DEPARTMENT ENGINEERING & DESIGN

DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 1


CONTRACT NO : PLS150234-E PAGE 1 OF 12 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM

Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION SUMMARY

A.) 11kV Outgoing Feeder

Ratio Class Burden Vk Rct Imag (mA) Item Type Item Application
Core No.
(A) (VA) (V) (Ohm) @ ½ Vk
P1 Circuit Breaker

1 600/300/1 5P20 15VA - - - 7SR1103 OCEF

Ammeter
2 600/300/1 0.5 15VA - - - Instrument
Current Transducer
P2 Line

B.) 11kV Transformer Incomer

Ratio Class Burden Vk Rct Imag (mA) Item Type Item Application
Core No.
(A) (VA) (V) (Ohm) @ ½ Vk
P1 Circuit Breaker
≥ 420V@2100/1A 9.0@2100/1A mA@2100/1A 7UT613 Tx. Differential
1 2100/1500/1A X -
≥ 300V@1500/1A 6.5@1500/1A mA@1500/1A 5B3 REF

2 2100/1500/1A 5P20 15VA - - - 7SR1103 OCEF

Digital Power Meter


3 2100/1500/1A 0.5 15VA - - - Instrument
W/Var Transducer
P2 20/25MVA, 33/11kV Transformer

C.) 11kV NER

Ratio Class Burden Vk Rct Imag (mA) Item Type Item Application
Core No.
(A) (VA) (V) (Ohm) @ ½ Vk
P1 NS1
≥ 420V@2100/1A 9.0@2100/1A mA@2100/1A
1 2100/1500/1A X - 5B3 REF
≥ 300V@1500/1A 6.5@1500/1A mA@1500/1A
30VA@2100/1A
2 2100/1500/1A 5P20 - - - 7SJ600 SBEF
15VA@1500/1A

P2 20/25MVA, 33/11kV Transformer

D.) 11kV Bus Section

Ratio Class Burden Vk Rct Imag (mA) Item Type Item Application
Core No.
(A) (VA) (V) (Ohm) @ ½ Vk
P1 Circuit Breaker
Ammeter
1 2000/1A 0.5 15VA - - - Instrument
Current Transducer

2 2000/1A 5P20 15VA - - - 7SR1103 OCEF

P2 RHS Busbar

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 1
CONTRACT NO : PLS150234-E PAGE 2 OF 12 PAGES
PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved
LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
BAY NAME: 11kV OUTGOING FEEDER
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : OCEF


COP Relay Designation : 50/51
Relay Manufacturer : SIEMENS
Relay Model : 7SR1103
Core : 1
CT Ratio : 600/300/1A
Class : 5P20
VA : 15VA

For VA calculation purposes,the lead resistance is assumed for 4.0mm² cross section copper multicore conductor as following

Copper Copper Estimated


Voltage Multicore Multicore distance for One way lead
Level Conductor Conductor calculation resistance in
cross-section Resistance/KM purposes ohm

11KV 4.0mm² 4.61Ω/km 50m 0.2305Ω

the lead burden in VA is calculated as following :


P = Isn2 R
I = secondary current = 1A
R = 2 ways lead resistance = 2RL = 0.461 Ohm

Burden VA = I² X 0.461
= 0.461Ω

Total VA connected to current transformer :

Device Burden
i. Relay 7SR1103 0.10 VA
ii. Lead (based on 4.0sq mm & 50 m length) 0.461 VA

0.561 VA

VA required is less than 15VA.

Hence , CT proposed of 600/300/1A 15VA is sufficient.

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 1
CONTRACT NO : PLS150234-E PAGE 3 OF 12 PAGES
PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved
LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
BAY NAME: 11kV OUTGOING FEEDER
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : Instrument


COP Relay Designation :
Relay Manufacturer :
Relay Model :
Core : 2
CT Ratio : 600/300/1A
Class : 0.5
VA : 15VA

For VA calculation purposes,the lead resistance is assumed for 4.0mm² cross section copper multicore conductor as following

Copper Copper Estimated


Voltage Multicore Multicore distance for One way lead
Level Conductor Conductor calculation resistance in
cross-section Resistance/KM purposes ohm

11KV 4.0mm² 4.61Ω/km 50m 0.2305Ω

the lead burden in VA is calculated as following :


P = Isn2 R
I = secondary current = 1A
R = 2 ways lead resistance = 2RL = 0.461 Ohm

Burden VA = I² X 0.461
= 0.461Ω

Total VA connected to current transformer :

Device Burden
i. Ammeter GOSSEN MEQB96 2.600 VA
ii. Current Transducer TAIK S3-ASD-1 1.500 VA
ii. Lead (based on 4.0sq mm & 50 m length) 0.461 VA

4.561 VA

VA required is less than 15VA

Hence , CT proposed of 600/300/1A 15VA is sufficient.

