
';; ~'10 f-- ._- --- - .. -- -- --
>
-, ,.<5
-- -- -- -- _. ._.- - ----
r-, -'--i-
"u 30 . -1/-
c 111 \
~ !tI - --- - 16-1--- - -- ._- -- .. -

10 - f-
i"'- 11. m
:--= 0-" 5 ] -- =~[ --
"
ee
.. -
I 6
2 .5
u - . eo
-
15 -10 - S 0 S 10 15 ,0 2') Ju lJ 40 ..J5 lJO 5:1
Temperature (~)

Fig. 3.4 Resistance Characteristics of Thermistor for Air Inlet Temperature

CAUTION
The thermo-off valve of the indoor unit air inlet thermistor is set at the temperature higher than the valve
indicated on the remote control switch by 4"C and the maximum is 34"C, because suction air
temperature during heating operation has a tendency to become higher than that of the occupied zone, {
intending comfortable heating operation.

3-10 HITACHI
(5) Thermistor for Discharge Air Temperature Control
(Indoor Unit Discharge Air Temperature Thermistor THM4)
-
This thermistor (THM4) has been installed to prevent cold blowduring heating operation. The
characteristics of the thermistor resistance is shown in Fig. 3.4.

(S) Thermistor for Liquid Pipe of Indoor Heat Exchanger

When the temperature of the indoor heatexchanger decreases to ot or lowerfor 3 minutes, the
thermostat is automatically turned off. When the temperature increase to 1SC or higher, the
thermostat is turned on.

The purpose of this function is to prevent frosting on the heat exchanger during cooling
operation and dry operation.

The characteristics of the thermistor resistance is shown in Fig. 3.4.

(7) Thermistor for Gas Pipe of Indoor Heat Exchanger


This thermistor senses the evaporating temperature during heating operation.
The characteristics of the thermistor resistance is shown in Fig. 3.4.

HITACHI 3-11

--------
- 3 .3 Electronic Expansion Valve
3.3.1 Electronic Expansion Valve for Outdoor Units
T

Pulse Motor
Micro-Computer I
~ Pulse Signal
2-Phase Permanent Magnetic Pulse Motor
Control 0 to SOO Pules by 1 Pulse
Need I e
Refrigerant Flow Control
Precise Control

Connector Color
Applied Cycle Main Bypass
Mark in Diagram MV1 MV2 MVB
For Unit Blue Red White
For Service Wh~e

Specifications

Items Specifications
Models to be Applied For RAS-8FS. RAS-8FX.
RAS-10FS and RAS-10FX For liquid Bypass of
and for Main Cycle of RAS-SFS and RAS-SFX
RAS-SFS and RAS-SFX
Type EKV (S.OUSRT) DKV (1.SUSRT)
Refrigerant Used R-22
Working Temperature Range -30"C-6S"C (Operating lime of Coil: less than SO%)
Mounting Direction Drive shaft in Vertical Direction within an Angle of 4S' as Maximum
Flow Direction Reversible
Drive Method 4-Phase Canned Motor Method
Rated Voltage DC12V1.8V
Drive Condition 88PPS (Pulse Width at ON: 36mm sec. OFF: 60mm sec)
1. 2 Phase Excitation
Coil Resistance (each Phase) 460 10% (at 20'C)
Wiring Diagram.
Drive Circuit and ON ,..-
Activation Mode A en
I--
@
'i, -"l"] WI ring
B

;..
OJ.gra.
B A'L-jjL A
I ii
!Dr!ve
J- J ~ ~
OC12vCircuit ..
>
>
Close Open

II Activation
(

3-12 HITACHI I
I
~
3.3.2 Electronic Expansion Valve for Indoor Units
-
) I
Micro-Computer ~
! Pulse Signal
Pulse 1I010r- -~

~~Jg
2-Phase Permanent Magnetic Pulse Motor
Control 0 to 2,000 Pules by 1 Pulse
Gear- f-

Refrigerant Flow Control


1::;:1 I
Or iver

Precise Control
IT, 8el lows

[
tff --Valve

Specifications

Items Specifications
Type EBM Type
Refrigerant Used R-22
Working Temperature Range -30t -70t (With Coils Not Electrified)
Mounting Direction Drive shaft in Vertical Direction, Motor Upside and 90 in Four Direction
Flow Direction Reversible
Rated Electricity
Drive Method 4-Phase Pulse Motor
Rated Voitage DC12V1.2V
Drive Condition 100 to 250PPS (Pulse Width Over 3mm)
2 Phase Excitation
Coil Resistance (1 Phase) 1500 100/0 (at 20t)
Wiring Diagram,
Drive Circuit and
Activation Mode
~oe:t
Ph.. ;d~O: 1 2 I 3- 4 1

G!@ ,.
1~
1 'J' I In. JL
2 -llLfl I JL
3fG~'4~ - Wj r i n9
DiagralR
3 In 1J'l
IL- L J 4 I In Jl
~
Dr ve Va Ive
Activa~ Close Open
Circuit
)3{ . .3 ).J 1lC12V
t ion

Activation Mode

HITACHI 3-13
- 3. 4 Pressure Sensor

(1) High Pressure Control


(
The high pressure during heating operation is detected I HeatingOperation I

by a high pressure sensor, and compressor frequencies ,- ------ -}. - - -_. --,
are controlled according to the PID controlling method
so that the high pressure is controlled in an appropriate High
.I

:
I
PIO Controlof
Compressor Frequency
I. I
I

range. The output of the high pressure sensor during


heating operation performs protective control; gas
Pressure
Control
I

Protective Control Gas


BypassValve Check
I' :

:
_ .. _ ..

....... _ _ ..... _1
by-pass control.

Electrical Box
51-------------"

Machine Chamber
High Pressure Sensor
~

-
~

"
~

'" 0.51--71'
0371 tI'-----'---- .L

-1 o 35
Pressure (kg/mG)
Output Characteristics of Pressure Sensor
(2) Low Pressure Control
The suction pressure during cooling operation is detected
by a low pressure sensor, and compressor frequencies Coolil1g Operation
are controlled according to the PID controlling method
so that the suction pressure is controlled in an appropriate
range. If the suction pressure reaches excessively low, Low
the cooling can be insufficient and parts composing Pressure
Control
the refrigeration cycle can be damaged. For this
reason,if the output of the Joe pressure sensor indicates
vacuum and the valve is maintained 10 minutes or
longer, the compressor is stopped for the purpose of
protection.

Electricel Box
>; 436 I----------~
"
<>

o
>
PCB2 - l.IS 1------,.
~

e 0.5
.5 037
-lOS 30
Pressure (kg/aJIG)
low Pressure Sensor
Output Characteristics of Pressure Sensor
lIachine Chamber

3-14 HITACHI
I
ip
3.5 Noise Filter (NF)

The noise filter decreases the leakage of noise made by the inverter to the power supply side.
--
Terminals indicated with "LINE" are connected to the inverter side and terminals indicated with "LOAD"
I to the power supply side.

Specifications

Items Specifications
Model 20TYS10-H
Rated Current AC415V 20A (L-L)
Permissible Temperature Range -25"C to 55"C
Circuit Diagram L1 L1

fC3 R[ CIG: C2
J"
,
L
L2
ie, Jj~l G: C2 t C4
L2
L

0
,
L3
hue, li"
L3

" G: 0
E
" ic", 1 "
CO" '"m'
L, b ~ eND

Minimum Insertion Loss (At 500HM System)

Frequency (MHz) 0.05 0.15 0.5 1.0 5.0 10 30


Com. Mode (dB) 18 32 45 50 55 55 45
Dif. Mode (dB) 12 45 60 55 42 50 45

218

Ie
"/ rI
0

..
.. ~

.,
N

....
.. I"i"

HITACHI 3-15
- 3.6 Capacitor (CB1, CB2)

This part is used for changing the alternative current to the direct current for the inverter. Connect two
1

capacitor in line and used.


(

Specifications

Items Specifications
Models HCGFAR2G272N
Capacity of Static Electricity 2700/LF
Rated Voltage 400V
Permissible Temperature Range -25C to 105C

Ij 3.7 Reactor (DCl)


, This part is used for changing the alternative current to the direct current for the inverter.

! Specifications

Character
Items Specifications
1mH10% (at 1kHz)
Rated Current 33A
Direct Resistance 25.1mQ 20% (at 20C)
, Permissible Temperature Range -20C to 60C

il
.I

~ n -
@ 1\ /I -- @ "l~i ,
, t.
I'
....
0 !~ I

@
76.2

1_ 3-16 HITACHI
3.8 Circuit Diagram for Printed Circuit Board of Outdoor Unit
I,

.
(3 8 Ci cuu Diagram for Printed Circuit Board of Outdoor Unit)
_l-
i)
Control Board (Low Voltage): PCB1 (1/2)

.! ~ '"....
V.
.. \Is Clf' H-!' v~
'm ,Of
.'"...
,--""" ~
iC102
~I '0' , ~H- UC1~~ MHO Ao 0IIlJ, ",.

10- aOi 1>-...


v." ,.0.... I
,,'/'
.....
om"

1: ",,,::,n ;,;.;, "'".


o.o4"1}'
~' 1<,
fl"
':~ ,.
MV, n
PE'
""AI ClINo!
1
'- em
I.,..... so.., fl',
" '
&1..

... I
r-"ll
10,2 "TWI 5
A> e....
Ok
._,
1~
~::fl,
""':~

v.
~

>, .,.. I "f" rr


.... , ~ ... '" ,
011'8
n D\TA ,-
-"",l"'-
QJf
CN~1 ee C1J< A, 11m.
" THI'13
I" <S
MV,
i" '-'!bm''''
.-
""
0.041,..
...... ....
""rr
I om r

..';r ,.Jim! ",,,"JIt!c,,, ._.


'-
I c..
G.047p. ...
:,0 !-
'.. ... "" !~ ..QJ'....t ~
Co A,
"",Yo

""
~ .. !
cm ...atlo
>,
1\1
,
" ""r
tI
e,
~'
~

O"l':r .' f~ Il"'C.';3i 1'114


v, "'r '" Of," r-

L C 10 1 RIB) ItI84 Foti'> 10k. 3 ... ,~

1''''110 I

.,
~-,'

;~
I, '"
._-~---'--h:;:+.:o'
AUI
.. L-----
L----
...
~TXA.

~,l"A.
- ..

v,,,

~I
100\Go1l
,r,
TI..
!-CIlI.
,, '' I 0.041...

,
T<>,, ,
'
._,
lOll
"
(Cluj

T.
.~'\,.
nu
0.0 .....
I
!.eu.
0.041...

o
';'-'!! I AI12 se lC
,
,-----------"11'0,

. ..
eifeHe
- . Ok

l"
~S

, .,
?'" '"
IR1-411
. "

HITACHI 3-17
-(3.8 Circuit Diagram for Printed Circuit Board of Outdoor Unit)

Control Board (Low Vo~age): PCBl (212)


1\
I:
1
I

y
r S:G 1.1 E:''lfl2!>GU
s ,

":H!
v,
l., ,'",,~'/ cr.'' ' !",'1, I ,,'".,.,. .1, '1"11
''''
"';,
np~ :> E:1T;,l lEM .. l'f1)3

""
~~101 , Lf~~.S. "f-'
s.P'~)4:.oP,

" ,,
"
C:AIUrtTiOlI
R'2U v, Iliit
N'
1 , "
III H
, W" ,.
ii~=;''''~~';'1.
Cl2'S e
I;i;U
iOKff '0( ,"
111'" ),
l!i Il, ~ 7

unru
11tn+"iC ,:.8
i ICI22
RM2


1o k '1

tiElMnc.75bAP PrC 710~'j

ic Il7 ICIll.
f.?!ol
J.1~/l&Jt I
I '::: 'NTo
~IN12

v,
- ....--J
C" :;.0 4" ...

" Ci'/
icns H
,
Htl6LIBO
..... , ,,
.,
1<6

.
"
,,.
f11

"'"
,.,
r

.
;' ."
~

!R~
,'"
,,, ,
1~.i:411

..
"" F'::l

,
""
c- ;:;.1Cl ...Fa5
c, --.;r- 100. 7
I '" ,
2Slo IIZIC

""T
F~m
~.

" '.... ,1) ... $


&

Aog'l
{
'" s qCIIO)
,,(.. ( 110

" RM'
l"k '"

15J1112lC

I (le=;) OTC1l41C
'.7 "" I I I~H:1

I -11 Y"T_
'Q

, " "
I.._--~
f'Ct41ot , R1G~fl1!
IO~
Cinirol line , .6

1') lodoor Unit "",

3-18 HITACHI
~:: .:: .~ :
Vs

5K301 f,9
ITI
1301
J b'
[
.301J ,.Jpa g
u E2i a.
J:
<0'
zr
--'---!>t4-
Z3<>4
~
!
~
-c
o
~
:I

