You are on page 1of 3

Technical Data Bulletin

MMX/2- 30198

MMX-2
Monitor Module Two Wire Conventional
Smoke Detector Interface

GENERAL INFORMATION
The Chemetron Fire Systems MMX-2 Monitor Module
is used with the Micro 200-I, 300-I, & 400-I control
panels to monitor a single Initiating Device Circuit
(IDC).

FEATURES
P Supports compatible two-wire smoke detectors.
P Supervises IDC wiring and connection of external
power source.
P High noise immunity (EMI/RFI).
P SEMS screws with clamping plates for ease of
MMX-2 Monitor Module
wiring.
P Two rotary switches for direct dial entry of DECADE
address (01-99).
P Built-in magnetic alarm test switch.
P LED flashes during normal operation (this is optional
on the Micro 200-I, 300-I & 400-I.)
P LED latches steady to indicate alarm on command
from control panel.

APPLICATIONS
Use to monitor a zone of 2-wire smoke detectors.
Monitored circuit may be wired as an NFPA Style B
(Class B) or Style D (Class A) Initiating Device Circuit
(IDC). A 3.9 K-ohm end-of-line resistor (provided)
terminates the end of the Style B or D (Class B or A)
circuit [maximum IDC loop resistance is 25 ohms].
Install ELR across terminals 8 and 9 for Style D
application.

Face Plate
OPERATION
Each MMX-2 uses one of 99 available module ad-
dresses on an SLC loop. It responds to regular polls COMPATIBILITY
from the control panel and reports its type and the
status (open/normal/short) of its Initiating Device Refer to document number 15378, UL Listed Com-
Circuit. A flashing LED indicates that the module is in patible Two-Wire Smoke Detectors for Chemetron Fire
communication with the control panel. The LED latches Systems Control Panels.
steady on alarm (subject to current limitations on the
loop).

1998 Chemetron Fire Systems All rights reserved (3/98). MANUFACTURED BY NOTIFIER
4801 Southwick Drive Matteson, IL 60443 708/748-1503 FAX 708/748-2847
Technical Data Bulletin
MMX/2- 30198

MMX-2 Field Wiring Connections

Mounting the MMX-2 to a 4" square,


2-1/8" deep junction box

INSTALLATION The MMX-2 mounts to a standard 4" square, 2-1/8"


deep junction box. Alternately, the MMX-2 may be

1998 Chemetron Fire Systems All rights reserved (3/98). MANUFACTURED BY NOTIFIER
4801 Southwick Drive Matteson, IL 60443 708/748-1503 FAX 708/748-2847
Technical Data Bulletin
MMX/2- 30198

mounted to the surface mount backbox, Part No.


70100740. Mounting hardware and installation instruc-
SPECIFICATIONS
tions are provided with each module.
Operating Voltage 22.2 25.5 VDC

PRODUCT LINE INFORMATION Standby Current: 200 FA maximum (Com-


munication line) (SLC)
Temperature Range: 0E to 49EC (32E to 120EF)
MODEL DESCRIPTION
Humidity Range: 10% 85% Relative
MMX-2 . . . . . Monitor Module.
Weight: 0.5 pounds (.225 kg)
70100740 . . . Surface mount backbox.
Supervisory Current: 7.0 mA maximum
70100756 . . . Test magnet.
Alarm Current: 20 mA maximum

Ordering Information

Shipping Weight
Stock Number Description lbs (kg)
70100723 MMX-2 Monitor Module .6 (.27)
70100740 Surface Mount Backbox .6 (.27)
70100756 Test Magnet for MMX-2 Monitor Module .2 (.09)

1998 Chemetron Fire Systems All rights reserved (3/98). MANUFACTURED BY NOTIFIER
4801 Southwick Drive Matteson, IL 60443 708/748-1503 FAX 708/748-2847

You might also like