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 1
CONTRACT NO : PLS150234-E PAGE 4 OF 12 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
BAY NAME: 11kV TRANSFORMER INCOMER
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : REF


COP Relay Designation : 64REF
Relay Manufacturer : SIEMENS
Relay Model : 5B3
Core : 1
CT Ratio : 2100/1500/1A
Class : X
VA : -

Since the CT is shared by REF and Transformer Differential relay, Siemens type 7UT613 and 5B3 respectively, the CT must
satisfy both the protection requirement:

A.) 7UT613 (Transformer Differential Protection)


To be calculated at 33kV side

B.) 5B3 (Restricted Earth Fault Protection)

1) Vstab = Ifs (RCT+2RL+Rr) ………………………………………(1)

Where Ifs = The CT secondary current corresponding to The maximum steady state through fault current
of the protected equipment.
2RL = The largest value of pilot-loop resistance between the CT and the relay, RL is based on the 50m of cable,
with 4.0mm2 cable core size
= 4.61 x '50 x 2 = 0.461
1000
RCT = The secondary winding resistance of The CT
= 9.0 Ohm @2100/1A and 6.5 Ohm @1500/1A
Vstab = The minimum voltage to ensure stability
Rr = burden of relay Connected in series, which is The transformer differential relay 7UT613
= 0.05VA (as refer to the Siemens Publication)

2) Ifs = 16 x transformer rating


( 3 x 11kV) ………………………………………(2)
Ifs = 16 x 25MVA
( 3 x 11kV)
=20994.56A

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 1
CONTRACT NO : PLS150234-E PAGE 5 OF 12 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
BAY NAME: 11kV TRANSFORMER INCOMER
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

for CT ratio 2100/1A


Secondary current wiil be,

Is = 20994.56A/2100
= 10 A

Vstab = Ifs (RCT+2RL+Rr)


= (10) (9.0+0.461+0.05)
= 95.11 V

For REF, the max voltage across the relay happens when max through fault current flows and 1 CT saturates.

The CT knee point voltage, Vk must be bigger than 2Vs to ensure positive operation.
Vk ≥ 2 Vs
≥ 2 x 95.11
≥ 190.22 V
Hence, Vk ≥ 190.22 V

for CT ratio 1500/1A


Secondary current will be,

Is = 20994.56/1500
= 14 A

Vstab = Ifs (RCT+2RL+Rr)


= (14) (6.5+0.461+0.05)
= 98.154 V

For REF, the max voltage across the relay happens when max through fault current flows and 1 CT saturates.

The CT knee point voltage, Vk must be bigger than 2Vs to ensure positive operation.
Vk ≥ 2 Vs
≥ 2 x 98.154
≥ 196.308 V
Hence, Vk ≥ 196.308 V

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 1
CONTRACT NO : PLS150234-E PAGE 6 OF 12 PAGES
PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved
LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
BAY NAME: 11kV TRANSFORMER INCOMER
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

Imag is calculated based on Sesco specification that sensitivity of REF should not exceed 25% of transformer rated current or 15%
of available current for an earth fault for resistance earth system, whichever is lower.
25% of Transformer rated current = 0.25 x 1312.16 = 328.04A

Available current with neutral resistor of 4Ω connected to Transformer Neutral is

11kV = 1587.7A
√3 x 4

15% of 1587.7A = 238.16A

We will take 238.16A since it is lower of the 2.

For 2100/1A,
Secondary current with CT connected to 2100/1A winding is = 238.16 = 0.11A
2100
(Imag x 4) + Is + Imet ≤ 0.11A Imag = CT magnetising current
Imet = Metrosil current
Imag ≤ 0.11- 0.02 - 0.01 = 0.01
4 Is = 0.02A
≤ 20mA @ Vs or ½ VK

For 1500/1A,
Secondary current with CT connected to 1500/1A winding is = 238.16 = 0.16A
1500
(Imag x 4) + Is + Imet ≤ 0.26A Imag = CT magnetising current
Imet = Metrosil current
Imag ≤ 0.16 - 0.02 - 0.01 = 0.01
4 Is = 0.02A
≤ 32.5mA @ Vs or ½ VK

Since VK requirement for Transformer Differential is higher, the CT specifications should be used. But I mag must still
apply to ensure sensitivity of REF is met.
Since SEB requires minimum Vkp of 300V,

Hence CT required is

At CT ratio 2100/1500/1A
CL.X
Vk ≥ 420V@2100/1A, Vk ≥ 300V@1500/1A
Rct ≤ 9.0Ω@2100/1A, Rct ≤ 6.5Ω@1500/1A
At half Vk, Imag ≤ 20mA @ 2100/1A or ≤ 29mA @1500/1A

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 1
CONTRACT NO : PLS150234-E PAGE 7 OF 12 PAGES
PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved
LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
BAY NAME: 11kV TRANSFORMER INCOMER
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : OCEF


COP Relay Designation : 50/51
Relay Manufacturer : SIEMENS
Relay Model : 7SR1103
Core : 2
CT Ratio : 2100/1500/1A
Class : 5P20
VA : 15VA

For VA calculation purposes,the lead resistance is assumed for 4.0mm² cross section copper multicore conductor as following

Copper Copper Estimated


Voltage Multicore Multicore distance for One way lead
Level Conductor Conductor calculation resistance in
cross-section Resistance/KM purposes ohm

11KV 4.0mm² 4.61Ω/km 50m 0.2305Ω

the lead burden in VA is calculated as following :


P = Isn2 R
I = secondary current = 1A
R = 2 ways lead resistance = 2RL = 0.461 Ohm

Burden VA = I² X 0.461
= 0.461Ω

Total VA connected to current transformer :

Device Burden
i. Relay 7SR1103 0.10 VA
ii. Lead (based on 4.0sq mm & 50 m length) 0.461 VA

0.561 VA

VA required is less than 15VA.

Hence , CT proposed of 2100/1500/1A 15VA is sufficient.

