NINGBO ANT

GLC Series Microprocessor Based Service Lift Controller

Users Manual VER 2.9

NINGBO ANT ELECTRONIC CO.,LTD


1.1 GLC-300 Main Controller Figure,Button Function and Interface Introduction

System power supply


A N T E L E C T R ON I C
GLC-300
GLC Series Microprocessor Based Service Lift Controller Users Manual

X29
Contactor Monitoring
P OW ER IN

X28

Door open contactor2


System parameters debug key

Lock circuit X27 AC2


Power supply terminal

Door open contactor1


Safety circuit X26 AC1
Power supply terminal

1
Overload signal X25 Y35 A1 A2
Door open contactor 2 output

Downstream contactor
Operate/Overhaul X24 Y34 A1 A2

Upstream contactor

Contactor power supply


Lower limit signal Door open contactor 1 output
X23 Y33 A1 A2
Downstream contactor output

Main contactor
Upper limit signal X22 Y32 A1 A2
Down overhaul Upstream contactor output
X21 Y31 A1 A2
Uplink overhaul Main contactor output
X15 COM2
5th floor leveling signal input Y31-Y35 Common
Y23
PROGRAM & MEMORY

X14
Buzzer output
OK
4th floor leveling signal input X13 Y22
3rd floor leveling signal input Downstream arrow indicator output
X12 Y21

1
Upstream arrow indicator output

-
2nd floor leveling signal input

+
X11 Y15

Jumping time setting key


1st floor leveling signal input Decimal code 5th floor display output

RESET
X07 Y14
Door open button signal input Decimal code 4th floor/BCD code D display output
2

X06 Y13
Door open button signal input Decimal code 3rd floor/BCD code C display output
1

X05 Y12
5th floor button signal input Decimal code 2nd floor/BCD code B display output
X04 Y11
4th floor button signal input Decimal code 1st floor/BCD code A display output

Outbound board Power supply


X03 Y05
3rd floor button signal input 5th floor button indicator output

B
X02 Y04
2nd floor button signal input 4th floor button indicator output

I NPUT
X01 Y03
1st floor button signal input 3rd floor button indicator output

OU T P U T
COM0 Y02 2nd floor button indicator output
Y01

A
1st floor button indicator output
COM1 Y01-Y23 Common

System display

Output display code


setting button
GLC Series Microprocessor Based Service Lift Controller Users Manual

A N T E L E C T R ON I C
GLC-400

X29

System power supply


Contactor monitoring
POWER IN

X28

Door open contactor2


Lock circuit
System parameters debug key

X27 AC2
1.2 GLC-400 Main Controller FigureButton Function And Interface Introduction

Door open contactor1


Power supply terminal

2
Safety circuit
AC1

Downstream contactor
X26

1
Overload signal Power supply terminal
X25 Y35
Operate /O verhaul
A1 A2
Door open contactor2 output

Upstream contactor
X24 Y34 Door open contactor1 output
A1 A2
Lower limit signal X23 Y33

Contactor power supply


A1 A2
Downstream contactor output

Main contactor
Upper limit signal X22 Y32 A1 A2
Down overhaul Upstream contactor output
X21 Y31 A1 A2
Main contactor output
Uplink overhaul X15 COM2 Y31- Y35 Common
Y23
PROGRAM & MEMORY

X14
OK
Buzzer output
X13 Y22
Downstream arrow indicator output
X12 Y21 Upstream arrow indicator output

2
-
Basement reset signal input

+
X11 Y15

Jumping time setting key


Leveling signal input Decimal code 5th floor display output

RESET
X07 Y14
Decimal code 4th floor display output
Door open button 2 signal input X06 Y13 Decimal code 3rd floor/BCD code C display output
Door open button 1signal input X05 Y12 Decimal code 2nd floor/BCD code B display output
5th floor button signal input X04 Y11
Decimal code 1st floor/BCD code A display output
4th floor button signal input X03 Y05 5th floor button indicator output

B
3rd floor button signal input X02 Y04 4th floor button indicator output

Outbound board Power supply


2nd floor button signal input

INPUT
X01 Y03 3rd floor button indicator output
1st floor button signal input

OU T P U T
COM0 Y02 2nd floor button indicator output
Y01

A
1st floor button indicator output
COM1
Y01-Y23 Common

Syetem display

code setting key


Output display
GLC Series Microprocessor Based Service Lift Controller Users Manual