~ .2

-
:I

~
---0..,...
---~
i"Hi
---~
----<~
_Yu>
2

~-- ., ,5

II

~~~J ', 9

I~
h;~
15

ilW..<I1 ;:t.~ ~,,'" :13

~.~
f'CN309 lG3'! '3'8

~
_I O orr,"
r-'I ~y211 ./7
i I a v_~--'
1':"-"
II 0 13

~ ,
" R33q 1m<>
I ~ 'l2la
~
;110 "-"'3 ..9
I: 0'1'F."t'------
_ :, 0 v I

ftI.l L.~
311 rc'J I ~Y20, ...
I",~
C\
/H>312
L. 21
t;3
0:>
':'n'------
PC.NL~
I II 0 u>--,,=--1
I ~~3R- Q
-Ilt~ll~ @:--~
i
3t2-r--~
Io-r-
-e ---------_.g
;:;.-
lolL ~ ~,R~ (J
PeN L.:J
r-v/ ~ v.;.,..
313 I O)-IH''------;; 1LEl>311- 0' " ~25
,E'
L~
I 1.3 0 ")-,-",,,--.J
f'CN I ~\l5'
'''7 R~ s3
31'1- i;p.11 - - - - - - --0 '0'"
_ Y.dPM lB)'IS C'"\ 27
,

L~
I 0 I
L,;Cl R~3 ',~;O
0'
~

31. rO>fl3=:.1-1
/'01 '"0
_ ~ Yc,Qol ;!EW14 1/\ 29 :::!.

ftNL~1/ I _ 0
I

~O3l7
~ ~.. R~
C::' " ~I
~
31' r-,31
I 0 I .
lo-1L -
_ _ YOEF o~.
LEl>~ ~;~
Ov ,
fOi l.._J
317 Iro.'=3t-----_
.!
I
l~
II -
0
YOP
~I~
I~~
c:
;:;.-

,LEll319""
V't 0 ' -
__ A r~

'3"'/

oc:
VsO (%aT
a: F~
o

'f
O'0r,..
4'7.....f'ii o
~

C
::J
~

CD 1126 .5
......
(3.8 Circuit Diagram for Printed Circuit Board of Outdoor Unit)

..
Inverter Board: PCB3 (1/2)
rc a ,<;>. & 10 I e.' ,
1. ,
. ~>-._'-r.:---''C:Y--"""1"----o REGI
R4I1
D"&~
-,
L

f '5O
..LT~OO"F ""12
'!'
IV

" '" ~
A501 AU2
!!.!.... I
"1J55123-T,8
I
-lfsov I
I
RJIS

'"
I R311
'" '" ~ ~1 "
i'
I"
I
11 + +.,C500 e919 L. .J

1 leT : AHS

'"
R4U
...
C403
,,.Jm' - ::S:
'"
, ,
AEGT
v RoUl

A
. ,
D49~
R413

'"
... '-<
'"
R509

"
R423
Rn4
,
DU
'l'rl
RSH
102 '" !CI
.... :==
~

" Rns
... 103.:t
.. :== v}----,
R1D6~110
103.5 "
"
~ .~ .,,:==~

) llllj "
..
D42 043
"
~
" v
" 0LJ Ie..: "
"
"
' f '"
P.-:-J 5 0'
v "
'I" t
50
"
~
,:~ r " ""
weu T ca02
"
..
lCt'lil
,
5
lOCi
~-If
.
" "2T LEn1

l.-. 1 IVId
"56 "
..
.. 103

"
. ,' "
"51
51
LSI
(19HI04)
R!!!,
21''1'

1 1 3 .. 1 2 3 .. 70S
"
il---'-'-l
" " COOl r - - .. (QHD)
"
DUI
CSD04
DSlO
UDO" ,
RIIS-Rlll
103x5
I
"
II---'-'-l
"
"
"
"
.
"
""
"
"
'" I'"
.
"0;

" " "


" " "
.,
[ I""
,n2 "
"
"
I"J-l!....-
0l"~1,-..,,,...
...
--!.'-1 "
"
" " f--!!. " "
~CI04 "
70
.!!!.!!.! 60
I----'- l-!---
1'02 ~7t-
'"
11 10 C609
103 61
i-L--
~T"
I _ C.12
= " I -r- '" I-!-
12

'"
..
7: 103
I LED. 't"
.:; 103 U IULUT31 " ~ i-L- " 1 14
<;> u., IS 12

)q.. ) I '" i-L-- "


.~"
II
,
10

x
5
" (2:C~52&l ~ 1~71 ,
rdJ ,
RIo..
'"
R102

r'"
lel03
y" "
"
~
11
, ,
,f
~
,., m
petIT, '"
Rl01
'1---'-'-'
" ~ " ,
I


ITLI 0'1'f-+-~--1 4~.'"
calO
" IE- "
(If 'I} I df--
C102
103
, "
\ J PC?
'" "
, 1---"4 I-!-
IT',j olf--
." ':~f--.--+-+ " 2!-
L poo..-f
r- 223 Lr---'-'-L_...J.!!-
"
;I,,,,,
." 1 ...
C101L

~'102
.... )
...
3-20 HITACHI
( ) Inverter Board: PCB3 (212)
-
(3.8 Circu t Diagram for Printed Circuit Board of Outdoor Unit)

TR
CNI 5
" PC,
ifF

6:'. "
'"
,.
A902
,., :~
~
s;q
PC817
I' 1
I , (PI

, "'" ,.m
A'GO
r-AU! ~~
, CNIB

I -", 1~
lGIl
CN13
r AIlS
,.
'"
I~

V
I

~u.
.. '" ,
, ( Ell
21U 103 lG3I
sO' ,
cooo_=
104.. _ , ,co
, 031
eaov ,.
RIOI
m ,::1 ~ , --'!E...
S
lG"
C902
m PC... --' \-'
D"
0"
~ ~:i~50' 2~~
,...-i " ~~
, ,CNI7
. (
D'D
" ."
LEDIi
,
~LEDS " eXI
100~F*T
+
, lE2)

'"
IciJ '"
(
, IE4)
S
lG"

m peal? 0"
>=f'=
__ A '"
4l..---~--___\1 0 I ....... '
9-d~ "
,I '"
" tRl lOS

'"
, '"
'" v-" A'l'l..,

[
RUD
'" ",
ClI._I..'
,,
'IOJlFLF

f: I~~--------------------I-'
IV'"

2~'-----------------------l-----'
3~!..-.-_-_--------------_ _1_~~:;::::I:"t-:,--+--,----+--.!Jj"
I
lew iL'X - I - - - o - - - '
121
'WI

4~!!...--------------------_----'
IGttDJ

.W<
2R2
,~
103
"
'"

'VN' ,'j',",= =
(UP) "'
'UtO
" 'I'
, D,F2 /Z',

'"

HITACHI 3-21
- (3.8 Circuit Diagram for Printed Circuit Board of Outdoor Unit)

Power Supply Board: PCB4


Tl
F11897A
06
ERA91-02
1
07
15953

1~3 I
1

"II~ DI,
~

I '----'
I T
2
~ Cl \z
82p ~+ lCl AN78N12
CI2
27C Z~+
~R13
:? 4. 7K
~
P
35V 50
2
08 09, ~ 15953 C3-L0.Olprv &2
-.-...r 1 .:I:..530V ~
ERD32-02
~ r 1 3 l +12V
Fl
lA
~,
L....,...J 2.
H90mA
~3:!.H C14 2 CI5 +
_ 25..2.".... 5Ul0V-03100
L1 ....--+_
51WB (A) 60
_+_---., 01,,.---,_----, ...-_...-.......----;_---., 330p2?:z+ lC2 PQI2RFII 82~i' :~RI4
. '""-' 35V 35V ~ 4.7K

+~-
3 3 1,C2
AC180- RI ~ >1,Cl __O.lp
220V 1I2W: !: T~' Ip - 010 011,~IS953
250V 250V -N
I I 560K EK04
"-,
VI
r 1 3 I 3
t5V
200-361ml
C3 C4
PCN401 PcN402
mop:::
400V .
'-TL
C16 Z
'/
2
lC3 24M05
C17
82p Z~+ :: RI5


330p ;L ~ > 4. 7K
x2 35V 35v
--
L2 SEC-02
1
"-I t24V
-Vvv ~y
10 012
v I
10-380mA
R2
15
'"5
1. ~ ERC30-02 C19 +
120p 2 ~i
5W IW
~
10
35V
4
&1
04 T C20 I-
B4B-XH-A
15t5,3 .I O.OlJL CN401
05 ,~
HZ4A2 '
016
15953
,L,
v

> R23
...rlN ~R18
: >3.6K
-- 630V

Cl~~5 ~.
~

:~ RI2 :S: RII 3= 4. 7K 47K


.<-IK :;> 1K
R22
Q2 '<,
e3Zl! rl--~-+------+---+-J
680
...
v~'{
- R2Q::::~
680.. s, :..J
: "'VRl

R24 014 IK
1~~ ~Z,5C3
v~'{ V\
~l--013
...
v~'{
...,
'\
.I~kZ9A3 ~R19
~~2K

R25 015
: : R26 100 HZ27-1
.,.. 4. 7K

3-22 HITACHI
I
Fan Controller Board: PCB5 (FS Only)
(3.8 Circ it Diagram for Printed Circuit Board of Outdoor Unit) -
)
PCN3
(H/P)
r@l
, 2'
.,
0'
L'6':J I
PCNI (POWER)
'';'
0
I
t
r, ,
L
h 1 RI7 RI9

fm
~ (5tH 2
-.00) R2 RI 2 10K 91K
R28 a 3W. 75t::: R. RS 220 R2l
C21 RI8 I &K
I, I, Cl'
330p
2$OV
DSA
-iiall
CI
350VAC QI
24K 2. 2K
l~
O. 047..
SO, 'SOK ,
II
O. 1,4
~
C. O.OH~
so, (25A&73C)
R& C3
60Hz
1
0
5 0 HZ
-om, C
R22
2.2K
R29
S9K
VR'
20K
I, J
0 r, 1 V'T l." o.Oil, C9 b E,
SW IC2 1ltA11901P!
/1a
lD' / .~
Z2
'T TRC 0.022'1 lC2
H0/4 A

I, I, l J (ACO SFt"O C8
H:f- " ~6
D3 (voge) "J9 ~

C19 SK L . -
1N5KG-11 $)
mop
ll'
I
~+7 .. D. I CNI
(SENSOR)
S30p ('09CI
I, I,
250Y

C18
R2S
SH D
'*' 'RlOOt:;
1 DS
(V09CI Cl
B f'' i,1,
330e C&
l 250 IDI

I ,:, I
s l l(p:PC110IC)
CI C. ~
GND OIZIALU

n
O.Ip: + I CI.
0 SO, ~cs 91K 25'
- R8
1 R20

:c __J --Ii
2 C20 0.1.-
10K 7It ,, 2200~

50' RS'
I[~I TH.a
,
PCN2 PULSE -
3 0'
OUTPUT 6 ,

,;.~TOR) 1- ,

r, '91, IC3
1 3 0. 01, .
AC INPUT
"
, 1]
(PC8 H 8 5
R26 Ii'
,i I
I, I, ct i
10K RSI
2.00~ I
R16
10K

l~~ j
D6 0.047-.
Q2 (voge) SOY
R' (2SCU5A) CIS ,
IW O. on.. IC2 I
I, I, .. 0
Y R2'
SOV 3 /1.
2~z/J
C'6
+
-
Q3 , 150t:: I
SO,
y (2SC945A.) C13
RIO
1 2 '-'J$
"
I, I Cl0
0.1.11
0.047 lOY
150~ ..:Rll F
C12
D. D47 R29
SOY 1.
. ~
'R'
~'O,

l-J:Ji I
fSOOK

r:
R3 DI 50Y I~

lOW IS5277NTPA,21 R9 1/2W.390"


S. It ,~

I W
r -9V V,
1 S {4/41
IC2
/11 I
--<l , Test
, PIn
R30 1/2W. 3901::
10

VJ
Reverse Phase Protection Relay Board: PCB6 RS
120K R.
180K
R1 R2
R o---t-.-1INv--J~\M,--~
.. K H'
VAl
C1 C2 C3 C.
S D--+--1f-j 1---1 f - j "

O. I p O. 1p O. I p O. 1p 0--''-<08
VA2 , -------,---
T o----l...---.-~R y}--r----J L----Q7

R3 C5

120 O. 1 p
HITACHI 3-23
--
(3.9 Circuit Diagram for Printed Circuit Board of Indoor Unit and CH Unit)

3.9 Circuit Diagram for Printed Circuit Board of Indoor Unit and CH Unit
I

i
Comiol Board (Low Voltage): PCB (~v1) of Indoor Unit, PCB1 of CH Unit
1
IW 300.

""
w,
In I
i-" ~IVB10
I
01,(1)' (11.j.: @

0
". e '"
vs VI" T
I '1 ~OV .10~

: _:) 01,1'/ ~-)-, cur: ", uNO


'" lG ,
11V: :.~IVB10 R15
,, '0
.~
~ 101:
, 's DI.l)
~lYBIO ~
RlO
21"- ,1 THMa
,
, zv I [EJ '- .J 2"-~ THI.l7

~t---':-----"-'-----+----------,=:-----i--o
" 1,.--- I _.J THUG
L" '- .I r'-~ THI.l$
"
'n" i l l lI
1,.--
---
,1 I..
2j-~-
J THJ,U

_~Tt1t.l)
~ LED. I..
J
TITTU LFfW--W--!-4 "',;'"
t \
",-en,l, ,
o. I,. I
au R)l RJ]
10( 4)1: 1)1:
III III I"
,.
'u

I 0 "" J: "
'0<
-
e)
."
1rIi
I 111.
"
SO! ~. 1" E =8J I (52
I~OOOP
leno.on"
.1(]7 0.00" I je: III
"a
I DOl
~~.PWKXO-
w~~Www
. cr~~:
.
~o_~~.
nn.~mmmmm
~
'41-")
1000p

'" > ~ ~ >


w

IC ,
I
HDli0180~

I
I

(NIl T
Rl0~

'" ,/
RT~:~
..,

G.I--
G,f--
1\"
I IOOOp
I
ATI
"
.l
."L,,,,
AI G,
~..";!'-+---+--I+1I+,.---"~''t, ,.
,;~
:! 100
~~
1,
I '"IDOOp !c"a
I
.. Ow o_ <>_

;J Il~l
I oOOp w~>w> ~~~~~~~>~~

, JOl
o QUIA '"
, J

RU
,U ,0< RI.
" " "
Dhll'
I '"
?1~'u~====~~H
DTAIU QUIU
, " RI' .1l
'" u

~ ..... R7
~
~
... III ,lL....o...J!.L
~ . ..---- "Tcr"
RIOl ~ tm '" ~".~
DTA~ f'C--- szJ P<J
lOt
b 025.026
2 , H5M1836
ok!
8 7 6 5 I 3 2 I
I2l OT_OI8
I J 1 I H51.128)&
~I 1 1
'Ot
D21_02t
I H5lol28l&
"J
OT AI14 I IOOOPT
:'Sr
R70
.1lI.
)
5
p(n1

. ~ -~ , ~ ~ -I' ~ I - ,
'''' ;-1\
1.5I:j"
I 8
C58 G LED?
YE
OS'W'l-_1-' OSw1 ~ _ pDSW' L _ '~D5"'J PC, tp~ ! O. 041J11 R82 RU
SZ QII II: '.1
2 1 2SC1618J:
.-:: (55
RU. ::b~1 ~ o.on,
-
,u '" I[ 10. ou,.
'"
'"
11<
11<
'" ." ~
'<1 11< '" '"
'" ",
'-I
(11
8
J C 10
I
'<J 11<
'" eN' )
p t> b asv
ORG
(La:]
OJ.
Do
I t.I~t.l, e.911 s
r
3-24 HITACHI
(3.9 Circuit Diagramrfor Printed Circuit Board of Indoor
- Unit and CH Unit)
Power Supply Board (High Voltage): PCB (P) of Indoor Unit, PCB2 of CH Unit

, I) PCN?
R o)f-'-l------------.

L1

ZNRl R204 CN20


3 L2 10K
S 1
R205 R206
TBl ZNR2
0
R202 1 K + 10K 2
DSA C202 C203 4.7fJ.
PCN1 820K O. 1P SOV
L3 SOV
f-' 49FE o 1 3
lK O.l.1l
PC4
2W 630V PC814
4
FS
PCN3
3

YSHi YSHi
R209 R210

YMe

3 R213 R214
fi YLo
YMe
Me YSo
YLo
YMS
YSo
R219 R220
YMS 11

YH2
3
YH2
f; I(~ R20?~R220:2KQ

Y52H
HITACHI 3-25
-
(3.9 Circuit Diagram for Printed Circuit Board of Indoor Unit and CH Unit)

Valve Control Board (High Vottage): PCB3 of CH Unit

52H 3

,, ,,

H2
20D2

3
SK2
MS
,
PCNS 1, ,

20D1

SHi 3

SK4
1 ,' ,
.~
PCN3 20S2

SK3 3

07
1 ,' . .
20S1

3-26 HITACHI
3 . 1 0 Circuit Diagram for Printed Circuit Board of Remote Control Switch
--
Cllh~12
PC-2H

IIp IIp

v. 1m rot
L
R60
v. 10K v.
R59 R53 22KX5
C17" 100 R54....
iC2 R55
8 l R56
CI: MB3773 R57
SOy CI41.
0.01" 1000pl v.
LCD
2KX3 iC4
10K 10K R50 I
R5 R6 R51 ' I
i CII -- R40 V. I
R52'
+C10
-16V

V\ V\ 13
IOKX4 10K
R63 v, b~ ~ ~ .~ 10", ,--~
77 10K 'i'S w7l sw8fSW9 R47 R49
76 .J,. ,J, IOV12 100 100
HD61603 '---
S 27
26 " ?VC
25 , v, C8l o! R48 L1
~
3
~*
O. Vc
VIa f9 4.7
Ua 1
~~
0> R36 Vs IflH ?TL
~ Q. I SOy
0.
r DTAI14EK k- O' 10"0.01,,
R46 L2 RJ~I
R35 IOKX3 R42 Q. -4.7 H?
R34 I ~
TG
IK l2SC C7 Ifl
2618C 50V
C22 L D, 0. 047fl
RI2 1000Pl
10K RI3
10K
c13.1
R30
10K v.
1
IOOOP l

RI6
RI7
RI8
100KX3
JP I;> JP2~
JJl .I
L~l
RI9
=
LED2
R20
lKX2

HITACHI 3-27
No. Contents Page
1 TROUBLESHOOTING
2 SERVICING 2-1-2-107
3 MAIN PARTS 3-1-3-27

4. OPTIONAL FUNCTION . 4-1


4.1 Indoor Unit . 4-1
4.1.1 Remote Control ONfOFF Function . 4-1
4.1.2 Automatic Restart Function (after Power Failure) . 4-3
4.1.3 Control by Field-Supplied Room Thermostat . 4-3
4.1.4 Operation Control by Remote Temperature Sensor . 4-4
4.1.5 Cooling or Heating Operation Mode Setting Change by External Input . 4-4
4.1.6 Picking Up Operation Signal . 4-5
4.2 Outdoor Unit . 4-8
4.2.1 Forced Defrosting . 4-8
4.2.2 Defrosting Condition Changeover . 4-8
4.2.3 Test Running of Outdoor Unit .. 4-9
4.2.4 Indoor Unit Fan Control When Indoor Unn at Heating Thermo-OFF . 4-9
4.2.5 All Season Heating (Cooling for FX Only) Mode . 4-9
4.2.6 Forced Stoppage of Compressor . 4-10
4.2.7 Operation Mode Lock . 4-10

4.2.8 Picking Up Signals from Outdoor Unit Printed Circuit Board


4.3 Remote Control Swnches, PC-2H and PC-2C
4.3.1 Name of Part
4.3.2 Simultaneous Operation
.
.
.
.
4-11
4-13
4-13
4-14
4.3.3 Operation System with Two Remote Control Switches . 4-16
4.3.4 Optional Functions of Remote Control Switch . 4-17
4.4 7-Day Timer, PSC-3T . 4-19
4.5 Central Station, PSC-3S1 .. 4-21
4.5.1 Name of Parts . 4-21
4.5.2 System . 4-22
4.5.3 Operation Procedure for the Central Station . 4-24

HITACHI
4. OPTIONAL FUNCTION
4. 1 Indoor Unit
...- (4.1 Indoor Unit)

4. 1 . 1 Remote Control ON/OFF Function

This function provides a control to stop and start the system automatically from a remote place. Three
methods are available by using each signal from a building management system.

(1) Remote Contrail (Level Signal Input)


This is an ON/OFF function from a remote place by using level signal (or ON/OFF). The basic
wiring is shown in Fig. 4.1 and time chart in Fig. 4.2 and the required parts are shown in
Table 4.1.

r
Power Source
When the unit is started by the remote
ON/OFF switch. the fan speed is subject
eN4 220'240V
.1~J to the mode memorized in the remote
control switch.

Fig. 4.1 Remote ON/OFF

Operation prioriTy is given to the remote


cemrcr of Remote
ON/OFF signal or remote control switch
Control Switch -:O"'N'~--'! signal which is given last.
Operation OFF
afUnil

Fig. 4.2 Time Chart


NOTES:
1. This function is available when "4.1.2 Automatic Restart Function (after Power Failure)"
is applied.
2. Picking up signal within 10 seconds after power supply is turned ON is not available due to
initializing of components.

(2) Remote Control 2 (Pulse Signal Input)


This is an ON/OFF function from a remote place by using pulse signal. The basic wiring is shown
in Fig. 4.3 and time chart in Fig. 4.4 and the required components are shown in Table 4.1 .
0$_2 on peElell) Indoor Unit
ON
.----.,.

PC B in EleClrical