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 1
CONTRACT NO : PLS150234-E PAGE 8 OF 12 PAGES
PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved
LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
BAY NAME: 11kV TRANSFORMER INCOMER
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : Digital Power Meter + Instrument


COP Relay Designation :
Relay Manufacturer :
Relay Model :
Core : 3
CT Ratio : 2100/1500/1A
Class : 0.5
VA : 15VA

For VA calculation purposes,the lead resistance is assumed for 4.0mm² cross section copper multicore conductor as following

Copper Copper Estimated


Voltage Multicore Multicore distance for One way lead
Level Conductor Conductor calculation resistance in
cross-section Resistance/KM purposes ohm

11KV 4.0mm² 4.61Ω/km 50m 0.2305Ω

the lead burden in VA is calculated as following :


P = Isn2 R
I = secondary current = 1A
R = 2 ways lead resistance = 2RL = 0.461 Ohm

Burden VA = I² X 0.461
= 0.461Ω

Total VA connected to current transformer :

Device Burden
i. Digital Power Meter - SCHNEIDER ION 6200 0.050 VA
ii. Combine watt & var transducer - TAIK S3-WRD-3 0.100 VA
ii. Lead (based on 4.0sq mm & 50 m length) 0.461 VA

0.611 VA

VA required is less than 15VA

Hence , CT proposed of 2100/1500/1A 15VA is sufficient.

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 1
CONTRACT NO : PLS150234-E PAGE 9 OF 12 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA KPTEO HDTAN KJLIM
BAY NAME: 11kV NER
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : Restricted Earthfault Protection


COP Relay Designation : 64REF
Relay Manufacturer : Alstom
Relay Model : 5B3
Core : 1
CT Ratio : 2100/1500/1A
Class : X

Since the CT has to satisfy the relay SIEMENS 5B3 (Restricted Earth Fault) protection which located at the 11kV Transformer Incomer,
then the entire requirement will be the same.

Therefore proposed CT characteristic will be:

At CT ratio 2100/1A, Vk ≥ 420V@2100/1A


At CT ratio 1500/1A, Vk ≥ 300V@1500/1A
CL.X
30VA @ 2100/1A
15VA @ 1500/1A
Rct ≤ 9.0Ω@2100/1A, Rct ≤ 6.5Ω@1500/1A
At half Vk, Imag ≤ 20mA @ 2100/1A or ≤ 29mA @ 1500/1A

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO appr
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 1
CONTRACT NO : PLS150234-E PAGE 10 OF 12 PAGES
PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved
LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
BAY NAME: 33kV TRANSFORMER FEEDER
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : SBEF


COP Relay Designation : 64SBEF
Relay Manufacturer : SIEMENS
Relay Model : 7SJ600
Core : 2
CT Ratio : 2100/1500/1A
Class : 5P20
VA : 15VA

For VA calculation purposes,the lead resistance is assumed for 4.0mm² cross section copper multicore conductor as following

Copper Copper Estimated


Voltage Multicore Multicore distance for One way lead
Level Conductor Conductor calculation resistance in
cross-section Resistance/KM purposes ohm

11KV 4.0mm² 4.61Ω/km 50m 0.2305Ω

the lead burden in VA is calculated as following :


P = Isn2 R
I = secondary current = 1A
R = 2 ways lead resistance = 2RL = 0.461 Ohm

Burden VA = I² X 0.461
= 0.461Ω

Total VA connected to current transformer :

Device Burden
i. Relay 7SJ600 0.10 VA
ii. Lead (based on 4.0sq mm & 50 m length) 0.461 VA

0.561 VA

VA required is less than 15VA.

Hence , CT proposed of 2100/1500/1A 15VA is sufficient.

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 1
CONTRACT NO : PLS150234-E PAGE 11 OF 12 PAGES
1
PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved
LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
BAY NAME: BUS SECTION
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : Meter + Instrument


COP Relay Designation :
Relay Manufacturer :
Relay Model :
Core : 1
CT Ratio : 2000/1A
Class : 0.5
VA : 15VA

For VA calculation purposes,the lead resistance is assumed for 4mm² cross section copper multicore conductor as following

Copper Copper Estimated


Voltage Multicore Multicore distance for One way lead
Level Conductor Conductor calculation resistance in
cross-section Resistance/KM purposes ohm

11KV 4.0mm² 4.61Ω/km 50m 0.2305Ω

the lead burden in VA is calculated as following :


P = Isn2 R
I = secondary current = 1A
R = 2 ways lead resistance = 2RL = 0.461Ohm

Burden VA = I² X 0.461
= 0.461Ω

Total VA connected to current transformer :

Device Burden
i. Ammeter - GOSSEN MEQB96 2.6 VA
ii. Current transducer - TAIK S3-ASD-1 1.5 VA
iii. Lead (based on 4.0sq mm & 50 m length) 0.461 VA

4.561 VA

VA required is less than 15VA

Hence , CT proposed of 2000/1A 15VA is sufficient.

