You are on page 1of 54

GEA Basic Geko

Air Treatment Division

DATA & FACTS


GEA Basic Geko
Fan coil unit for an air of cooperation

1 VK_2052751GB Subject to technical modifications Status 09/2005


Table of Contents GEA Basic Geko

Content Page

Sizes .......................................................................................................................................................................... 1.2


Components of the fan coil units .............................................................................................................................. 2
Selecting a unit ............................................................................................................................................................ 3
Description of units .................................................................................................................................................... 4
Component description .............................................................................................................................................. 6
Coil pressure drop for warm and chilled water....................................................................................................... 26
Example on determining the capacity ..................................................................................................................... 27
Acoustics ................................................................................................................................................................... 28
Sound pressure level, sound power level .............................................................................................................. 29
NR and NC limiting curves ....................................................................................................................................... 30
Installation examples ................................................................................................................................................. 31
Dimensions for basic units without casings .......................................................................................................... 32
Dimensions for casing and accessories ................................................................................................................. 34
Control behaviour of valves ..................................................................................................................................... 36
Overview of valves .................................................................................................................................................... 37
Valves (loose) with modulating actuators (230 V~)............................................................................................ 38
Valves with thermoelectric actuators (230 V~)................................................................................................... 39
Control with thermostat switch MCR 2000 / control by others .............................................................................. 40
GEA MATRIX control system ................................................................................................................................. 42
System description / overview of performance characteristics .......................................................................... 42
Installing the operator panels ............................................................................................................................. 44
Sensors / accessories........................................................................................................................................ 45
Global modules .................................................................................................................................................. 46
Global modules / central timer ........................................................................................................................... 49
Service tools ...................................................................................................................................................... 50

Unit type code ........................................................................................................................................................... 51

2
1.1 VK_2052751GB Subject to technical modifications Status 09/2005
Sizes GEA Basic Geko

For wall and ceiling mounting



Heating capacity QH 2)
Size Width Air volume flow 1)
Sound pressure level
Cooling capacity QK 2)

[mm] [m 3/h] [dB(A)] [kW]

1.0-3.1
1 827 130-280 13-36
0.8-1.7

1.4-5.3
2 977 165-540 22-52
1.4-2.8

2.6-8.0
3 1127 350-840 24-50
2.4-4.1

2.9-10.9
4 1277 360-1260 24-58
2.5-5.4

5.1-15.2
5 1577 710-1350 43-59
4.8-8.3
1)
See Acoustics on page 28 for ambient conditions
2)
The performance data applies for the input parameters: warm water 70/50 C, tL1 = +20 C; chilled water 6/12 C, tL1 = 27 C, 46 % r.h.
For different input parameters, use the following correction factors to roughly determine the performance data.

Correction factors 3)
Correction factors f K for Correction factors fH for

cooling capacity QK heating capacity QH
The following correction factors can Chilled Warm
2-pipe system 4-pipe system
be used to determine the performance water Air intake: tL1 [C], 1 [% RH] water
Air intake: tL1 [C] Air intake: tL1 [C]
data in accordance with EUROVENT temperature temperature
classification requirements: [C] 32/40 30/40 27/46 26/50 24/50 [C] +10 +15 +20 +10 +15 +20
cooling recirculation air 6/12 1.38 1.18 1.00 0.98 0.78 90/70 1.77 1.65 1.53 1.90 1.76 1.62
(2+4-pipe system): 0.99 7/12 1.29 1.09 0.91 0.89 0.70 80/60 1.51 1.39 1.27 1.60 1.45 1.30
8/12 1.32 1.12 0.95 0.92 0.73 70/55 1.32 1.19 1.07 1.40 1.27 1.12
heating recirculation air
8/14 1.19 1.00 0.82 0.80 0.61 70/50 1.25 1.13 1.00 1.28 1.14 1.00
(2-pipe system): 0.67
10/15 1.07 0.88 0.71 0.68 0.51 60/50 1.13 1.00 0.88 1.23 1.08 0.94
heating recirculation air 12/16 0.94 0.76 0.61 0.57 0.44 60/40 0.99 0.86 0.73 0.96 0.81 0.66
(4-pipe system): 1.25 12/18 0.83 0.68 0.52 0.47 0.37 50/40 0.87 0.75 0.62 0.91 0.77 0.62
14/18 0.76 0.63 0.49 0.44 0.34 40/30 0.61 0.48 0.35 0.62 0.46 0.31

3)
All named correction factors have been arithmetically calculated for the different unit models and thus only serve to help approximate the
performance data for other parameters.
Contact our employees for exact data.

2
1.2 VK_2052751GB Subject to technical modifications Status 09/2005
Components of the fan coil GEA Basic Geko

units

3
2
1 4 18

15

6
7
9

16

15 10 14
8

17
13
11

12
11

Fig. 2-1:Unit parts (depending on unit model)

Pos. 1: Holding plate Pos. 11: Casing spacer, right/left


Pos. 2: Heat exchanger Pos. 12: Air intake grille
Pos. 3: Operator panel Pos. 13: Casing
Pos. 4: Sheet-steel electric control box Pos. 14: Discharge grille
Pos. 5: Rear panel with side plates Pos. 15: Spacer (on suction side), right/left
(base housing) Pos. 16: Lateral wall condensate tray
Pos. 6: Filter element Pos. 17: Lateral ceiling condensate tray
Pos. 7: Main condensate tray Pos. 18: Heat exchanger with electric heating
Pos. 8: Fan with housing
Pos. 9: Front panel (base housing)
Pos. 10: Access flap

GEA participates in the EUROVENT certification program.


The certified products are listed in the corresponding EUROVENT lists.

23 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko Selecting a unit

Description of units

Recirculation
4-pipe chilled and warm water
air
Cooling
and
heating

2-pipe chilled water and electric heating

Cooling
or 2-pipe chilled or warm water
heating

Heating 2-pipe warm water

Cooling 2-pipe chilled water

Druckverluste im Wrmetauscher

4 Rohrreihen Khlen, 2-Leiter-System

25 1 3
2 4
20 5
6
15
7

Technical data, dimensions and descriptions of accessories


10
9,0
8,0
7,0
6,0
DruckverlustDp [kPa]

5,0
4,5
4,0 30
3,5
3,0
2,5
2,0

1,5

1,0
0,9
0,8
0,7
0,6
0,5
50
60
70
80
90
100

150

200
250
300
350
400
450
500
600
700
800
900
1000

1500

2000

Wasservolumenstrom VW [l/h]
Abb. 25.3
GEA Top-Geko nderungen vorbehalten Stand 08/00 (D) 25

Valves

Thermostat switch / GEA MATRIX control system

VK_2052751GB Subject to technical modifications Status 09/2005 3


Description of units GEA Basic Geko

Ceiling unit Wall unit Recirculation air units


heating/cooling/filtering
2-/4-pipe system
wall and ceiling mounting
base construction out of
galvanized sheet steel with sound
and heat insulation made of
polyethylene
(electric and valve equipment
according to function and need)

Fig. 4-1

Unit casing Unit casing Front panel based of sheet


with air intake grille and spacer casing made with air intake grille and spacer casing made steel,
of plastic of sheet steel colour white, similar to RAL 9010
Access flaps and discharge
grille made of plastic, colour
grey, similar to RAL 7035
also with
spacer casing and air intake
grille made of plastic
colour grey; similar to RAL 7035
alternative:
Spacer casing and air intake
Fig. 4-2 grille made of sheet steel
colour white; similar to RAL 9010
Thermoelectric valve equipment Modulating valve equipment Valve equipment
(loose or installed)
2- and 3-port valves (on/off control
mode) with thermoelectric servo
actuator
2- and 3-port valves (modulating
control mode) with modulating
actuator

Fig. 4-3

Electrical equipment Electrical equipment


plastic terminal box
sheet-steel electric control box
(as needed, model and function of
the unit)

Fig. 4-4

MCR 2000 MATRIX control system Control systems


in accordance with:
unit application,
valve equipment,
internal/external electronic
components

Fig. 4-5

4 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko Description of units

Heat exchanger Heat exchanger Copper pipes with aluminium fins,


for warm or chilled water (2-pipe) for warm and chilled water (4-pipe) max. operating pressure 16 bar
cooling medium water,
50 % glycol
heating medium water,
max. inlet temperature 90 C
coil connection " internal thread;
vent and drain screws

Fig. 5-1

Electric heating (1-speed) Filter element Finned radiator made of


230 V ~ 50 Hz aluminium
heating capacity 1-speed
switchable
1 contactor
2 safety temperature limiters

Synthetic, washable filter


medium, easily interchangeable,
filter quality G1 (EN 779)

Fig. 5-2

Centrifugal fan Centrifugal fan with quiet sleeve


230 V ~ 50 Hz bearings, type and number of
Single Tandem bearings depends on the unit size
and selection, enclosure IP32,
insulation class B

Fig. 5-3

Lateral wall condensate tray Lateral ceiling condensate tray For collecting the entire
condensate from the heat
exchanger and valve pipework, for
an unpressurised condensate
removal, made of plastic.

Fig. 5-4

VK_2052751GB Subject to technical modifications Status 09/2005 5


Recirculation air unit / cooling and heating GEA Basic Geko
Chilled water 6/12 C Warm water 70/
4-pipe chilled and warm water tL1 = +27 C 50 C
Sizes 1 to 5 1 = 46 % RH tL1 = +20 C

Capacity stage 1 Capacity stage 2

Sound pressure *
Cooling capacity

Cooling capacity
Heating capacity

Heating capacity
Air volume flow

Pressure drop

Pressure drop

Pressure drop

Pressure drop

Sound power
Speeds

Size

QK pK QH pH QK pK QH pH
3
m /h kW kPa kW kPa kW kPa kW kPa dB(A) dB(A)

I 130 0.8 3.4 1.0 0.3 1.0 8.7 1.0 0.3 22 13


Plastic terminal box
II 200 1.0 5.6 1.3 0.4 1.4 14.8 1.3 0.4 36 27 1 (select sheet-steel electric
control box for GEA MATRIX)
III 280 1.2 7.8 1.6 0.6 1.7 22.1 1.6 0.6 45 36

I 165 1.4 19.2 1.4 0.7 31 22

II 240 1.8 31.3 1.8 1.0 41 32

III 340 2.3 46.6 2.2 1.4 48 39


2
I 240 1.6 3.7 1.8 1.0 41 32

II 350 2.1 6.0 2.2 1.5 50 41

III 540 2.7 9.4 2.9 2.2 61 52 Speed combination

I 350 2.4 9.1 2.6 2.3 33 24 1-2-3 A

II 470 3.0 13.2 3.1 3.1 42 33

III 620 3.5 17.7 3.6 4.0 53 44


3
I 350 2.4 9.1 2.6 2.3 33 24

II 620 3.5 17.7 3.6 4.0 53 44

III 840 4.1 24.0 4.2 5.4 59 50

I 360 2.5 5.1 2.9 3.3 33 24

II 610 3.6 9.9 4.0 5.7 52 43


Sheet-steel electric control box
III 1030 4.9 17.1 5.3 9.5 63 54 with terminal strip or
4 for integrated control
I 700 3.9 11.5 4.3 6.6 53 44

II 800 4.3 13.4 4.7 7.5 56 47

III 1260 5.4 20.4 6.0 11.6 67 58

I 710 4.7 19.8 5.1 11.5 52 43

II 920 5.6 26.3 5.9 14.9 58 49 5


III 1350 6.9 39.0 7.3 21.6 68 59

1 2 Speed combination

Capacity stage 1-2-3 K

Left 1
connection **

Wall
Right 2
Coil

Left 3
Ceiling
Right 4

* See Acoustics on page 28 for ambient conditions


** Connection side from the front, with view to the discharge
Order code G B . U W W .

6 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko Accessories / valve equipment
Recirculation air unit / cooling and heating
4-pipe chilled and warm water, sizes 1 to 5

Accessories

Unit casing 0 2 Spare filter 0 6

Wall/ceiling mounting

Casing spacer and air intake grille


made of plastic 0 5 Flexible discharge connection 0 1
unit casing required
Wall/ceiling mounting

Casing spacer and air intake grille


Discharge plenum for primary air
made of sheet steel 0 7 0 8
spigot
unit casing required
Wall/ceiling mounting

Spacer
0 3
(independent of size) *
Wall/ceiling mounting

Sizes 1 to 5
* 0, if independent
of size Order code Z G B

Valve equipment
Heating circuit
MATRIX 3000/4000
MATRIX 2000

Terminal box

Cooling circuit kvs values

Actuator Operating voltage/circuit Cooling/heating

On/off
230 V AC T 2.50 2 5
Open/closed
2 3
Modulating
230 V AC R
Open/stop/closed 0.63 0 6
1.00 1 0
1.60 1 6
2.50 2 5

kvs values as above for


on/off actuators (T)
only kvs 2.5 possible

Cooling Heating
Coil connection left L
Coil connection right R

Order code V . B

VK_2052751GB Subject to technical modifications Status 09/2005 7


Control equipment GEA Basic Geko
Recirculation air unit / cooling and heating
4-pipe chilled and warm water, sizes 1 to 5

