You are on page 1of 10

ICC EVALUATION SERVICE, INC.

Evaluate P Inform P Protect

ACCEPTANCE CRITERIA FOR


SEISMIC QUALIFICATION BY SHAKE-TABLE TESTING
OF NONSTRUCTURAL COMPONENTS AND SYSTEMS

AC156

Approved December 2006

Effective January 1, 2007

Previously approved June 2004, January 2000

PREFACE
Evaluation reports issued by ICC Evaluation Service, Inc. (ICC-ES), are based upon performance features of the International family
of codes and other widely adopted code families, including the Uniform Codes, the BOCA National Codes, and the SBCCI Standard Codes.
Section 104.11 of the International Building Code® reads as follows:

The provisions of this code are not intended to prevent the installation of any materials or to prohibit any design or method
of construction not specifically prescribed by this code, provided that any such alternative has been approved. An alternative
material, design or method of construction shall be approved where the building official finds that the proposed design is
satisfactory and complies with the intent of the provisions of this code, and that the material, method or work offered is, for
the purpose intended, at least the equivalent of that prescribed in this code in quality, strength, effectiveness, fire resistance,
durability and safety.

Similar provisions are contained in the Uniform Codes, the National Codes, and the Standard Codes.

This acceptance criteria has been issued to provide all interested parties with guidelines for demonstrating compliance with performance
features of the applicable code(s) referenced in the acceptance criteria. The criteria was developed and adopted following public hearings
conducted by the ICC-ES Evaluation Committee, and is effective on the date shown above. All reports issued or reissued on or after the effective
date must comply with this criteria, while reports issued prior to this date may be in compliance with this criteria or with the previous edition. If the
criteria is an updated version from the previous edition, a solid vertical line (›) in the margin within the criteria indicates a technical change, addition,
or deletion from the previous edition. A deletion indicator (º) is provided in the margin where a paragraph has been deleted if the deletion involved
a technical change. This criteria may be further revised as the need dictates.

ICC-ES may consider alternate criteria, provided the report applicant submits valid data demonstrating that the alternate criteria are
at least equivalent to the criteria set forth in this document, and otherwise demonstrate compliance with the performance features of the codes.
Notwithstanding that a product, material, or type or method of construction meets the requirements of the criteria set forth in this document, or
that it can be demonstrated that valid alternate criteria are equivalent to the criteria in this document and otherwise demonstrate compliance with
the performance features of the codes, ICC-ES retains the right to refuse to issue or renew an evaluation report, if the product, material, or type
or method of construction is such that either unusual care with its installation or use must be exercised for satisfactory performance, or if
malfunctioning is apt to cause unreasonable property damage or personal injury or sickness relative to the benefits to be achieved by the use of
the product, material, or type or method of construction.