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 1
CONTRACT NO : PLS150234-E PAGE 12 OF 12 PAGES
PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved
LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
BAY NAME: BUS SECTION
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : OCEF


COP Relay Designation : 50/51
Relay Manufacturer : SIEMENS
Relay Model : 7SR1206
Core : 2
CT Ratio : 2000/1A
Class : 5P20
VA : 15VA

For VA calculation purposes,the lead resistance is assumed for 4mm² cross section copper multicore conductor as following

Copper Copper Estimated


Voltage Multicore Multicore distance for One way lead
Level Conductor Conductor calculation resistance in
cross-section Resistance/KM purposes ohm

11KV 4.0mm² 4.61Ω/km 50m 0.2305Ω

the lead burden in VA is calculated as following :


P = Isn2 R
I = secondary current = 1A
R = 2 ways lead resistance = 2RL = 0.461 Ohm

Burden VA = I² X 0.461
= 0.461Ω

Total VA connected to current transformer :

Device Burden
i. Relay 7SR1206 0.10 VA
ii. Lead (based on 4.0sq mm & 50 m length) 0.461 VA

0.561 VA

VA required is less than 15VA

Hence , CT proposed of 2000/1A 15VA is sufficient.

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001
REV NO : 2
CONTRACT NO : PLS150234-E PAGE 1 OF 15 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM

Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION - SUMMARY

A.) 33kV Transformer Feeder

Ratio Class Burden Vk Rct Imag (mA) Item Type Item Application
Core No.
(A) (VA) (V) (Ohm) @ ½ Vk
Circuit Breaker
≥ 300 @ 500/1A @500/1A mA@500/1A
1 700/500/1A X - 7UT613 Tx. Bias Differential
≥ 300 @ 700/1A @700/1A mA@700/1A

2 700/500/1A 5P20 10 - - - 7SR1103 OCEF

Digital Power Meter


3 700/500/1A 0.2 10 - - - Instrument
W/Var Transducer
20/25MVA, 33/11kV Transformer

B.) 33kV Line Feeder - With Current Differential (Kota 2 No.1, Kota 2 No.2, Pulau Salam No.1 and Pulau Salam No.2 Feeders)

Ratio Class Burden Vk Rct Imag (mA) Item Type Item Application
Core No.
(A) (VA) (V) (Ohm) @ ½ Vk
Circuit Breaker
≥ 300 @ 600/1A @600/1A mA@600/1A
1 1200/600/1A X - 7SD610 Current Differential
≥ 300 @1200/1A @1200/1A mA@1200/1A

2 1200/600/1A 5P20 15 - - - 7SR1206 DOCEF

Digital Power Meter


3 1200/600/1A 0.2 15 - - - Instrument
W/Var Transducer
Line

C.) 33kV Line Feeder - Without Current Differential (Spare Feeders)

Ratio Class Burden Vk Rct Imag (mA) Item Type Item Application
Core No.
(A) (VA) (V) (Ohm) @ ½ Vk
Circuit Breaker
≥ 300 @ 600/1A @600/1A mA@600/1A
1 1200/600/1A X - 7SD610 For Future
≥ 300 @1200/1A @1200/1A mA@1200/1A

2 1200/600/1A 5P20 15 - - - 7SR1206 DOCEF

Digital Power Meter


3 1200/600/1A 0.2 15 - - - Instrument
W/Var Transducer
Line

D.) 33kV Bus Section

Ratio Class Burden Vk Rct Imag (mA) Item Type Item Application
Core No.
(A) (VA) (V) (Ohm) @ ½ Vk
Circuit Breaker
Ammeter
1 2000/1A 0.2 15 - - - Instrument
Current Transducer

2 2000/1A 5P20 15 - - - 7SR1103 OCEF

Isolator

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 2
CONTRACT NO : PLS150234-E PAGE 2 OF 15 PAGES
PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved
LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
33kV TRANSFORMER FEEDER
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : Transformer Differential Protection


COP Relay Designation : 87T
Relay Manufacturer : SIEMENS
Relay Model : 7UT613
Core : 1
CT Ratio : 700/500/1A
Class : X
Vk : 300V@ 500/1A
Rct : 2.8Ω @700/1A, 2.0Ω @500/1A
Imag : ≤40mA @ ½Vk @ 500/1A

A.) 7UT613 (Transformer Differential Protection)

CT requirement as per the attached pg 2/52 & 2/53 Siemens SIP - 2008 publication is as follows:-

1) Accuracy limiting factor formula from pg 2/53:-


K'ssc = ISCC.max.(external fault) x Ktd
IN
where,
ISCC.max. = maximum short circuit current
IN = nominal primary CT current
K'ssc = operating
effective symmetrical
CT accuracyshort
limiting
circuit
factor
current factor
Ktd = transient dimensioning factor = 1.2 for line feeder

2) Knee-point voltage formula from pg 2/53:-


Vk ≥ (Rb + Rct) x ISN x K'ssc
1.3
where,
Rb = connected resistive burden
Rct = internal CT resistance
ISN = nominal (rated) secondary current = 1A
K'ssc = effective symmetrical short circuit current factor

CALCULATION
At 700/1A,
Isccmax (ext fault) will be taken as 16 times transformer rating current of 25MVA = 437.39A
3 x 33kV

Then
K'ssc = 437.39A x 3
700
= 1.875

Rb = connected burden
= lead burden + relay burden
= RL + Rr
Rr = 0.05Ω

RL = Total lead impedance (for cable size of 4.0sqmm & length of 50m(loop))
= 4.61 x 50 x 2
1000
= 0.461Ω

Rb = 0.461Ω + 0.05Ω
= 0.511Ω

Rct = 2.8 Ω (Assume 0.4Ω per 100 turns)

Vk ≥ (0.511 + 2.8) x 1 x 1.875 x 16


1.3

≥ 76.4V

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 2
CONTRACT NO : PLS150234-E PAGE 3 OF 15 PAGES
PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved
LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
33kV TRANSFORMER FEEDER
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : Transformer Differential Protection