GEA MATRIX 2000


System features: MATRIX OP21C
Operator panel for MATRIX 2000 control system
Specification of temp. 7 ... 40 C
Housing in pure white, enclosure IP20
(default 10 ... 30 C)
Set-point temperature setting
Specification of the speed
Speed selector switch 0 - Auto - 1-2-3 A
Restrictable adjusting range
Energy saving mode pushbutton
Switch from normal / energy saving mode on the
LEDs for operation / malfunction / external
operator panel
influence
Recording of room temperature via operator panel
Integrated room sensor
External room sensors can be connected
Valve control (2xon/off)
Temperature regulation via fan and/or valve(s)
Room frost protection function
Status messages via LED
Group control
Group shutdown in the event of a malfunction
Network-compatible

GEA MATRIX 3000


MATRIX 3000 system features MATRIX OP30C
Operator panel for MATRIX 3000 control system
Specification of temp. 7 ... 40 C Housing in pure white, enclosure IP20
(default 10 ... 30 C) Set-point temperature setting
Specification of the speed B
Speed selector switch 0 - Auto - 1-2-3
Restrictable adjusting range LEDs for operation / malfunction / external
Switch from normal / energy saving mode on the influence
operator panel
Integrated room sensor
Input for switching from normal / energy saving
mode or AUS unit with frost protection MATRIX OP31C
Recording of room temperature via operator panel Like operator panel OP30C, but including:
External room sensors can be connected Normal / energy saving mode pushbuttons
Valve control (2 x on/off or 2 x modulating)
Temperature regulation via fan and/or valve(s) C
Room frost protection function
Status messages via LED
Operating and error messages via potential-free
change-over contacts
Individual-unit or group control MATRIX OP44C
Shutdown of the individual units in the event of a Like operator panel OP31C, but including
malfunction pushbuttons for:
Network-compatible Switch heating / cooling / automatic mode
D

MATRIX OP50C
Operator panel for MATRIX 3000 control system
Housing in pure white, enclosure IP20
Menu-controlled operation via rotary navigator
LCD display with plain text display 100
R E 14:08

C E
Status messages via pictograms 21 .5
Integrated room sensor
MATRIX OP51C
Like operator panel OP50C, but including: F
Integrated week timer with program for holiday
and exceptional daily program

MATRIX.IR
Remote control for unit for MATRIX 3000
control system
Housing in black, similar to RAL 9004 %

N
on off

LCD display approx. 45x30 mm func

send
- +

Functions like OP44C (without operating,


malfunction and external influence message, no
integrated room temperature sensor)
Transmission range max. 20 m

8 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko

Master Slave units


unit 1-15

4x2x0.8 J-Y(ST)Y 4x2x0.8 J-Y(ST)Y

3x1.5 mm2 NYM 3x1.5 mm2 NYM Cooling / heating medium

230 V ~
50 Hz
Without return air sensor * 0
With return air sensor * 5

Order code D 2 . 2 1 . A A D 2 . 2 0 1 . Z D

Master Slave units


unit 1-15
e.g. 2x2x0.75 Unitronic Bus CAN e.g. 1x2x0.75 Unitronic Bus CAN

3x1.5 mm2 NYM 3x1.5 mm2 NYM Cooling / heating medium

230 V ~
50 Hz
Individual unit control

Input for unit switch

Input energy-saving
Group control with
with operating and

off with room frost


error messages

error messages
operating and

protection
Speeds

contact

1 2 0 1
Up 2 2 0 1
to 3-
speed 1 3 1
2 3 2

Without return air sensor * 0


With return air sensor * 5

Operator panel

Order code D 3 . 2 . A D . 2 . Z D

* Alternative room sensor (see page 45)

VK_2052751GB Subject to technical modifications Status 09/2005 9


Recirculation air unit / cooling and heating GEA Basic Geko
Chilled water 6/12 C Electrical heater
2-pipe chilled water and electrical heating tL1 = +27 C 230 V~N/P/E
Sizes 1 to 5 1 = 46 % RH 50 Hz

Capacity stage 1 Capacity stage 2

Sound pressure *
Electrical heating

Electrical heating
Cooling capacity

Cooling capacity
Air volume flow

Pressure drop

Pressure drop

Pressure drop

Pressure drop

Sound power
Speeds

Size

QK pK QH pH QK pK QH pH
m3/h kW kPa kW kPa kW kPa kW kPa dB(A) dB(A)

I 130 0.8 3.4 0.8 1.0 8.7 0.8 22 13


Plastic terminal box
II 200 1.0 5.6 0.8 1.4 14.8 0.8 36 27 1 (select sheet-steel electric
control box for GEA MATRIX)
III 280 1.2 7.8 0.8 1.7 22.1 0.8 45 36

I 165 1.4 19.2 1.1 31 22

II 240 1.8 31.3 1.1 41 32

III 340 2.3 46.6 1.1 48 39


2
I 240 1.6 3.7 1.1 41 32

II 350 2.1 6.0 1.1 50 41

III 540 2.7 9.4 1.1 61 52 Speed combination

I 350 2.4 9.1 2.0 33 24 1-2-3 A

II 470 3.0 13.2 2.0 41 33

III 620 3.5 17.7 2.0 53 44


3
I 350 2.4 9.1 2.0 33 24

II 620 3.5 17.7 2.0 53 44

III 840 4.1 24.0 2.0 59 50

I 360 2.5 5.1 3.0 33 24

II 610 3.6 9.9 3.0 52 43


Sheet-steel electric control box
III 1030 4.9 17.1 3.0 63 54 with terminal strip or
4 for integrated control
I 700 3.9 11.5 3.0 53 44

II 800 4.3 13.4 3.0 56 47

III 1260 5.4 20.4 3.0 67 58

I 710 4.7 19.8 4.0 5.4 14.9 4.0 52 43

II 920 5.6 26.3 4.0 6.4 20.3 4.0 58 49 5


III 1350 6.9 39.0 4.0 8.3 32.5 4.0 68 59

1 2 Speed combination

Capacity stage 1-2-3 K

Left 1
connection **

Wall
Right 2
Coil

Left 3
Ceiling
Right 4

* See Acoustics on page 28 for ambient conditions


** Connection side from the front, with view to the discharge
Order code G B . U W E .

10 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko Accessories / valve equipment
Recirculation air unit / cooling and heating
2-pipe chilled water and electrical heating, sizes 1 to 5

Accessories

Unit casing 0 2 Spare filter 0 6

Wall/ceiling mounting

Casing spacer and air intake grille


made of plastic 0 5 Flexible discharge connection 0 1
unit casing required
Wall/ceiling mounting

Casing spacer and air intake grille


Discharge plenum for primary air
made of sheet steel 0 7 0 8
spigot
unit casing required
Wall/ceiling mounting

Spacer
0 3
(independent of size) *
Wall/ceiling mounting

Sizes 1 to 5
* 0, if independent
of size Order code Z G B

Valve equipment
MATRIX 3000/4000
MATRIX 2000

Terminal box

Cooling circuit kvs values

Actuator Operating voltage/circuit Cooling

On/off
230 V AC T 2.50 2 5
Open/closed
2 3
Modulating
230 V AC R
Open/stop/closed 0.63 0 6
1.00 1 0
1.60 1 6
2.50 2 5

kvs values as above for


on/off actuators (T)
only kvs 2.5 possible

Cooling
Coil connection left L
Coil connection right R

Order code V . B

VK_2052751GB Subject to technical modifications Status 09/2005 11


Control equipment GEA Basic Geko
Recirculation air unit / cooling and heating
2-pipe chilled water and electrical heating, sizes 1 to 5

GEA MATRIX 2000


System features: MATRIX OP21C
Operator panel for MATRIX 2000 control system
Specification of temp. 7 ... 40 C
Housing in pure white, enclosure IP20
(default 10 ... 30 C)
Set-point temperature setting
Specification of the speed
Speed selector switch 0 - Auto - 1-2-3 A
Restrictable adjusting range
Energy saving mode pushbutton
Switch from normal / energy saving mode on the
LEDs for operation / malfunction / external
operator panel
influence
Recording of room temperature via operator panel
Integrated room temperature sensor
External room temperature sensors can be
connected
Valve control (on/off)
Temperature regulation via fan and/or valve(s)
Room frost protection function
Status messages via LED
Group control
Group switch-off in the event of a malfunction
Network-compatible

GEA MATRIX 3000


MATRIX 3000 system features MATRIX OP30C
Operator panel for MATRIX 3000 control system
Specification of temp. 7 ... 40 C Housing in pure white, enclosure IP20
(default 10 ... 30 C) Set-point temperature setting
Specification of the speed B
Speed selector switch 0 - Auto - 1-2-3
Restrictable adjusting range LEDs for operation / malfunction / external
Switch from normal / energy saving mode on the influence
operator panel
Integrated room temperature sensor
Input for switching from normal / energy saving
mode or AUS unit with frost protection MATRIX OP31C
Recording of room temperature via operator panel Like operator panel OP30C, but including:
External room temperature sensors can be Normal / energy saving mode pushbuttons
connected
Valve control (on/off or modulating) C
Temperature regulation via fan and/or valve(s)
Room frost protection function
Status messages via LED
Operating and error messages via potential-free
change-over contacts MATRIX OP44C
Individual-unit or group control Like operator panel OP31C, but including
Switch-off of the individual units in the event of a pushbuttons for:
malfunction Switch heating / cooling / automatic mode
D
Network-compatible

MATRIX OP50C
Operator panel for MATRIX 3000 control system
Housing in pure white, enclosure IP20
Menu-controlled operation via rotary navigator
LCD display with plain text display 100
R E 14:08

C E
Status messages via pictograms 21 .5
Integrated room temperature sensor
MATRIX OP51C
Like operator panel OP50C, but including: F
Integrated week timer with program for holiday
and exceptional daily program

MATRIX.IR
Remote control for unit for MATRIX 3000
control system
Housing in black, similar to RAL 9004 %

N
on off

LCD display approx. 45x30 mm func

send
- +

Functions like OP44C (without operating,


malfunction and external influence message, no
integrated room temperature sensor)
Transmission range max. 20 m

12 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko

230 V ~ 230 V ~
50 Hz 50 Hz
Master Slave units
unit 1-15

4x2x0.8 J-Y(ST)Y 4x2x0.8 J-Y(ST)Y

3x1.5 mm2 NYM 3x2.5 mm2 NYM 3x1.5 mm2 NYM Cooling medium

230 V ~ 230 V ~ 3x2.5 mm2 NYM


50 Hz 50 Hz
Without return air sensor * 2 230 V ~
With return air sensor * 7 50 Hz

Order code D 2 . 2 1 . A A D 2 . 2 2 1 . Z D

230 V ~ 230 V ~
50 Hz 50 Hz
Master Slave units
unit 1-15
e.g. 2x2x0.75 Unitronic Bus CAN e.g. 1x2x0.75 Unitronic Bus CAN

3x1.5 mm2 NYM 3x2.5 mm2 NYM 3x1.5 mm2 NYM Cooling medium

230 V ~ 230 V ~ 3x2.5 mm2 NYM


50 Hz 50 Hz

230 V ~
Individual unit control

50 Hz
Input for unit switch

Input energy saving


Group control with
with operating and

off with room frost


error messages

error messages
operating and

protection
Speeds

contact

1 2 2 1
Up 2 2 2 1
to 3-
speed 1 3 1
2 3 2

Without return air sensor * 2


With return air sensor * 7

Operator panel

Order code D 3 . 2 . A D . 2 . Z D

* Alternative room temperature sensor (see page 45)

VK_2052751GB Subject to technical modifications Status 09/2005 13


Recirculation air unit / cooling or heating GEA Basic Geko
Chilled water 6/12 C Warm water 70/
2-pipe chilled or warm water tL1 = +27 C 50 C
Sizes 1 to 5 1 = 46 % r.h. tL1 = +20 C

Capacity stage 1 Capacity stage 2

Sound pressure *
Cooling capacity

Cooling capacity
Heating capacity

Heating capacity
Air volume flow

Pressure drop

Pressure drop

Pressure drop

Pressure drop

Sound power
Speeds

Size

QK pK QH pH QK pK QH pH
3
m /h kW kPa kW kPa kW kPa kW kPa dB(A) dB(A)

I 130 0.8 3.4 1.4 1.0 1.0 8.7 1.8 2.2 22 13


Plastic terminal box
II 200 1.0 5.6 1.9 1.7 1.4 14.8 2.5 3.9 36 27 1 (select sheet-steel electric
control box for GEA MATRIX)
III 280 1.2 7.8 2.4 2.6 1.7 22.1 3.1 5.9 45 36