2.1 Input signal terminals Introduction


Input terminals serial number Element function Remarks

COM0 Signal input common terminal X01-X29 signal common terminal

X01 1st floor selection button signal input Effective connection

X02 2nd floor selection button signal input Effective connection

X03 3rd floor selection button signal input Effective connection

X04 4th floor selection button signal input Effective connection


X05 5th floor selection button signal input Effective connection
X06 Door open button signal input Effective connection
X07 Door open button 2 signal input Effective connection
1st floor leveling signal input( 300)
X11 Leveling signal input( 400 ) Effective connection
2nd floor leveling signal input(300)
X12 Basement reset signal input(400) Effective connection
X13 3rd floor leveling signal input(300) Effective connection

X14 4th floor leveling signal input(300) Effective connection

X15 5th floor leveling signal input(300) Effective connection


X21 Overhaul box uplink button signal input Effective connection

X22 Overhaul box down button signal input Effective connection

X23 Upper limit detect signal input Closed normally


X24 Lower limit detect signal input Closed normally
X25 Overhaul\operate detecting signal input On Run
X26 Overload detect signal input Closed overload
X27 Safety circuit detect signal input Closed normally
X28 Lock circuit detect signal input Closed normally
X29 Auxiliary contacts input P4 parameter alternative

3
GLC Series Microprocessor Based Service Lift Controller Users Manual
2.2 Output signal terminals introduction

Input terminals serial number Element function Remarks

COM1 Y01Y23 output common terminal


Y01 1st floor selection button light signal output Normally open contact

Y02 2nd floor selection button light signal output Normally open contact

Y03 3rd floor selection button light signal output Normally open contact

Y04 4th floor selection button light signal output Normally open contact

Y05 5th floor selection button light signal output Normally open contact
Decimal code display code output1
Y11 BCD code display code outputA
Normally open contact
Y12 Decimal code display code output2 Normally open contact
BCD code display code outputB
Y13 Decimal code display code output3
BCD code display code outputC Normally open contact
Y14 Decimal code display code output4 Normally open contact
Y15 Decimal code display code output5 Normally open contact
Y21 Uplink indicator signal output Normally open contact
Y22 Downstream indicator signal output Normally open contact
Y23 Buzzer control signal output Normally open contact
COM2 Y31Y35 output common terminal
Y31 Main contactor control signal output Normally open contact
Y32 Uplink contactor control signal output Normally open contact

Y33 Downstream contactor control signal output Normally open contact


Y34 Door open contactor signal output Normally open contact
Door open contactor2 signal output(300/400)
Y35 Door close contactor signal output(500)
Normally open contact

2 . 3Power Input Terminal Introduction


AC1 System power supply System power supply is divided
AC 6 5- 4 40 V into two kinds, please subject to the
Or
AC2 A C/D C24 V5 %
voltage which marked on controller shell

4
GLC Series Microprocessor Based Service Lift controller Users Manual
3 Main controller function feature
3.1 Overhaul function
Refer to overhaul Priority which defined in Gb7588any overhaul switch on the top of car and PC room,
when located at overhaul point lift is in overhaul state.
A In overhual statepress updown buttonlift for jog operationrelease
buttonstop immediatly.

B When overhaulingdown to lower limitliftwill stop downward operation


down command is invalidbut it can repond to up signaloperate at upwardthe control
logic of upgoing to upper limit conversely

C When overhaulingcontroller still respond to the signal of safety circuitlock


circuitoverload

3.2 Floors automatic learning


Lift instllation and debugging or other circumstanceslead to incorrect of floor signal
when lift go to next leveling signal, GLC-300 and GLC-500 main controller will do floor
figure calibration automaticallyGLC-400 main controller can do floor figure calibration when
lift operate to basement reset signalto make sure normal floor positioning

3.3 Main operating output contactor motor protection


During the operationwill do contactor auxiliary contacts monitoring every floor
system will reset once if operate normally if contactor was in adhesions state system will
stop automaticallyand display fault code, cant recover to normal until faults were cleared

3.4 Door jump timecar stuckmonitor


Elevator in automatic operation, the system will always monitor the door zone signal
acquisition and the car running state, in a predetermined period of time(visible to the user lifting
height, speed enhancement and other specific circumstances can set freely), if nowhere zone
signal, determine the car stuck, parking immediately, suggesting failure, according to the
principle of GB7588, maintaining parking state, manually reset (emergency stop or power cutoff)
in order to restore normal operation next time.
3.5 Overload protection
A Elevator runs automatically and in leveling state, overload signal is valid, system will
not respond to operation command, output buzzer sound automatically to prompt the user, and keep
stopping state until the overload signal is canceled. Overload signal is canceled, the system enters
positive normal operation state automatically.

5
GLC Series Microprocessor Based Service Lift Controller Users Manual
B Overload signal only effective when elevator stopped, the elevator once in operating
status, system will not respond to overload signal until the next stopping, if overload signal has
been effective before entering overload condition.

