LARSEN & TOUBRO LIMITED


TRANSPORTATION INFRASTRUCTURE IC - RAILWAY SBG - EDRC
CLIENT : CONSULTANT :

DEDICATED FREIGHT CORRIDOR


CORPORATION OF INDIA

PROJECT :

WDFCC EMP 4 - REWARI TO MAKARPURA

TOTAL NO. OF PAGES TITLE :


NAME DATE
LOAD CALCULATION FOR 100KV, 25KV/230KV LT
DSGN Ankur Gupta
SUPPLY TRANSFORMER AT TRACTION SUB STATION
CHKD P. Hariharan
APPD C. Zakeer
CODE REV.
DOC. No.
IS A

RELEASED FOR PRELIMINARY TENDER INFORMATION APPROVAL CONSTRUCTION


LARSEN & TOUBRO LIMITED
TRANSPORTATION INFRA IC - RAILWAY SBG - EDRC
DOCUMENT No: DATE
PROJECT WDFCC EMP 4 - REWARI TO MAKARPURA
EDFCC-SS-06-02 ###
DESIGNED CHECKEDAPPROVED SHEET
LOAD CALCULATION FOR 100KV, 25KV/230KV LT SUPPLY TRANSFORMER
TITLE AT TRACTION SUB STATION
AG PH CZ

INPUTS

Vendor Ref Drawing no. = -

Supporting Structure Ref Drawing = Details of structure for mounting of 100


KV,25KV/230KV LT Supply Transformer at Traction
sub station

Total Height of Equipment from Supporting Structure Top = 1.85 m

Length of LT Transformer = 1 m

Width of LT Transformer = 1 m

Height of supporting structure from PL = 5.2 m

Wind pressure = 155 Kg/m2

LOAD CALCULATION
(A) Vertical Load

Self Weight of 25kV LT Transforemr = 1000 Kg

Self Weight ( in kN ) = (1000 x 9.81) / 1000 = 9.81 kN

Imposed Load (Man with tools) = 100 Kg

Imposed Load (Man with tools) in kN = (100 x 9.81) / 1000 = 0.981 kN

Weight of ISMC 100 = 9.56 x 1.0 = 9.56 Kg

Weight of ISMC 100 (in KN) = (9.56 x 9.81) / 1000 = 0.094

Total Vertical load = 9.81 + 0.981+0.094 = 10.885 kN

Total Vertical load per node = 10.885/ 2 = 5.4425

(B) Horizontal Load


Wind along Z direction
(i) Wind on Supporting Structure
Wind on supporting structure with height 5.2 mtr

Exposed area, Ae = (0.065 x 2 x5.2)+(22 x 0.04 x 0.340)+(0.24 x 0.07)+(0.24 x 0.04)

= 1.002 m2

Overall area, Ao = 0.3 x 5.2 = 1.56 m2

Solidity Ratio = 1.002/1.56 0.642

Force Coefficient (Table 28, IS 875-3) = 1.6


LARSEN & TOUBRO LIMITED
TRANSPORTATION INFRA IC - RAILWAY SBG - EDRC
DOCUMENT No: DATE
PROJECT WDFCC EMP 4 - REWARI TO MAKARPURA
EDFCC-SS-06-02 ###
DESIGNED CHECKEDAPPROVED SHEET
LOAD CALCULATION FOR 100KV, 25KV/230KV LT SUPPLY TRANSFORMER
TITLE AT TRACTION SUB STATION
AG PH CZ

Total Wind Load in Kg = 1.002 x 155 x 1.6 = 248.496 Kg

Total Wind Load in KN = (248.496 x 9.81) / 1000 = 2.438 kN

Load in the form of UDL = 2.438/ 5.2 = 0.469 KN/m

Wind on supporting structure with height 3.0 mtr

Exposed area, Ae = (0.065 x 2 x3.0)+(12 x 0.04 x 0.23)+(0.24 x 0.07)+(0.24 x 0.04)

= 0.527 m2

Overall area, Ao = 0.25 x 3.0 = 0.75 m2

Solidity Ratio = 0.527/0.75 0.703

Force Coefficient (Table 28, IS 875-3) = 1.6

Total Wind Load in Kg = 0.527 x 155 x 1.6 = 130.696 Kg

Total Wind Load in KN = (130.696 x 9.81) / 1000 = 1.282 kN

Load in the form of UDL = 1.282/ 3.0 = 0.427 KN/m

Wind on beam of length 2.15 mtr

Total wind load on Beam (in Kg) = 155 x 1.55 x 0.2 = 48.050 Kg

Total wind load on Beam (in KN) = (48.05 x 9.81) / 1000 = 0.471 kN

Load in the form of UDL = 0.471/1.55 = 0.304 KN/m

(ii) Wind on Equipment

Force Coefficient (Table 23, IS 875-3) = 1

Wind load on LT Transformer in Kg = 1 x 1.85 x 155 x 1

= 286.750 Kg

Wind load on LT Transformer in kN = (286.75 x 9.81) / 1000

= 2.813 kN

Total Wind Force on structure = 2.813 kN

Moment due to Wind Load (at Supporting Structure Top Level)


LARSEN & TOUBRO LIMITED
TRANSPORTATION INFRA IC - RAILWAY SBG - EDRC
DOCUMENT No: DATE
PROJECT WDFCC EMP 4 - REWARI TO MAKARPURA
EDFCC-SS-06-02 ###
DESIGNED CHECKEDAPPROVED SHEET
LOAD CALCULATION FOR 100KV, 25KV/230KV LT SUPPLY TRANSFORMER
TITLE AT TRACTION SUB STATION
AG PH CZ

Moment due to Wind on LT Transformer =2.813 x ((1.85/2) + 0.1) = 2.883 kNm

Wind along X direction


(i) Wind on Supporting Structure

Total Wind Load in Kg = 0.125 x 5.2 x 155 = 100.75 Kg

Total Wind Load in KN = (100.75 x 9.81) / 1000 = 0.988 kN

Total Load in the form of UDL = 0.988/5.2 = 0.190 KN/m

(ii) Wind on Equipment

Force Coefficient (Table 23, IS 875-3) = 1

Wind load on Lightning Arrester in Kg = 1.85 x 1 x 155 x 1

= 286.750 Kg

Wind load on LT Transformer in kN = (286.75 x 9.81) / 1000

= 2.813 kN

Total Wind Force on structure = 2.813 kN

Moment due to Wind Load (at Supporting Structure Top Level)

Moment due to Wind on LT Transformer = 2.813 x ((1.85/ 2)+0.1) = 2.883 kNm

Apply these loads in staad and get the results.


LARSEN & TOUBRO LIMITED
TRANSPORTATION INFRA IC - RAILWAY SBG - EDRC
DOCUMENT No: DATE
PROJECT WDFCC EMP 4 - REWARI TO MAKARPURA
EDFCC-SS-06-02 ###
DESIGNED CHECKEDAPPROVED SHEET
LOAD CALCULATION FOR 100KV, 25KV/230KV LT SUPPLY TRANSFORMER
TITLE AT TRACTION SUB STATION
AG PH CZ