I 165 1.4 19.2 2.3 4.6 31 22

II 240 1.8 31.3 3.1 7.7 41 32

III 340 2.3 46.6 4.1 12.3 48 39


2
I 240 1.6 3.7 3.0 1.0 41 32

II 350 2.1 6.0 3.9 1.7 50 41

III 540 2.7 9.4 5.3 2.9 61 52 Speed combination

I 350 2.4 9.1 4.3 2.5 33 24 1-2-3 A

II 470 3.0 13.2 5.3 3.6 41 33

III 620 3.5 17.7 6.5 5.1 53 44


3
I 350 2.4 9.1 4.3 2.5 33 24

II 620 3.5 17.7 6.5 5.1 53 44

III 840 4.1 24.0 8.0 7.4 59 50

I 360 2.5 5.1 4.6 1.4 33 24

II 610 3.6 9.9 6.7 2.8 52 43


Sheet-steel electric control box
III 1030 4.9 17.1 9.6 5.3 63 54 with terminal strip or
4 for integrated control
I 700 3.9 11.5 7.4 3.3 53 44

II 800 4.3 13.4 8.0 3.9 56 47

III 1260 5.4 20.4 10.8 6.7 67 58

I 710 4.7 19.8 8.4 5.2 5.4 14.9 9.4 3.8 52 43

II 920 5.6 26.3 10.1 7.2 6.4 20.3 11.6 5.7 58 49 5


III 1350 6.9 39.0 13.1 11.4 8.3 32.5 15.1 9.2 68 59

1 2 Speed combination

Capacity stage 1-2-3 K

Left 1
connection **

Wall
Right 2
Coil

Left 3
Ceiling
Right 4

* See Acoustics on page 28 for ambient conditions


** Connection side from the front, with view to the discharge
Order code G B . U W C .

14 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko Accessories / valve equipment
Recirculation air unit / cooling or heating
2-pipe chilled or warm water, sizes 1 to 5

Accessories

Unit casing 0 2 Spare filter 0 6

Wall/ceiling mounting

Casing spacer and air intake grille


made of plastic 0 5 Flexible discharge connection 0 1
unit casing required
Wall/ceiling mounting

Casing spacer and air intake grille


Discharge plenum for primary air
made of sheet steel 0 7 0 8
spigot
unit casing required
Wall/ceiling mounting

Spacer
0 3
(independent of size) *
Wall/ceiling mounting

Sizes 1 to 5
* 0, if independent
of size Order code Z G B

Valve equipment
MATRIX 3000/4000
MATRIX 2000

Terminal box

Heating circuit/cooling circuit kvs values

Actuator Operating voltage/circuit Cooling/heating

On/off
230 V AC T 2.50 2 5
Open/closed
Modulating
230 V AC R
Open/stop/closed 0.63 0 6
1.00 1 0
1.60 1 6
2.50 2 5

kvs values as above for


on/off actuators (T)
only kvs 2.5 possible

Coil connection left L


Coil connection right R

Order code V 3 . B

VK_2052751GB Subject to technical modifications Status 09/2005 15


Control equipment GEA Basic Geko
Recirculation air unit / cooling or heating
2-pipe chilled or warm water, sizes 1 to 5

GEA MATRIX 2000


System features: MATRIX OP21C
Operator panel for MATRIX 2000 control system
Specification of temp. 7 ... 40 C
Housing in pure white, enclosure IP20
(default 10 ... 30 C)
Set-point temperature setting
Specification of the speed
Speed selector switch 0 - Auto - 1-2-3 A
Restrictable adjusting range
Energy saving mode pushbutton
Switch from normal / energy saving mode on the
LEDs for operation / malfunction / external
operator panel
influence
Recording of room temperature via operator panel
Integrated room temperature sensor
Valve control (on/off or modulating)
Temperature regulation via fan and/or valve(s)
Room frost protection function
Status messages via LED
Group control
Group shutdown in the event of a malfunction
Network-compatible

GEA MATRIX 3000


MATRIX 3000 system features MATRIX OP30C
Operator panel for MATRIX 3000 control system
Specification of temp. 7 ... 40 C Housing in pure white, enclosure IP20
(default 10 ... 30 C) Set-point temperature setting
Specification of the speed B
Speed selector switch 0 - Auto - 1-2-3
Restrictable adjusting range LEDs for operation / malfunction / external
Switch from normal / energy saving mode on the influence
operator panel Integrated room temperature sensor
Input for switching from normal / energy saving
mode or AUS unit with frost protection MATRIX OP31C
Recording of room temperature via operator panel Like operator panel OP30C, but including:
External room temperature sensors can be Normal / energy saving mode pushbuttons
connected
Valve control (on/off or modulating) C
Temperature regulation via fan and/or valve
Room frost protection function
Status messages via LED
Operating and error messages via potential-free
change-over contacts MATRIX OP44C
Individual-unit or group control Like operator panel OP31C, but including
Shutdown of the individual units in the event of a pushbuttons for:
malfunction Switch heating / cooling / automatic mode
D
Network-compatible

MATRIX OP50C
Operator panel for MATRIX 3000 control system
Housing in pure white, enclosure IP20
Menu-controlled operation via rotary navigator
LCD display with plain text display 100
R E 14:08

C E
Status messages via pictograms 21 .5
Integrated room temperature sensor
MATRIX OP51C
Like operator panel OP50C, but including: F
Integrated week timer with program for holiday
and exceptional daily program

MATRIX.IR
Remote control for unit for MATRIX 3000
control system
Housing in black, similar to RAL 9004 %

N
off

LCD display approx. 45x30 mm


on

func - +

send

Functions like OP44C (without operating,


malfunction and external influence message, no
integrated room temperature sensor)
Transmission range max. 20 m

16 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko

Master Slave units


unit 1-15

4x2x0.8 J-Y(ST)Y 4x2x0.8 J-Y(ST)Y

3x1.5 mm2 NYM 3x1.5 mm2 NYM Cooling / heating medium

4x2x0.8 J-Y(ST)Y Flow sensor


230 V ~
50 Hz

Order code D 2 . 1 0 1 . A A D 2 . 1 0 1 . Z D

Master Slave units


unit 1-15
e.g. 2x2x0.75 Unitronic Bus CAN e.g. 1x2x0.75 Unitronic Bus CAN

3x1.5 mm2 NYM 3x1.5 mm2 NYM Cooling / heating medium

4x2x0.8 J-Y(ST)Y Flow sensor


230 V ~
50 Hz
Individual unit control

Input for unit switch

Input energy saving


Group control with
with operating and

off with room frost


error messages

error message
operating and

protection
Speeds

contact

1 2 0 1
Up 2 2 0 1
to 3-
speed 1 3 1
2 3 2

Without return air sensor * 0


With return air sensor * 5

Operator panel

Order code D 3 . 1 . A D . 1 . Z D

* Alternative room temperature sensor (see page 45)

VK_2052751GB Subject to technical modifications Status 09/2005 17


Recirculation air unit / heating GEA Basic Geko
Warm water 70/50 C
2-pipe warm water tL1 = +20 C
Sizes 1 to 5

Capacity stage 1 Capacity stage 2

Sound pressure *
Cooling capacity

Cooling capacity
Heating capacity

Heating capacity
Air volume flow

Pressure drop

Pressure drop

Pressure drop

Pressure drop

Sound power
Speeds

Size

QK pK QH pH QK pK QH pH
3
m /h kW kPa kW kPa kW kPa kW kPa dB(A) dB(A)

I 130 1.4 1.0 1.8 2.2 22 13


Plastic terminal box
II 200 1.9 1.7 2.5 3.9 36 27 1 (select sheet-steel electric
control box for GEA MATRIX)
III 280 2.4 2.6 3.1 5.9 45 36

I 165 2.3 4.6 31 22

II 240 3.1 7.7 41 32

III 340 4.1 12.3 48 39


2
I 240 3.0 1.0 41 32

II 350 3.9 1.7 50 41

III 540 5.3 2.9 61 52 Speed combination

I 350 4.3 2.5 33 24 1-2-3 A

II 470 5.3 3.6 41 33

III 620 6.5 5.1 53 44


3
I 350 4.3 2.5 33 24

II 620 6.5 5.1 53 44

III 840 8.0 7.4 59 50

I 360 4.6 1.4 33 24

II 610 6.7 2.8 52 43


Sheet-steel electric control box
III 1030 9.6 5.3 63 54 with terminal strip or
4 for integrated control
I 700 7.4 3.3 53 44

II 800 8.0 3.9 56 47

III 1260 10.8 6.7 67 58

I 710 8.4 5.2 9.4 3.8 52 43

II 920 10.1 7.2 11.6 5.7 58 49 5


III 1350 13.1 11.4 15.1 9.2 68 59

1 2 Speed combination

Capacity stage 1-2-3 K

Left 1
connection **

Wall
Right 2
Coil

Left 3
Ceiling
Right 4

* See Acoustics on page 28 for ambient conditions


** Connection side from the front, with view to the discharge
Order code G B . U 0 W .

18 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko Accessories / valve equipment
Recirculation air unit / heating
2-pipe warm water, sizes 1 to 5

Accessories

Unit casing 0 2 Spare filter 0 6

Wall/ceiling mounting

Casing spacer and air intake grille


made of plastic 0 5 Flexible discharge connection 0 1
unit casing required
Wall/ceiling mounting

Casing spacer and air intake grille


Discharge plenum for primary air
made of sheet steel 0 7 0 8
spigot
unit casing required
Wall/ceiling mounting

Spacer
0 3
(independent of size) *
Wall/ceiling mounting

Sizes 1 to 5
* 0, if independent
of size Order code Z G B

Valve equipment
MATRIX 3000/4000
MATRIX 2000

Terminal box

Heating circuit kvs values

Actuator Operating voltage/circuit Cooling/heating

On/off
230 V AC T 2.50 2 5
Open/closed
2 3
Modulating
230 V AC R
Open/stop/closed 0.63 0 6
1.00 1 0
1.60 1 6
2.50 2 5

kvs values as above for


on/off actuators (T)
only kvs 2.5 possible

Heating
Coil connection left L
Coil connection right R

Order code V . B

VK_2052751GB Subject to technical modifications Status 09/2005 19


Control equipment GEA Basic Geko
Recirculation air unit / heating
2-pipe warm water, sizes 1 to 5

GEA MATRIX 2000


System features: MATRIX OP21C
Operator panel for MATRIX 2000 control system
Specification of temp. 7 ... 40 C
Housing in pure white, enclosure IP20
(default 10 ... 30 C)
Set-point temperature setting
Specification of the speed
Speed selector switch 0 - Auto - 1-2-3 A
Restrictable adjusting range
Energy saving mode pushbutton
Switch from normal / energy saving mode on the
LEDs for operation / malfunction / external
operator panel
influence
Recording of room temperature via operator panel
Integrated room temperature sensor
External room temperature sensors can be
connected
Valve control (on/off or modulating)
Temperature regulation via fan and/or valve
Room frost protection function
Status messages via LED
Group control
Group shutdown in the event of a malfunction
Network-compatible

GEA MATRIX 3000


MATRIX 3000 system features MATRIX OP30C
Operator panel for MATRIX 3000 control system
Specification of temp. 7 ... 40 C
Housing in pure white, enclosure IP20
(default 10 ... 30 C)
Set-point temperature setting
Specification of the speed B
Speed selector switch 0 - Auto - 1-2-3
Restrictable adjusting range
LEDs for operation / malfunction / external
Switch from normal / energy saving mode on the
influence
operator panel
Integrated room temperature sensor
Input for switching from normal / energy saving
mode or AUS unit with frost protection MATRIX OP31C
Recording of room temperature via operator panel Like operator panel OP30C, but including:
External room temperature sensors can be Normal / energy saving mode pushbuttons
connected
Valve control (on/off or modulating) C
Temperature regulation via fan and/or valve
Room frost protection function
Status messages via LED
Operating and error messages via potential-free
change-over contacts MATRIX OP50C
Individual-unit or group control Operator panel for MATRIX 3000 control system
Shutdown of the individual units in the event of a Housing in pure white, enclosure IP20
malfunction Menu-controlled operation via rotary navigator
Network-compatible LCD display with plain text display 100
R E 14:08

C E
Status messages via pictograms 21 .5
Integrated room temperature sensor
MATRIX OP51C
Like operator panel OP50C, but including: F
Integrated week timer with program for holiday
and exceptional daily program

MATRIX.IR
Remote control for unit for MATRIX 3000
control system
Housing in black, similar to RAL 9004 %

N
on off

LCD display approx. 45x30 mm func

send
- +

Functions like OP44C (without operating,


malfunction and external influence message, no
integrated room temperature sensor)
Transmission range max. 20 m