9o.to"ndootUr.~ rTI The pulse width shall be
~ ~ wider than 200ms.
#ON L
Connector Power Source
"''''",--'.10 CN-4 un OFr 2201240V
3P Housiro:I
pins .,2,3 XI
Set 1IQ6 It OFF side <:0-00.
xl
Fig. 4.3 Remote ON/OFF

$ional to let.inlls 2 ,nd 3 ot CN4


---.flL_--'n,
.
_
(Operation Si;n41) :
Signll to hr.inals I and 2 It CN4 -i-"" L_-:- ~
(Stopp;ng Signll)

Ooetu;on of Unit

Fig. 4.4 Time Chart


NOTES:
1. This function is available when "4-.1.2 Automatic Restart Function (after Power Failure)"
is applied.
2. Picking up signal within 10 seconds after power supply is turned ON is not available due to
initializing of components.

HITACHI 4-1
- (4.1 Indoor Unit)
(3) Remote Control 3
By using the signal from a building managementsystem, the air conditioners can be stopped.
If a signal is input during stoppage of air conditioner, the air conditioner remains unchanged.
The basic wiring is shown in Fig. 4.5, time chart in Fig. 4.6. The required parts are shown in
Table 4.1.

The pulse signal shall be


IOFF i
Power Source
longer than 200ms.
Set .6 at OfF ,ide 2201240V

Fig. 4.5 Remote ON/OFF

Signal to Te~lIinaJ 1 and 2 at CN4 -------.....JfL-


Operation by ReIDote Control SWitch---fL--.fl---.f1L.-.i....._ _
, ;
Operation of Unit

Fig. 4.6 Time Chart


NOTES:
1. This function is available when automatic restarting after power failure is used.
2. Picking up signal within 10 seconds after power supply is turned ON is not available due to
initializing of components.

Table 4.1 Specifications on Required Components

Component Manufacturer or Specifications Remarks


Auxiliary Relay (X1, X2) OMRON Mini Power Relay
Model: MY1 F or Equivalent Voltage
220Vor 240V
ChangeoverSwitch (SS2, SS3) ManualType
3P ConnectorCord Optional Part PCG-l Five Cords with
(Able to Connect JST ConnectorXHP-3) Connectors as one set
Cord Low Voltage 0.3mm' less than 24V
(Indoor)

Cord
220V/240VClass
Low Voltage
0.5-0.75mm'
0.3-0.75mm' less than 24V
e
(Outdoor)
220V/240VClass 2mm'

NOTES:
Make the wires CN4 as short as possible. Do not install the wires along the 200-400V power line.
Separately install them at a distance of more than 30cm. (Intersecting as applicable.)
If the wires are installed along the power line, put the wires in a metal tube and connect a wire to an end
for grounding. The maximum wiring length is 70m.
In the case that this function is used, it is recommended that safety devices such as electric leakage
breaker or smoke detector, etc be used.

I 4-2 HITACHI
......
r
,
4 . 1 . 2 Automatic Restart Function (after Power Failure)
_ '
"t' _ _ ... '"...... . '

(4.1 Indoor Unit)


._

"
.n:
..'
.... . ._
. .' ... _
- . ,,'

Set the dip switch on the PCB for the indoor unit as shown in the figure below to restart the system
automatically even if power failure continues for more than 2 seconds.
The standard setting provides automatic restarting in less than 2 seconds after a power failure.
The compressor starts in 2 seconds after a 3 minute time guard after power failure.

Indoor Unit NOTE:


Set NO.5 at OFF Side In the case that the dip switch is set at the automatic
DSW2 restart function, the unit will be automatically restarted
after power resupply or tuming ON the power switch

BBBB BBB ON
OFF
even if the unit is stopped by using the remote control
switch, etc. before power failure or tuming OFF the
1 2 3 4 5 6 7 8 main switch, except the case of that the "REMOTE" is
indicated on the LCD of the remote control switch.

4 . 1 . 3 Control by Field-Supplied Room Thermostat

In the case that a field-supplied room thermostat instead of the inlet thermistor of the indoor unit is
used. connect wires as shown below.

3P c~nnector~~~3:::::::::::::::::::::::::::~~
~ Q
r--l
HOUSing Thermostat

o 1
0 o
---l
: '- I

~m~~ Increasej

o PCB for No.30FF


Indoor Urlft~oN
Connector
CN3 '.
BBIIBBBBB OFF
12345678
DSW2

Fig. 4.7 Field-Supplied Room Thermostat

Operation
Cooling Operation: Compressor is ON by closing terminals 2 and 3 at CN3
Compressor is OFF by opening terminals 2 and 3 at CN3
Heating Operation: Compressor is ON by closing terminals 1 and 2 at CN3
Compressor is OFF by opening terminals 1 and 2 at CN3

NOTES:
1. When setting the dip switch DSW2, turn OFF power source and set the dip switCh. If the dip switch
is set without turning OFF the power source, it does not correctly function.
2. When a field-supplied room thermostat is used, select the specified thermostat as below.
Contactor Load: DC24V 50 to 6 mA
Differential: more than 1.5 degree
3. Do not use a thermostat utilizing mercury.
~ 4. This function can be used together with "4.1.1 Remote Control ON/OFF Function".

HITACHI 4-3

1
- (4.1 Indoor Unit)
4 . 1 . 4 Operation Control by Remote Temperature Sensor

By using an optional remote temperature sensor, the following are available.

(1) The unit is controlled by the average temperature of the inlet air thermistor and remote temperature
sensor.

(2) In the case that the discharge air temperature exceeds 60"C, the fan speed increases from
"Medium" to "High" or Low" to "Medium".
II

NOTES:
1. In the case that the outdoor temperature is high, the high pressure switch may activate.
2. Operation sound, changes according to fan speed.
3. During the heating operation, "Heating Temperature Calibration" is automatically cancelled.
(Ref. Page 4-17)

PCB

1""---_ Remote Control


Switch
.'
Remote 1
Sensor Inlet Air
Temperature
Thermistor

4.1 .5 Cooling or Heating Operation Mode Setting Change by External Input

By utilizing this function, the cooling or heating operation mode can be changed by giving a contact
signal from the outside to the unit. The operation mode is followed by the field-supplied switch or the
remote control switch, which is used last.

Printed Circu~
Board PCB(M) in
Indoor Unit

CN4
I
Power
Source
110001 3

Signal to 1 & 2 of CN4 Heat


Cool
_----iW$&/ff#7~
Control by R.C.S Heat -~--'~ ,

Control by R.C.S Cool --01~_----l~_~-'--_


Operation Mode of Unit Heat
Cool

4-4 HITACHI
4 . 1 . G Picking Up Operation Signal
.- (4.1 Indoor Unit)

(1) Picking Up Operation Signal


This function is utilized to pick up the operation signal. By this function, operation signal at a
remote place can be checked, or operation at the fresh air intake fan motor can be interlocked.
Connect wires as shown below. The required parts are indicated in Table 4.2. Please note that the
contact of the auxiliary relay "RYa" is closed when this operation signal is given.

CNG Connector

PCB(M) PCB in
Indoor Unit

o o

o a

3P Connector
Housing
JST-XHP-3
Auxiliary Relay

Fig. 4.8 Wiring Connection for Picking Up Operation Signal

Table 4.2 Required Parts for Modification


Parts Name Specifications
Auxiliary Relay OM RON made High Power Relay Model LY2F DC24V

(2) Picking Up Alarm Signal


This signal is utilized to pick-up activation of safety devices and is normally indicated on the remote
control switch. However, this function is not available under abnormal transmission conditions.
Connect the wires as shown below. The required parts are indicated in Table 4.2. Please note that
the contact of auxiliary relay, RYa is closed when one of the safety devices is activated.

CN7 Connector PCB for


Indoor Unit

o o

o o
o IRYa

~
.:..~i_n ~RY--~I
. Auxiliary
3P Connector - - - - Relay
Housing
JST-XHP-3

Fig. 4.9 Picking Up Alarm Signal

HITACHI 4-5
_ ', '. -

(4.1 Indoor Unit)


, - "'-':
.

(3) Picking Up Heating Operation Signal


This function is utilized to pick up the heating operation signal. The contact of RYa is closed when
heating operation signal is ON despite 'Thermo-ON" or 'Thermo-OFF". Connect the wires as
shown below.

CNS Connector PCB for


Indoor Unit
PCB(M)

o o
o IRYa

-----m'_~i_"----1~ -_~_~_r__
I L ~ Auxiliary
3P Connector Relay
Housing


JST-XHP-3

Fig. 4.10 Picking Up Heating Operation Signal

(4) Picking Up 'Thermo-ON" Signal during Heating Operation


This function is utilized to pick up the heating 'Thermo-ON" signal of compressor running to control
a circulator or a humidifier. Connect wires as shown below. The required paris are indicated in
Table 4.2. The contact of RYa is closed when 'THERMOSTAT" is ON during heating operation
mode.

CNS Connector PCB for


Indoor Unit
PCB(M)
o o
eNS


@l

o o

iW P
--;P'
T-'-----I~AUXiliary
/ "

3P Connector Relay
Housing
JST-XHP-3

Fig.4.11 Picking Up 'Thermo-ON" Signal during Heating Operation

NOTE:
'Thermo-ON" indicates that one of the micro-computer control function 'THERMOSTAT" is ON as a
thermostat.

4-6 HITACHI
1
(5) Picking Up Cooling Operation Signal
-m--- _-_--l-,-~-, - _.'_
(4.1 Indoor Unit)

This function is utilized to pick up the cooling signal. The contact of RVa is closed when cooling
'-_~, __ '_n__-_'_}':~,:~

operation signal is ON despite "Thermo-ON" or ''Thermo-OFF''. Connect the wires as shown


below. The required main parts are indicated in Table 4.2

CNS Connector PCB for


Indoor Unit

o o

o o
__~~a

RY
Auxiliary
3P Connector Relay
Housing
JST-XHP-3

Fig. 4.12 Picking Up Cooling Operation Signal

(6) Picking Up ''Thermo-ON'' Signal during Cooling Operation


This function is utilized to pick up the cooling ''Thermo-ON" signal of compressor running. Connect
the wires as shown below. The required parts are indicated in Table 4.2. The contact of RVa is
closed when ''THERMOSTAT'' is ON during cooling operation mode.

CNS Connector PCB for


Indoor Unit
PCB(M)
o o
eNS

I. o
ll

21~--~..tL
o

Auxiliary
3P Connector Relay
Housing
JST-XHP-3

Fig. 4.13 Picking Up ''Thermo-ON'' Signal during Cooling Operation

NOTE:
''Thermo-ON'' indicates that one of the micro-computer control function ''THERMOSTAT'' is ON as a
thermostat.

HITACHI 4-7
.. ~
(4.2 Outdoor Unit)
4.2 Outdoor Unit
4 . 2 . 1 Forced Defrosting

By pressing the switch, PSW1 on PCB1 for the outdoor unit for more than 3 seconds during the heating
operation, defrosting operation is started if the forced defrosting conditions meet requirements.
By pressing the forced defrosting switch, PSW1 during the defrosting operation, the defrosting operation
is stopped immediately and heating operation is started.

Forced Defrosting Conditions Reselling Condition to Forced Defrosting


(1) 4 minutes after start-up, and 10 minutes after defrosting is started,
(2) Evaporating Temperature or
THM 1 or 3 during heating Within 2 minutes after defrosting is started: The thermistor for
operation is lower than 10"C, and evaporating temperature during heating operation is higher
(3) Discharge pressure is than 20"C.
lower than 22kg/crdG. From 2 minutes to 10 minutes after defrosting is started: The
thermistor for evaporating temperature during heating
operation is higher than 10"C.

PCB 1 in Electrical
Box for Outdoor Unit

Forced
P~I-l-If-- Defrosting Switch
L..-_"";";;';';';'---J

4 . 2 . 2 Defrosting Condition Changeover

By changing the position of NO.5 on dip switch, DSW5, defrosting operation conditions can be changed.

Standard Specifications Cold Area Specifications

IBBBB~BI IBBBB~BI
..
Dip Switch ON Set NO.5
Setting OFF at ON side.
1 234 5 6 1 2 3 4 5 6
DSW5 DSW5
Defrosting Defrosting
Termination Area Termination Area
15 15
Outdoor Heat Outdoor Heat
ExchangerLiquid 10 ExchangerLiquid 10
Temperature Temperature eC) Temperature eC)
(Pipe) S (Pipe) ~ 5
Conditions ~
under 0 56 10 15 0 5 10 15
Defrosting -15 -10 -5 -2 -15 -10 -5 -2
Operation ++

Defrosting Defrosting
Operation Operation
-15 StartingArea Starting Area

(1) NO.5 of DSW5 is set at OFF before shipment.

(2) Turn OFF the main switch and set the dip switch.

4-8 HITACHI
L
1
4 . 2 . 3 Test Running of Outdoor Unit
_ .. (4.2 Outdoor Unit)

i ,( ~ Using the operation dip switch DSW4 on the outdoor unit, the outdoor unit can be operated in the test
running mode.

DSW4
Contents
1 2 3 4
ON OFF - OFF The cooling operation test running signal is transmitted to the indoor units.
ON ON - OFF The heating operation test running signal is transmitted to the indoor units.
OFF OFF - OFF The test running is terminated.

NOTE:
Do not set the DSW4 at the test running mode of heating operation when using PC-2C, Remote Control
Switch.

Operation during Test Running


The unit is not turned off when outdoor temperature increases during heating operation and decreases
during cooling operation. The operation is not controlled by outdoor temperature.

,:~.
4.2.4 Indoor Unit Fan Control When Indoor Unit at Heating Thermo-OFF
1 Under operation condhions below, by setting No.1 and No.2 01 dip switch DSW4, the indoor fan