Copyright © 2007

Business/Regional Office P 5360 Workman Mill Road, Whittier, California 90601 P (562) 699-0543
www.icc-es.org Regional Office P 900 Montclair Road, Suite A, Birmingham, Alabama 35213 P (205) 599-9800
Regional Office P 4051 West Flossmoor Road, Country Club Hills, Illinois 60478 P (708) 799-2305
ACCEPTANCE CRITERIA FOR
SEISMIC QUALIFICATION BY SHAKE-TABLE TESTING
OF NONSTRUCTURAL COMPONENTS AND SYSTEMS
1.0 SCOPE AND PURPOSE component and the hazard exposure
importance factor of the structure, as set forth in
This criteria establishes minimum requirements for the
issuance of ICC Evaluation Service, Inc., evaluation reports
% Section 13.1.3 of ASCE 7.
on seismic qualification shake-table testing of nonstructural 2.3 Common to UBC and IBC: The following symbols
components and systems (hereinafter referred to as and notations have the noted meaning in this document:
“equipment”). Such reports relate to the seismic design ARRS = Spectral acceleration as calculated from design
requirements for architectural, mechanical, electrical and seismic forces, Fp, and equipment weight, Wp.
other nonstructural systems, components, and elements
permanently attached to structures, as specified in Section = Fp/Wp.
1632 of the 1997 Uniform Building Code™ (UBC) and AFLX = Horizontal spectral acceleration calculated for
% Section 1613 of the 2006 International Building Code® (IBC). flexible equipment.
This acceptance criteria is applicable for shake-table testing
of nonstructural components and systems that have ARIG = Horizontal spectral acceleration calculated for
fundamental frequencies greater than or equal to 1.3 Hz. rigid equipment.
2.0 NOMENCLATURE ap = In-structure equipment amplification factor. The
ap represents the dynamic amplification of the
2.1 UBC: The following symbols and notations have the equipment relative to the fundamental frequency
noted meaning in this document: of the building structure.
Ca = Seismic coefficient, as set forth in Table 16-Q of Fp = Horizontal seismic design force centered at the
the UBC. equipment’s center of gravity, and distributed
Na = Near-source factor used in the determination of Ca relative to the equipment’s mass distribution.
in Seismic Zone 4, related to the proximity of the Wp = Equipment operating weight.
building or structure to known faults having
magnitudes and slip rates as set forth in Tables 3.0 DEFINITIONS
16-S and 16-U of the UBC. 3.1 Attachments: The means by which equipment is
Hx = Equipment attachment elevation with respect to secured or restrained by the seismic force resisting system
grade. For items at or below the base, Hx shall not of the building structure. Such attachments and restraints
be taken to be less than 0.0. may include anchor bolting, welded connections and
mechanical fasteners.
Hr = Building or structure roof elevation with respect to
grade. 3.2 Biaxial Test: A dynamic test in which the test
specimen is subjected to acceleration in one principal
Rp = Equipment response modification factor. Rp horizontal axis and the vertical axis simultaneously. The
represents the energy absorption capability of the horizontal and vertical acceleration components are derived
equipment's structure and attachments, set forth from two different input signals that are phase-incoherent.
in Table 16-O of the UBC.
3.3 Build-hold-decay (BHD): The build-hold-decay time
Ip = Equipment importance factor. Ip represents the interval envelope (5 + 0 / – 3 seconds, 20 + 6 / – 0 seconds
greater of the life-safety importance of the and 5 + 0 / – 3 seconds, respectively) imposed on the drive
component and the hazard exposure importance signal of the shake table to simulate the nonstationary
of the structure, set forth in Table 16-K of the nature of an earthquake event. The build time includes time
UBC. necessary for acceleration ramp-up, the hold time
2.2 IBC:The following symbols and notations have the represents the earthquake strong motion time duration, and
noted meaning in this document: the decay time includes the de-acceleration ring down time.
A straight linear approximation is acceptable.
SDS = Design spectral response acceleration at short
% period, as determined in Section 1613.5.4 of the 3.4 Damping: An energy dissipation mechanism that
IBC. reduces the amplification and broadens the vibratory
response in the region of resonance. Damping is expressed
z = Height of structure (in feet) with respect to as a percentage of critical damping.
grade, at point of attachment of equipment. For
items at or below the base, z shall not be taken 3.5 Flexible Equipment: Component, including its
to be less than 0.0. attachments and force-resisting structural members, having
a fundamental period greater than 0.06 second (less than
h = Average building/structure roof height (in feet) 16.67 Hz).
relative to the base elevation.
3.6 Equipment Force-resisting System: Equipment
Rp = Equipment response modification factor. Rp force-resisting systems are those members or assemblies
represents the energy absorption capability of of members, including braces, frames, struts and
the equipment's structure and attachments, set attachments, that transmit all loads and forces between the
% forth in Table 13.5-1 or 13.6-1 of ASCE 7. equipment and the building structure. Equipment supports
Ip = Equipment importance factor. Ip represents the also transmit lateral forces and/or provide structural stability
greater of the life-safety importance factor of the for the connected equipment.