20 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko

Master Slave units


unit 1-15

4x2x0.8 J-Y(ST)Y 4x2x0.8 J-Y(ST)Y

3x1.5 mm2 NYM 3x1.5 mm2 NYM Heating medium

230 V ~
50 Hz
Without return air sensor * 0
With return air sensor * 5

Order code D 2 . 0 1 . A A D 2 . 0 0 1 . Z D

Master Slave units


unit 1-15
e.g. 2x2x0.75 Unitronic Bus CAN e.g. 1x2x0.75 Unitronic Bus CAN

3x1.5 mm2 NYM 3x1.5 mm2 NYM Heating medium

230 V ~
50 Hz
Individual unit control

Input for unit switch

Input energy saving


Group control with
with operating and

off with room frost


error messages

error message
operating and

protection
Speeds

contact

1 2 0 1
up to 2 2 0 1
3-stage 1 3 1
2 3 2

Without return air sensor * 0


With return air sensor * 5

Operator panel

Order code D 3 . 0 . A D . 0 . Z D

* Alternative room temperature sensor (see page 45)

VK_2052751GB Subject to technical modifications Status 09/2005 21


Recirculation air unit / cooling GEA Basic Geko
Chilled water 6/12 C
2-pipe chilled water tL1 = +27 C
Sizes 1 to 5 1 = 46 % RH

Capacity stage 1 Capacity stage 2

Sound pressure *
Cooling capacity

Cooling capacity
Heating capacity

Heating capacity
Air volume flow

Pressure drop

Pressure drop

Pressure drop

Pressure drop

Sound power
Speeds

Size

QK pK QH pH QK pK QH pH
3
m /h kW kPa kW kPa kW kPa kW kPa dB(A) dB(A)

I 130 0.8 3.4 1.0 8.7 22 13


Plastic terminal box
II 200 1.0 5.6 1.4 14.8 36 27 1 (select sheet-steel electric
control box for GEA MATRIX)
III 280 1.2 7.8 1.7 22.1 45 36

I 165 1.4 19.2 31 22

II 240 1.8 31.3 41 32

III 340 2.3 46.6 48 39


2
I 240 1.6 3.7 41 32

II 350 2.1 6.0 50 41

III 540 2.7 9.4 61 52 Speed combination

I 350 2.4 9.1 33 24 1-2-3 A

II 470 3.0 13.2 41 33

III 620 3.5 17.7 53 44


3
I 350 2.4 9.1 33 24

II 620 3.5 17.7 53 44

III 840 4.1 24.0 59 50

I 360 2.5 5.1 33 24

II 610 3.6 9.9 52 43


Sheet-steel electric control box
III 1030 4.9 17.1 63 54 with terminal strip or
4 for integrated control
I 700 3.9 11.5 53 44

II 800 4.3 13.4 56 47

III 1260 5.4 20.4 67 58

I 710 4.7 19.8 5.4 14.9 52 43

II 920 5.6 26.3 6.4 20.3 58 49 5


III 1350 6.9 39.0 8.3 32.5 68 59

1 2 Speed combination

Capacity stage 1-2-3 K

Left 1
connection **

Wall
Right 2
Coil

Left 3
Ceiling
Right 4

* See Acoustics on page 28 for ambient conditions


** Connection side from the front, with view to the discharge
Order code G B . U W 0 .

22 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko Accessories / valve equipment
Recirculation air unit / cooling
2-pipe chilled water, sizes 1 o 5

Accessories

Unit casing 0 2 Spare filter 0 6

Wall/ceiling mounting

Casing spacer and air intake grille


made of plastic 0 5 Flexible discharge connection 0 1
unit casing required
Wall/ceiling mounting

Casing spacer and air intake grille


Discharge plenum for primary air
made of sheet steel 0 7 0 8
spigot
unit casing required
Wall/ceiling mounting

Spacer
0 3
(independent of size) *
Wall/ceiling mounting

Sizes 1 to 5
* 0, if independent
of size Order code Z G B

Valve equipment
MATRIX 3000/4000
MATRIX 2000

Terminal box

Cooling circuit kvs values

Actuator Operating voltage/circuit Cooling

On/off
230 V AC T 2.50 2 5
Open/closed
2 3
Modulating
230 V AC R
Open/stop/closed 0.63 0 6
1.00 1 0
1.60 1 6
2.50 2 5

kvs values as above for


on/off actuators (T)
only kvs 2.5 possible

Cooling
Coil connection left L
Coil connection right R

Order code V . B

VK_2052751GB Subject to technical modifications Status 09/2005 23


Control equipment GEA Basic Geko
Recirculation air unit / cooling
2-pipe chilled water, sizes 1 to 5

GEA MATRIX 2000


System features: MATRIX OP21C
Operator panel for MATRIX 2000 control system
Specification of temp. 7 ... 40 C
Housing in pure white, enclosure IP20
(default 10 ... 30 C)
Set-point temperature setting
Specification of the speed
Speed selector switch 0 - Auto - 1-2-3 A
Restrictable adjusting range
Energy saving mode pushbutton
Switch from normal / energy saving mode on the
LEDs for operation / malfunction / external
operator panel
influence
Recording of room temperature via operator panel
Integrated room temperature sensor
External room temperature sensors can be
connected
Valve control (on/off or modulating)
Temperature regulation via fan and/or valve
Status messages via LED
Group control
Group shutdown in the event of a malfunction
Network-compatible

GEA MATRIX 3000


MATRIX 3000 system features MATRIX OP30C
Operator panel for MATRIX 3000 control system
Specification of temp. 7 ... 40 C
Housing in pure white, enclosure IP20
(default 10 ... 30 C)
Set-point temperature setting
Specification of the speed B
Speed selector switch 0 - Auto - 1-2-3
Restrictable adjusting range
LEDs for operation / malfunction / external
Switch from normal / energy saving mode on the
influence
operator panel
Integrated room temperature sensor
Input for switching from normal / energy saving
mode or AUS unit with frost protection MATRIX OP31C
Recording of room temperature via operator panel Like operator panel OP30C, but including:
External room temperature sensors can be Normal / energy saving mode pushbuttons
connected
Valve control (on/off or modulating) C
Temperature regulation via fan and/or valve
Status messages via LED
Operating and error messages via potential-free
change-over contacts
Individual-unit or group control MATRIX OP50C
Shutdown of the individual units in the event of a Operator panel for MATRIX 3000 control system
malfunction Housing in pure white, enclosure IP20
Network-compatible Menu-controlled operation via rotary navigator
LCD display with plain text display 100
R E 14:08

C E
Status messages via pictograms 21 .5
Integrated room temperature sensor
MATRIX OP51C
Like operator panel OP50C, but including: F
Integrated week timer with program for holiday
and exceptional daily program

MATRIX.IR
Remote control for unit for MATRIX 3000
control system
Housing in black, similar to RAL 9004 %

N
on off

LCD display approx. 45x30 mm func

send
- +

Functions like OP44C (without operating,


malfunction and external influence message, no
integrated room temperature sensor)
Transmission range max. 20 m

24 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko

Master Slave units


unit 1-15

4x2x0.8 J-Y(ST)Y 4x2x0.8 J-Y(ST)Y

3x1.5 mm2 NYM 3x1.5 mm2 NYM Cooling medium

230 V ~
50 Hz
Without return air sensor * 0
With return air sensor * 5

Order code D 2 . 0 1 . A A D 2 . 0 0 1 . Z D

Master Slave units


unit 1-15
e.g. 2x2x0.75 Unitronic Bus CAN e.g. 1x2x0.75 Unitronic Bus CAN

3x1.5 mm2 NYM 3x1.5 mm2 NYM Cooling medium

230 V ~
50 Hz
Individual unit control

Input for unit switch

Input energy saving


Group control with
with operating and

off with room frost


error messages

error message
operating and

protection
Speeds

contact

1 2 0 1
Up 2 2 0 1
to 3-
speed 1 3 1
2 3 2

Without return air sensor * 0


With return air sensor * 5

Operator panel

Activation of an external heating valve upon request

Order code D 3 . 0 . A D . 0 . Z D
* Alternative room temperature sensor (see page 45)

VK_2052751GB Subject to technical modifications Status 09/2005 25


Coil pressure drop GEA Basic Geko

for warm and chilled water


Cooling, 2-pipe system Cooling, 4-pipe system
30 30
3,1/2 3,1/2
25 Size,LG* 25 Size,LG*

20 20
2,2 2,2
15 15

2,1 2,1
10 10

Pressure drop [kPa]


Pressure drop [kPa]

9,0 9,0
8,0 8,0
7,0 1,2 5,1 7,0 1,2 5,1
6,0 6,0
5,0 5,0
4,5 1,1 4,5 1,1
4,0 4,0
3,5 3,5
3,0 4,1/2 3,0 4,1/2

2,5 2,5

2,0 2,0

1,5 5,2 1,5

1,0 1,0
0,9 0,9
0,8 0,8
0,7 0,7
0,6 Fig. 26-1 0,6 Fig. 26-2
0,5 0,5
50
60
70
80
90
100

150

200
250
300
350
400
450
500
600
700
800
900

50
60
70
80
90
100

150

200
250
300
350
400
450
500
600
700
800
900
1000

1000

Water flow rate Vw [l/h] Water flow rate Vw [l/h]

Heating, 2-pipe system Heating, 4-pipe system


30 30
3,1/2
25 Size,LG* 25 Size,LG*

20 20
2,2
15 15 5,1
3,1/2
2,1
10 10
Pressure drop [kPa]

Pressure drop [kPa]

9,0 9,0
8,0 8,0
7,0 1,2 5,1 7,0
6,0 6,0
4,1/2
5,0 5,0
4,5 1,1 4,5 2,1/2
4,0 4,0
3,5 3,5
3,0 4,1/2 3,0
2,5 2,5

2,0 2,0

1,5 5,2 1,5 1,1/2

1,0 1,0
0,9 0,9
0,8 0,8
0,7 0,7
0,6 Fig. 26-3 0,6 Fig. 26-4
0,5 0,5
50
60
70
80
90
100

150

200
250
300
350
400
450
500
600
700
800
900

50
60
70
80
90
100

150

200
250
300
350
400
450
500
600
700
800
900
1000

1000


Water flow rate Vw [l/h] Water flow rate Vw [l/h]

* LG = capacity stage

26 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko Example on determining the capacity

The heating capacities for warm water 70/50 C and the air intake temperature tL1= +20 C as well as the cooling capacities for chilled water
6/12 C and air intake condition tL1=+27 C/46 % r.h. are specified in the tables on pages 6 through 61.
The capacities for other states can be determined using the correction factors on foldout page 1.2.
Sample calculation for a Basic Geko for Selected unit type: GB21.UWC#.###
cooling or heating in a 2-pipe system for a heating See page 14
capacity of min. 4.5 kW for warm water 70/50/+15 C
Example speed 3 = 340 m3/h
and cooling with chilled water 8/12 (24/50) C.

Heating capacity at LPHW 70/50 C and tL1 = + 15 C



QH (70/50/+15)
fH (70/50/+15)
=
=
new heating capacity
1.13 (see page 1.2)
QH (70/50/+15) = fH (70/50/+15) QH (70/50/+20)

QH (70/50/+20) = 4.1 (see page 14) QH (70/50/+15) = 1.13 4.1 kW = 4.6 kW
Cooling capacity for chilled water 8/12 C and tL1= +24 C/50 %
r.h.