3.6 Door interlock monitor


Elevator door opening every time and during operation , system always monitor the door
lock circuit working state, if the state meets the normal conditions, the system will automatically
stop, and a fault signal (floor display flickers at a frequency of once per second, main controller
displays E1), troubleshooting until it resumes normal operation.

3.7 Emergency stop button alert


Lift is in automatic operation state and no other system faults, since user p ress the emergency
stop button,leaving lift in emergency stop, the system will prompt user that lift stop is due to
handling emergency stop button by himself with a way that down and up light of floor indicator
flickers synchronously , which can effectively prevent abnormal stop which caused by misuse or
forget to recover after finish operation, release emergency stop button timely and recover to
automatic operation

3.8 Lift-calling alert


Elevator runs automatically and in leveling open state, if other floors call elevator(The user
presses the current floor button), system will output the buzzer sounds five seconds tips, floor
indicator prompts user by flashing once per second which on corresponding floor lift-calling
button simultaneously.

3.9 Level switch detect function


In the overhaul of non-stop state, input a leveling signal, indicator will show corresponding
floor number, easy to the overhaul of leveling switch.

3.10 Electromagnetic locks or door switch output function


In the statement of leveling stoppress door open button1 or button2GLC-300 or
GLC-400,system output open signal1 or signal2 correspondingly for using and controlling
electromagnetic lockpress open or close buttonGLC-500),system outputs switch door
corresponding Switch signal respectively and shows current statement.

3.11 Support system software programming upgrade online


Microprocessor based service lift main controller support software programming online
same system can achieve system software change that caused by users different requirements,
no need to change harware configuration.

6
GLC Series Microprocessor Based Service Lift Controller User's Manual

4 Main controller code function


Code Operate statement Remarks

Lift in the state of 2nd floor upward. Normal

Lift in the state of 2nd floor downward. Normal

Lift stop at 2nd floor Normal

5 Common fault code and Countermeasures


Fault code Fault name Reason and Countermeasures
Safety circuit failure or safety circuit relay broken.
Safety circuit fault Check the input circuit and safety circuit relay.
Outbound monitor up and
downward indicator flickers

Lock circuit open or switch broken.


Outbound monitor floor
Lock circuit fault Check input line of lock circuit and switch.
indicator flickers

Upper limit circuit open or switch damaged.


Upper limit fault Check input line of upper limit circuit and switch.

Lower limit circuit open or switch broken.


Lower limit fault Check input line of lower limit circuit and switch.
Leveling sensor input circuit has two or more
Leveling sensor fault channels input simultaneously.
Check leveling sensor each floor if been magnetized or broken.
Motor stalled or car stuck. Check motor
Door zone jumping
operation if normalcar stuck extremly
time protection fault change motor or clear obstacles.

Contactor circuit open or adhered. Check input


Contactor fault
circuit or change contactor.

Car overloaded.Check car rated load,


Overload Release load.

Operate cumulative Lift's operate time already reached setting figure.


time fault Revise P3 parameter to 01",reset cumulative time.

7
GLC Series Microprocessor Based Service Lift Controller Users Manual
6.1 Menu parameter functionsetting introduction

Key Key function introduction


A Display code selection setting key
B Jumping time setting key
R E S E T Return keydebugging key
O K Enter keydebugging key
+ Page up keyplus1

- Page downminus1
6. 2 System display code selectiondecimal codeB C D code
System power-up, elevator is in overhaul mode, press the "A" key to enter the
display coding options, the system four LED digital display "A" which is a decimal code,
"b" that is,BCD code, each press cycles in two menus flashing display, 5 seconds no
Corresponding operation, the system will automatically recognize and output encoding
options currently displayed.
6. 3 System jumping protection time option
System power-up, elevator is in overhaul mode, press the "B" key to enter jumping
protection time selection, system four LED digital tube to 00 ~ 20 ~ 36 ~ 45 ~ 60 ~ 75
seconds numerical circulation flashing alternately shows every click, numerical values
d own a jump,5 seconds without the corresponding operation, the system will
automatically remember the currently displayed digital value.(LED digital display of
numbers that is the desired time, in seconds, 00 is cancellation of jumping time protection. )

6.4 System detail parameter setting method


System power-up, elevator is in overhaul mode, press the "RESET" button and "OK"
key to enter the password input state, then press the "+" or "-" key to modify the first bit
value, finished press "OK" button to move to the next one operation, when the four
password-election selection is correct (the default password is 1234) and press "OK" to
enter the parameter setting state. Parameter changes are complete, press the "RESET"
to save all modified parameters.
( This case is the debugging procedure of modifying P6 parameter value separately)
Now showing Now showing Now showing Now showing
Now showing Now showing Now showing parameter P6 parameter P6 parameter P6 parameter P6
input password input password debugging menu value value menu