2
ACCEPTANCE CRITERIA FOR SEISMIC QUALIFICATION BY SHAKE-TABLE TESTING
ON NONSTRUCTURAL COMPONENTS AND SYSTEMS

3.7 Octave: The interval between two frequencies that correspondence regarding the seismic qualification testing
have a frequency ratio of 2. per this procedure.
3.8 One-third Octave: The interval between two 4.1.2 Test laboratory’s name and address and the
frequencies that have a frequency ratio of 21/3. individual(s) representing the primary point of contact for all
correspondence regarding the seismic qualification testing
3.9 One-sixth Octave: The interval between two
per this procedure.
frequencies that have a frequency ratio of 21/6.
3.10 Required Response Spectrum (RRS): The response 4.2 UUT Description: A description of the UUT shall be
spectrum generated using the formulas and normalized provided, including the following items:
spectra detailed in Section 6.5.1 of this acceptance criteria. 4.2.1 General description of the UUT’s primary function.
The RRS constitutes a requirement to be met.
4.2.2 Detailed description of the UUT’s hardware
3.11 Rigid Equipment: A component, including its
configuration, including subassemblies and unique product
attachments and force-resisting structural members, having identification numbers and/or serial numbers.
a fundamental period less than or equal to 0.06 second
(greater than or equal to 16.67 Hz). 4.2.3 Overall dimensions and weight of the UUT.
3.12 Subassemblies: A grouping or assemblage of 4.2.4 Any restrictions or limitations on equipment use.
secondary components and/or structural elements that
require attachment to the equipment’s primary force 4.3 Seismic Parameters:
resisting system to achieve structural stability.
4.3.1 UBC: The following seismic parameters, used to
3.13 Test Response Spectrum (TRS): The acceleration establish maximum UUT seismic qualification test
response spectrum that is developed from the actual time requirements, shall be provided:
history of the motion of the shake table test.
Hx = Equipment attachment elevation with respect to
3.14 Transmissibility: The nondimensional ratio of the grade.
response amplitude of a system in steady-state forced
vibration to the excitation amplitude. The ratio may be one Hr = Building or structure roof elevation with respect
of forces, displacements, velocities, or accelerations and is to grade.
used to characterize resonant modes of structural vibration. Ca = Seismic coefficient.
3.15 Triaxial Test: A dynamic test in which the test Ip = Equipment importance factor.
specimen is subjected to acceleration in two principal
horizontal axes and the vertical axis simultaneously. The two 4.3.2 IBC: The following seismic parameters, used to
horizontal and the vertical acceleration components are establish maximum UUT seismic qualification test
derived from three different input signals that are phase- requirements, shall be provided:
incoherent.
z = Equipment attachment elevation with respect to
3.16 Uniaxial Test: A dynamic test in which the test grade.
specimen is subjected to acceleration in one principal axis.
The acceleration components are derived from a single h = Average building/structure roof elevation with
input signal. respect to grade.
3.17 Unit Under Test (UUT): The equipment item to be SDS = Spectral response acceleration at short period.
qualification-tested. Ip = Equipment importance factor.
3.18 Zero Period Acceleration (ZPA): The peak
4.4 Functional and Operability Requirements: A listing
acceleration of motion time-history that corresponds to the
and detailed description shall be provided of the functional
high-frequency asymptote on the response spectrum. This
and operability equipment requirements and/or tests used to
acceleration corresponds to the maximum peak acceleration
verify pre- and post-seismic-testing functional compliance.
of the time history used to derive the spectrum. For use in
this acceptance criteria, the ZPA is assumed to be the 4.5 Equipment Product Line Extrapolation and
acceleration response at 33.3 Hz or greater. Interpolation: Testing every single configuration of a given
4.0 UUT REQUIRED INFORMATION equipment product line may not be feasible. Therefore, it
may be necessary to select test specimens that adequately
Sections 4.1 through 4.7 detail the necessary information represent the entire equipment product line. The following
to be provided for each UUT. Section 4 shall be a complete criteria shall be used to establish UUT configuration
document, submitted by the UUT manufacturer or the requirements for representing an equipment product line
manufacturer’s representative and included as an appendix (UUT configuration rationale shall be provided):
to the Qualification Test Plan described in Section 6.1.
Appendix A of this document sets forth the information 4.5.1 Structural Features: A rationale shall be provided
necessary to meet the requirements of Section 4.0. explaining that the selected UUT’s structural configuration
is one offering the least seismic withstand capacity
4.1 Manufacturer and Test Laboratory Contact
compared to other options that are available within the
Information: The following contact information shall be product line being qualified. The UUT’s force-resisting
specified: systems shall be similar to the major structural
4.1.1 Manufacturer’s name and address and the configurations being supplied in the product line. If more
individual(s) representing the primary point of contact for all than one major structure is a configurable option, then these