QK (8/12/+24/50%)
fK (8/12/+24/50%)
=
=
new cooling capacity
0.73 (see page 1.2)
QK (8/12/+24/50%) = fK (8/12/+24/50%) QK (6/12/+27/46%)

QK (6/12/+27/46%) = 2.3 (see page 14) QK (8/12/+24/50%) = 0.73 2.3 kW = 1.7 kW

Power and current consumption

Air volume flow Capacity stage 1 Capacity stage 2


Size Speed
[m3/h] Power [W] Current [A] Power [W] Current [A]

1 130 27 0.13 27 0.13

1 2 200 32 0.15 32 0.15

3 280 39 0.18 39 0.18

1 165 30 0.14

2 240 35 0.16

3 340 43 0.19
2
1 240 49 0.23

2 350 62 0.28

3 540 86 0.38

1 350 70 0.33

2 470 81 0.37

3 620 97 0.44
3
1 350 70 0.33

2 620 97 0.44

3 840 118 0.52

1 360 70 0.33

2 610 97 0.44

3 1030 142 0.62


4
1 700 99 0.47

2 800 103 0.47

3 1260 195 0.88

1 710 96 0.45 96 0.45

5 2 920 124 0.57 124 0.57

3 1350 200 0.89 200 0.89

VK_2052751GB Subject to technical modifications Status 09/2005 27


Acoustics GEA Basic Geko

Sound pressure
Sound power level (dB)
Capacity stage

Air volume
level *

flow
Speeds Sum level valuated according to
Size

Octave centre frequency (Hz) non-


valuated
valuated
m3/h 63 125 250 500 1000 2000 4000 8000 dB dB(A) dB(A) NR NC
1 130 38 34 28 <20 <20 <20 <20 <20 40 <30 ** 13 8 4
1 2 200 43 36 37 36 32 <20 <20 <20 45 36 27 23 21
3 280 <20 37 40 45 40 35 24 <20 49 45 36 33 32
1
1 130 38 34 28 <20 <20 <20 <20 <20 40 <30 ** 13 8 4
2 2 200 43 36 37 36 32 <20 <20 <20 45 36 27 23 21
3 280 <20 37 40 45 40 35 24 <20 49 45 36 33 32
1 165 50 38 33 30 <20 <20 <20 <20 50 31 22 17 14
1 2 240 49 39 41 40 37 30 <20 <20 51 41 32 28 26
3 340 48 41 45 46 44 40 31 <20 53 48 39 35 34
2
1 240 39 52 40 38 35 25 <20 <20 53 41 32 26 24
2 2 350 <20 51 47 48 46 43 34 <20 54 50 41 37 36
3 540 49 52 57 57 56 55 49 42 63 61 52 49 47
1 350 <20 35 38 33 <20 <20 <20 <20 41 33 24 20 18
1 2 470 <20 39 42 42 38 30 <20 <20 47 42 33 29 27
3 620 38 45 50 53 47 43 32 <20 56 53 44 41 39
3
1 350 <20 35 38 33 <20 <20 <20 <20 41 33 24 20 18
2 2 620 38 45 50 53 47 43 32 <20 56 53 44 41 39
3 840 45 50 55 58 54 51 44 35 62 59 50 46 45
1 360 <20 35 38 33 <20 <20 <20 <20 40 33 24 20 18
1 2 610 37 48 47 53 45 40 30 <20 48 52 43 41 39
3 1030 49 52 58 62 58 55 49 41 65 63 54 50 49
4
1 700 43 49 50 53 48 44 35 <20 57 53 44 41 39
2 2 800 45 51 52 54 51 48 39 27 59 56 47 42 41
3 1260 52 58 63 64 63 60 56 49 69 67 58 54 53
1 710 <20 51 49 50 48 45 34 <20 56 52 43 39 38
1 2 920 41 52 54 56 53 52 42 32 61 58 49 46 44
3 1350 50 58 64 64 63 61 57 50 70 68 59 55 53
5
1 710 <20 51 49 50 48 45 34 <20 56 52 43 39 38
2 2 920 41 52 54 56 53 52 42 32 61 58 49 46 44
3 1350 50 58 64 64 63 61 57 50 70 68 59 55 53

*) The sound pressure level refers to a reverberation field in a 100-m3 room and a reverberation time of 0.5 seconds
**) Audibility threshold

= for the values extracted for the sample calculation, see page 30

28 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko Sound pressure level, sound power level

Sound pressure level dB(A) The anticipated sound pressure level in the Sound pressure increase (dB)
The sound pressure specifications in the tables room is thus:

Sound pressure increase dB


10
on pages 6-25 and 28 apply in the LPges. = LP + 4.5 dB = 32.5 dB(A) + 4.5 dB 9
reverberation field of a room with a volume of = 37 dB(A) 8

100 m3 and a reverberation time of 0.5 s.


7

The value for the increased requirement for 6


5
To determine the anticipated sound pressure large offices from Fig. 29-1 is thus fulfilled. 4,5
4
level at the installation location, refer to the A- 3
2
rated sound power level in conjunction with the
Table A-sound pressure level LP 1) as guide 1
conversion diagram in Fig. 29-4.
values from VDI 2081 1 2 3 4 5 6 8 10
Example: Room type A-sound pressure Average
Number of units

Three fan units of size 2 and capacity stage 1 level dB(A) reverb-
eration Fig. 29-2
are to be installed in an office space with the time s
dimensions (15 x 6 x 3 m). It should operate at Flat * **
speed 2, i.e. the sound power level of a unit (Hotel room) at night 35/30 30/25 0.5 Direction coefficients
Living space (daytime) 35 30 0.5
should be 41 dB(A), see page 28. Auditoriums
TV studio 30 25 1.5
Determining the sound pressure level Concert hall 30 25 2.0 2 4
Opera house 30 25 1.5
1. Based on the room volume (270 m 3), an Theatre 35 30 1.0
8
absorption surface of approx. 50 m2 Sabin is Cinema 40 30 1.0
estimated in accordance with the diagram in Lecture hall 40 35 1.0
Reading room 40 35 1.0 8 2 4
Fig. 29-4 Flats, offices, hotel rooms, Seminar room 40 35 1.0
conference rooms. School classroom 40 35 1.0
Offices
2. The mean distance to the fan coil units is Conference room 40 35 1.0 Fig. 29-3
assumed to be approx. 3 m and the direction Relaxation room 40 35 0.5 Direction coefficient 2
Break room 40 35 0.5 (hemispherical radiation):
coefficient to be 4, Fig. 29-3. The intersection Small office space 40 35 0.5
Unit is mounted freely in the middle of a
of the sample lines in the diagram in Fig. 29-4 Large office space 50 45 0.5
surface
Church 35 25 3.0
produces the sound level difference: Museum 40 35 1.5 Direction coefficient 4
L~8.5 dB Booking hall 45 40 1.5 (quarter-spherical radiation):
Computer room 55 40 1.5 Unit borders on two room surfaces
3. The anticipated A-rated sound pressure Laboratory 45 40 2.0
55 2) Direction coefficient 8
level LP for a unit is thus: Restaurant 40 to 1.0
Kitchen 45 to 60 2) 1.5 (eighth-spherical radiation):
LP = LW L = 41 dB(A) 8.5 dB = 32.5 dB(A) Showroom 45 to 60 2) 1.0 Unit borders on three room surfaces
The level increase with 3 units is, according to Fig. 29-1
Fig. 29-2, approx. 4.5 dB. * = minimum requirements
** = increased requirements
1)
See also applicable building authority guidelines, DIN
standards and VDI guidelines (e.g. DIN 4109, DIN 1946, VDI
2058);
2) Depending on use

Conversion of sound power level to sound pressure level

0
F
Faabct 5
riko-ruie. s
Scahn
wd imsmw 10
[dB]

haim
LP[dB]

5 LW
ivion SSch llemn ing a=
Sabin]

hgnrs chouo 0,0 20


p ace,e lrlruomoe
]

um 3
L=LW- -LP

s m
2 Sabin

8,5 R B , ro s a=
Leesa ofsf,ic 0,0
edsin Heost 5
10 leg, ro e,lzhim
ote
2

Fero 50
Sound level differenceDL=LW

nsmes
[ m[m

mel a=
hs, tT rroo
udVios ms 0,1
s tud
Absorption surface

RRad ios a= Ho Lar 100


0,1 Ksrapi gger
15 unio 5 nktaenl zro oche
uKrirc
Absorbtionsflche

dfus
ntkusd a= Co imomm
tuio nfe chhees 200
ss
dio 0,2 ers,,
Schallpegelgifferenz

reKno n
5 ksle
mina
ncfe
erero ellKc
a= nozrm irhcuherc
20 0,4 De usm
, et,hTe
n he 500
par haetr
s
tme atees
nKta s r
ufthor
3

uess 1000
270 m

MM er
25 usui
scikrzo
imom mes 2000
r

30
OFr

5000
p ee
nife
spld

Gert grenzt on
Unit borders an three
drei Raumflchen
room surfaces
ac
e

35 50 100 200 500 1000 2000 5000 10000 30000


8

Room m 33]]
volume[ [m
Raumvolumen
Richtungsfaktor

Unit borders
Gert onzwei
grenzt an two room surfaces
Raumflchen
Absorption factor
4

A wall surface that absorbs all sound waves that hit it has an absorption
Direction

Unit isist
Gert mounted
frei infreely in the middle
der Mitte einer ofFlche
a surface
factor of = 1. The above m values represent the relationship between
2

the actual absorption and the ideally absorbing wall. They represent
mean values.
Absorption surface m2 (Sabin)
0,5 1 2 3 4 5 6 8 10 15 20 30 40 60 70 This is the surface that completely absorbs all sound waves that hit it. It
Distance from is not identical to the whole room surface.
Abstand von derthe sound source
Schallquelle [ m ] [m]
Fig. 29-4

VK_2052751GB Subject to technical modifications Status 09/2005 29


NR and NC limiting curves GEA Basic Geko

Limiting curves
If narrower frequency components or outstanding single tones ISO NR-Bewertungskurven
ISO NR evaluation curves
with high intensity peaks occur in a broader frequency range (e.g. 90
in a fan), the dB(A) specification (level) is not sufficient as it does
not sufficiently address the percieved noisiness. For this reason,
80
limiting curves (curves of equal perceived noisiness) are added
that also take the combination of frequencies of the noise into NR 80
account. 70
Although various noise-rating curves exist, NR curves (noise

in dB
70
rating) as per Fig. 30-2 have become accepted internationally. 60

in dB
NC curves (noise criteria) are now only used for noise rating in

pressure level
the USA, as per Fig. 30-3. 60

Schalldruckpegel
If the observance of a particular NR or NC curve is required for a 50
room, the measured sound pressure must not exceed this limiting
curve in any octave. 50
40
The total level across all eight octaves as per DIN is always
around 7 to 10 dB higher than the limiting curve value. In the case 40

Sound
of air treatment systems, the sound pressure level difference is 30
on average 5 dB(A) because the spectrum of these sounds does
30
not always reach the same limiting curve in all octaves. 20
NR 29
20
10

0
63 125 250 500 1000 2000 4000 8000 Hz
Example Octave band/medium
Oktavband/Mittenfrequenz
The requirements of NR 30 or NC 28 for a unit must be observed.
The tabulated data on page 28 serves as a basis. In order to Fig. 30-2
identify the sound pressure level in the individual octaves, the
sound power values listed on page 28 should be entered under
size 2, capacity stage 1 and speed 2 in a table, see Fig. 30-1.
In order to maintain the sound pressure levels in the individual
octaves, the calculated value of 8.5 dB must be subtracted from NC evaluation curves
NC-Bewertungskurven
the sound power specifications in Fig. 30-1. The new values 90
attained can be entered in the nomograms Fig. 30-2 (NR) or Fig.
30-3 (NC).
80
The highest point in the NR evaluation is NR 29 (1000 Hz), and
in the NC evaluation NC 27 (1000 Hz).
The requirement of NR 30 (NR 28 is below NR 30) or NC 28 70
NC 70
(NC 27 is below NC 28) is thus maintained.
in dB

60
in dB

60
pressure level
Schalldruckpegel

50
50

40
40
Sound

Octave centre frequency for size 2, capacity stage 1


30
and speed 2 30
28
63 125 250 500 1000 2000 4000 8000 [Hz]
20
49 39 41 40 37 30 20 20 [dB] 20
-8.5 -8.5 -8.5 -8.5 -8.5 -8.5 -8.5 -8.5 [dB] NR
NC 21
27
10
40.5 30.5 32.5 31.5 28.5 21.5 11.5 11.5 [dB]

Fig. 30-1 0
63 125 250 500 1000 2000 4000 8000 Hz
Octave band/medium
Oktavband/Mittenfrequenz

Fig. 30-3

30 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko Installation examples

Wall units
Recirculation air units with unit casing (cooling/heating) Recirculation air units with
casing by others (cooling/heating)

Fig. 31-1 Fig. 31-2 Fig. 31-3

Ceiling units
Recirculation air units with unit casing

Cooling/heating Cooling/heating Heating *)

*) Electrical heating
not available

Fig. 31-4 Fig. 31-5 Fig. 31-6

Recirculation air units with casing by others

Fig. 31-7

VK_2052751GB Subject to technical modifications Status 09/2005 31


Dimensions for basic units without casings GEA Basic Geko

Unit for ceiling mounting Lateral condensate tray for ceiling coolers

b + 40
b

140

227

80 450
Fig. 32-1 Fig. 32-2

Unit for wall mounting 140 Lateral condensate tray for wall coolers
227

b+40
b
90
450

100

Fig. 32-3 Fig. 32-4

Mounting measurements - wall Mounting measurements - ceiling

429
306
b + 20
80
b + 20

429
100
306

80

100

Fig. 32-5 Fig. 32-6

Measurements and weights


(See type key for order numbers)

Size
Weight
b [mm] * Basic unit including The unit dimensions depicted in the figures above are
[kg]*
unit casing independent of the unit size.
1 25 464
The unit length and width vary depending on the size and can
2 32 614
be taken from the accompanying table.
3 40 764
4 43 914
5 48 1214

32 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko Dimensions for basic units without casings

Dimensions for channels by others on the intake and Dimensions for services for installation behind casings
discharge side installed by others

90

450 140

150
84
227
97

100

412
16

Fig. 33-1 Fig. 33-2

Coil connections (warm/chilled water) Coil connections (warm/chilled water)

