PANEL MDP 25 16184.9711
SYSTEM Three Phase, 3 wire, 60hz, 230V 3500 70.36943956
LOCATION DPWH RO XIII
CONNECTED LOAD
CIRCUIT OVERCURRENT PROTECTION CONDUCTORS mm2, Cu-B/W CONDUIT mm2Ø
LOAD DESCRIPTION LIGHTING LUMINAIRES AMPERE LOAD GROUND WIRE mm2Ø, Cu-Green REMARKS
NO. #C.O. VOLT AMP
CFL T8(FL) LED TT FLC ØAB ØBC ØCA 3Ø AT AF P SIZE TYPE SIZE TYPE
C1 LP1 22 9 4 27 8 0 32450 100 100 2 30 THW/THWN/THHN 25 PVC-Sch40 1x5.5 TW
C2 UTM 28000 60 60 2 14 THW/THWN/THHN 25 PVC-Sch40 1x5.5 TW
C3 Pipe Tester 2200 30 60 2 8 THW/THWN/THHN 25 PVC-Sch40 1x5.5 TW
C4 ACU 8049 40 60 2 8 THW/THWN/THHN 25 PVC-Sch40 1x5.5 TW
C5
C6
TOTALS 22 9 4 27 8 70699 200 200 3 100 THW/THWN/THHN 40 PVC-Sch40 1x30TW
ITEM# COMPUTATIONS REMARKS MAIN: 200AT/200AF/3POLE
FEEDER SIZE PEC2009, Part 1. Vol. 1, Section2.10.2.1 a/b (Mandatory) Connected Load: 70699 VA
1 WIRE AMPACITY = ( 68x25% ) + ( 177.68 ) Amps Demand Factor: 80%
WIRE AMPACITY= 194.68 Amps Volts: 230
Therefore as per ampacity above use: PEC2009, Part 1. Vol. 1, Table B- 310-1 Main kAIC: 22.5kAIC
2
Three (3) wire - 100 mm2 THWN Cu. Wire + One (1) - 30 mm2 TW Cu. Wire Branch kAIC: 10kAIC
3 40 mm Dia Conduit PEC2009, Part 1. Vol. 1, Table C-10 Amperes: 194.68
OVERCURRENT PROTECTION COMPUTATION PEC2009, Part 1. Vol. 1, Section2.15.2.1 a/b (Mandatory) Three (3) wire - 100 mm2 THWN Cu. Wire + One (1) - 30 mm2 TW Cu. Wire
Feeder:
4 BREAKER AMPACITY = ( 68x250% ) + ( 109.68 ) Amps Flush
Mounting:
BREAKER AMPACITY= 211.68 Amps Enclosure: NEMA-1
TRANSFORMER
Total Load= 70699 VA
Demand Load= 80% Load Growth Rate= 120%
70699 VA x 0.8 x 1.2
5 =
80%
= 84838.8
Use 3 X 37.5 kVA Transformer, 230V, 60Hz