A.1 INTRODUCTION
This section includes the basic standards, codes of practice, design criteria, loads and
materials that will be applicable in the design; and gives a brief description of the
proposed structural system to be used.
The structural steel Moment frames should be integrated with concrete core walls and
secondary steel beams transferring lateral loads via rigid diaphragm.
Design should be based on the use of Indian standards and American standards
wherever applicable. The following paragraphs describe in details the different design
aspects and parameters that should be utilized for designing and detailing this project.
NOTE: Column should not be designed as composite sections. Only structural steel
should be used for column and beam design
AISC 360-10, American Institute of Steel Construction, Specification for Structural Steel
Buildings .
Structural Welding Code: American Welding Society, ANSI/AWS D1.1/D1.1M-2008
Steel Structure painting Manual: steel structures Painting Council.SSPC-2000
AISC 360-10, American Institute of Steel Construction, Specification for Structural Steel
Buildings.
Superimposed dead load (SDL) to account the flooring, partition, cladding, false ceilings,
waterproofing systems, electromechanical loads, and fixtures.
2
Partition loads of 2kN/m to be considered in SDL
*Note: Fire engine load in ground floor will come in RCC scope so, neglected while modeling.
static.
Load combinations for both service and ultimate limit states (SLS & ULS) are based on relevant (IS/ACI)
codes.
A.5 MATERIALS
The classes of concrete are indicated in the table below and reflect the 28 days concrete cube strength
Cement
Ordinary Portland cement Grade 53: IS 12269 shall be used for super-structure elements.
Moderate Sulphate Resisting cement: IS 12330 shall be used for substructures reinforced concrete
elements in contact with soil.
Sulphate Resisting Cement conforming to IS 12330 for blinding concrete.
Reinforcement
Deformed high tensile steel bars having minimum yield strength fy=500 N/mm and confirming
High strength Bolts: ASTM A 490M, Type 1, or DIN 6914 grade 10.9 or 8.8 heavy hex steel
structural bolts.
2. Shear Connectors: AWS D1.1, type B, minimum yield strength 345 N/mm [50 ksi] at
0.2% offset, made from steel to ASTM A108, with mechanical properties to ASTM
A370.
Metal-Arc Welding Electrodes:
E70XX series of the Specification for Mild Steel Covered Arc-Welding Electrodes, AWS A5.1,
or the Specification for Low-Alloy Steel Covered Arc-Welding Electrodes, AWS A5.5.
Bare Electrodes and Granular Flux used in the submerged-arc process: E70XX AWS flux
classifications of the Specification for Base Mild Steel Electrodes and Fluxes for Submerged Arc
Welding, AWS A5.17, or A5.23.
Deflection
Type of Member Deflection to be considered
Limitation
Flat roofs not supporting or attached Immediate deflection due to live load LL using
Floors not supporting or attached to Immediate deflection due to live load LL using
non-structural elements likely to be Cracked section.
Span/360
damaged by large deflections.
Roof or Floor construction supporting The part of the total deflection occurring after
or attached to non-structural attachment of non-structural elements (sum of Span/480
elements likely to be damaged by the long-term deflection due to all sustained
large deflection. loads and the immediate deflection due to any
additional live load).
Roof or floor construction supporting The part of the total deflection occurring after
or attached to non-structural attachment of non-structural elements (sum of Span/240
elements not likely to be damaged by the long term deflection due to all sustained
large deflections. loads and immediate deflection due to any
additional live load).
1. Third Party design proof check by any educational institute (any IIT or Decided by SETU
Infrastructure/client).
2. Steel structure, Connection bolts, shear studs, base plate and deck sheeting design & its execution
3. Consider 2 Hours fire rating cement base coating in your scope of work
4. Fabrication tolerances as per IS 7215 to be maintained.
5. Welding processes as per AWS D 1.1 to be maintained.
6. Erection tolerances as per MBMA.
7. Welded Splice joints have been allowed but need get it approved from
SETU INFRASTRUCTURE.
8. Design Criteria and Input data as per Technical specification.
9. Design to be done in ETABS 2015 or Higher.
10. Anchor bolt details & anchor bolt setting out plan for grouting.
11. Any other detail/ drawing as required by Client.
12. Structural Shop and erection drawings with connection detailing need to be approved from
SETU INFRASTRUCTURE.
13. Erection sequence / Methodology: The erection sequence shall be submitted to the SETU & after
getting approval, the same shall be distributed to others.
14. Details of Primary & Secondary members (fabrication details).
15. Forces/reactions for foundation design and Anchor bolt plan to be submitted to SETU.
16. Details of strut, bracings, Ties
17. Details at corners, joints etc.
18. Detailed Quality Assurance Plan Specifying all shop and site test and also plan for joint
inspection of materials.
19. Performance Warranty Certificates with Defect Liability Agreement.
20. Structural stability certificate for super structure.
21. Warranty against Color fading.
22. Warranty against Thermal Insulation
23. Guarantee against weather Tightness
Note: -
1) All above documents shall be provided in hard as well as soft copy.
2) ETABS file and all calculation in excel sheets with formula are to be provided.
3) The Supplier shall transport the material to site after fabrication is complete and 100%
Inspection at shop by the Client / Consultant is completed.