227 227
1/2" 116 37,5 37,5 153,5
74,5
66,5

1/2" 37,5

66,5
239,5

3
131

197,5
33
239,5

2
450

16
33

450
16

1
100

1
100

2-pipe system for wall and ceiling mounting 4-pipe system for wall and ceiling mounting
Heat exchanger for LG1 and LG2, Heat exchanger for heating and cooling circuit,
" internal thread " internal thread
1 Filter removal 1 Filter removal
2 Cooling
3 Heating
HE content HE content
Size LG1 (l) LG 2 (l) Size Cooling circuit Heating
(l) circuit (l)
1 0.5 0.8
LG1 LG2
2 1.1 1.1
1 0.5 0.8 0.2
3 1.4 1.4
2 1.1 1.1 0.3
4 1.7 1.7
3 1.4 1.4 0.4
5 2.2 2.9
4 1.7 1.7 0.5
5 2.2 - 0.8

Fig. 33-3 Fig. 33-4

VK_2052751GB Subject to technical modifications Status 09/2005 33


Dimensions for casing and accessories GEA Basic Geko

Unit casing colour white; similar to RAL 9010


with discharge grille colour grey; similar to RAL 7035
(wall and ceiling mounting)
Size Order no. Weight [kg]
1 ZGB102 7,3
2 ZGB202 8.4
3 ZGB302 9.5
4 ZGB402 10.3
5 ZGB502 12.6

* including grille height


Fig. 34-1

Air intake grille and casing spacer


colour grey; similar to RAL 7035 made of plastic
(wall and ceiling mounting)
Size Order no. Weight [kg]
1 ZGB105 0.36
2 ZGB205 0.40
3 ZGB305 0.47
4 ZGB405 0.52
5 ZGB505 0.63

Only in combination with unit casing

Fig. 34-2

Air intake grille and casing spacer


colour white; similar to RAL 9010 made of sheet steel
(wall and ceiling mounting)
Size Order no. Weight [kg]
1 ZGB107 1.15
2 ZGB207 1.27
3 ZGB307 1.42
4 ZGB407 1.52
5 ZGB507 1.76

Only in combination with unit casing

Fig. 34-3

Spacer (on suction side)


(1 set = 2 pieces)
Size Order no. Weight [kg]
1-5 ZGB003 0.26

Fig. 34-4

Size 1 2 3 4 5
L [mm] 827 977 1127 1277 1577

34 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko Dimensions for casing and accessories

Flexible discharge connection


(fire classification B1)
Size Order no. Weight [kg]
Hole size for 1 ZGB101 1.6
162
connection frame:
2 ZGB201 2.1
b+20 x 142
3 ZGB301 2.6
4 ZGB401 3.1
b + 40 5 ZGB501 4.1

* max. length
Fig. 35-1

Spare filter (1 set = 5 pieces)


quality level G1 (EN 779)
regenerative filter medium
Size Order no. Weight [kg]
1 ZGB106 0.15
2 ZGB206 0.26
3 ZGB306 0.34
4 ZGB406 0.37
5 ZGB506 0.43

Fig. 35-2

Size 1 2 3 4 5
Width b [mm] 464 614 764 915 1214

Discharge plenum with primary air spigot


(made of galvanized sheet steel, non-insulated)
Size Order no. Weight [kg]
1 ZGB108 1.9
2 ZGB208 2,3
3 ZGB308 2.8
4 ZGB408 3.3
5 ZGB508 4.2
Hole size for connection
frame: b+20 x 142

Fig. 35-3

VK_2052751GB Subject to technical modifications Status 09/2005 35


Control behaviour of valves GEA Basic Geko

On/off control mode On/off control mode


3-port valve
Warmer
Fig. 36-5
Set-point Temperature set in room with
on/off control mode.
Cooler Fig. 36-5

Warmer
Fig. 36-6
M
Set-point Temperature set on average
R AB
B
A

Cooler
with on/off control mode at air
V Fig. 36-6 outlet.

Fig. 36-1 (on/off control mode)

Fig. 36-7
2-port valve
The valve is either open or shut.

Fig. 36-7
Fig. 36-8
+
Set command for valve.
+ = valve open
0 0 = valve closed
Fig. 36-8
M

V Performance viewed over time

Fig. 36-2 (on/off control mode)

Modulating control mode Modulating control mode


3-port valve
Warmer
Fig. 36-9
Set-point Temperature set in room with
GEA Fig. 36-9 modulating control mode.
Cooler

Warmer Fig. 36-10


Temperature set on average
Set-point with modulating control mode at
M

R AB
B
A
Cooler Fig. 36-10 air outlet.
V

Fig. 36-3 (modulating control mode)

Fig. 36-11
2-port valve
The valve setting corresponds
to the percentage of the flow
amount (0 . . .100 %).

Fig. 36-11

GEA
+ Fig. 36-12
0 Set command for valve.
M Fig. 36-12 + = valve direction open
R - = valve direction closed
V
Performance viewed over time

Fig. 36-4 (modulating control mode)

36 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko Overview of valves
Selection table
The following selection table presents all available valve The following symbols are used:
equipment variants with the main features and compatible 9 = Valve type compatible with the respective control unit
control equipment. or electrical equipment.
= Valve type not compatible with the corresponding control
unit or electrical equipment.

Valve type Function Control Voltage Compatible control equipment Control by Catalogue
type type others page
MATRIX MATRIX Thermostat
2000 3000 switch
Mod. 230 V~ 9 9 9 38
control
AB A
B

R
(2-pipe
system only)

On/off 230 V~ 9 9 9 9 39
AB A
B

VK_2052751GB Subject to technical modifications Status 09/2005 37


Overview of valves GEA Basic Geko

Valves (loose) with modulating actuators (230 V~)


Two- and three-port valves with modulating actuator for
100
3-port valve upstream control (modulating control mode).
Connecting cable, plastic motor housing, brass (G 1/2"A)
or red-brass (G 3/4"A) valve housing, stainless-steel
spindle and cone.
~ 92

Technical data:
Nominal pressure: 16 bar
Max. perm. ambient temperature: 60 C
AB A Max. flow temperature: 110 C
B Operating voltage 230 V~/50/60 Hz
Power consumption: 7 VA
40

M
Enclosure: IP 43
R AB A
Running time: 120 s at 50 Hz (100 s at 60 Hz)
B

V
Water with maximum 50 % glycol permissible.
56 (66)
Do not fit actuator upside down!
Measurements for G3/4" in brackets
Fig. 38-1

Valve connection values


kvs value pmax.1) Valve
100
2-port valve [m3/h] [kPa] outer thread
0.63 1600 / 8002) G 1/2" A
1.0 1200 / 2502) G 1/2" A
1.6 1200 / 2502) G 1/2" A
~ 92

2.5 400 / 1002) G 3/4" A


1)
Max. permissible pressure difference at which the valve
M still shuts against the pressure (for 2-port valves)
R 2)
For 3-port valves

56 (66) V

Measurements for G3/4" in brackets


Fig. 38-2
The control valves can be supplied either loose or fitted
k VS = 0,63 k VS = 1,6
at the manufacturer's, i.e. piped and wired. Cap nuts with
k VS = 1,0 k VS = 2,5
capillary sockets for Cu pipes are also supplied with
30
pipes fitted at the manufacturer's.
20 Order no.
kvs Loose valves Pre-fitted
10
value valve equipment
[kPa]
p (kPa)

8 2-port 3-port 2-port 3-port


6 0.63 935.423 935.413 VR206.B# VR306.B#
dropp

5
1.00 935.424 935.414 VR210.B# VR310.B#
Druckverlust

4
1.60 935.425 935.415 VR216.B# VR316.B#
Pressure

3
2.50 935.426 935.416 VR225.B# VR325.B#
2

With pre-fitted valve equipment for a 4-pipe system, the order no. needs
to be supplemented by the reference number for the kvs value of the
1
heating valve, e.g. VR31610.B# (compare unit type code, page 51)
200

300

400

500
600

700

The # symbol is a placeholder for coil connection on the left (L) or


100

2000
1000

right (R).
Note:
Water flow rate V [l/h] V (l/h)
Wasservolumenstrom
The maximum pressure drop in the heat exchanger with a fully opened
Fig. 38-3 valve should not exceed 25 kPa in cooling mode and 20 kPa in heating
mode!

38 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko Overview of valves
Valves with thermoelectric actuators (230 V~)
Two- and three-port valves with thermoelectric actuator
42
for upstream control (on/off control mode).
3-port valve
Plastic connecting cable and motor casing, red-brass
valve body, stainless-steel spindle and cone.
Technical data:
Nominal pressure 16 bar
~ 92

Max. perm. ambient temperature: 50 C


Max. flow temperature: 110 C
Operating voltage: 230 V~/50/60 Hz
AB A Starting current: 0.3 A
B Operating current: 0.013 A
M
40

Power consumption: 3 VA
R AB A
Enclosure: IP 43
B
Running time: approx. 3 min
V
66
Water with maximum 50 % glycol permissible.
Do not fit actuator upside down!
Fig. 39-1

42 Valve connection values


2-port valve
kvs value pmax. Valve
[m3/h] [kPa] outer thread
2.50 2001) / 502) G 3/4" A
1) Max. permissible pressure difference at which the valve
~ 92

still shuts against the pressure (for 2-port valves)


2)
For 3-port valves

66 V

Fig. 39-2

k vs= 2,5
The control valves can be supplied either loose or fitted
30 at the manufacturer's, i.e. piped and wired. Cap nuts with
20
capillary sockets for Cu pipes are also supplied with
pipes fitted at the manufacturer's.
10 Order no.
[kPa]
p [kPa]

8
6
kvs Loose valves Pre-fitted
valu valve equipment
Pressure dropp

5
4 e 2-port 3-port 2-port 3-port
Druckverlust

2
2.50 935.464 935.354 VT225.B# VT325.B#

1
0,8 With pre-fitted valve equipment for a 4-pipe system, the order no. needs
0,6 to be supplemented by the reference number for the kvs value of the
0,5
heating valve, e.g. VT32525.B# (compare unit type code, page 51)
0,4
The # symbol is a placeholder for coil connection on the left (L) or
0,3
right (R).
Note:
The maximum pressure drop in the heat exchanger with a fully opened
1000

2000
100

400

500
200

300

600

800

valve should not exceed 25 kPa in cooling mode and 20 kPa in heating
mode.
Water flow rate VW [l/h]V (l/h)
Wasservolumenstrom
w

Fig. 39-3

VK_2052751GB Subject to technical modifications Status 09/2005 39


Control with thermostat switch MCR 2000 / GEA Basic Geko

control by others
The MCR 2000 thermostat switch allows standard control of the Basic Geko.
The switch can be used with: Valve type Unit model
Wall Ceiling
Recirculation air 4-pipe system

Cooling and Chilled and warm water
heating 2-pipe system

Chilled water and electrical heater
Cooling or 2-pipe system

heating Chilled or warm water

2-pipe system
Heating
Warm water

2-pipe system
Cooling
Warm water

Please note:
- Only on/off valve actuators (T) can be used.
- Only one Geko may be operated with the MCR 2000 thermostat switch, or the fan motor speeds must not be switched directly
in parallel

Terminal box with connections for Geko components.


Basic unit order code
Plastic terminal box For connection to a controller, components such as fan(s) and valve(s) are wired in a
terminal box.
GBxx.xxxx.Axx
Depending on the selected unit model and valve equipment, the terminal box is made of
Sheet-steel electric plastic or sheet steel. As shown here, a selection is made via the unit type key, additional
control box loose sensors and switches can be ordered separately, as described in the following list.
GBxx.xxxx.Kxx

Functionalities of speed switch and flow sensor:


Switch type / sensor type / accessories
MCR 2000 MCR 2000
Electronic temperature controller for on-wall mounting or installation in the Geko (with
controller installation kit ZE 2000); integrated room temperature sensor; option of
connecting NTC sensors for recording the room and inlet temperature for
2-pipe system (cooling or heating with water)
2-pipe system (cooling with water and electric heating 230 V~)
4-pipe system (cooling and heating with water)

When combining multiple Basic Gekos with an MCR 2000, the speeds of the fan motors
must not be switched or activated in parallel.

Functions and operation elements


Automatic switching between cooling and heating
Integrated room temperature sensor
Valve control, on/off control mode
Set-point range 5 C to 30 C
Set-point limitation
Switch 0 - 1 for operation
Switch 1 - 2 - 3 for fan speeds
Enclosure IP30
Colour white; similar to RAL 9010
External control input unit switch off with room frost protection function
ZE 2000 Controller adapter kit ZE 2000
For installation of the MCR 2000 thermostat switch on the basic unit.
A room temperature sensor or a return air sensor is also required here.