I operates lor 6 minutes and stops for 2 minutes in cycles to discharge excessive heat in heating

I operation.
Set No.1 at "OFF"
and No.2 at "ON" Side

I 1 2 3 4
DSW4

Operation Conditions Operation


The compressor is operating due to a thermo-ON When the indoor unit is at thermo-OFF during
unit except for the delrosting period the heating operation, the indoor fan operates
and stops for 6 minutes in 2 minute cycles.
NOTE: Stanat Random
ON

,II).
When the indoor Ian is turned off by another
control, it cannot be turned on by this control.
OFF
J il i1 il
I OFF -I 2-I I. r I- -I-21
I 6 6 2 6 6
(min.)

1
4 . 2 . 5 All Season Heating (Cooling for FX Only) Mode

By operating No.3 (No.4) of dip switch DSW5 ON


Thermo-OFF
on the PCB of the outdoor unit, the thermo-
1iI1iI!!!!1iI1iI1iI
123456 ON
OFF- t 1Signalto Indoor Unlt
ON/OFF setting of standard heating (cooling) Standard
Diagram of
operation is cancelled and a year-round Heating 23 26
heating (cooling) operation is set. Operation OutdoorTemp. eCl

oN~FXOn~)
CAUTION iii iii!!!! iii Thermo-OFF
S
r~~F
123456 Signal to Indoor Unit
In the case that outdoor temperature becomes Standard
/) high (low), the system will stop. Diagram of
-8 -5
Cooling
Operation of OutdoorTemp. ("C)
FXSystem

HITACHI 4-9
i
J.
- (4.2 Outdoor Unit)
4 . 2 . 6 Forced Stoppage of Compressor

When the indoor unit is operating under normal conditions, the start and stoppage of the outdoor unit
can be confirmed by manually starting or stopping the compressor.

Use field-supplied switch, connector and


When the indoor and outdoor units are
cable for the following wiring.
operating, the compressor can be stopped
by short-circuiting pins No.1 and No.2 on L~onnector
the connector CN1 07 of the outdoor unit
I
~2
I--
printed circuit board. CN107rn]
(The indoor units will be stopped.)
~
When the start and stoppage of the outdoor
PCB1
unit is confirmed by performing a manual
start and stoppage of the compressor, remove Printed Manual Stoppage
Circuit Board Sw~ch
the short circuit pins NO.1 and NO.2 of
(low Voltage) (Field-Supplied)
connector CN1 07.

CAUTION
1.

2.
These procedures are performed w~hout turning off the power source. Therefore, do not touch
any electrically charged parts on the units.
Do not restart the compressor within 3 minutes after compressor stoppage. Do not perform

excessively frequent ON and OFF operation of the compressor.
3. Even if the compressor is turned off, the operation of the indoor unit can be confirmed.

NOTE:
The compressor can be stopped by setting DSW4 switch #4 at ON position. This is useful for
prohibiting operation by the remote control switch during servicing.

4 . 2 . 7 Operation Mode Lock

The operation mode, cooling and heating, of the outdoor unit can be rocked by using CN123 on PCB1.

NOTE:
The indoor unit is stopped by thermo-OFF Use field-supplied switch, connector and
cable for the following wiring.
when:
Connector
CD The outdoor unit cooling operation mode
(JST-XHP-3)
is locked, and the indoor unit operation 3

CN123~
mode is heating.
The outdoor unit heating operation mode
is locked, and the indoor unit operation
mode is cooling. PCB1

Printed Operation Mode


This stoppage can be checked by the
Circuit Board Lock Switch
indication of "d1 20" in "Check Mode 1" (Low Voltage) (Field-Supplied)
on the remote control switch.

4-10 HITACHI
1
4 . 2 . 8 Picking Up Signals from Outdoor Unit Printed Circuit Board
-- (4.2 Outdoor Unit)

Arrangement in Outdoor Unit Electrical Box


. Fan Contro
<, ~
-, ~~ PCB3
'-0+ pe N317...... Inverter
11""- LJI- f'CN.lJn '" PCB5
<,
~ ...1+
",
peNj15

J+ peN:!1/, - PCB I
,-UI- "Ct~31.1 Control
1"-"
Power Supply Board of Outdoor Unit (pe82) --- -- "
Pour $UDp1'l
PC", ~EJ PCB4

,
DC Power Supp I y

The parts applied to picking up operation signals are shown in Table 4.3.

Table 4.3 Main Required Part

Part Name Manufacturer etc.


Auxiliary Relay OMRON High Power Relay
Model: LY2F AC220-240V

(1) Picking Up Alarm Signals


With this procedure the indoor unit alarm signals
can be picked up. The method is explained in o o 3P Connector Hauling
Power Supply Board JSrYHlt-3N
Fig. 4.14. The required part is indicated in (Contact SVH-21T-Pl. 1)
of Outdoor Unit (pe82)
Table 4.3. Connecting relay contactors (RYa) are
open at the time of alarm. (When either one of
the units issues an alarm, an alarm signal is
o
indicated.) Connector PCN314
Auxiliary Relay

II~. Fig. 4.14 Alarm Signal Pick Up Method

(2) Picking Up Operation Signals


(PCB of Service Parts Only)
W~h this procedure the operation signal of cooling
o
or heating can be picked up. The method for
Power Supply Board
picking up the signal is explained in Fig. 4.15. of Outdoor Uni t (peB2)
The required part is the same as in Table 4.3.
Connecting relay contactors RYa are closed at the o
time of cooling or heating. These signals can be Connector PCN317
applied to the operation of circulators and Auxi I iery Relay RY
humidifiers.
Fig. 4.15 Operating Signals Pick Up Method

)~
I

1 HITACHI 4-11
--
~',__ '" --..> , , - ,

(4.2 Outdoor Unit)


",.},E : _' '~'_ ~ '.

(3) Picking Up Compressor Running Signal


(PCB of Service Parts Only)
Co,," _, _
1

With this procedure the compressor operation


signal can be picked up. The method is explained
o o 3P Connector Housing
in Fig. 4.16. The required part is the same part JST-VHR-3N
Power Supply Board
(Contact SVH-21T-Pl.~
of Outdoor Uni t (PCB2)
as in Table 4.3. Connecting relay contactors RYa I
are closed at the time of compressor running. =1--,
This signal can be applied to the confirmation of o Pin J

signals at the time of remote controlling and to the Connector PCN315


AUK iii ary Re I ay
.fan interlock of outdoor air.

Fig. 4.16 Compressor Running Signal Pick Up Method

(4) Picking Up Defrosting Signal


(PCB of Service Parts Only)
Wnh this procedure the defrosting signal can be
o o 3P Connector Housing
picked up. The method is explained in Fig. 4.17. JST-VHR-3N
Power Supply Board
(Contact SVH-2IT-Pl.l
The required part is the same as in Table 4.3. of Outdoor Unit (peB2)
I

o
Connector PCN316
Auxiliary Relay

Fig. 4.17 Defrosting Signal Pick Up Method


NOTE:
The standard unit is not equipped wnh functions (2), (3) and (4), because these are very rarely required.
If required, we are pleased to comply with the requirements by utilizing service spare parts.

4-12 HITACHI
[tl.'_
:: .-..-,.-, -- - ,. r_ . _, A -. .-."'-

(4.3 Remote Control Switch)


4.3 Remote Control Switches, PC-2H and PC-2C
4.3.1 Name of Part

liquid Crystal Display (L.C.D) Section


CHECK Indicator
TEST RUN Inc:ricator
Alarm Indicator
Timer Indicator
Temperature
Indicator
Number of System
Indicator

Remote Control Indicator


Mode IndicatClf

Fan Speed Indicator -+-


SWING
lOUV(R _ ..--t-- DEFROST Indicator
FILTER [ndicatOf ---t- ~--tIIIllillD 1t--t-- Power Monitor

v TEMP

t--+--t- Filter RESET Switch

.---SWING LOUVER Switch ---j-+-1t


.-+-(AUTO COOL/HEAT Switchl
t--+--+- CHECK Swilch
FAN SPEED Switch ~-r--l.;====:=! ~======j--tTIMESwitch
Peel a patch On for the unit with
swing lower.

Concealed with a patch and not Remote Control Switch (OpUon)


available fOt this "FS series.
available for "FX series only.
Models :PC-2H:lor Heat Pump Type ]
[ PC-2C: for Exclusive Cooling Type

NOTES:
1. In-the-Ceiling type indoor unlt RPI-O.8FS and RPI-1 FS have approximately the same fan speed
when "MEDIUM" and "LOW" are pressed.
2. Distinguish the revised remote control sw~ch after from before, w~h HITACHI mark at the upper

(~. left of L.C.D, as below.


And see page 4-17 for the difference of optional function.

Before Revised After Revised

'!' . -
. '; I '1""" =
=
'.". = = mm ==
lrDl GTIIl a:I3J
;1"::1
~;::'I'ii:'1 ;;",';;,; ;,;;: t,"::1

I.~~i~~~ ;)~::i;~c
:;":1' :;"~l:
~ . ,. CHI,,,!,,
,,,;,,::1
,
.... 111111 ~ lEIm 88s"I-,ne CO
'''J~:;l
,,111:11

- I'f:'rtsr'!, V f(VI'
1\
- ~l:~isr~' V mt' 1\

!
I
I (,'It\

r HITACHI 4-13
--
(4.3 Remote Control Switch)
4 .3 . 2 Simultaneous Operation

(1) Simultaneous Indoor UnttOperation with Remote Control Swttch

(All power sources must be turned off!!)

Up to 16 indoor units can be simultaneously controlled


using one remote control switch. The operation mode,
including the selectionof ventilation, cooling or heating, the
setting of air flow, the setting of temperature and the
setting of run/stopcan only be set uniformlyfor all units.
However, on/off operation of each thermostat can be done
indiVidually. Defrosting, protective devicesfunction, etc are
indiVidually performed.

a. Perform wiring between indoor units as shown in the following figure.

The total length ofthewire shall be200m or


shorter. (for O.75mm 2 wire 500m orshorter)
Use thefollowing three cable wire in thesystem
parts.

Model PRC-10E PRC-15E PRC-20E


Length 10m 15m 20m

Yel low Connector CH12


Blue Connector CN13

CAUTION
When O.3mm2 wires are used, the length between units must be 100m or
shorter, and the total length must be 200m or shorter.
(When O.75mm2 wires are used, the total length can be extendedup to 500m.)

b. Connectedunit controlwires should not be installed


parallel to 200-400V power cables. Fix them by
utilizing bands. It is recommended, that cables be
installed at least 30cm away from power cables or be
put into grounded metal pipes.

4-14 HITACHI
... ..
(4.3 Remote Control Switch)
c. Set dip switches DSW1 on the printed circuit boards of respective units as shown in the
~

following figure.
() (Turn off all power sources!!)

(Selting of Dip Switches) When indoor units are connected to the same outdoor unit, it is
unnecessary to set dip switches, because they are automatically addressed.

Master Unit No.1 Unil NO.2 Unn NO.3 Unn NO.4 Unit NO.5 Unit No.6 Unn NO.7 Unit

Dip All ON 1 OFF 2 OFF 1,2 OFF 3 OFF 1,3 OFF 2,3 OFF 1,2,3 OFF
SW
Setting 111111111
123~ 1:, IIIIIIIIIION
1234 OFF
ml
III1234 ON
OFF ml:.
III1234 1111111111:,
123 .-
11111111
1 1234 1:.
11111111
1 1234 1:. 1111111111:,
123 -4

NO.8 Unit NO.9 Unit NO.l0 Unit NO.ll Unn NO.12 Unit NO.13 Unit No.14Unn No.15 Unn

Dip 40FF 1,4 OFF 2,4 OFF 1,2,4 OFF 3,4 OFF 1,3,4 OFF 2,3,4 OFF All OFF
SW
Setting
11111111
11234 1:. Imill:'
1 23 .. 111I11III1
1234 :,
11I11III
1123 .. 1:. 1I11III11
1234 1 ~:, 1111111111:.
1234
11111111
1 123 .. 1:.
1IIIIIIIII0N
1234 OFf

CAUTION
Pay altention not to overlap addresses.

d. Confirming Method of Number of Connected Units


Perform this confirmation when test running units after finishing wiring, refrigerant piping,
additional refrigerant charge and other items required for operation.
Test Running Mode
(j) Turn ON the power sources of all unns.
Depress the CHECK switch and the MODE switch on the remote control switch simultaneously
for three seconds or longer, to change the unn(s) to the test running mode. (Refer to the
checking procedure by the CHECK switch.)
Number of Units Connected
@ When the number of units connected is indicated where usually the temperature is indicated, the
system is functioning normally.
False Number of Connected Units is Indicated
@ When the indicated number of connected units is smaller than the actual number or zero,
presumable causes are as follows:
1) The power source of some units is not turned ON.
2) Incorrect selting of unit numbers was performed.
3) Control wires between units or remote control switch were incorrectly connected regarding
polarity and order.

Ending of Test Running Mode


e. When the confirmation of the number of connected units and the wiring-checking are finished,
end the test running mode by depressing the "RESET" switch.

HITACHI 4-15
_IUiIIII
~,'~V;,;.::ik0
(4.3 Remote Control Switch)
4.3.3 Operation System with Two Remote Control Switches

(1) By installing an additional remote control switch, a maximum of 16 units can be controlled from two
different locations. Altering Methodto Sub Control Switch

-.
CutJumper WireJP1 with Nippers
Main and Sub Control Switch "-

Determine one of the two remote control


switches to be the main switch and the other as -,
a sub switch. Cut the jumper wire JP1 in the ~ Uquid Crystal
Display
sub remote control switch as shown in the
following figure.
d\P1 -CJ-

(2) Wiring Method


a. Plilrlorm wiring between units as shown in the following figure:
(Three Unit Case)

Control Cable Between Cabl. (3 Wires or 2 Wires)


Re_ote Control
Switc:h Cable
(3 Vires) Na.O Uni t D NeLl Unit No.2 Un i t Re.ote Control
(RD) o (R:) (R2) Switch Cabl,
(3 Wires)

Indoor Unit Printed


Circuit Board

