Partial Discharge (PD) is an electrical discharge that does not completely bridge the space between two
conducting electrodes. The discharge may be in a gas filled void in a solid insulating material, in a gas
bubble in a liquid insulator, or around an electrode in a gas. When partial discharge occurs in a gas, it is
usually known as corona.

Partial discharge is generally accepted as the predominant cause of long term degradation and eventual
failure of electrical insulation. As a result, its measurement is standard procedure in the factory testing of
many types of high voltage equipment. In addition, partial discharge activity can be tested for or
monitored on in-service equipment to warn against pending insulation failure.

PD in bushing How does Partial Discharge Occur?


Partial discharge occurs in gas filled cavities or defects in the high voltage insulation. These defects can
originate in a number of ways;

During ma nufa cture Solid insulators are designed to give an even distribution of electrical stress
MV cable fault as a result of PD between the conducting electrodes. However, in practice, defects can arise during manufacture that give
rise to small cavities or voids in the insulation bulk.

E q uip me nt insta lla tion When electrical equipment is factory assembled or installed on site, mistakes
can be made that either damage and therefore weaken the insulation, or cause increased electrical stress
across the insulation.

Age ing a nd d e te riora tion Most insulating materials naturally deteriorate with age as internal chemical
bonds break down. This process makes the insulation weaker and less durable when withstanding the
electrical stresses arising under normal working conditions.

Ove r stre sse d in-se rvice A short circuit fault or lightening impulse is likely to impose stress on the
insulation due to a fault current or an overvoltage. Although such events usually have a short duration, the
increased electrical stress or heating from the current overload can cause permanent damage to the
insulation.

In-se rvice d a ma ge Electrical equipment can be physically damaged whilst in service due to external
factors. Underground cables are particularly susceptible to third party damage, by, for instance road
works near buried cables or the cumulative effect of heavy vehicles passing over them.

Why PD occurs at normal working voltages


The defects or cavities in solid insulation are usually filled with a gas of significantly lower breakdown strength than the surrounding material. In addition to this,
the permittivity of the gas is invariably lower than that of the solid insulation, causing the electric field intensity in the cavity to be higher than that in the
surrounding dielectric. Therefore, under the normal working stress of the insulation, the voltage across the cavity may exceed the breakdown value and initiate
electrical breakdown, or Pa rtia l Discha rge in the void.

Electrical power is generally transmitted with a sinusoidal alternating current. The insulation undergoes PRPD display

http://www.ipec.co.uk/about-partial-discharge/ 1/3
10/16/2017 About Partial Discharge
varying electrical stress throughout the power cycle, with two peaks in stress per cycle. This creates a very
distinctive distribution of discharge activity. The pattern, or distribution of the discharges in the power
cycle, is key to recognising PD and distinguishing it from other unrelated noise sources and identifying the
source. The pattern is sometimes called a PRPD (Phase Resolved Partial Discharge) or -q-n pattern.

Surface Tracking Damage caused by surface tracking

Tracking is the formation of a permanent conducting path across an insulator surface. Usually, the
conduction path results from degradation of the insulation. Tracking occurs in carbon based compounds.

High voltage plants are often very difficult to clean and are therefore susceptible to dirt and contaminant
can build up. In the presence of moisture, these contaminating layers give rise to leakage current over the
insulator surface. This heats the surface and through evaporation causes interruption in the moisture film.
Large potential differences are generated over the gaps in the moisture film and small sparks can bridge
the gaps. Heat from the sparks causes carbonisation of the insulation and leads to the formation of
permanent carbon tracks on the surface. Under such conditions, this process will develop over time and
eventually lead to flashover and full breakdown of the insulation.

Tracking as a phenomenon severely limits the use of organic insulators in outdoor environments. The rate
of tracking depends on the structure of the polymers and can be significantly reduced by adding
appropriate fillers to the polymer, which inhibits carbonisation.

Research & Development


IPEC have a strong research and development team and as a result are able to offer test and monitoring solutions incorporating the latest technological
advancesWith almost 20 years experience, IPEC has built a database containing over 400 million examples of Partial Discharge, all sampled at a high resolution
from a wide range of HV assets. This unique data resource is used for the continuous development of PD detection algorithms; improving the accuracy and
reliability of analysis. New products under development will make PD detection and location easier than ever before.

Published Papers
IPEC regularly contribute papers to industry and academic conferences.

Detection and location of PD in MV Cables in Electrically Noisy Industrial Environments

Carl Eastham, IPEC Ltd, UK Colin Smith, IPEC Ltd, UK Fa-Chung Chen, Wain Tsiang Enterprise Co., Ltd, Taiwan

Paper 1205, CIRED 2011 21st International Conference on Electricity Distribution

The Location of Switchgear Partial Discharge by Panel and Techniques to Correlate Switchgear and Cable Partial Discharge with Load and Substation Environment

Cliff Walton, PPA Energy, UK C Smith, IPEC Ltd, UK Matthieu Michel, UK Power Networks, UK
Paper 0862, CIRED 2011 21st International Conference on Electricity Distribution

Improving the Management of MV Underground Cable Circuits Using Automated On-line Cable Partial Discharge Mapping

Carl Eastham, IPEC Ltd, UK

Paper 0479, CIRED 2011 21st International Conference on Electricity Distribution

Data Mining Methods to Predict Failure due to Partial Discharge

Gareth Poulton, IPEC Ltd, UK C Smith, IPEC Ltd, UK Wai-Shing Ho, University of Hong Kong, HK

Paper 0907, CIRED 2011 21st International Conference on Electricity Distribution

Avoidance of MV Switchgear Failure Case Studies of On-line Condition Monitoring

Cliff Walton, PPA Energy, UK Sarah Carter, PPA Energy, UK Matthieu Michel, UK Power Networks, UK Carl Eastham, IPEC Ltd, UK

Paper 0422, CIRED 2009 20th International Conference on Electricity Distribution

Integrated Condition Monitoring for Subsea Power Cable Systems

http://www.ipec.co.uk/about-partial-discharge/ 2/3
10/16/2017 About Partial Discharge
Roman Svoma, PowerSure Technology Ltd, UK Colin Smith, IPEC Ltd, UK Chris Conway, Bandweaver, UK
Paper 1000, CIRED 2009 20th International Conference on Electricity Distribution

Influence of Network Events on Partial Discharge Activity and Cable Health

Colin Smith, IPEC Ltd, UK Matthieu Michel, EDF Energy Networks, UK

Paper 0487, CIRED 2009 20th International Conference on Electricity Distribution