3
ACCEPTANCE CRITERIA FOR SEISMIC QUALIFICATION BY SHAKE-TABLE TESTING
ON NONSTRUCTURAL COMPONENTS AND SYSTEMS

other structural configurations shall be considered in the accelerometers, or requesting electronic data output of
equipment product line extrapolation and interpolation accelerometer sensors, etc.).
rationalization process.
5.0 TESTING LABORATORIES AND REPORTS OF
4.5.2 Mounting Features: A rationale shall be provided TESTS
that explains that the selected UUT’s mounting configuration
5.1 Laboratories: Testing laboratories shall comply with
is one offering the least seismic withstand capacity
Section 2 of the ICC-ES Acceptance Criteria for Test
compared to other mounting options that are available within
Reports (AC85) and Section 4.2 of the ICC-ES Rules of
the product line being qualified. The configuration mounting
Procedure for Evaluation Reports.
of the UUT to the shake-table shall simulate mounting
conditions for the product line. Seismic testing of equipment 5.2 Test Reports:
may be conducted using the smallest diameter tie-down bolt
size (or minimum weld size) that can be accommodated with 5.2.1 General: Test reports shall comply with AC85.
the provided tie-down clearance holes (or base structural 5.2.2 Specific: Reports of all tests noted in Section 6
members) on the equipment. If several mounting are required. In addition, the following items must be
configurations are used, they shall be simulated in the test. reported:
4.5.3 Subassemblies: A rationale shall be provided 5.2.2.1 Identification of equipment being qualified.
explaining that the selected UUT’s subassemblies are
representative of production hardware and offer the least 5.2.2.2 Seismic parameters and derived RRS levels
seismic withstand capacity of the UUT compared to other for equipment that is being qualified.
subassembly options that are available within the product 5.2.2.3 Results of functionality and operability
line being qualified. The major subassembly components requirements and/or testing.
shall be included in the UUT. These components shall be
mounted to the specimen structure at locations similar to 5.2.2.4 Test facility location.
those specified for proposed installations. The components 5.2.2.5 Testing equipment and calibration.
shall be mounted to the structure using the same type of
mounting hardware specified for proposed installations. 5.2.2.6 Equipment mounting details, including all
Substitution of nonhazardous materials and fluids is interface connections.
permitted for verification of equipment or subassemblies that 5.2.2.7 Test data, including proof of performance, TRS
contain hazardous materials or fluids, provided the plots, acceleration time histories of the shake table input
substitution does not reduce the functional demand on the motion, transmissibility plots, UUT measured weight, etc.
equipment or subassembly.
5.2.2.8 Test results and conclusions (including a
4.5.4 Mass Distribution: A rationale shall be provided statement of any anomalies, and justification that the
explaining that the selected UUT’s mass distribution is one equipment is still qualified).
contributing to the least seismic capacity of the UUT
compared to other mass distribution options that are 5.3 Product Sampling: Sampling of components for tests
available within the product line being qualified. The weight under this criteria shall comply with Section 3.1 of AC85.
and mass distribution shall be similar to the typical weight 6.0 SEISMIC QUALIFICATION TEST PROCEDURE
and mass distribution of the equipment being represented.
Weights equal to or greater than the typical weight shall be 6.1 Qualification Test Plan: The UUT shall be subjected
acceptable. to a seismic qualification test program, considering all
elements noted in this section. The qualification test plan is
4.5.5 Equipment Variations: A rationale shall be
intended to satisfy the requirements of Section 1632 of the
provided explaining that the selected UUT’s overall % UBC and/or Section 1613 of the IBC for equipment.
variations contribute to the least seismic withstand capacity
of the UUT compared to other variations that are available 6.2 Pre-test Inspection: Upon arrival at the test facility,
within the product line being qualified. Other equipment the UUT shall be visually examined and results documented
variations, such as number of units/components in by the testing laboratory, to verify that no damage has
production assemblies, indoor and outdoor applications, occurred during shipping and handling.
etc., shall be considered in the equipment product line
6.3 Pre-test Functional Compliance Verification:
extrapolation and interpolation rationalization process.
Functional and operability requirements and/or tests, as
4.6 Installation Instructions: Instructions shall include specified in Section 4.4, shall be performed by an accredited
the following items: testing laboratory to verify pre-test functional performance.
Functional testing could be performed at either the test
1. Description of how the UUT will be installed in the
facility or at the UUT manufacturing facility. Test description
field.
and results shall be documented in accordance with Section
2. Description of how the UUT will be installed during the 5.2 (Test Reports).
qualification test.
6.4 Seismic Simulation Test Setup: Seismic ground
4.7 Special Test Requirements (Optional): The UUT motion occurs simultaneously in all directions in a random
manufacturer or the manufacturer’s representative can list fashion. The requirement is to perform qualification testing
any test requirements that would be deemed special or in all three principal axes, two horizontal and vertical.
beyond the norm for seismic qualification testing (i.e., However, for qualification test purposes, uniaxial, biaxial or
requesting displacement and/or force monitoring triaxial test machines are allowed in accordance with the
instrumentation, requesting additional response monitoring following test requirements.