COP Relay Designation : 87T
Relay Manufacturer : SIEMENS
Relay Model : 7UT613
Core : 1
CT Ratio : 700/500/1A
Class : X
Vk : 300V @500/1A
Rct : 2.8Ω @700/1A, 2.0Ω @500/1A
Imag : ≤40mA @ ½Vk @ 500/1A

CALCULATION
At 500/1A,
Isccmax (ext fault) will be taken as 16 times transformer rating current of 25MVA = 437.39A
3 x 33kV

Then
K'ssc = 437.39A x 3
500
= 2.62

Rb = connected burden
= lead burden + relay burden
= RL + Rr
Rr = 0.05Ω

RL = Total lead impedance (for cable size of 4.0sqmm & length of 50m(loop))
= 4.61 x 50 x 2
1000
= 0.461Ω

Rb = 0.461Ω + 0.05Ω
= 0.511Ω

Rct = 2.0 Ω (Assume 0.4Ω per 100 turns)

Vk ≥ (0.511 + 2.0) x 1 x 2.62 x 16


1.3

≥ 80.97V

As per SESCO requirement, Vk ≥ 300V


Proposed CT selection:

Item Calculate Value Selected Value


CT ratio 700/500/1A 700/500/1A
Class X X
≥76.4V@500/1A ≥300V@500/1A
Vk
≥80.97V@700/1A ≥300V@700/1A
Rct ≤2.8/2.0Ω ≤2.8/2.0Ω
Imag ≤40mA @ 1/2 Vk ≤40mA @ 1/2 Vk

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 2
CONTRACT NO : PLS150234-E PAGE 4 OF 15 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
33kV TRANSFORMER FEEDER
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : OCEF


COP Relay Designation : 50/51
Relay Manufacturer : SIEMENS
Relay Model : 7SR1103
Core : 2
CT Ratio : 700/500/1A
Class : 5P20
VA : 10VA

For VA calculation purposes,the lead resistance is assumed for 4.0mm² cross section copper multicore conductor as following

Copper Copper Estimated


Voltage Multicore Multicore distance for One way lead
Level Conductor Conductor calculation resistance in
cross-section Resistance/KM purposes ohm

33KV 4.0mm² 4.61Ω/km 50m 0.2305Ω

the lead burden in VA is calculated as following :


P = Isn2 R
I = secondary current = 1A
R = 2 ways lead resistance = 2RL = 0.461 Ohm

Burden VA = I² X 0.461
= 0.461Ω

Total VA connected to current transformer :

Device Burden
i. Relay 7SR1103 0.10 VA
ii. Lead (based on 4.0sq mm & 50 m length) 0.461 VA

0.561 VA

VA required is less than 10VA.

Hence , CT proposed of 700/500/1A 10VA is sufficient.

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 2
CONTRACT NO : PLS150234-E PAGE 5 OF 15 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
33kV TRANSFORMER FEEDER
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : Digital Power Meter + Instrument


COP Relay Designation :
Relay Manufacturer :
Relay Model :
Core : 3
CT Ratio : 700/500/1A
Class : 0.2
VA : 10VA

For VA calculation purposes,the lead resistance is assumed for 4.0mm² cross section copper multicore conductor as following

Copper Copper Estimated


Voltage Multicore Multicore distance for One way lead
Level Conductor Conductor calculation resistance in
cross-section Resistance/KM purposes ohm

33KV 4.0mm² 4.61Ω/km 50m 0.2305Ω

the lead burden in VA is calculated as following :


P = Isn2 R
I = secondary current = 1A
R = 2 ways lead resistance = 2RL = 0.461 Ohm

Burden VA = I² X 0.461
= 0.461Ω

Total VA connected to current transformer :

Device Burden
i. Digital Power Meter - SCHNEIDER ION 6200 0.050 VA
ii. Combine watt & var transducer - TAIK S3-WRD-3 0.100 VA
ii. Lead (based on 4.0sq mm & 50 m length) 0.461 VA

0.611 VA

VA required is less than 10VA

Hence , CT proposed of 700/500/1A 10VA is sufficient.

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 2
CONTRACT NO : PLS150234-E PAGE 6 OF 15 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
33kV FEEDER (Kota 2 and Pulau Salam Feeders)
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : Current Differential Protection


COP Relay Designation : 87CD
Relay Manufacturer : SIEMENS
Relay Model : 7SD610
Core : 1
CT Ratio : 1200/600/1A
Class : X

CT requirement as per the attached pg 2/52 & 2/53 Siemens SIP - 2008 publication is as follows:-
1) Accuracy limiting factor formula from pg 2/53:-
K'ssc = ISCC.max.(external fault) x Ktd & Kssc ≥ 20 ………………(1)
IN
where,
ISCC.max.(esternal fault) = maximum short circuit current for external fault
IN = nominal primary CT current
K'ssc = operating CT accuracy limiting factor
Ktd = transient dimensioning factor = 1.2 for line feeder
Kssc = rated CT accuracy limiting factor

2) Knee-point voltage formula from pg 2/53:- ………………………………………(2)


Vk ≥ (Rb + Rct) x ISN x Kssc'
1.3
where,
R b' = connected CT burden
Rct = internal CT resistance
ISN = nominal (rated) secondary current = 1A
Kssc' = operating CT accuracy limiting factor