40 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko Control with thermostat switch MCR 2000 /
control by others
Functionalities of speed switch and flow sensor:
Switch type / sensor type / accessories
903.414 Room temperature sensor order no. 903.414
Sensor thermistor for on-wall mounting
NTC sensor element
Plastic housing; white; similar to RAL 9010
Resistance coefficient at 25 C = 10 k
Enclosure IP 20
Dimensions in mm (W x H x D): 84 x 84 x 22
903.474 Return air sensor order no. 903.414 with rubber bushing
Sensor thermistor for unit installation
NTC sensor element
Sensor casing made of stainless steel
Sensor casing length 100 mm; cable length 1.5 m
Max. ambient temperature 105 C
Resistance coefficient at 25 C = 10 k
Enclosure IP 43
The room temperature sensor 903.414 or the return air sensor 903.474 replaces the room temperature sensor in the thermostat switch
MCR 2000.
The additional sensor will need to be installed if the control unit is installed in the Geko or is mounted in a bad location for temperature recording.
903.434 Flow sensor sensor thermistor for installation on the inlet
NTC sensor element
Sensor on baseplate; plastic housing; white; similar to RAL 9010
With tightening strap installed on flow pipe
Max. ambient temperature 100 C
Dimensions in mm (W x H x D): 85 x 53 x 65
Resistance coefficient at 25 C = 10 kW
Enclosure IP 43

Example for the use with thermostat / speed switch


Master unit
Fhrungsgert

Flow
sensor
903.434

2 x 0,8 mm2

5 . . .7 x 1,5 mm2 3 x 1,5 mm2

B6A
MCR 2000

2
L N PE
Supply cable 230 V /230
Versogungsleitung 1.5 V
mm/ 1,5 mm 2

Accessory
Zubehrteil,part, Infeed control
Einspeisung Steuerung
only in 2-pipe
nur im system
2-Leiter for heating/cooling.
-System Heizen/Khlen. 230
230 V~
V~ 11 N
N PE
PE5050Hz
Hz
Achtung! Use
Attention! 3-W ege-Ventile
3-port valves.verwenden. Enclosure
bauseitige by others
Absicherung
max.
max.66A A

Fig. 41-1

VK_2052751GB Subject to technical modifications Status 09/2005 41


GEA MATRIX control system GEA Basic Geko

System description
Overview

MATRIX 2000
Drive-type valves The MATRIX 2000 control system supports all basic functions (heating / cooling) of the
On/off Modulating recirculation air Basic Geko. The controller can be used in the following system types:
2-pipe systems Heating only
2-pipe systems Cooling only
2-pipe systems Heating or cooling (change over)
4-pipe systems Heating and cooling
The 3-speed ventilator control occurs automatically depending on the set-point / actual
temperature deviation. The operator panel enables the speed to be specified manually
and the unit to be switched off (with frost protection). For the regulation of the heating
and/or cooling performance, valves with on/off or modulating behaviour can be
controlled with a supply voltage of 24 V or 230 VAC. The 4-pipe systems are an
exception; use is limited to on/off actuators here. MATRIX 2000 also enables the
monitoring of the fan motor via implemented thermocontacts with external leads as
well as control of the condensate water level in coolers with a condensate pump.
The OP21 operator panel enables the quick and easy adjustment of the set points
without more extensive previous knowledge. A limitation of the adjusting range for set-
point temperature and setting is possible through mechanical stops. The room
LEDs for temperature is recorded via a sensor that is integrated in the operator panel. If the
operation /
operator panel is unfavourably placed, e.g. next to the door, an external temperature
malfunction /
Normal / energy external sensor or return air sensor can be connected (not possible with change over systems).
saving mode System malfunctions are signaled as an accumulative error message via the red
Speed selector Set-point Malfunction LED. If energy saving mode is activated, this is indicated via the yellow
switch temperature LED that is integrated in the pushbutton.
In addition to enclosure IP20 (OP21 C), a moisture-proof IP54 operator panel variant
(OP21 I) is available, for example.
The connection in the unit takes place via plug-in type cage clamps. Electronics as well
as fans and valves (230 V) are protected separately via two micro-fuses on the power
print; a backup fuse of B 10 A is to be provided for the necessary protection of the line.
MATRIX 2000 can be used to control recirculation air single units as well as
recirculation air unit groups. Several groups can be combined to form one network with
up to 16 groups via the integrated GEA MATRIX.Net bus system. The combination
with the MATRIX 3000 controllers as well as the connection of global modules and
communications interfaces is thus also possible.

42 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko GEA MATRIX control system
System description / overview of performance characteristics
MATRIX 3000
Drive-type valves
The Matrix 3000 control system is based on the MATRIX 2000 system and also
On/off Modulating
provides additional functionalities. Primarily, these are:

Valves with a modulating behaviour can be used for 4-pipe systems. Mixed operation
(on/off cooling valve / modulating heating valve or modulating cooling valve / on/off
heating valve) is also possible.

The unit displays operating and error messages via two change-over contacts. The

contact load at is 230 VAC maximum 4 A ohmic / 2 A inductive.
The temperature of the supply air can be limited for heating and cooling. Both fixed and
floating limits can thereby be specified.
An external temperature sensor or return air sensor can be connected to all system
types.
An additional control input allows the external specification of the following operating
modes:
Normal / energy saving mode
or
Unit OFF with frost protection

100 R E 14:08
Different types of operator panels are available. The selection ranges from a simple
variant with the selection of the set-point temperature and fan operation mode to a
C
21 .5 %
on o ff
func - +

remote control or an operator panel with a display. The display unit is also available
send

with an integrated week timer.

Performance characteristics MATRIX 2000 MATRIX 3000

Unit type 2-pipe systems Heating only 9 9


2-pipe systems Cooling only 9 9
2-pipe systems Heating or cooling 9 9
4-pipe systems Cooling and heating 9 9
Fan up to 3 speeds (1 x 230 V) 9 9
Temperature-dependent fan control 9 9
Valve control 1 x on/off; 1 x modulating; 2 x on/off 9 9
1 x on/off; 1 x modulating; 2 x on/off; 2 x modulating 9
External heating valve for coolers, with fan switch-off 9 9
Electric heating 1-speed 9 9
Frost protection Room frost protection 9 9
Summer / winter compensation 9* 9
Control inputs Energy saving mode or gate / window contact 9* 9
Recording the exterior temperature via GEA MATRIX.AI 9 9
Recording the inlet temperature via local sensor connection 9 9
Recording the return air temperature via local sensor connection 9** 9
Messages Condensate level alarm with unit switch-off 9 9
Operating message via change-over contact 9
Error message via change-over contact 9
Control types Room temperature control 9 9
GEA MATRIX.Net bus system 9 9
possible expansions: GEA MATRIX.DI 9 9
GEA MATRIX.AI 9 9
GEA MATRIX.DO 9 9
GEA MATRIX.LON 9 9
GEA MATRIX.WEB 9 9
Service tools GEA MATRIX.PDA 9 9
GEA MATRIX.PC 9 9
Operator panels GEA MATRIX OP21x 9
GEA MATRIX OP30x 9
GEA MATRIX OP31x 9
GEA MATRIX OP44x 9
GEA MATRIX OP50x / 51x 9

* only with add-on module


** not for cooling or heating units

VK_2052751GB Subject to technical modifications Status 09/2005 43


GEA MATRIX control system GEA Basic Geko

Installing the operator panels


Because the two units are separate, it is possible wait until commissioning before
snapping the front cover of the operator panel onto the mounting plate. This provides
optimal protection against contamination and damage of the operator panels during
the construction phase.

The cable connection is established via cage clamps. This enables the quick and easy
use of solid and flexible wires.

Holes are provided in the mounting plate so that the operator panel can be mounted
on a standard flush mount.

Direct installation on the wall (cables concealed or laid in a cavity wall) is also possible.

The operator panel can be mounted on the basic unit by means of installation kit ZE
OPC. In this case, an external room or return air temperature sensor is to be provided.

Moisture-proof IP54 operator panels are available on request.

In order to prevent contamination or accidental operation, unit covers are available as


accessories (see Fig. 45-4 on page 45).

44 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko GEA MATRIX control system
Sensors / accessories
Room temperature sensor order no. 903.414
Sensor thermistor for on-wall mounting
NTC sensor element
Plastic housing: white, similar to RAL 9010
Resistance coefficient at 25 C = 10 k
Enclosure IP 20
Dimensions in mm (W x H x D): 84 x 84 x 22

Fig. 45-1

Return air sensor order no. 903.414 with rubber


bushing
Sensor thermistor for unit installation
NTC sensor element
Sensor casing made of stainless steel
Sensor casing length 100 mm; cable length 1.5 m
Max. ambient temperature 105 C
Resistance coefficient at 25 C = 10 k
Enclosure IP 43

Fig. 45-2

The 903.414 room temperature sensor or the 903.474 return air sensor replaces the room temperature sensor in the
MATRIX OP XXC control units.
The additional sensor will need to be installed if the control unit is installed in the Geko or is mounted in a bad location for
temperature recording.
Flow sensor order no. 903.434
Sensor thermistor for fitting on flow side
NTC sensor element
Sensor on base frame; plastic housing; white;
similar to RAL 9010
Fitted to flow pipe with tightening strap
Max. ambient temperature 100 C
Dimensions in mm (W x H x D): 85 x 53 x 65
Resistance coefficient at 25 C = 10 k
Enclosure IP 43
Fig. 45-3

Unit cover
White order no. OPD.C
(for OP21C / OP30C / OP31C / OP44C)
Light grey order no. OPD.C
(for OP21I / OP30I / OP31I / OP44I)
For covering the operating elements of the control unit.
The unit cover is hung into the guide slots of the control
unit and protects the control unit from dirt accumulation
and unintentional operation.
Fig. 45-4

ZE OPC 2 ZE OPC 3 Controller adapter kit order no. ZE OPC 2 / ZE OPC 3


for installing the MATRIX OP XXC (only IP 20) control
units on the basic unit. A room temperature sensor or a
return air sensor is also required here.
ZE OPC 2 for operator panel OPC21 C
ZE OPC 3 for operator panel OPC30 C and higher

Fig. 45-5

VK_2052751GB Subject to technical modifications Status 09/2005 45


GEA MATRIX control system GEA Basic Geko

Global modules
MATRIX.DI digital input module
The MATRIX.DI digital input module belongs to the global modules of the GEA MATRIX
control system and is used for receiving digital control signals. It thus enables the
control system to be influenced by external systems. The module can be integrated into
the MATRIX network at any point. A maximum of two MATRIX.DI modules may be
operated in the same network simultaneously.
The module has eight independent digital inputs that are controlled via potential-free
contacts. LEDs display the current input status. Commands entered via the DI module
have priority over the settings of the local operator panel. The following functions and
operating modes can be defined via the module:
HVAC mode (heating / cooling / automatic)
Normal / energy saving mode
Fan speed (1/2/3/4/5/auto/mute)
Activate mixed-air mode
Unit off with frost protection
Activate controller operating values
The module is shipped with a manufacturer's configuration. Different configurations can
be set via the MATRIX.PC service software. The function allocation of the inputs and
the respective allocation to the group(s) can be freely selected.

Technical data:

Power supply 24 V DC 15 %
Enclosure IP 20
Max. current consumption 0.0.1 A
Dimensions 106 mm x 90 mm x 58 mm
Operating temperature 0 to +45 C
Fusing 10 A T
Mounting Mounting rail

Manufacturer's configuration:

Input Valid for Closed contact means:


1 All groups HVAC mode heating
2 All groups HVAC mode cooling
3 All groups Normal mode
4 All groups Energy saving mode
5 Group 0 Fan in speed 3
6
7
8 Group 0 Mixed-air mode active

46 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko GEA MATRIX control system
Global modules
MATRIX.DO digital output module
The MATRIX.DO digital output module belongs to the global modules of the MATRIX
control systems and is used for outputting signals from the MATRIX system. It thus
enables messages and states to be forwarded to external systems. The module can be
integrated into the MATRIX network at any point. A maximum of two MATRIX.DO
modules may be operated in the same network simultaneously.
The module has eight separate digital outputs with potential-free change-over contacts.
LEDs display the current output status. Messages and states of the system
components of one or more groups can be output directly or in conjunction with further
states. For instance, compare functions, arithmetic functions or time functions are
available for this.
The following messages / states can be output amongst others:
Error messages (e.g. motor overheating, risk of frost, sensor error, condensate
level too high)
Current fan speed
Normal mode / energy saving mode
Bypass mode
Current HVAC mode (heating / cooling / automatic)
Mixed-air / recirculation air mode
Electric heater active
X number of units are in heating or cooling mode
The module is shipped with a manufacturer's configuration. Different configurations can
be set via the MATRIX.PC service software. The function allocation of the outputs and
the respective allocation to the group(s) can be freely selected.