4
ACCEPTANCE CRITERIA FOR SEISMIC QUALIFICATION BY SHAKE-TABLE TESTING
ON NONSTRUCTURAL COMPONENTS AND SYSTEMS

6.4.1 Triaxial, Biaxial, and Uniaxial Testing two octaves per minute, or less, to ensure adequate time for
Requirements: The preferred method of performing testing maximum response at the resonant frequencies.
is using a triaxial shake table. However, it is recognized that Transmissibility plots of the in-line UUT response monitoring
capable triaxial testing facilities are limited in number, and sensors shall be provided.
this may restrict testing access. The following requirements 6.5 Multifrequency Seismic Simulation Tests:
shall be used when performing triaxial, biaxial, or uniaxial
testing. 6.5.1 Derivation of Seismic RRS: The equipment
earthquake effects shall be determined for combined
6.4.1.1 Triaxial Testing: If a triaxial test is performed,
horizontal and vertical load effects. The required response
the test shall be performed in one stage with the two
spectra for the horizontal direction shall be developed based
principal horizontal axes and the vertical axis of the UUT
on the normalized response spectra shown in Figure 1, and
simultaneously tested.
the formula for total design horizontal force, Fp. The required
6.4.1.2 Biaxial Testing: If a biaxial test is performed, response spectra for the vertical direction shall be
the test shall be performed in two stages, with the UUT developed based on two-thirds of the ground-level base
rotated 90 degrees about the vertical axis for the second acceleration. The seismic parameters specified in Section
stage. 4.3 shall be used to calculate the RRS levels as defined by
AFLX and ARIG. The RRS shall be defined using a damping
6.4.1.3 Uniaxial Testing: If a uniaxial test is value equal to 5 percent of critical damping.
performed, the test shall be performed in three distinct
stages, with the UUT rotated after each stage, such that all
three principal axes of the UUT have been tested.
6.4.2 Weighing: The UUT shall be weighed prior to
performing the Seismic Simulation Tests. The measured
UUT weight shall be recorded in the Test Report of Section
7.2.
6.4.3 Mounting: The UUT shall be mounted on the
shake table in a manner that simulates the intended service
mounting in accordance with Section 4.6. The mounting
method shall be the same as that recommended for actual
service, and shall use the minimum recommended bolt size,
bolt type, bolt torque, configuration, weld pattern and type (if
applicable), etc. The orientation of the UUT during the tests
shall be such that the principal axes of the UUT are collinear
with the axes of excitation of the shake table. A description
of any interposing fixtures and connections between the
UUT and the shake table shall be provided.
FIGURE 1—REQUIRED RESPONSE SPECTRUM,
6.4.4 Monitoring: Sufficient vibration response NORMALIZED FOR EQUIPMENT
monitoring instrumentation shall be used to allow
determination of the applied acceleration levels in the 6.5.1.1 UBC: The required response spectra for both
principal horizontal and vertical axes of the shake table. horizontal and vertical directions shall be developed based
Reference control accelerometers shall be mounted on the on the formula for total design lateral force as specified in
shake table at a location near the base of the UUT. Vibration Equation (32-2) of the UBC:
response monitoring instrumentation shall also be used to
determine the response of the UUT, at those points within ap Ca ⎛ H ⎞
the structure that reflect the UUT’s response associated with Fp = ⎜ 1+ 3 x ⎟ Wp
(R p / I p ) ⎝ Hr ⎠
its structural fundamental frequencies. Placement locations
for the response sensors shall be at the discretion of the
UUT manufacturer or the manufacturer’s representative, and The height factor ratio (Hx / Hr) accounts for above grade-
approved by the test laboratory prior to testing. Sensors
level equipment installations within the primary supporting
shall be installed, calibrated and approved by the test
structure and ranges from zero at grade-level to one at roof-
laboratory prior to testing. The accredited laboratory shall
level, essentially acting as a force increase factor to
document the location, orientation, and calibration of all
recognize building amplification as you move up within the
vibration monitoring sensors.
primary structure. The site-specific seismic coefficient, Ca,
6.4.5 Resonant Frequency Search: The resonant varies per geographic location (as set forth in Table 16-Q of
frequency search test is for determining the resonant the UBC) and site soil conditions. The Ca factor is used to
frequencies and damping of equipment. The data obtained define the general design earthquake response spectrum
from the search test is an essential part of an equipment curve and is used to determine the design seismic forces for
qualification; however, the search test does not constitute a the primary building structure. The Ca factor ranges from
seismic test qualification by itself. A low-level amplitude (0.1 0.06 to 0.66 depending on the seismicity of a given location.
± 0.05 g peak input; a lower input level may be used to avoid The ratio of Rp over Ip (Rp / Ip) is considered to be a design
equipment damage) single-axis sinusoidal sweep from 1.3 reduction factor to account for inelastic response, and
to 33.3 Hz shall be performed in each orthogonal UUT axis represents the allowable inelastic energy absorption
to determine resonant frequencies. The sweep rate shall be capacity of the equipment’s force-resisting system. During

5
ACCEPTANCE CRITERIA FOR SEISMIC QUALIFICATION BY SHAKE-TABLE TESTING
ON NONSTRUCTURAL COMPONENTS AND SYSTEMS

the seismic simulation test, the UUT will respond to the Ip, does not increase the seismic test input motion but does
excitation and inelastic behavior will naturally occur. affect the requirement for the UUT to demonstrate a level of
Therefore, the ratio (Rp / Ip) shall be set equal to 1, which is functionality following seismic simulation testing, and is used
indicative of an unreduced response. The importance factor, in this criteria to determine post test UUT functionality
Ip, does not increase the seismic test input motion but does compliance in accordance with Section 6.7. The component
affect the requirement for the UUT to demonstrate a level of amplification factor, ap, acts as a force increase factor by
functionality following seismic simulation testing, and is used accounting for probable amplification of response
in this criteria to determine post-test UUT functionality associated with the inherent flexibility of the nonstructural
compliance in accordance with Section 6.7. The component component. The component amplification factor, ap, shall be
amplification factor, ap, acts as a force increase factor by taken from the formal definition of flexible and rigid
accounting for probable amplification of response components. By definition, for fundamental frequencies less
associated with the inherent flexibility of the nonstructural than 16.7 Hz the equipment is considered flexible (maximum
component. The component amplification factor, ap, shall be amplification ap = 2.5), which corresponds to the amplified
taken from the formal definition of flexible and rigid region of the RRS. For fundamental frequencies greater
components. By definition, for fundamental frequencies less than 16.7 Hz the equipment is considered rigid (minimum ap
than 16.7 Hz the equipment is considered flexible (maximum = 1.0), which corresponds to the ZPA. This results in two
amplification ap = 2.5), which corresponds to the amplified normalizing acceleration factors, that when combined,
region of the RRS. For fundamental frequencies greater defines the horizontal equipment qualification RRS:
than 16.7 Hz the equipment is considered rigid (minimum ap
= 1.0), which corresponds to the ZPA. This results in two ⎛ z⎞ ⎛ z⎞
AFLX = SDS ⎜ 1 + 2 ⎟ and ARIG = 0.4 SDS ⎜ 1 + 2 ⎟
normalizing acceleration factors that, when combined, ⎝ h ⎠ ⎝ h⎠
define the horizontal equipment qualification RRS:

⎛ H ⎞ ⎛ H ⎞
AFLX = 2.5 Ca ⎜ 1 + 3 x ⎟ and ARIG = Ca ⎜ 1 + 3 x ⎟ , where AFLX is limited to a maximum value of 1.6 times SDS.
⎝ H r ⎠ ⎝ Hr ⎠ For vertical response, z may be taken to be 0.0 for all
attachment heights.
where AFLX is limited to a maximum value of 4 times Ca and 6.5.1.2.2 B u i l d i n g - s p e c i f i c : Equipment
ARIG is limited to a maximum value of 3 times Ca. For vertical requirements may alternatively be defined using the results
response, Hx may be taken to be 0.0 for all attachment of a dynamic analysis procedure for the seismic design of a
heights. % specific building per Sections 12.9, 16.1 and 16.2 of ASCE
% 7. Response spectra constructed in accordance with Section
6.5.1.2 IBC: The required response spectra for both % 1613.5 of the IBC, using R = 1.0, shall be used in the
horizontal and vertical directions shall be developed based analysis of the building structural system. A result of the
on the formula for total design horizontal force, Fp, in dynamic analysis procedure yields the following parameters
accordance with either Section 6.5.1.2.1 or Section 6.5.1.2.2 for AFLX and ARIG:
of this acceptance criteria.
AFLX = 2.5 Ax ai and ARIG = Ax ai,
6.5.1.2.1 Building—Generic: When the building
dynamic characteristics are not known or specified, the where Ax is the torsional amplification factor per Section
horizontal force requirements shall be as determined using % 12.8.4.3 of ASCE 7 and ai is the acceleration at level i,
% Equation 13.3-1 of ASCE 7, which reads as follows: obtained from the dynamic analysis procedure. For vertical
response, two-thirds of the response spectra used in the
0.4 ap SDSW p ⎛ z⎞ analysis of the building structural system may be used.
Fp = ⎜ 1+ 2 ⎟
(Rp / Ip ) ⎝ h⎠ 6.5.2 Derivation of Test Input Motion: To meet the
required response spectra as defined in Section 6.5.1, the
The height factor ratio (z / h) accounts for above grade-level corresponding shake-table drive signals shall be
equipment installations within the primary supporting nonstationary broadband random excitations having an
structure and ranges from zero at grade–level to one at roof- energy content ranging from 1.3 to 33.3 Hz. The drive signal
level, essentially acting as a force increase factor to composition shall be multiple-frequency random excitations,
recognize building amplification as you move up within the the amplitudes of which adjusted either manually or
primary structure. The site-specific ground spectral automatically based on multiple-frequency bands. The exact
acceleration factor, SDS, varies per geographic location bandwidth of individual bands employed shall be left to the
(taken from the design value maps) and site soil conditions. discretion of the test laboratory. Typically, one-third-octave
The SDS factor is used to define the general design bandwidth resolution is used with analog synthesis
earthquake response spectrum curve and is used to equipment. However, the use digital synthesis equipment
determine the design seismic forces for the primary building may require narrower frequency bands on the order of one-
structure. The ratio of Rp over Ip (Rp / Ip) is considered to be sixth-octave bandwidth. The process involves use of an
a design reduction factor to account for inelastic response aggregate of multiple narrowband signals that is input to the
and represents the allowable inelastic energy absorption shake-table with each band adjusted until the TRS envelops
capacity of the equipment’s force-resisting system. During the RRS according to the criteria specified in Section 6.5.3.
the seismic simulation test, the UUT will respond to the The total duration of the input motion shall be 30 seconds
excitation and inelastic behavior will naturally occur. (nominal), with the non-stationary character being
Therefore, the ratio (Rp / Ip) shall be set equal to 1, which is synthesized by an input signal build-hold-decay envelope of
indicative of an unreduced response. The importance factor, 5 seconds, 20 seconds, and 5 seconds, respectively. The