~~~-Ch.ck Switch

Check Switch

Main Switch Sub-Switch


Connect the main remote control switch to CN13 (or CN12)
and the sub-remote control switch to CN12 (or CN13).
Wiring Method

b. Decide the number of units. The method should be the


same as in "Simultaneous Indoor Unit Operation with
One Remote Control Switch".

(3) Checking the Main and Sub Remote Control Switches


When, during the self-checking procedure of a remote
control switch, an '88" is displayed where usually the
temperature is indicated, it is a sub-remote control
switch. If a '77" is indicated, it is the main remote
control switch.

CAUTION
1. When a main remote control switch malfunctions, unit operation stops. Units cannot be operated
with only a sub-remote control switch.
2. When a main switch and a sub-switch are simultaneously operated, the units will operate
according to either one of the modes after 30 seconds.

4-16 HITACHI
1
I

,)
4 . 3 . 4 Optional Functions of Remote Control Switch
---
~i::::::L
. (4.3 Remote Control Switch)

The following optional functions are available with a remote control switch (PC-2H or PC-2C) .

Changeover to Option Modes Setting


After
For R.C.S Before Revised 7 Seconds

Remove
Normal Mode
~
I

Simultaneouslv Deoress
I
.. LUt1lJJ
RESET Switch,I
I~
RESETI and I CHECKI
Switches for 3 Seconds
or Lonoer
Unit No. (01 Some Optional
Functions are Set)
(00 Not Set)
De ress
t
CHECK Switch
,.....------..,
~
OptionSelling Mode I
I
Depress r
V TEMP 1\ I
I, Switch to Set UO, U1, U2
Selling
, ... UU Optional
(01 Set)
Item
!~(. UU: All Indoor Units (00 Not Set)

I
I
I
Depress
V TEMP
t
1\
I Switch to Set

I
i, No.
Table 4.3 Optional Functions with Remote Control Sw~ch

Item Display on Remote Control Switch


I,
(1) Removal of Heating Temperature Calibration bl (NOT SEOOa -- 0: (SET)

(2) Circulator Function at Heating Thermo-OFF b2 (NOT SEnOa -- 0: (SET)

J3 Enforced 3 Minutes Minimum Operation Time of Compressor b3 (NOT SEnOa -- 0: (SET)

(4) Change of Filter Cleaning Interval Time b'l 00- 0: - 02- 03- 0'-/
(5) Fixing of Operation Mode bS 00 -- 0: (SET)
(HOT SEn

I".
l'r7I.la.
I
,
(6)
(7)

NOTE:
- -
Fixing of Setting Temperature
Fixing of Operation as Exclusive Cooling Unit
b6 (NOT SET) 00 -- 0: (SET)
b 7 (NOT SEnOa -- 0: (SET)

Optional Function NO.6 and 7 are for the revised remote control switch only. See page 4-13 to

II distinguish.

I
I
(1) Removal of Heating Temperature Calibration

I When the temperature settings of the remote control switch and the suction air temperature of the
indoor unit are required to be equal, this optional function can be used.
I
I In standard heating operation, the suction air temperature is higher than the room temperature,
I therefore the suction air temperature is calibrated -4"C.
(Indicated Setting Temperature = Inlet Air Temperature -4"C <=> O"C)
This is useful when the thermistor at the suction side of an indoor unit is removed and installed in
another place.

HITACHI 4-17

1
--
(4.3 Remote Control Switch)
(2) Circulator Function at Heating Thermo-OFF
In heating operation, there is a case that the room air is stratificated because warm air stagnates
near the ceiling. In this case, it is recommended that the circulator function explained below be
utilized .

Circulator Function
Units can be programmed so that a set level of air flow will be held on, when the heating is turned
thermo-OFF. In this case, air movement in the room will be kept on the same level as before,
ensuring a homogenous air distribution. Additionally, when the temperature of discharge air
decreases to 25"C or lower, the unit is programmed so that the air flow is automatically adjusted to
"LOW". In the case that an Auto Louver is equipped, this operation will be also held on when the
heating is turned thermo-OFF.

CAUTION
Perceptions of coolness, heat and air flow are subject to personal tastes and behaviors. It is therefore
recommended to discuss this with customers thoroughly and then to set the unit accordingly.

(3) Enforced 3 Minutes Minimum Operation Time of Compressor


When a compressor frequently starts and stops in short intervals, this function should be used to
guard the compressor. By selling this function, the mode of a minimum 3 minutes operation will be
added to the standard mode of a minimum 3 minutes stoppage.

(4) Change of Filter Cleaning Time


Filter cleaning time is set by the NO.7 switch of
Indication on LCD of
DSW2 on the indoor unit PCB, when the Filter Cleaning Time .Remote Control Switch
indication on LCD of Remote Control Switch is set Factory Set b't ""
LJ LJ
at "00 (Factory Set)".
Selling of No.7 Switch of DSW2
Approx. 100 hours b't "
LJ ,.
Approx. 1,200 hours b't 02
OFF - - Filter cleaning time is set at approx.
Approx. 2,500 hours b't 03
1,200 hours.
No Indication b't O'-{
ON - - - Filter cleaning time is set at approx.
100 hours.
However, this filter cleaning time can be changed
depending on the condition of the filter.

(5) Fixing of Operation Mode


When changes in operation modes are not required, this mode can be used.
The operation mode which has been set cannnot be changed.

(6) Fixing of Selling Temperature (Revised Remote Control Switch Only)


When changes in selling temperature are not required, this mode can be used.
The selling temperature which has been set cannot be changed.

(7) Fixing of Operation as Exclusive Cooling Unit (Revised Remote Control Switch Only)
When exclusive cooling operation is required, this mode can be used. This function invalidates the
heating operation and the automatic COOUHEAT operation, as the operation of exclusive cooling
unit.

4-18 HITACHI
4,4 7-Day Timer, PSC-3T

, ) (1) Name of Parts

Indication of I Indication
of
Present Time and Mode Selection
ON/OFF Setting Time

Indication of I
CONTROL TIMER OHITACHI
Present Day I Indication of
Running TIme
L- - ::IB:BB~m
' , Schedule and
Indication of
Running Day of
... "", .,,,'1""'
IIIQII.l16lDCIi=llloU "
~ Remaining Running
Time
I ~II 0
a Week

Setting Switch of
Present Time I
BIllIE
.... 81~'11~'1~
~Offlllill I Change Switch of
I Operation Mode

~8'--' I Setting
Setting Switch of I Switch of
Present Day of a JlI(SLVI Sl!..~ srr rOIl-TtME
1

~ '",n
ION/OFF Time
Week
';;;;i ';;wo.' I
Return Switch for ~~ "-"l' ~"'"~ ~ I I Monitor Switch of
Present Time,
Present Day. ION/OFF Time
Running Day and
ON/OFF Time
I I SET/CANCEL Switch
I I for ON/OFF Time
Selection Switch for SET/RESET Switch for kl
Running Day of a Week Running Day of a Week

(2) Functions
liquid Crystal Display Indication Function

Indication of Present Time and This indicates present time and


ON/OFF Setting Time
AM
PM I 'B'BB@J
'
ON or OFFsetting time.

Indication of Present Day This indicates the present day of a week.

.... ...
Indication of Running Day of a Week In the case that the running day is set, this light
is ON.
V. '0 1'..1 ~ lHJ 1A SoIl
' ~

Indication of Mode Selection In the case that "SET" is not shown, this indi-
cates "MONITOR" mode.
In the case that "SET" is shown, this indicates
"SETTING" mode,
In the case that "SET"' is flickered, this indicates
"CLOCK" mode.

Indication of Running Time Schedule In case of "MONITOR" mode, the operation


and Remaining Running Time time schedule is indicated.
In case of "CLOCK" mode, the remaining
running time is, indicated.

HITACHI 4-19
....
1
- (4.4 7-Day Timer)
Operation Switch
Present time is set by this switch at "CLOCK
Setting Switch of Present Time ~m~~nu3 mode.
~ (MI~urrl

Setting Switch of Present Day of Present day of a week is set by this switch
a Week
mM!l
IPREiNT)
Dll
at "CLOCK" mode.

Return Switch for Present Time, In the case that this switch is depressed and
Present Day. Running Day the other switch is simultaneously depressed
and ON/OFF Time at "SETTING" mode or "CLOCK" mode. the.
I I
R!1U1l "Present Time". "Present Day", "Run Day" and
"ON/OFF Time" are returned into reverse.

Change Switch of Operation Mode "SETTING" mode. "MONITOR" mode and


"CLOCK" mode are set by this switch.
In the case that "SET" is indicated after depress-


ing this switch, the control is changed to "SET
l~l TING" mode.
If "SET" indication is turned off, this indicates
"MONITOR" mode.

Change Switch of When this switch is continuously depressed for


Operation Mode longer that 3(three) seconds at the "MONITOR"
1%;;;1 mode, the "SET" indication is flicked and "Monitor"
mode appears.

Setting Switch of "ON or OFF Time" of running operation is set by

fEi~
ON/OFFTime this switch.

Monitor Switch of By depressing the "ON TIME" or "OFF TIME"


ON Time and OFr Time switch at "SETTING" mode, the set "ON Time" or
ION n!lltl "OFF Time" is indicated on the "Present Time and
MONTOR ON/OFF setting Time" indication area.
~"nM~


=
SET/CANCELSwitch By depressing the "SET' switch after adjusting the
"ON TIME" or "OFF TIME" switch at the required

0
:. ;l;iJD:
time, the "ON Time" or "OFF Time" is set.
By depressing the "CANCEL" switch, the set "ON
TIME" or "OFF TIME" is canceled at the "SETTING"
Ic.ucnl mode.
=
Selection Switch for Running days of a week are selected by this switch.
Running Day of a Week The" T" mark is flickered at the position of the
-ou~r~~ required running day.

SET/RESET Switch By depressing this switch, the selected running


R'~~OU days of a week are set or reset.
for Running Day
of a Week 1%;;1
NOTE:
In the case that power is turned ON to the system, set the 7-day timer at the OFF-TIME. If
not set, the unit is not automatically restarted until the OFF - TIME period is over, even iftime
reaches the ON-TIME setting.

4-20 HITACHI
4.5 Central Station, PSC-3S1
..,.....
~,',=::==
(4.5 Central Station)

This central station is of the soft touch type. (Operation except with finger is not recommended.)
Activation can be checked by referring 10Ihe liquid cryslal display and LEOs.

4 . 5. 1 Name of Parts

.INOICATION RUN IndicatIon -


RUN status is
Operation Mode Indication - Unit No. Indication- indicated. r - - MODE Indicator
FAN. COOL, HEAT, Of DAY The unit No. is Setting mode or
is indicated. indicated. monitoring mode
Temperature Indicator - is indicated.
This indicates a setting
70ay Timer IndicatiOn~:l temperature.
By touching PRGM TIMER L ---,
switch. TIMER is indicated. r- Alarm Indication
(With 7~day Timer) '-----, ABNML is indi-
cated when the
operat ion is
Control Switch Selection - abnormal.
By touching AMT.
SW AVLlNAVL, CENTRAL ~:rATION
AVL or NAVL is indicated.

1-
NOTE: The set part
Operation Status Indication and the part which
Operation status of each corresponds to actual
unil is indicated. operation are
:ON O:OFF indicated
---------1
Operalion Switch
UNIT Switch
Your required unit can
be selected by touching
::" Of QJ switch to
change operation mode
or setting temperature.
All units can be set at
the same mode when
RUN/STOP Switch-----...J
AA is selected.
By touching this switch,
the unit is started or
stopped.