Technical data:

Power supply 24 V DC 15 %
Enclosure IP 20
Max. nominal current consumption 0.14 A
Dimensions 160 mm x 90 mm x 58 mm
Operating temperature 0 to +45 C
Fusing 10 A T
Mounting Mounting rail
Contact load 250 V / 5 A (ohmic); 2 A (inductive)

Manufacturer's configuration:

Input Valid for Relay on signals:


1 All groups Operation
2 All groups Error message
3 All groups Frost message
4 Group 0 Error message
5 Group 1 Error message
6 Group 2 Error message
7 Group 3 Error message
8 Group 4 Error message

VK_2052751GB Subject to technical modifications Status 09/2005 47


GEA MATRIX control system GEA Basic Geko

Global modules
MATRIX.AI analogue input module
MATRIX.AI analogue input module belongs to the global modules of the MATRIX
control system and is used for receiving analogue actual and set-point values. It thus
enables the MATRIX control system to be coupled with external systems. The module
can be integrated into the MATRIX network at any point. A maximum of two MATRIX.AI
modules may be operated in the same network simultaneously.
The module has eight independent analogue inputs that can be controlled via
010 V / 2..10 V signals or charged with NTC sensors (10 kOhm / 25 C). Commands
entered via the AI module have priority over the settings of the local operator panel. The
following set-point and actual values can be defined or received via the module:
Actual values:
Room, exterior and inlet temperature
Fresh air humidity
Room air CO 2 content
Supply air channel pressure and flow rate
Exhaust air channel pressure and flow rate
Set-point values:
Room temperature, supply air temperature
Fresh air component
The module is shipped with a manufacturer's configuration. Different configurations can
be set via the MATRIX.PC service software. The allocation of the inputs and the
respective assignment to the group(s) can be freely selected. Additionally, the range of
the input voltage can be selected, and the measuring range of the sensor and a filter
value for signal balancing can be defined.

Technical data:

Power supply 24 V DC 15 %
Enclosure IP 20
Nominal current consumption 0.03 A
Dimensions 160 mm x 90 mm x 58 mm
Operating temperature 0 to +45 C
Fusing 10 A T
Mounting Mounting rail

Manufacturer's configuration:

Input Valid for Parameter Type Filter Measuring


value range
1 All groups Outside temperature NTC 20
2 All groups Inlet temperature NTC 20
3 Group 0 Room set-point 0 ... 10 V 20 10 35 C
4 Group 1 Room set-point 0 ... 10 V 20 10 35 C
5 Group 2 Room set-point 0 ... 10 V 20 10 35 C
6 Group 1 Fresh air component 0 ... 10 V 20 0 ... 100 %
7 Group 2 Fresh air component 0 ... 10 V 20 0 ... 100 %
8 Group 3 Fresh air component 0 ... 10 V 20 0 ... 100 %

48 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko GEA MATRIX control system
Global modules / central timer
MATRIX.LON module
The MATRIX.LON communication module belongs to the global modules of the GEA
MATRIX control systems and is used for connecting the MATRIX control system to a
network structure in accordance with the LON WORKS standard. It thus enables the
connection of air-treatment components to a building management system or other
facility management systems. It also enables external systems such as shutters or
lighting systems to be controlled via the MATRIX OP50/51 operator panel. The module
can be integrated into the MATRIX network at any point. A maximum of 16
Group 2 Group 4 Group 16
MATRIX.LON modules can be deployed in any one MATRIX network.

Group 3 Group 1
Technical data:

Power supply 24 V DC 15 %
Enclosure IP 20
Nominal current consumption 0.03 A
Dimensions 106 mm x 90 mm x 58 mm
Operating temperature 0 to +45 C
Fusing 10 A T
Mounting Mounting rail

MATRIX.Clock timer module


The MATRIX.Clock timer module is intended for use as a central week timer. The
module can be integrated into the MATRIX network at any point and supports up to 16
groups in a network. The groups can be assigned individually to the six weekly
programs, the exceptional daily programs and the holiday program. In each weekly
program, up to four switching times (2 x on / 2 x off) can be defined per day.
Additionally, up to six exceptional daily programs with with up to four switching times (2
x on / 2 x off) can be defined per exceptional daily program. Holiday periods can be
defined via the holiday days that can be programmed for the whole calendar year. Entry
is done via a straightforward push&turn control. User navigation is ensured by means
of structured menus, plain text messages and pictographs. The current status of the
individual programs is displayed via a menu.
The timer module can be toggled between six different languages online. The switch
between summer and winter time is automatic. If required, blocking protection e.g. for
pumps can be activated (once a week). Further, the time format can be switched
between 12- and 24-hour display.
The timer voltage is supplied via the MATRIX controllers power print.
Two different variants are available:
MATRIX.Clock C in enclosure IP 20; colour white (similar to RAL 9016)
MATRIX.Clock I in enclosure IP 54; colour light grey (similar to RAL 7035)

VK_2052751GB Subject to technical modifications Status 09/2005 49


GEA MATRIX control system GEA Basic Geko

Service tools

MATRIX.PDA service tool


The MATRIX.PDA service tool is used for setting the parameters of the MATRIX control
system and considerably facilitates startup and maintenance of systems. The service
tool can be connected via the service interface that is integrated into all operator
panels, controllers, global modules, the timer and the communication modules. Entry
is done via a straightforward push&turn control. The following main functions are
available:
Automatic network scanning with display of users found
Plain-text error display
Modification of parameters such as temperature limits, times or control type
Display of actual values
Display of current unit status such as HVAC mode or valve position
Manual control of actuators such as fans and valves
Reading, saving and writing of configuration data
The service tool can be toggled between six different languages online. The unit is
protected from damage during transit and use via a rubber protector.

MATRIX.PC service software


Building on the functions of the MATRIX.PDA service tool, the MATRIX.PC service
software provides further comprehensive functions in the field of parameter setting,
startup and data recording of the GEA MATRIX controller system.
The service software can be connected via the service interface that is integrated into
all operator panels, controllers, global modules, the timer and the communication
modules. A USB interface is required on the PC side. The accompanying adaptor
establishes the necessary connection between the PC and the service interface.
In addition to the functions of the MATRIX.PDA, the following main functions are also
available:
Online display of module, status and network data
Recording and saving of temperature progressions and switching states of the
actors with adjustable sample rate
Offline parameter setting
Programming of the inputs and outputs provided for this purpose
(controllers, global modules)
Release of messages and network data
Parameter setting for controller and operator panel functionality
Input of sensor correction factors
PC system requirements:
PC with 233 MHz clock speed or higher
20 MB of free hard drive space
Minimum screen resolution of 800x600 pixels
USB interface for CAN adaptor
The software can run on the following operating systems:
Windows 98 Second Edition; Windows 2000; Windows XP
In addition to the program CD, an installation guide and the interface module for
connecting to the PC's USB port are also provided.

50 VK_2052751GB Subject to technical modifications Status 09/2005


GEA Basic Geko Unit type code

Unit code Controller package Valve code


G B 1 1 . U 0 W 1 . A D 3 . 0 0 1 . B A V R 3 2 5 1 0 . B L

Size Controller type Function type


1 = Size 1 2 = MATRIX 2000 2-pipe/4-pipe
2 = Size 2 3 = MATRIX 3000 T = Thermoelectric (230 V, on/off)
3 = Size 3 R = Modulating actuator
Controller package no. (230 V, modulating)
4 = Size 4
5 = Size 5
Operator panel Water connection
Capacity stage IP20 2 = 2-port (cooling), 2-port (heating)
1 = Capacity stage 1 A = MATRIX OP21C 3 = 3-port (cooling), 3-port (heating)
2 = Capacity stage 2 B = MATRIX OP30C 8 = 2-port (cooling), 3-port (heating)
C = MATRIX OP31C 9 = 3-port (cooling), 2-port (heating)
Air-flow function
D = MATRIX OP44C
U = Recirculation air unit Circuit 1 (2-pipe cooling/heating, 4-pipe cooling)
E = MATRIX OP50C
F = MATRIX OP51C 06 = Kvs value 0.63 (R)
Medium-flow function 10 = Kvs value 1.0 (R)
IP54
Heating only 16 = Kvs value 1.6 (R)
G = MATRIX OP21I
0W = Warm water H = MATRIX OP30I 25 = Kvs value 2.5 (R, T)
Cooling only I = MATRIX OP31I
W0 = Chilled water Circuit 2 (4-pipe heating)
K = MATRIX OP44I
Cooling or heating L = MATRIX OP50I 06 = Kvs value 0.63 (R)
WC = Chilled water warm water M = MATRIX OP51I 10 = Kvs value 1.0 (R)
Cooling and heating 16 = Kvs value 1.6 (R)
N = MATRIX.IR
HW = Chilled water warm water Z = No operator panel 25 = Kvs value 2.5 (R, T)
WE = Chilled water - electric heating
Unit type Coil connection
Coil connection ** L = Left
Master unit, operating unit
Wall A = Included R = Right
1 = Left C = No operator panel
2 = Right Slave unit
Ceiling D = No operator panel
3 = Left
4 = Right

Fan speeds
Plastic terminal box with terminal block
A = Speed 1, 2, 3
Sheet-steel electric control box with terminal
strip or for integrated control
K = Speed 1, 2, 3

** Connection side from front with view of discharge

VK_2052751GB Subject to technical modifications Status 09/2005 51


GEA Basic Geko

Our Market in Europe

A GEA DK GEA Klimateknik ApS IS Rafn Jensson RUS GEA Kondicioner

VK_2052751GB Status 09/2005 Subject to modifications Copyright GEA Air Treatment


Klimatechnik GmbH DK-2400 Kbenhavn NV IS-110 Reykjavik Moskva
A-4673 Gaspoltshofen Tel. +45 / 38 / 887070 Tel. +354 / 56 / 780-30 RUS -105094 Moskva
Tel. +43 / 7735 / 8000-0 Tel. +7 / 095 / 9566674
E GEA Air Treatment L GEA Happel Luxembourg
B GEA Happel Belgium N.V. Marketing Services L-4940 Bascharage S GEA EXOS
B-1130 Brussels Int. GmbH - oficina Espaa Tel. +352 / 26 / 502970 Ventilation AB
Tel. +32 / 2 / 2406161 E-28036 Madrid S -74528 Enkping
Tel. +34 / 91 / 3837701 LT GEA Klimatechnik UAB Tel. +46 / 171 / 85530
BG EVISS Ltd. LT-01141 Vilnius
BG-7000 Rousse EST GEA Klimatechnik UAB Tel. +370 / 5 / 2106060 SCG GEA Klimatehnika
Tel. +359 / 82 / 81000 LT-01141 Vilnius SCG-11070 Novi Beograd
Tel. +370 / 5 / 2106060 LV GEA Klimatechnik UAB Tel. +381 / 11 / 3193955
BIH GEA Klimatehnika LT-01141 Vilnius
SCG-11070 Novi Beograd F GEA Happel France sarl Tel. +370 / 5 / 2106060 SK GEA Klimatizcia s.r.o.
Tel. +381 / 11 / 3193955 F-59436 Roncq Cedex SK-83104 Bratislava
Tel. +33 / 3 / 20689020 NL GEA Happel Tel. +421 / 7 / 44457917
BY GEA Klimatechnik UAB Nederland B.V.
LT-01141 Vilnius FIN OY TEKNOCALOR AB NL-2909 LL SLO GEA Klimatizacijska
Tel. +370 / 5 / 2106060 FIN-01300 Vantaa Capelle a/d Ijssel Tehnika d.o.o.
Tel. + 358 / 9 / 82546020 Tel. +31 / 10 / 2350606 SI-1000 Ljubljana
CH GEA Klimatec Tel. +386 / 1 / 2573850
Schweiz AG GB SAS Aircon Ltd. P Nnio, Lda.
CH-3065 Bolligen-Station GB-CO11QB Colchester P-1269-090 Lisboa TR ISISAN
Tel. +41 / 31 / 9171919 Tel. +44 / 1206 / 578 833 Tel. +351 / 21 / 3826160 TR-80700 Balmumcu
Istanbul
CZ GEA LVZ, a.s. H GEA Klimatechnika Kft PL GEA Tel. +90 / 212 / 2757171
CZ-46312 Liberec H-1037 Budapest Klimatyzacja Sp. z o.o.
Tel. +420 / 48 / 5225-111 Tel. +36 / 1 / 4393200 PL-54610 Wroclaw UA GEA Ukraina t.o.v.
GEA Klimatizace spol. s r.o. Tel. +48 / 71 / 3737952 UA-01135 Kyiv
CZ-46312 Liberec HR GEA Klima-rashladna Tel. +38 / 044 / 4619356
Tel. +420 / 48 / 5225-303 tehnika d.o.o. RO CORES Climatizare s.r.l.
HR-10000 Zagreb RO-1900 Timisoara
D GEA Happel Tel. +385 / 1 / 6064900 Tel. +40 / 256 / 490051
Klimatechnik GmbH Thermics s.r.l.
D-44625 Herne RO-7000 Bucuresti-sector 4
Tel. +49 / 2325 / 468-00 Tel. +40 / 21 / 4603496

Air Treatment Division For detailed information on all corporate areas, go


to www.gea-airtreatment.com or contact us by
A company of the GEA group email info@gea-airtreatment.com

52 VK_2052751GB Subject to technical modifications Status 09/2005

You might also like