6
ACCEPTANCE CRITERIA FOR SEISMIC QUALIFICATION BY SHAKE-TABLE TESTING
ON NONSTRUCTURAL COMPONENTS AND SYSTEMS

input duration of the time history tests shall contain at least 6.5.3.2.2 A maximum of two of the one-sixth-octave
20 seconds of strong motion. Strong motion durations analysis points may be below the RRS (frequencies greater
greater than 20 seconds shall be considered acceptable. than 8.3 Hz), as under the same constraints as noted in
Independent random signals that result from an aggregate Section 6.5.3.2.1.
of the narrowband signals shall be used as the excitation to
produce phase incoherent motions in the principal horizontal 6.6 Post-test Inspection: The UUT shall be visually
and vertical axes of the shake table. examined and results documented upon completion of the
multifrequency seismic simulation tests performed in
6.5.3 Test Response Spectrum Analysis: The test accordance with Section 6.5. The following conditions shall
response spectrum (TRS) shall be computed using either apply:
justifiable analytical techniques or response spectrum
6.6.1 Attachments: Equipment design must ensure that
analysis equipment using the control accelerometers located
at the UUT base per Section 6.4.3. The TRS shall be the anchored UUT will not leave its mounting and cause
calculated using a damping value equal to 5 percent of damage to other building components or injury to personnel
critical damping. The TRS must envelop the RRS based on during the seismic event. Structural integrity of the
a maximum-one-sixth octave bandwidth resolution over the equipment attachment system shall be maintained.
frequency range from 1.3 to 33.3 Hz, or up to the shake 6.6.2 Equipment Force-resisting System: Equipment
table limits. The amplitude of each narrowband signal shall design must ensure that structural failure of the lateral
be independently adjusted in each of the principal axes until force–resisting system of the UUT would not cause a safety
the TRS envelops the RRS, within the limitations of the test hazard to life or limb. Structural damage, such as local
machine. It is recommended that the TRS should not exceed yielding, to UUT force-resisting members is acceptable and
the RRS by more than 30 percent over the amplified region structural members and joints comprising the UUT force-
of the RRS (within the limitations of the shake table control resisting system shall be allowed minor fractures and
system). Any acceleration-signal filtering performed within anomalies.
the range of analysis must be defined. The general
requirement for the enveloping of the RRS by the TRS can 6.7 Post-test Functional Compliance Verification:
be modified under the following conditions: Based upon the specified UUT importance factor in Section
4.3, equipment being qualified must be capable of
6.5.3.1 Amplified Region of RRS: In the performance performing its intended functions after the seismic event.
of a test program, the TRS may not fully envelop the Functionality and operability requirements and/or tests, as
amplified region of the RRS (frequencies less than or equal specified in Section 4.4, shall be performed on the UUT to
to 8.3 Hz). The general requirement for a retest may be verify post-test functional and operational compliance.
exempted if the following criteria are met: Functional testing may be performed by an accredited
6.5.3.1.1 In those cases in which it can be shown by testing laboratory at either the test facility or at the UUT
use of the resonance search in Section 6.4.4 that no manufacturing facility when required test equipment is not
resonance response phenomena exist below 5 Hz, the TRS available at the test facility. (Requirements of this section
is required to envelop the RRS only down to 3.5 Hz. are satisfied if one of the following criteria is met.)
Excitation must continue to be maintained in the 1.3 Hz to 6.7.1 Components with Ip = 1.0: At the completion of
3.5 Hz range, within the limitations of the shake table. the seismic testing, the UUT does not pose a life or limb
6.5.3.1.2 When resonance phenomena exist below safety hazard due to collapse or due to major
5 Hz, the TRS is required to envelop the RRS only down to subassemblies becoming separated. Structural integrity of
75 percent of the lowest frequency of resonance. anchorage system shall be maintained. Structural damage,
such as local yielding, to UUT force-resisting members is
6.5.3.1.3 When the absence of resonance response acceptable and structural members and joints comprising
phenomena below 5 Hz cannot be justified, the general the UUT force-resisting system shall be allowed minor
requirement applies and the low-frequency enveloping fractures and anomalies.
should be maintained down to 1.3 Hz.
6.7.2 Components with Ip = 1.5: The equipment is
6.5.3.1.4 A single point of the TRS may fall below
deemed to be essential to the continued operation of a
the RRS (for frequencies less than or equal to 8.3 Hz) by 10
facility, and/or essential to maintaining critical life support
percent or less, provided the adjacent one-sixth-octave
systems, and/or contains materials deemed to be
points are at least equal to the RRS.
hazardous, to humans or the environment, in quantities
6.5.3.1.5 A maximum of two of the one-sixth-octave greater than the exempted amounts listed in the code. After
analysis points may be below the RRS (for frequencies less completion of the seismic testing, the UUT shall satisfy the
than or equal to 8.3 Hz), as under the same constraints as functional and operational requirements and/or tests
noted in 6.5.3.1.4. specified in Section 4.4, with equivalent results to those of
6.5.3.2 ZPA Region of RRS: In the performance of a the pre-test functional compliance testing of Section 6.3.
UUT materials deemed to be hazardous shall not have been
test program the TRS may not fully envelop the ZPA region
released into the environment in quantities greater than the
of the RRS (frequencies greater than 8.3 Hz). The general
exempted amounts listed in the code. In addition, at the
requirement for a retest may be exempted if the following
completion of the seismic testing, the UUT does not pose a
criteria are met:
life-safety hazard due to collapse or major subassemblies
6.5.3.2.1 A single point of the TRS may fall below becoming separated. Structural integrity of anchorage
the RRS (for frequencies greater than 8.3 Hz) by 10 percent system shall be maintained. Structural damage, such as
or less, provided the adjacent one-sixth-octave points are at local yielding, to UUT force-resisting members is acceptable
least equal to the RRS. and structural members and joints comprising the UUT