No action within
5 seconds

In the overhaul state while


Press the [OK] key Press [+] key and [OK] key Press [RESET] key
press [ok] key
Press [OK] key Exit debug state
And [RESET] keys, 5 Select the input initial password Press [OK] keyEnter Press [+] or [-] key finish modification of
Press [+] button Display P6. restored to normal
Seconds no pressing 1234Within 5 seconds no pressing the correct password modify P6 into 13 P6 parameter value
Select P6 parameters. Parameter values. display state
Then restore the display state restored to normal display. Enter debug state.

*RemarksModify other parameter values in the same way, finish modifying, press [RESET] key to exit debug state was only after the data is recorded.

8
GLC Series Microprocessor Based Service Lift Controller User's Manual
7 Menu structureparameter setting instruction

03 - Model:GLC-300
production model selection 03
04 - Model:GLC-400

System password setting (0000-9999) - password value 1234

System operate
00 - cancel limitation of cumulative time
Cumulative time 00
(01~24)- 1-24 months
setting
System operate 00 - keep current cumulative time
cumulative time 00
01 - Reset cumulative time
reset
00 - cancel contactor detecting
Contactor monitor signal
input control terminal setting
01 - Contactor normal close terminal detecting 01
02 - Contactor normal open terminal detecting

Overload signal input 00 - Enable overload signal normal open


00
control terminal setting 01 -Enable overload signal normal close

Door open signal1 (03~15)- time of opening door


10
time setting keeps 3-15 seconds

Door open signal2 time setting (03~15)- Time of door open 2 keeps 10
3-15 seconds(300/400)

00-Manual button of electromagnetic


value to open the door
01-Manual Button pusher motor to open
the door
02-Press the open button to open the door
manually, press the close button to move
Door Switch the door
Model Setting 03-Automatic door station,press the close
00
button to close the door;
04-Automatic door station,press close the
door button to close automatically
05-Automatic door station,press the close
button automatic, automatic the door
after selecting layer

9
GLC Series Microprocessor Based Service Lift Controller Users Manual

Parameter Name Parameter Function Parameter values and meanings defaults

( 01-150)-It represents automatic the door


Automatic door after closing when in station, delay 1- 150 seconds after
time delay setting completing output, and output the close door 10
signal automatically.

( 01-10)-It represents the arrival voice time


Arrival voice prompts setting keeping 1- 10 seconds
05

Inspection/ Run signa l input 00-on is operation, off is overhaul


control terminal setting 01-on is overhaul, off is operation 00

Allow elevator open and 00 - Leveling position in response to the switching


gate
close position setting
00
01-Response door switch in anywhere position

When the door lock is discon-


-nected, call the number flas- 00-Allow the floor number is flashing
-hing display floor setting 00
01-Ban the floor number flashing

The main controller and up/ ( 0. 1- 3. 0) - It represents the action time


interval of the main controller and up/ down
down contactor operation time
interval setting contactors is 0. 1~ 3 seconds. 1.0

Alternate 00

Alternate 00

Alternate 00

Alternate 00

10
T
S
R
202 301

202
R

N
1st floor button light 1st floor storey-selection button

0V +24V
201

Name

Design

( inside 24V
2nd floor button light
2nd floor storey-selection button

203
3rd floor button light 3rd floor storey-selection button

4th floor button light 4th floor storey-selection button

5th floor button light 5th floor storey-selection button

204
R1

Three-phase air switch

1st floor display


1
S1

2nd floor display

single-phase air switch


0V

205
2
T1 5
3
1

3rd floor display 1st floor leveling switch


3
1st floor door-opening button 1

NINGBO ANT ELECTRONIC CO. , LTD


GLC-300 service lift control cabinet circuit Diagram V1.5
4th floor display 2nd floor leveling switch
6
4
2

4 1st floor door-opening button 2


5th floor display 3rd floor leveling switch
Phase sequence protector

206
R2

5
101
Main contactor

Upstream arrow 4th floor leveling switch


102 L
N
S2

UP
2nd floor door-opening button 1

11
Downstream arrow 5th floor leveling switch
DN 2nd floor door-opening button 2
5
3
1
T2 5
3
1

207
Buzzer Overhaul uplink button

outbound display board


BELL
Overhaul down button
6
4
2
6
4
2
8.1 GLC-300 control cabinet typical application