Assuming cable of 630sqmm Cu of length = 5km, cable impedance = 0.54 Ohm


Source Impedance = 33kV = 0.6 Ohm
√3 x 31.5KA
External through fault current = 33kV = 16.7kA
√3 x (0.6+0.54)
Then
K'ssc = 16.7kA/1200 x1.2 = 16.7 @ 1200/1A
K'ssc = 16.7kA/600 x1.2 = 33.4 @ 600/1A

To meet requirement on equation (1), we select K'ssc = 16.7 for 1200/1A


For equation (2)

R'b = connected burden


= lead burden + relay burden
= RL + Rr
= [2 x ( lc x r)] + 0.1
A
=[2 x (50 x 4.61)/1000] +0.1
=0.561 ohm
Rct = Internal CT burden
= 4.8 Ohm @1200/1A

To meet requirement on equation (1), we select K'ssc = 33.4 for 600/1A


For equation (2)
R'b = connected burden
= lead burden + relay burden
= RL + Rr
= [2 x ( lc x r)] + 0.1
A
=[2 x (50 x 4.61)/1000] +0.1
=0.561 ohm
Rct = Internal CT burden
= 2.4 Ohm @600/1A

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 2
CONTRACT NO : PLS150234-E PAGE 7 OF 15 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
33kV FEEDER (Kota 2 and Pulau Salam Feeders)
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CALCULATION

From equation (2)

Vk ≥ (R'b + Rct) x ISN x K'ssc


1.3
≥ (0.561+4.8) x 1 x 16.7
1.3
≥ 68.9 V @1200/1A

CT requirement shall be 1200/1A, CL.PX, Vk ≥ 68.9V, Rct Ω, ImagmA at 1/2Vk @1200/1A

From equation (2)

Vk ≥ (R'b + Rct) x ISN x K'ssc


1.3
≥ (0.561+2.4) x 1 x 33.4
1.3
≥ 76.1 V @600/1A

CT requirement shall be 600/1A, CL.PX, Vk ≥ 75.6V, Rct Ω, ImagmA at 1/2Vk @600/1A
Since 600/1A CT requirement is more stringent, the CT specification shall be based of requirement at ratio 600/1A.
From the calculation, the minimum Vk for each ratio is summarized as below.

Turns Ratio Vk (V) Rct Imag at 1/2Vk


1200/1A ≥ 68.9 ≤4.8Ω ≤40mA
600/1A ≥ 76.1 ≤2.4Ω ≤40mA

Since SESCO requires minimum Vkp of 300V,


Hence CT required is

1200/600/1A, CL.X,
Vk≥300V@600/1A, Rct≤2.4Ω@600/1A,
Vk≥300V@1200/1A, Rct≤4.8Ω@1200/1A,
At half Vk, Imag≤40mA@600/1A or Imag≤40mA@1200/1A

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 2
CONTRACT NO : PLS150234-E PAGE 8 OF 15 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
33kV FEEDER (Kota 2 and Pulau Salam Feeders)
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : DOCEF


COP Relay Designation : 67/67N
Relay Manufacturer : SIEMENS
Relay Model : 7SR1206
Core : 2
CT Ratio : 1200/600/1A
Class : 5P20
VA : 15VA

For VA calculation purposes,the lead resistance is assumed for 4.0mm² cross section copper multicore conductor as following

Copper Copper Estimated


Voltage Multicore Multicore distance for One way lead
Level Conductor Conductor calculation resistance in
cross-section Resistance/KM purposes ohm

33KV 4.0mm² 4.61Ω/km 50m 0.2305Ω

the lead burden in VA is calculated as following :


P = Isn2 R
I = secondary current = 1A
R = 2 ways lead resistance = 2RL = 0.461 Ohm

Burden VA = I² X 0.461
= 0.461Ω

Total VA connected to current transformer :

Device Burden
i. Relay 7SR1206 0.10 VA
ii. Lead (based on 4.0sq mm & 50 m length) 0.461 VA

0.561 VA

VA required is less than 15VA

Hence , CT proposed of 1200/600/1A 15VA is sufficient.

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 2
CONTRACT NO : PLS150234-E PAGE 9 OF 15 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
33kV FEEDER (Kota 2 and Pulau Salam Feeders)
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : Digital Power Meter + Instrument


COP Relay Designation :
Relay Manufacturer :
Relay Model :
Core : 3
CT Ratio : 1200/600/1A
Class : 0.2
VA : 15VA

For VA calculation purposes,the lead resistance is assumed for 4.0mm² cross section copper multicore conductor as following

Copper Copper Estimated


Voltage Multicore Multicore distance for One way lead
Level Conductor Conductor calculation resistance in
cross-section Resistance/KM purposes ohm

33KV 4.0mm² 4.61Ω/km 50m 0.2305Ω

the lead burden in VA is calculated as following :


P = Isn2 R
I = secondary current = 1A
R = 2 ways lead resistance = 2RL = 0.461 Ohm

Burden VA = I² X 0.461
= 0.461Ω

Total VA connected to current transformer :

Device Burden
i. Digital Power Meter - SCHNEIDER ION 6200 0.050 VA
ii. Combine watt & var transducer - TAIK S3-WRD-3 0.10 VA
iii. Lead (based on 4.0sq mm & 50 m length) 0.461 VA

0.611 VA

VA required is less than 15VA

Hence , CT proposed of 1200/600/1A 15VA is sufficient.