7
ACCEPTANCE CRITERIA FOR SEISMIC QUALIFICATION BY SHAKE-TABLE TESTING
ON NONSTRUCTURAL COMPONENTS AND SYSTEMS

force-resisting system shall be allowed minor fractures and Nuclear Power Generating Stations (1987), Institute of
anomalies. Minor repairs to the UUT (such as replacing a Electrical and Electronics Engineers, Inc.
bulb) are allowed for the equipment to satisfy this section.
7.4 IEEE Standard 693-1997, IEEE Recommended
Any repairs shall be documented and included in the final
test report noted in Section 5.2. Practice for Seismic Design of Substations (1997), Institute
of Electrical and Electronics Engineers, Inc.
7.0 REFERENCES
% 7.5 ASCE Standard, SEI/ASCE 7-05, Minimum Design
7.1 1997 Uniform Building Code™. Loads for Buildings and Other Structures, American Society
% 7.2 2006 International Building Code®, International Code of Civil Engineers.#
Council.
7.3 ANSI/IEEE Standard 344-1987, IEEE Recommended
Practice for Seismic Qualification of Class 1E Equipment for

8
ACCEPTANCE CRITERIA FOR SEISMIC QUALIFICATION BY SHAKE-TABLE TESTING
ON NONSTRUCTURAL COMPONENTS AND SYSTEMS

ANNEX A

Section 4.0 UUT Required Information Template


UUT: Name

This appendix details the necessary required information to be provided to the test laboratory for each equipment item (UUT) to
be seismically qualified. Sections in parentheses refer to sections of this criteria.

Manufacturer’s Contact Information (Section 4.1.1)

Manufacturer: Company name


Address: Company address

Primary Contact: Representative(s) name


Phone Number: Representative(s) phone number

Test Laboratory’s Contact Information (Section 4.1.2)

Test Laboratory: Lab name


Address: Lab address

Primary Contact: Representative(s) name


Phone Number: Representative(s) phone number

Test Specimen Description (Section 4.2)

Name: Product name


UUT Designation: Short alphanumeric UUT designator used for plotting and test run purposes.
UUT Function: A general description of the primary function or end use of the product.
Description: A detailed description of the UUT configuration. This should include a listing of major subassemblies and
components (e.g., bills of material) and any other applicable product differentiation.
Identification No.: Supply UUT’s unique identification number or serial number.
Dimensions: Height = xx in. Width = xx in. Depth = xx in.
Weight: Approximately xxx lbs.
Restrictions: Provide any product restrictions or limitations on use.

Seismic Parameters (Section 4.3)

% Building Code: List the required code (1997 UBC and/or 2006 IBC)
Height Factors: The ratio of (Hx/Hr) for UBC and/or the ratio of (z/h) for IBC shall be provided
Seismic Coefficient: Provide the specific seismic coefficient as required per the building code (SDS value for IBC and Ca value
for the UBC)
Importance Factor: Specify the desired importance factor. The Ip value will dictate the level of acceptance criteria used during
qualification testing.

Functional and Operability Requirements (Section 4.4)

Required Testing: List and define any testing that will be used in the determination of pre- and post-functional compliance.
Each test and/or requirement should be listed as a separate line item.

Equipment Product Line Extrapolation and Interpolation (Section 4.5)

Structural: A rationale shall be provided explaining that the selected UUT’s structural configuration is one offering the
least seismic withstand capacity compared to other options that are available within the product line being
qualified.
Mounting: A rationale shall be provided explaining that the selected UUT’s mounting configuration is one offering the
least seismic withstand capacity compared to other mounting options that are available within the product
line being qualified.

9
ACCEPTANCE CRITERIA FOR SEISMIC QUALIFICATION BY SHAKE-TABLE TESTING
ON NONSTRUCTURAL COMPONENTS AND SYSTEMS

Subassemblies: A rationale shall be provided explaining that the selected UUT’s subassemblies are representative of
production hardware and offer the least seismic withstand capacity of the UUT compared to other
subassembly options that are available within the product line being qualified.
Mass
Distribution: A rationale shall be provided explaining that the selected UUT’s mass distribution is one contributing to the
least seismic withstand capacity of the UUT compared to other mass distribution options that are available
within the product line being qualified.

Variations: A rationale shall be provided explaining that the selected UUT’s overall variations contribute to the least
seismic withstand capacity of the UUT compared to other variations that are available within the product
line being qualified.

Installation Instructions (Section 4.6)

Field Mounting: Describe how the product is to be mounted in field applications. This should include the quantity, size,
grade and installation torque of mounting fasteners, or weld size and weld type for welded installations.

Sketch: Provide a sketch of the UUT mounting hole bolt pattern or welding details.

Test Mounting: The preferred test specimen mounting is to directly attach the UUT to the shake-table using the field-
mounting configuration. Alternatively, the UUT may be secured to a rigid interface test fixture and then the
test fixture is secured to the shake table. Details of recommended interface test fixtures should be defined.

Special Test Instructions (Optional)

Request: Define any special instructions that may be beyond the standard test requirements of AC156. This could
include requests for additional response accelerometers or displacement and force monitors, digital output
from accelerometers, etc. Each unique request should be listed as a separate line item.

10

You might also like