- PRGM TIMER Switch


Operation MOde Switch This switch is used
8y touching this switch. only when the 1-Oay
FAN. COOL, HEAT, DRY Tlme- is used.
operation is selected.

I '-----TEMP. Switch

'(r~"
MNTRISET Switch By tOUChing
When seting mode is or 2; swirch. the
selected. the following setting temperature
are available. is increased Of
.Setting of FAN. COOL, HEAT decreased by 1''C
or DRY Operation The maximum setting
.Room Temperature Setting is 3O'C and the
.Permission or PrOhibition minimum is 17"C.
of Control by Remote
Control Switch
.Setting, whether 7-0ay
timer control is reowed -,lNOVL MNTA - RMT. SW AVUNAVL
or not. Switch Switch
By Pl'essing this By touching this switch,
When monitoring mode is sW1tCh, operation control by each remote
selected, the above mentioned status of the selected control switch is permitted
operation modes and setting group lor unit) is or not.
temperature are indicated. indicated. AVL Indication: Control by
.:ON O:OFF each remote control and the
Ouring individual Central Station is available.
monitOling operation, NAVL Indication: Control only by
indication of UNlr the Central Station is available.
is OFF.
NOTES:
In the case that the unit is operated under the following conditions, "REMOTE"
is indicated on the LCDand control by the remote control switch is not available.
1. NAVL is selected by the Central Station.
2. Two Minutes after Resetting of the Central Station even if AVL is selected

HITACHI
-'..
-
.---
- ~ ,. -~

(4.5 Central Station)


- _; .- .:: '. -,

4 . 5 . 2 System
-,
_:,u~ -,. ";----'
.:'
--.1-
.

(1) System of Up to 16 Units

Layout and Electrical Wiring

Central
Station

Connector Number
DSWl

PC-2 H '" PC-2C

'-\
Control Cable
2nd Unit

No.1

PC~2 H or PC-2C

I
I
I
I
I
I

16th Unit

No. 15


PC-2 H or PC-2C

Selting of Dip Switches


Set the unit number of all the units using the dip switch (DSW1) of indoor unit PCB.

1st Unit 2nd Unit 3rt! Unit 4th Unit 5th Unit 6th Unit 7th Un" 8th Unit
Dip All ON 1 OFF 2 OFF 1,2 OFF 3 OFF 1,3 OFF 2,3 OFF 1,2,3 OFF
SW
Setting 1111111111:;,
'23"
111111111:.
11 2 3 ..
Imlll:;, Imlll:;,
1234 1234
111IIII111
1234
ON
0FF IlIml:;,
1234 1111111111:.
1234 1111111111:;,
1234

9th Unit 10th Uit 11thUnit 12th Un" 13th Unit 14th Un" 15th Unit 16th unit
Dip 40FF 1,4 OFF 2,4 OFF 1,2,4 OFF 3,4 OFF 1,3,4 OFF 2,3,4 OFF All OFF
SW
Setting 11111IIII1 :. 1111111111:'
123'" 123 4
IlIml:,
1 2 3" 111m
1234 I:, 1111111111:, 1111111111:.
123 4 1234
IIIIIIIIIION
1234
0FF 11111111
11234 1:'
NOTE:
The above selting is same with the selting when the remote control switch (PC-2H) is used.

4-22 HITACHI
_."~'~~1W"~_ .. .
::.,I."... ~
(4.5 Central Station)
(2) System of more than 16 Units

Layout and Electrical Wiring


A maximum of 16 groups can be controlled by the Central Station and each group can consist of a
maximum of 16 units. ON/OFF control of each group is available. Furthermore, the operation
status of all indoor units can be monitored by the Central Station.
RemoteCon~::::::h Cable 13 WI,es)
/ of Group 1 Branch Unit Branch Unit

No. a No.1 No. 15


Central , 1 ~.

iiiiil
Station ~

Connector
Number
PC2H
or PC-2C
Control Main Unit
Cable

)-,
01 Group 2 Branch Unit Branch Unit
(3Wite~

\
No.1 No.2 No. 0
" l .
I ~6,.~!

' - - - - - - ' "----- - - - - ----'

PC-2H
or PC-2C
I
I
I
I
I
Main Unit
of Group 16 Branch Unit Branch Unit

No. 15 No.O No. 14

=
CN9
c::::JCNIO
....
I""101"
i;LPj
I

orPC.2C~
PC2H .I;
Setting of Dip Switches
Set the number by using the dip switch, DSW1 on the PCB in the indoor units. Firstly set the unit
number for the main unit in group 1 and secondly set the unit numbers for the branch units one by
one according to the figure below. Next, set the unit number for the main unit in group 2 and set
the unit numbers for the branch units one by one. However, please note that the unit number for
the main unit in group 2 should be set from the next number as shown below. Repeat this work for
the remaining units.
Start Here. (Group 1)

Start Here. (Group 2)

Start Here. (Group 3)

I .....
Unit No.
Dip
SW
Setting
Unit No.
NO.a
All ON

11l1l1l1l1~
1 23 ..

NO.6
No.1

[llllllllloNIllml ~,
1 OFF

1234

NO.9
0 FF
NO.2
2 OFF

123 ..

NO.l0
No.3
1,2 OFF

11l1l1l1l1~
123 ..

NO.ll
. No.4
3 OFF
Imlll
1234 Off

No.12
ON
NO.5
1,3 OFF

Illlllllll~
123 ..

NO.13
No.6
2,3 OFF 1,2,3 OFF

Illml:, IIlllllll]
1 234

NO.14
No.7

1234 OFF

NO.1S
ON
-
go to
No.8

1,4 OFF
1IllllllljoN Illml Illm/ ~, Illml:. IIlIlIlIlIONIllml :F IIlllllilI:, IllmloN
Dip 40FF 2,4 OFF 1,2,4 OFF I- go to
3,4 OFF 1,3,4 OFF 2,3,4 OFF All OFF
SW No.O
ON
1234 OFF 1234 OFF 1234 0FF 1234 OFF
Setting 1234 1234 1234 1234

HITACHI 4-23
...
,
--
:Z::::::,0S
(4.5 Central Station)
4 . 5 . 3 Operation Procedure for the Central Station

(Multi-Function Centralized Controller)

ISetting (or Changing) Operation Patterns I


Mode Operation Procedure Display Example
I . Press the mode selection switch [MNTR/SET]
to select the [SET] mode.
2. Press the unit selection switch [UNIT]
< or (l) to select the unit number to be set. CENTRAL STATION

(When setting all the units simultaneously, ClIlOl


lIIIiEII IJaE] UNl r r. tal ""'"
select the "AA' indication.) II1ml}MO 03 25. =
3. Press one or the operation selection switches
.." Ql!ulilo/l",t:oUll4lldiia mKJ

[FAN]. [COOL], [HEAT] and [DRY] to


select the operation mode. :::3 Qi.1J1VS1C~ r:n
<: UNIT

4. Press the temperature adjustment switch
'-t. 0..:;// i~
[TEMP] <@ or (l) to set the temperature. (In /~B~0~T:R
the [ FAN] mode, there is no need to set the
temperature. The temperature range which ~~nI 'l/III !'-=MoAio
,_, ,. .

can be set is from 17"C to 3O"C.) /. /.


When the temperature is not set by the
Setting multi-function centralized- controller <the
temperature is set by the individual remote
control switch). set the temperature to 17"C ,
or 30'C and press and hold the (l) or @ switch CENTRAL STATION

for more than 3 seconds to display " --


5. When the timer operation is to be performed 1I1ml}~o
,,;,.:- ,,':Sf
~

RR 25.
=
=
,.Il oc,,~,!,,;,!: =:: :::';.:i:E::
by an optional control timer. press the 7 -day
timer selection switch [PRGM TIMER] to
select the [TIMER] mode. O~UtVS;:~ r.:;z; U~; r r

6. \Vhen the operation by the individual remote :::..:: /// ~//

control switch is not required, press the remote ~B~~~~


control selection switch
[RMT. SW AVL/NAVL] to select "NAVL".
~~ IVT=~p.AID
;/////////////////////,
7. Press the [RUN/STOP] switch to set
RUN or STOP.

By doing this, the operation choices are set.


However, the operation choices cannot be sent to
the unit in this status. Press the mode selection
switch [MNTR/SET] to select the [MNTR] mode. CENTRAL STA'TION

=
:IIiE _CEiiti:i "'.' so.:of "'"'"
NOTE: ~J-. 03 25. =
When the switch is left unpressed for more than ..." """i>C:,,,.~=:O~~:i,"';:i

I minute in the [SET] mode, the mode will


Monitor automatically change to the [MNTR] mode. o (JMlI5 :Cf) ,V\ USi1 'A}
:...:.~~ -'..
~,

..,
'-
-r-r-rr-rr

~G]~~~:
~~ Iii [VlliiP!J 0:
1V'Il'
;///////////,. ../ / / /.. // , ',.'/ /

4-24 HITACHI
_
."_ .'."- '.. , '""'. -

(4.5 Central Station)


" -,,;><. - -.v"" Y.
.

ISimultaneous Run/Stop Operation I


Mode Operation Procedure
I . Press the unit selection switch [UNIT]
(0) or Q)) to display "AA".
Display Example

2. If the [RUN/STOP] switch is pressed when the CENTRAL STATION


operation of more than one unit is set, all the
units will stop simultaneously.
CXIU

=}_. RR 25. """


UNIT !if11&1'. =
3. If the [RUN/STOP] switch is pressed again ........ U UiliUUi
all the units will operate simultaneously.

Monitor o(RiiIVSTO~ <9 UNlT


C!:' /j~
~B~EB]T~~
~~ IVTEMP,\ID
(//////////////////////

IIndividual Run/Stop Operation I


Mode Operation Procedure Display Example
I. Press the [UNIT] switch < or Q) to set the
unit number.
2. When the (RUN/STOP] switch is pressed in
CENTRAl. STATION
this status, the unit will operate or stop.
= UNIT snlBf' =
=}_. 03 25. ""'"
""" 1I~ .""/ioQUO"O~~,;.s

Monitor O(C;UttlSTO~
I(2J u""
:..! .:!:/~ ~ ~-~.!:./~ ~././ " / / / / /
~B~El]~
~~
" "" Ivm'?'i\ID
//////////////////////

\~9
I

I
i HITACHI 4-25
.L
_'I
(4.5 Central Station)

Operation Procedure
Monitoring Contents Mode Display Example
and Display Contents
. : Run
o: Stop or not Connected
I:'ll (Flickering) : Alarm
[Tho (ALARM] lamp
the lower right of
J
00
CENTAAL STATION
ClXl!J
UH:T sr:"<II' =
the display section 1lmJ}_ RR 25, ""'"
lights simultaneously. ......... ;,,;1 ,
Operation Status
of All Units
Monitor
(Up to 16 Units o~UNlSTOp) ~""'T
Connected) :.!. ~ /
~B~0~~
~~ IVW!?I\IO
/////

This indicates a normal operation.

~UNlT


2 5
~
1 4
: One' or more air
conditioners in the group
are operated.
IO

o: All units in the group are CENTRAL STATION


stopped or not connected. = uo.::- SF'"'3I =
I:'ll (Flickering) : =}_. 03 25,=
One or more air
loperatio, conditioners in the group
... " 11

"""
o~ (0,,',:T
.
Status of Monitor are faulty.
Group
[The [ALARM] lamp on] /~'L/'~' /~ /// 'f/
the lower right of
the display section ~E1~0B~
~l ' - ' -,", TlloE~

lights simultaneously. v~~


1lJIIl.
IT~ Iv 7,'." 1\10
t////lfl////////'//////..

This indicates when a fault exists


17 or in the group 3.
,,",ore Units


Connected Press the unit selection switch pU1'.1T 1 2 3 4 5
[U1'.1T] to set the unit number ~
and press the [INDVL MNTR]
switch. The display disappears


CENTFV.l S"TA.1"I0N
and "UNIT 03" will change to = U>;;- SO:ll" =
"03". mm}- 03 25, =
The air conditioner operation
pperatior status in the group which is
~'a.;~i~.~i~=i.;;
""'"
Status in Monitor specified by the unit number is O(P.l!N/S1;:~ (.. ' r.7\:..
~.I ;
~

Group monitored.
. ////,,"////.- .." /.' ~/
. : Run
0: Stop ~BlEJ]~
oJ .1,.....
I~P ~~ I~", no,(~'

E<i! (Flickering) : Alarm ~~III '!L'1\,l1'


I/T,''''''I 0
[The [ALARM] lamp on] ////////// / / / / -'//////
the lower right of
the display section This indicates that the first unit
lights simultaneously. (Unit ~o.2) in the group 3 is faulty.

NOTE:
- --
When the system is controlled only by the central station, select "NAVL" for "RMT. SW AVUNAVL"
switch, and:
ill Fan speed setting will be "Hi" and not be selected.
Automatic-louver position will be horizontal and not be selected.

4-26 HITACHI
No.
1
2
TROUBLESHOOTING
SERVICING
Contents Page
1-1-1-101
2-1-2-107
3 MAIN PARTS 3-1-3-27
4 OPTIONAL FUNCTIONS 4-1-4-26

5. FIELD WORK INSTRUCTION....................................................... 5-1


5.1 Abnormal Flickering of "RUN" Lamp on Remote Control Switch during Automatic Selling of
Unit Address. . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . 5-1
5.2 Intake Air Temperature and Selling Temperature by Remote Control Switch. . . . . . . . . . . . . . 5-2

1ft. 5.3 Discharge Air Temperature by Check Mode "b3" . .. . . .. . . . . . .. . . .. . .. . . . . . .. . . . . . . . . . . 5-3


5.4 Power Monitor on Remote Control Switch 5-4
5.5 What is the relation between Compressor Frequency and Other Factors? 5-5
5.6 How are the discharge and suction pressure checked? . . .. . . . . . . .. . .. . . .. . . . . . . . . .. . . . 5-6
5.7 Select Guide of Drain Pipe for Indoor Unit 5-8
5.8 Caution for Installation Height of CH Unit (FX System) .............................. 5-9
5.9 Allention for SET-FREE FX Series. . . . . . . .. . . . . .. . . . . .. . . .. . . . . ... . . . . . .. . . .. . .. . . . 5-10
5.10 Caution on Refrigerant Leakage. . . . . .. . .. . . .. . .. . . . . . . .. . . . . . .. . . . . . . . . . . . . .. . . . . . . 5-12
5.11 Maintenance Work............................................................... 5-14
5.12 Service & Maintenance Record by 7-Segment Display................................ 5-15
5.13 Service & Maintenance Record by Remote Control Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-16

((~ . 5.14 Service & Maintenance Record 5-17

HITACHI
J
5. FIELD WORK INSTRUCTION

5. 1 Abnormal Flickering of "RUN" Lamp on Remote Control Switch during Automatic Selting of
Unit Address

Question and Answer for Field Work

I:xample 1: Abnormal Flickering of "RUN" Lamp on Remote Control


Switch during Automatic Setting of Unit Address

[Phenomenon]
In the case that multiple indoor units are controlled by one remote control switch and indoor units are
started by the remote control switch after power supply, the "RUN" lamp may flicker 30 seconds after
the start-up.