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 2
CONTRACT NO : PLS150234-E PAGE 10 OF 15 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
33kV FEEDER (Spare Feeders)
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : Current Differential Protection


COP Relay Designation : 87CD
Relay Manufacturer : SIEMENS (Assumption)
Relay Model : 7SD610 (Assumption)
Core : 1
CT Ratio : 1200/600/1A
Class : X

CT requirement as per the attached pg 2/52 & 2/53 Siemens SIP - 2008 publication is as follows:-
1) Accuracy limiting factor formula from pg 2/53:-
K'ssc = ISCC.max.(external fault) x Ktd & Kssc ≥ 20 ………………(1)
IN
where,
ISCC.max.(esternal fault) = maximum short circuit current for external fault
IN = nominal primary CT current
K'ssc = operating CT accuracy limiting factor
Ktd = transient dimensioning factor = 1.2 for line feeder
Kssc = rated CT accuracy limiting factor

2) Knee-point voltage formula from pg 2/53:- ………………………………………(2)


Vk ≥ (Rb + Rct) x ISN x Kssc'
1.3
where,
R b' = connected CT burden
Rct = internal CT resistance
ISN = nominal (rated) secondary current = 1A
Kssc' = operating CT accuracy limiting factor

Assuming cable of 630sqmm Cu of length = 5km, cable impedance = 0.54 Ohm


Source Impedance = 33kV = 0.6 Ohm
√3 x 31.5KA
External through fault current = 33kV = 16.7kA
√3 x (0.6+0.54)
Then
K'ssc = 16.7kA/1200 x1.2 = 16.7 @ 1200/1A
K'ssc = 16.7kA/600 x1.2 = 33.4 @ 600/1A

To meet requirement on equation (1), we select K'ssc = 16.7 for 1200/1A


For equation (2)

R'b = connected burden


= lead burden + relay burden
= RL + Rr
= [2 x ( lc x r)] + 0.1
A
=[2 x (50 x 4.61)/1000] +0.1
=0.561 ohm
Rct = Internal CT burden
= 4.8 Ohm @1200/1A

To meet requirement on equation (1), we select K'ssc = 33.4 for 600/1A


For equation (2)
R'b = connected burden
= lead burden + relay burden
= RL + Rr
= [2 x ( lc x r)] + 0.1
A
=[2 x (50 x 4.61)/1000] +0.1
=0.561 ohm
Rct = Internal CT burden
= 2.4 Ohm @600/1A

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 2
CONTRACT NO : PLS150234-E PAGE 11 OF 15 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
33kV FEEDER (Spare Feeders)
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CALCULATION

From equation (2)

Vk ≥ (R'b + Rct) x ISN x K'ssc


1.3
≥ (0.561+4.8) x 1 x 16.7
1.3
≥ 68.9 V @1200/1A

CT requirement shall be 1200/1A, CL.PX, Vk ≥ 68.9V, Rct Ω, ImagmA at 1/2Vk @1200/1A

From equation (2)

Vk ≥ (R'b + Rct) x ISN x K'ssc


1.3
≥ (0.561+2.4) x 1 x 33.4
1.3
≥ 76.1 V @600/1A

CT requirement shall be 600/1A, CL.PX, Vk ≥ 75.6V, Rct Ω, ImagmA at 1/2Vk @600/1A
Since 600/1A CT requirement is more stringent, the CT specification shall be based of requirement at ratio 600/1A.
From the calculation, the minimum Vk for each ratio is summarized as below.

Turns Ratio Vk (V) Rct Imag at 1/2Vk


1200/1A ≥ 68.9 ≤4.8Ω ≤40mA
600/1A ≥ 76.1 ≤2.4Ω ≤40mA

Since SESCO requires minimum Vkp of 300V,


Hence CT required is

1200/600/1A, CL.X,
Vk≥300V@600/1A, Rct≤2.4Ω@600/1A,
Vk≥300V@1200/1A, Rct≤4.8Ω@1200/1A,
At half Vk, Imag≤40mA@600/1A or Imag≤40mA@1200/1A

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 2
CONTRACT NO : PLS150234-E PAGE 12 OF 15 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
33kV FEEDER (Spare Feeders)
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : DOCEF


COP Relay Designation : 67/67N
Relay Manufacturer : SIEMENS
Relay Model : 7SR1206
Core : 2
CT Ratio : 1200/600/1A
Class : 5P20
VA : 15VA

For VA calculation purposes,the lead resistance is assumed for 4.0mm² cross section copper multicore conductor as following

Copper Copper Estimated


Voltage Multicore Multicore distance for One way lead
Level Conductor Conductor calculation resistance in
cross-section Resistance/KM purposes ohm

33KV 4.0mm² 4.61Ω/km 50m 0.2305Ω

the lead burden in VA is calculated as following :


P = Isn2 R
I = secondary current = 1A
R = 2 ways lead resistance = 2RL = 0.461 Ohm

Burden VA = I² X 0.461
= 0.461Ω

Total VA connected to current transformer :

Device Burden
i. Relay 7SR1206 0.10 VA
ii. Lead (based on 4.0sq mm & 50 m length) 0.461 VA

0.561 VA

VA required is less than 15VA

Hence , CT proposed of 1200/600/1A 15VA is sufficient.