102 3rd floor door-opening button 1


24V
0V

1st floor emergency stop


U

Upper limit switch


101 Safety circuit relay Main contactor

COM1 Y01 Y02 Y03 Y04 Y05 Y11 Y12 Y13 Y14 Y15 Y21 Y22 Y23 COM2 31
3rd floor door-opening button 2
V

A2
24V Switch Power Supply

A1
Upstream contactor

Car top emergency stop PC room emergency stop Phase-sequence protection Upper limit position Upper limit position 1st floor door lock

Door interlock relay Up contactor Lower limit switch


Down contactor
Downstream contactor
W

GLC-300 Main Controller


A1 A2 4th floor door-opening button 1
Down contactor Overhaul/operate switch
Up contactor
A1 A2
209
208

Door-open contactor 1
N floor door lock

Overload switch4th floor door-opening button 2


13
13
N floor emergency stop

A1 A2
Safety circuit relay
3
~

Door open contactor 2


YD

101 A1 A2 5th floor door-opening button 1


14
14

(201) Door interlock relay


Safety circuit reply

Basement power lock switch 5th floor door-opening button 2


201
102

202
101

COM0 X01 X02 X03 X04 X05 X06 X07 X11 X12 X13 X14 X15 X21 X22 X23 X24 X25 X26 X27 X28 X29

power supply input

Y32 Y33 Y34 Y35 AC1 AC2


Up contactor
Main contactor

102
Down contactor
201

Door interlock circuit relay

(202)
Motor / traction machine
GLC Series Microprocessor Based Service Lift Controller Users Manual
GLC Series Microprocessor Based Service Lift Controller Users Manual
8.2 GLC-400 Control Cabinet Typical Application
Main contactor Upstream contactor
R R1 1 2 R2 1 2 U

S S1 S2 V YD
3 4 3 4
~
T T1 5 6 T2 5 6 W 3

Three-phase air switch


Motor/traction machine
Downstream contactor
1 2

Phase sequence protector 3 4

5 6
102
R 101
N 101 201
0V N
Single- phase air switch 24V switch power supply 202
102 L
24V

Name GLC-400 service lift control cabinet circuit diagram V1.5 208
13 14
1st floor emergency stop N floor emergency stop
Design NINGBO ANT ELECTRONIC CO.,LTD
Safety circuit relay

202 203 204 205 206 207 209 201


13 14
N floor door lock
Car top emergency stopPC room emergency stop Phase sequence protection Upper limit position Upper limit position 1st floor door lock
Door interlock circuit relay
1st floor door-opening button 1 1st floor door-opening button 2
Y11 Y11
2nd floor door-opening button 1 2nd floor door-opening button 2
Y12 Y12
3rd floor door-opening button 1 3rd floor door-opening button 2
Y13 131 14 Y13 13 button 14
4th floor door-opening button 201 4th floor door-opening 2 201
301

Y14 Door-opening relay 1 Y14 Door-opening relay 2


5th floor door-opening button 1 5th floor door-opening button 2
Y15 Y15
1st floor storey-selection button

2nd floor storey-selection button

5th floor storey-selection button


4th floor storey-selection button
3rd floor storey-selection button

Door-opening relay 2
Door-opening relay 1

Overhaul/operate switch

Overload switch
Basement reset switch

Overhaul uplink button

Upper limit switch

Lower limit switch


Overhaul down button

Door interlock relay


Leveling switch

Main contactor
Safety circuit relay

Up contactor

Down contactor

COM0 X01 X02 X03 X04 X05 X06 X07 X11 X12 X13 X14 X15 X21 X22 X23 X24 X25 X26 X27 X28 X29

0 V + 2 4V
(inside 24V GLC-400 Main Controller
Power supply input

COM1 Y01 Y02 Y03 Y04 Y05 Y11 Y12 Y13 Y14 Y15 Y21 Y22 Y23 COM2 Y31 Y32 Y33 Y34 Y35 AC1 AC2
Up contactor
4th floor display
2nd floor display

5th floor display


3rd floor display
1st floor display

Downstreamarrow
Upstream arrow

Down contactor

Door-opening contactor 2

Basement power lock switch


Door-opening contactor 1
5th floor button light
4th floor button light
3rd floor button light
1st floor button light

2nd floor button light

Buzzer

Down contactor
Main contactor

Up contactor
A1 A2

A1 A2

A1 A2

A1 A2

A2
BELL
UP

DN
1

A1
0V

Safety circuit relay

Door interlockrelay

Outbound display board


(202)
(201)
202

201

102
102

101
101

12
GLC Series Microprocessor Based Service Lift Controller Users Manual

13
GLC Series Microprocessor Based Service Lift Controller Users Manual

14