[Cause]
The automatic selting of each unit address is performed within 5 minutes after power supply. During
this period, if the unit is started, the"RUN" lamp may flicker approximately 30 seconds after start-up due
to this automatic selting.

[Countermeasure]
Start the system 5 minutes after power supply.

[Remarks]
The following example indicates three indoor units controlled by one remote control switch. During
the period up to completion of automatic selting of unit addresses, all indoor unit addresses are
registered as No. 0 unit. Therefore, if the units are started before completion of the automatic selting, a
micro-computer judges that duplicated unit address exist, resulting in flickering of "RUN" lamp.
However, this flickering will disappear after the automatic selting of unit addresses is completed.

(ct.
System Example

I I

I I
I Indoor
Unit
I I
Outdoor
'--_...J Unit

HITACHI 5-1
5.2 Intake Air Temperature and Setting Temperature by Remote Control Switch

Question and Answer for Field Work

Example 2: Intake Air Temperature and Setting Temperature by


Remote Control Switch
[Phenomenon)
An actual room temperature does not reach the temperature shown on the remote control switch.

[Cause]
In case of normal one-to-one system air conditioners, air conditioners are simply controlled by
comparing the setting temperature and the indoor intake air temperature. Therefore, the intake air
temperature reaches the setting temperature.
However, regarding the FS Series, the intake air target temperature varies between the setting
temperature and setting temperature plus 4"C during the cooling operation, and between the setting
temperature minus 4"C and setting temperature plus 8"C during the heating operation.
This is due to the temperature calibration control, capacity control and fuzzy control.

[Countermeasure)
Change of Room Temperature Setting by Remote Control Switch

[Remarks)
Operation Example
During a cooling operation, the room temperature and the indoor intake air temperature (this
temperature can be shown by using Check Mode "b2") did not reach the setting temperature despite

..
light heat load. By changing the room temperature setting using the remote control switch, the room
temperature reached the setting.

5-2 HITACHI
5 .3 Discharge Air Temperature by Check Mode "b3"

Question and Answer for Field Work

Example 3: Discharge Air Temperature by Check Mode "b3"

[Phenomena]
During a cooling operation, the discharge air temperature indicated by the Check Mode ''b3'' was
higher than the intake air temperature indicated by the Check Mode "b2" by the remote control.
Therefore, it was judged that abnormality with the air conditioner existed.

[Cause]
The discharge air temperature indicated by Check Mode "b3" is the temperature at the discharge air
thermistor. This temperature is differentfrom the average discharge air temperature.

[Countermeasure]
Use the temperature indicated by the Check Mode "b3" as reference.

HITACHI 5-3
-- 5.4 PowerMonitoron Remote Control Switch

Question and Answer for Field Work

Example 4: Power Monitor on Remote Control Switch

[ Phenomenon]
The power monitordata indicated on the remote control switch is differentfrom the compressor
frequency.

[Cause]

..
The power monitor data indicated on the remote control switch is based on the following relation and
is different from the compressor frequency.

[Countermeasure]
No special countermeasure is required.

@HlTACHI

[[TI] 1m]
SIl":'
~:'.', -: ~
.:'N
\1::-.....
rEIT!l c::::::'J !ITm
:: ~ ~
:~
':.1'1 I
: II:;:
:-;:
::'1 v.
. ::\1.:::
:::':S
c.;
~
-'G" ;I\l:~l

H'
88s I':"':'
:V ;~I;::
[illillJ '- u C .11111111

ON/OFF-+-r--- '"",STQ' v /\ Power


Monitor
Lamp

Indication
No Indication
Power Monitor on Remote Control Switch
Mode
FAN
Temperature .'
Small
t
Temperature
COOL Difference
and Setting and
HEAT Intake Air
Temperatures

I
Large

5-4 HITACHI
5.5 What is the relation between Compressor Frequency and Other Factors?
--

Question and Answer for Field Work

Example 5: What is the relation between Compressor Frequency and


Other Factors?

[Answer]
The compressor control frequency is changed by the PIO calculation method according to cooling or
heating load and the degree of ~s change. Based on this target frequency, frequency output is given to
the compressor or the constant speed compressor is started or stopped. Therefore, in the case that the
heat load is comparatively small, the constant speed compressor may not run.

I (~
Relation between Inverter-driven Compressor Speed and Target Frequency

1. AAS-5FS and AA5-5FX

Inverter Driven Compressor


Frequency(Hz)

20 130
Target Frequency(Hz)

2. AAS-8FS and AAS-8FX ON -- -------:--..------,,,


,,
Constant Speed OFF I- ~_.J
Compressor
115 - --- -
-:. -- -:- - -'
-~- ---
Inverter Driven Compressor 100 ,
___ ...... __ ..........

,,
I

Frequency(Hz) , ,
20 -"--1 _ .. I

20 70 100 165
Target Frequency(Hz)

3. AAS-l0FS and AAS-10FX ON ---------~--r------_,


Constant Speed OFF I I
Compressor
115 ----- .. ----:---~----- .. I
100 _-------r---
. .,'
Inverter Driven Compressor
Frequency(Hz) 20 :
20 82 100 177
Target Frequency(Hz)

/
HITACHI 5-5
5.6 How are the discharge and suction pressure checked?

Question and Answer for Field Work

Example 6: How are the discharge and suction pressure checked?

[Answer]
The suction pressure during the cooling operation or discharge pressure during the heating operation
regarding this FS and FX series are always controlled by an inverter.
In order to check the unit operation conditions, please perform checking according to the following
procedures.
1. Set all the indoor units at the same C09ling or heating mode.
2. Operate all the units at the high speed.
3. Wait for a while until the system becomes stable.
4. Compare the measured data with the pressures shown in the figures below,
NOTES:
1) During the cooling operation, use the discharge pressure data as a reference, since
the discharge pressure depends on the accumulated actual indoor unit capacity, outdoor coil
inlet temperature, etc.
2) During the heating operation, use the suction pressure data as a reference, since the
suction pressure depends on the accumulated actual indoor unit capacity, outdoor coil inlet air
temperature, etc.

Piping length" Sm Piping Length" sam


I O~:doot Unit' . 1

-
Outdoor Unit
I- -..;-
Infet Temp.IDB'C) - Inlet ~emp.IDB'C I I

...
'I
'I-- "I

,-
0
V I-- I

-- - ---
I--
3:1 l-
-, bJ I
f-
21
I
...;-- -- '"
- -- --
l- f-II
I I
V
f-
I
I

0 I o I
,

I
Outdoo; Unit
5
?
<;
i3
Inlel Temp.(DB'C) is ~

.~
I
~ ~ "2'
5 Octooor Unit
o I Inlel Temp.lDS t 1

-
115
0: I

e
~ ~I);
,9
g I
I5 2:l .
2~
J
"'
I,
1~ 1:
II 25
J
Indoor Unit Inlet (We 'C) Indoor Unit Inlet (We 'C)

Operating Pressure Curves during Cooling Operation f

5-6 HITACHI
--
Piping Length' SOm
p",p,ng l ."9 th Sm
II IT 1111 \ \1 I \ II III
11111\1111 III
IIIIIIIIII II
..
Indoor Unil If
III I
I rT
r~ u1 indoor Unit ..

lC:f-H++'b>~*'rb:'++++-!+j++++J
Inlet Te,mp,(DB,t.1
I If
1+f-H-4++++-H
II
20

r'
Inlet Temp.(OSt}

II
, II
I
II
II
II j II III
f-l::~17'i4-Ji:HOH-l4-t+1+H-JH--l-H++-H
II I
'1, II II
1 ,A I II
'S
2
1

I
1-1
I.S H -H-1r+1-H+++l-1+H-'
II
"
H-l++++++-I
II
I II II fT
I Indoor Unit I Irndoor Unit
, Inlet Temp.(OSt: I
6 H-H-f-t-ji-H+++++-
j. I,nlet Temp,(DS'C1 11 6
10
! I , , 21
'0 I
I I II I)'
II I I J,-!' S I
"
II 2'
2'S ~
1'1 I 1-1 ' I II ~
'/I J;:j; , I
I! 'v,
1
II
I ~
: I 1 ja
I I 1 I
,I I . 'ij
/I I I I 2 II 2 ~
II I II II I
I i
5 0 5
i I I1
10 IS
, I
5 0
II
5 JO 'S I
Outdoor Unit Inlet (WB 'C) Outdoor Unit Inlet (WB 'C)

Operating PressureCurves during HeatingOperation

HITACHI 5-7
-
.
5.7 Select Guide of Drain Pipe for Indoor Unn

Selecting Method of Drain Pipe Diameter

Step 1. Calculation of Drain Flow Volume


Calculate from that the drain flow volume is approximately 3 (f/hr) per 1HP of the indoor unit
nominal capacity.
For Example:
Common drain pipe for four 2HP indoor units and four 2.5HP indoor units.
CD Total Horse Power of Indoor Unit: 4X2HP+4X2.5HP=18HP
Total Drain Flow Volume: 18HP X3 (f/hr' HP) =54 (f/hr)

Step 2. Select Drain Pipe from Table A and B


CD Horizontal Common Pipe wnh Slope 1/50: VP30 for above Example

..
Horizontal Common Pipe wnh Slope 11100: VP30 for above Example
@ Vertical Common Pipe: VP30 for above Example

Table A. Permissible Drain Flow Volume of Horizontal Vinyl Pipe

Inner Diameter Permissible Flow Volume (f/hr)


JIS Symbol NOTE
(mm) Slope=1/50 Slope=1/100
VP20 20 39 27 Not Applicable to
VP25 25 70 50 Common Pipe
VP30 31 125 88
Applicable to
VP40 40 247 175
Common Pipe
VP50 51 473 334

Table B. Permissible Drain Flow Volume of Vertical Vinyl Pipe


Inner Diameter Permissible Flow Volume
JIS Symbol NOTE
(mm) (f/hr)
VP20 20 220 Not Applicable to
VP25 25 410 Common Pipe
VP30 31 730
VP40 40 1,440
Applicable to
VP50 51 2,760
Common Pipe
VP65 67 5,710
VP75 77 8,280

Drain Piping E
E
0
0
-
c
1/25-1/100 Down-Slope .-
::;
-,
'9\ f5\\. z
11 '"
V


ftonnecting Pipe
S h a I I be Downwa rd.
Drain Piping
(Horizontal)
Common Ora i n :;~
(v e r r L'c e ! I f

5-8 HITACHI
5. 8 Caution for Installation Height of CH Un~ (FX System l
- ,'--, " - - . - ; - ','


All the indoor units, especially CH units, in the same refrigerant cycle (connected to the same
outdoor unit.) shall be installed on a same floor level as possible as.
All the CH units in the same refrigerant cycle must be installed within four floor levels as shown in
the folloWing figure (2).
If not installed, uneven refrigerant distribution to indoor units will occur during the heating operation.
(Insufficient capacity of indoor un~ located at the lowest level will occur.)

(1) Good Example: All indoor units and CH units are located on the same floor level.
Outdoor Unit
g :!ndoorUnit

Floor

(2) Permissible Example: CH unlts are located within 4 floor levels, and the lowest CH units are not
OutdOOr Unit one.

Maximum
4 Floor Levels
15 Meters

2nd F 1.0.0.:...'_ _

... (3) Incorrect Example:


(j) CH units are located w~hin 4 floor levels,
but the lowest CH unit is one.
CH units are located on each floor more
than 5 floors.
OutdoorUnlt Outdoor Unit

ill.....! 9.o_r_ _ .. t~::..:.=:::=;

!.i!.D.I_~ - - l " -__ , _ _

CH

1st Floor
-----_ .. - - - . _ - .. _- ~9.0_r_ _ .. _ _ .. +__'= .. - - -

~99_' _ _ .. _ _ .. _ _ .. _ _

HITACHI 5-9
-- 5.9 Attention for SET-FREE FX Series

,
(1) Attention for Application
The SET-FREE FX series has been designed for the system to provide simultaneous cooling
and heating operations during the temperate season. However, the current SET-FREE FS
series is unable to function as a cooling and heating system simultaneously.
The FX series is for general office bUilding air conditioning. Therefore, it is recommended that
different air conditioning systems be selected where systems are utilized for machine rooms or
computer rooms, providing big heat load.
During the simultaneous cooling and heating operations, the actual capacity is decreased for a
short period of time due to the influence of heat balance if the cooling or heating operation on
some indoor units is started or stopped. Therefore, in the case that there is a room where the
heat load change is big or an ON/OFF operation of an indoor unit is excessively frequent, it is
not appropriate to use this system, since other indoor units may be influenced by the indoor unit.
However, this system can be applied to a room where gradual heat load change is given, such
as a heating operation in the morning, cooling operation during day time and heating operation
in the evening.
During the simultaneous cooling and heating operation, the performance comparatively
decreases when compared with the performance whilst operating all the indoor units at the
same mode.

[Cooling Operation]
All Indoor Units in
Mainly Cooling Cooling Operation
Operation
. . ~ ............

Cooling
100 Mainly Heating
opera\on

- --- .- -\
- -
-,-- ~cooling
---
Capacity 50
(%) Load

o
-' 5 10 15
Outdoor Air Temperature CC
21
DB)
(Example)

[Heating Operation]
All Indoor Units in
Heating Operation

100
J.... Mainly Heating
/Operation

<,
Cooling
Capacity
(%)
50 r-:
Heating ,
Mainly Cooling
Operation

Load

o
(Example)

5 10 15

Outdoor Air Temperature ("C DB)


21 ,.
5-10 HITACHI
_ ,_.
.. " ..' ~: :. . _ - _/,4.... _-._~-

(2) Attention for Automatic COOUHEAT Operation

. In the case that the indoor units are operated under an automatic cooling/heating operation by
pressing the AUTO COOUHEAT switch, pay attention to the following.

(j) In the case that more than 2 indoor units are closely installed and operated in the same room,
each indoor unit interferes with the next unit, resultinq in inefficient operation.

I , I
COOII n g~-...;.-Y---~
.... Heating

@ In the case that room temperature rapidly increases during this automatic COOUHEAT
operation, the operation mode is changed in order, heating operation - fan operation -cooling
operation. During this mode change, the fan operation continues for more than 10 minutes in
order to avoid unwanted influences to other indoor units. Therefore, it is recommended that
other systems be considered if very precise temperature control is required.

(3) Attention for Installing CH Unit


Before installing the CH units, pay attention to the service access and sound.
(j)The CH unit consists of mechanical components such as solenoid valves in order to change the
operation mode from cooling to heating or heating to cooling respectively. Therefore, please
provide a service access door(minimum of 600 x 1,000 mm) beneath the CH unit.
@ Flowing sound of refrigerant may be heard from the CH unit when the solenoid valve in the CH
unit is activated. Therefore, take the following action to minimize the sound .
Install the CH unit inside the ceiling. As for the ceiling material, select a material which

..
minimizes operation sound.
Do not install the CH units in near a bed room or hospital room.

HITACHI 5-11
-- 5. 10 Caution on Refrigerant Leakage

(1) Maximum Permissible Concentration of HCFC Gas ,


The refrigerant R-22. charged in the SET-FREE FS and FX system, is an incombustible and
non-toxic gas. However, if leakage occurs and gas fills a room, it may cause SUffocation.
The maximum permissible concantration of HCFC gas, R-22 in air is 0.3 kg/m 3 , according to the
refrigeration and air conditioning facility standard (KHK S 0010) by the KHK (High Pressure Gas
Protection Association) Japan.
Therefore, some effective measure must be taken to lower the R-22 concentration in air below
0.3 kg/m 3 in case of leakage.

(2) Calculation of Refrigerant Concentration


<D Calculate the total quantity of refrigerant R (kg) charged in the system connecting all the indoor
units of rooms to be air conditioned.
(2) Calculate the room volume V (m3) of each objective room.
@ Calculate the refrigerant concentration C (kg/m3 ) of the room according to the following
equation.

R: Total Quantity of Charged Refrigerant (kg) = C: Refrigerant Concentration


V: Room Volume (m3 ) ;:;; 0.3 (kg/m 3 )

(3) Countermeasure for Refrigerant Leakage According to KHK Standards


The facility shall be arranged as follows referring to the KHK standards. so that the refrigerant
concentration will be below 0.3 kg/ma.
<D. Provide a shutterless opening which will allow fresh air to circulate into the room.
(2) Provide a doorless opening of 0.15% or more size to the floor area.
@ Provide a ventilator, linked with a gas leak detector. of 0.4 m3/min. or more ventilating capacity
per Japanese Refrigeration Ton(= compressor displacement m3th / 8.5) of the air conditioning
system utilizing refrigerant R-22.
RAS-5FS and RAS-5FX 2.49 ton
RAS-8FS and RAS-8FX 4.32 ton
RAS-10FS and RAS-10FX 4.64 ton

5-12 HITACHI
<Example)

System A
Refrigerant: 35kg
System A
Outdoor Unit
System B
Outdoor Unit

Height
E D C B A 2.5m
Floor Floor Floor Floor 200m 2 Floor 60m 2
20m 2 40m 2 40m 2

Gas Leak Detector Opening: 0.06m 2


Ventilator 2m3/min.

Room R (kg) V (mO) C (kg/mO) Countermeasure


A 30 150 0.2 -
B 65 500 0.13 -
C 35 100 0.35 0.06 m2 Opening
D 35 100 0.35 0.06 m2 Opening
C+D 35 200 0.175 -
2 m3/min. Ventilator I.inked with
E 35 50 0.7
Gas Leak Detector

If local codes or regulations are specified. follow them.

<Example)
British Standard BS4434 1989
R22 Commercial Office Building Class D Occupancy
MR=CxV
MR: Maximum Charge or Leakage of Refrigerant (kg)
C: Maximum Allowable Concentration = 0.17 (kg/m3 )
V: Volume of Space (m3 )

HITACHI 5-13
5. 1 1 Maintenance Work

(1) For Indoor Unit and Outdoor Unit


CD Fan and Fan Motor
,
Lubrication - All fan motors are pre-lubricated and sealed at the factory. Therefore, no
lubricating maintenance is required.
Sound and Vibration - Inspect for abnormal sound and vibration.
Rotation - Inspect for clockwise rotation and rotating speed.
Insulation - Inspect for electrical insulation resistance.
~ Heat Exchanger
Clog - Inspect and remove any accumulated dirt and dust from the heat exchanger at
regular intervals. As for outdoor unit, other obstacles such as growing grass and pieces of
paper, which might restrict air flow, should also be removed.
@ Piping Connection
Leakage - Inspect for refrigerant leakage at piping connection.
@ Cabinet
Stain and Lubrication - Inspect and remove any stain and lubrication.
Fixing Screw - Inspect and fix loosened or lost screws.
Insulation - Inspect and repair peeled thermal insulation material on cabinet.
@ Electrical Equipment
Activation - Inspect for abnormal activation of the magnetic contactor, auxiliary relay, PCB
and etc.
Line Condition - Pay attention to working voltage, amperage and phase balance. Inspect for
faUlty contact caused by loosened terminal connections, oxidized contacts, foreign matter,
and other items. Inspect for electrical insulation resistance.
@ Control and Protective Devices
Setting - Do not readjust the setting in the field unless the setting is maintained at a point
other than the point listed in "11. SAFETY AND CONTROL DEVICE SETIING" of 'TC IT",
(2) For Indoor Unit
CD Air Filter

.,.
Cleaning - Inspect and remove any accumulated dirt and dust according to "12.2 Filter
Cleaning" of 'TC IT".
~ Drain Pan, Drain-up Mechanism and Drain Pipe
Drain Line - Inspect and clean the condensate drain line at least twice a year.
Drain-up Mechanism - Inspect for activation of drain-up mechanism.
@ Float Switch
Activation - Inspect for activation of float switch.

(3) For Outdoor Unit


CD Compressor
Sound and Vibration - Inspect for abnormal sound and vibration.
Activation - Inspect for that the voltage drop of power supply line is within 16% at start and
within 2% during operation.
~ Reverse Valve
Activation - Inspect for any abnormal activating sound.
@ Strainer

,
Clog - Inspect for that no temperature difference between both ends.
@ EarthWire
Earth Line - Inspect for continuity to the earth.
@ Oil Heater
Activation - The oil heater should be activated at least 12 hours before start-up, by
switching ON the main power source.
5-14 HITACHI
5. 12 Servics & Maintenance Record by 7-Segrr

Data Sheet for Checking by 7-Segment Dis]


System No.
O.U. Model ISeriai No.
Indoor Unit No.
I I
Date
Unit

No.
Mode ---
Fan Speed HiIMe/Lo
Temp. Set b1 C
R.C. C
Inlet b2
SW
Discharge b3 C
liquid Pipe b4 C
Gas Pipe b7 "'C
Protection Control Code Indication I ---

,
,

Thermostat ON I.U. op I x1/SHP*


Frequency MC1 H1 I Hz
1
ofComp. 1
MC2 H2 I
Hz
Opening MV1 oE1 I
I %
ofO.U. ,
Ex. Valve MV2 oE2 I %
MVb oEb I %
Discharge Pressure Pd I kg/cm 2G
O.U.
Suction Pressure Ps , kg/cm 2G
Discharge Gas Temp. Td1 , "'C
Td2 C
liquid Temp. Te1 ,
"'C
Te2 C
C
Outdoor Air Temp. To I
Running Current of Compo A1 I
I
A
A2 I A
Opening of Indoor Ex. Valve. iE %
Heat Exchanger Temp. TL C
Inlet Air Temp. T! "'C
I.U.
I.U. Capacity CA x1/8HP*
Total Capacity CP , x1/8HP*
Connected I.U. Q'ty. AA i set
Activation of RVR1/RVR2 ;OFF IONOFF FXonly
Activation of SVNSVB iOFF IONOFF ---
Time Checked Startl Finish .. I ---
I

, ,:
;
R.C. Sw: Remote Control Switch, O.U.: Outc

*: Multiply 1/8 by the code on the 7-segment.

5-15
: en "."x
c
,~:' , , r
5.1 2 Service & Maintenance Record by 7-Segment Display

Data Sheet for Checking by 7-Segment Display


System No.
O.U. Model/Serial No.
Indoor Unit No.
I I
Client:

I
Checked by:

I
I I
Date:
Unit

No.
Mode ---
Fan Speed Hi/Me/lo
Temp. Set b1 'C
R.C.
Inlet b2 "C
SW
Discharge b3 'C
Liquid Pipe b4 "C
Gas Pipe b7 "C
Protection Control Code Indication ---

, Thermostat ON I.U.
Frequency
of Compo

Opening
ofO.U.
MC1
MC2
MV1
op
H1
H2
oE1
I
x1/8HP'
Hz
Hz
%

Ex. Valve MV2 oE2 %


MVb oEb %
Discharge Pressure Pd kg/cm 2G
O.U.
Suction Pressure Ps kg/cm 2G
Discharge Gas Temp. Td1 I 'C
Td2 'C
Liquid Temp. Te1 'C
Te2 "C
Outdoor Air Temp. To 'C

, Running Current of Compo

Opening of Indoor Ex. Valve.


Heat Exchanger Temp.
Inlet Air Temp.
A1
A2
iE
Tl
T!
!
A
A
%
'C
"C
I.U.
I.U. Capacity CA x 1/8HP'
Total Capacity CP X 1/8HP'
Connected I.U. Q'ty. AA set
Activation of RVR1/RVR2 ONOFF IONOFF ON'OFF IONOFF ONOFF IONOFF ON OFF IONOFF FX only
Activation of SVNSVB ONOFF I ONOFF ON'OFF I ONOFF ONOFF I ONOFF ON OFF IONOFF ---
Time Checked Start! Finish I I I I ---

R.C. Sw: Remote Control Switch, O.U.: Outdoor Unit, I.U.: Indoor Unit

': Multiply 1/8 by the code on the 7-segment.

HITACHI 5-15
5. 13 Service & Maintenance Record by Remote Control Switch
Data Sheet for Checking by Remote Control Switch
II ..
lime I Clieiit:
I.U. Model Installation Date:
I.U. Serial No. I System No.:
I.U. No.lAlarm Code Date Checked:
Check Mode 1 Check Mode 2 1 . 2 1 . 2 1 . 2 1 2 1 . 2 1 . 2 1 2 1 . 2 Checked by:
B Temp. Indication I
Set Temp. b1 -- I Hssult I
InletAir Temp. b2 q1
Discharge Air Temp. b3 q2
Liquid Pipe Temp. b4 q3
Remote Thermistor Temp. b5 --
OutdoorAir Temp. b6 q4 I
Gas Pipe Temp. b7 q5 I
Evaporating Temp. at Heating
Control Information
Compo TopTemp.
C Micro-Computer State Indication
b8
b9
bA
q6
q7
q8
I
I
I
I

I.U. Micro-Computer C1 - I
O.U. Micro-Computer C2 -- I,
o Stopping Cause State Indication I
Stopping Cause State Indication d1 - ,
E Alarm Occurrence i
Times of Abnormality E1 -- I
Times of Power Failure E2 -
Times of Abnormal Transmitting E3 -- I
Times of InverterTripping E4 --
F Automatic Louver State
Louver Sensor State
H Pressure. Frequency State Indication
Discharge Pressure
Suction Pressure
F1

H1
H2
-

q9
qA
,,
I

Control Information H3 qb I
Operating Frequency H4 qC
J I.U. Capactty Indication
I.U. Capacity (X 1/8HP) J1 I
L Opening of Ex. Valve
I.U. Ex. Valve L1 qd !

O.U. Ex. Valve 1 L2 qE


i
O.U. Ex. Valve 2 L3 -
O.U. Ex. Valve B lA-. - .
,I ... .....

I
P Running Current Indication (Reference) I
Compo Current P1 qF

5-16 HITACHI
5. 14 Service & Maintenance Record

Service & Maintenance Record

No. Check Item Action Judgement


1 Is service space YES or NO
sufficient?
2 Short Circuit of YES or NO
Discharged Air?
3 Any Heat Influence YES or NO
4 Is earth wire connected? YES or NO
5 Refrigeration Piping GOOD or
NOT GOOD
6 Fixing of Units GOOD or
NOT GOOD
7 Any Damage on Outer or YES or NO
Internal Surface?
8 Checking of Screw and Tighten if loosen. TIGHTENED or
Bolts NOT TIGHTENED
9 Tightening of Terminal Tighten all terminal screws by TIGHTEN or
screws philipes driver. NOT TIGHTENED
10 Are compressor Push all terminals. PUSHED or
terminals tightly fixed? NOT PUSHED
11 Insulation Resistance Measure insulation resistance by
insulation resistance-meter.
Compo and Fan GOOD
Motor: greater than 3M Q or
Others: greater than 1M Q NOT GOOD

12 Does drain water Check for smooth flow by GOOD


smoothly flow? pouring water. or
NOT GOOD
13 Check for leakage Check for any leakage. GOOD or
at compressor. NOT GOOD
.

14 Check for leakage at ditto GOOD or


outdoor heat exchanger. NOT GOOD
15 Check for leakage at ditto GOOD or
indoor heat exchanger. NOT GOOD
16 Check for leakage at ditto GOOD or
4-way valve. NOT GOOD
17 Check for leakage at ditto GOOD or
accumulator. NOT GOOD
18 Check for leakage at ditto GOOD or
strainer. NOT GOOD
19 Check for leakage at ditto GOOD or

20
electronic Ex. Valve.
Check for leakage at
piping.
ditto

HITACHI
NOT GOOD
GOOD or
NOT GOOD

5-17
No. Check Item Action Judgement
21 Check direction of by Viewing or Air Flow Volume GOOD or
fans. NOT GOOD
22 Voltage among each higher than 220V GOOD or
Phase NOT GOOD
23 Vibration and Sound Check fan, compressor, piping, GOOD or
etc. NOT GOOD
24 Activation of Each Check activation of COOL, GOOD or
Operation Mode HEAT, STOP and TEMP. NOT GOOD
switches.
25 High Pressure Cut-out Check actual activation value. GOOD or
Switch NOT GOOD
26 Check activation of drain Check it during cooling GOOD or
mechanism. operation. NOT GOOD
27 Indoor Inlet Air Temp. 'CDBI 'CWB
DBIWB
28 Indoor Outlet Air Temp. 'CDBI 'CWB
DBIWB
29 Outdoor Inlet Air Temp. "CDBI 'CWB
DBIWB
30 Outdoor Outlet Air Temp. 'CDBI 'CWB
DBIWB
31 High Pressure Switch kg/cm2G
32 Low Pressure Switch kg/cm2G
33 Operating Voltage V
34 Operating Current A
35 Instruction Cleaning of DONE or
Air Filter to Client NOT YET
36 Instruction for Cleaning DONE or
Method to Client NOT YET

37 Instruction for Operation DONE or


to Client NOT YET

5-18 HITACHI
I

Specifications in this catalog are subject to change without notice, in order that HITACHI may bring the latest innovations to our customers.

HITACHI
Hitachi, Ud. TokyO.Japan

Catalog No. P5412493P 1934 Printed ln Japan ($)

You might also like