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 2
CONTRACT NO : PLS150234-E PAGE 13 OF 15 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
33kV FEEDER (Spare Feeders)
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : Digital Power Meter + Instrument


COP Relay Designation :
Relay Manufacturer :
Relay Model :
Core : 3
CT Ratio : 1200/600/1A
Class : 0.2
VA : 15VA

For VA calculation purposes,the lead resistance is assumed for 4.0mm² cross section copper multicore conductor as following

Copper Copper Estimated


Voltage Multicore Multicore distance for One way lead
Level Conductor Conductor calculation resistance in
cross-section Resistance/KM purposes ohm

33KV 4.0mm² 4.61Ω/km 50m 0.2305Ω

the lead burden in VA is calculated as following :


P = Isn2 R
I = secondary current = 1A
R = 2 ways lead resistance = 2RL = 0.461 Ohm

Burden VA = I² X 0.461
= 0.461Ω

Total VA connected to current transformer :

Device Burden
i. Digital Power Meter - SCHNEIDER ION 6200 0.050 VA
ii. Combine watt & var transducer - TAIK S3-WRD-3 0.10 VA
iii. Lead (based on 4.0sq mm & 50 m length) 0.461 VA

0.611 VA

VA required is less than 15VA

Hence , CT proposed of 1200/600/1A 15VA is sufficient.

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 2
CONTRACT NO : PLS150234-E PAGE 14 OF 15 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
BAY NAME: BUS SECTION
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : Meter + Instrument


COP Relay Designation :
Relay Manufacturer :
Relay Model :
Core : 1
CT Ratio : 2000/1A
Class : 0.2
VA : 15VA

For VA calculation purposes,the lead resistance is assumed for 4mm² cross section copper multicore conductor as following

Copper Copper Estimated


Voltage Multicore Multicore distance for One way lead
Level Conductor Conductor calculation resistance in
cross-section Resistance/KM purposes ohm

33KV 4.0mm² 4.61Ω/km 50m 0.2305Ω

the lead burden in VA is calculated as following :


P = Isn2 R
I = secondary current = 1A
R = 2 ways lead resistance = 2RL = 0.461Ohm

Burden VA = I² X 0.461
= 0.461Ω

Total VA connected to current transformer :

Device Burden
i. Ammeter - GOSSEN MEQB96 2.6 VA
ii. Current transducer - TAIK S3-ASD-1 1.5 VA
iii. Lead (based on 4.0sq mm & 50 m length) 0.461 VA

4.561 VA

VA required is less than 15VA

Hence , CT proposed of 2000/1A 15VA is sufficient.

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-LGS-E-CAL-CT-0001 REV NO : 2
CONTRACT NO : PLS150234-E PAGE 15 OF 15 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS.
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
BUS SECTION
Date: 24.11.16 Date: 24.11.16 Date: 24.11.16 Date: 24.11.16

CURRENT TRANSFORMER CALCULATION

CT Core Duty : OCEF


COP Relay Designation : 50/51
Relay Manufacturer : SIEMENS
Relay Model : 7SR1103
Core : 2
CT Ratio : 2000/1A
Class : 5P20
VA : 15VA

For VA calculation purposes,the lead resistance is assumed for 4mm² cross section copper multicore conductor as following

Copper Copper Estimated


Voltage Multicore Multicore distance for One way lead
Level Conductor Conductor calculation resistance in
cross-section Resistance/KM purposes ohm

33KV 4.0mm² 4.61Ω/km 50m 0.2305Ω

the lead burden in VA is calculated as following :


P = Isn2 R
I = secondary current = 1A
R = 2 ways lead resistance = 2RL = 0.461 Ohm

Burden VA = I² X 0.461
= 0.461Ω

Total VA connected to current transformer :

Device Burden
i. Relay 7SR1103 0.10 VA
ii. Lead (based on 4.0sq mm & 50 m length) 0.461 VA

0.561 VA

VA required is less than 15VA

Hence , CT proposed of 2000/1A 15VA is sufficient.

*NOTE: All the CT ratio are given by SESCO during tendering stage. However, it may different subjected to SESCO approval.
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-SAP-E-CAL-VT-0001 REV NO : 1
CONTRACT NO : PLS150234-E PAGE 1 OF 6 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM

Date: 14.09.16 Date: 14.09.16 Date: 14.09.16 Date: 14.09.16

VOLTAGE TRANSFORMER CALCULATION SUMMARY

a) 33kV Cable Feeder

Winding No. Ratio Class Burden Item Type Item Application


1 33kV : 110V 0.5 40 Multifunction Power Meter Instrument & Synchronising
√3 √3 Synchronising circuit
Watt/Var Transducer
2 33kV : 110V 3P 35 Directional Overcurrent Protection
√3 √3 Earth Fault Relay

b) 33/11kV Transformer Feeder

Winding No. Ratio Class Burden Item Type Item Application


1 33kV : 110V 0.5 50 Multifunction Power Meter Instrument
√3 √3 Watt/Var Transducer

c) 33kV Bus VT

Winding No. Ratio Class Burden Item Type Item Application


1 33kV : 110V 0.5 50 Voltmeter Instrument & Protection
√3 √3 Voltage Transducer
Synhcronising Circuit
Under Frequency Relay

d) 11kV Transformer Incomer

Winding No. Ratio Class Burden Item Type Item Application


1 11kV : 110V 0.5 100 Multifunction Power Meter Instrument
√3 √3 Watt/Var Transducer

e) 11kV Bus VT

Winding No. Ratio Class Burden Item Type Item Application


1 11kV : 110V 0.5 100 Voltmeter Instrument & Protection
√3 √3 Voltage Transducer
Under Frequency Relay
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-SAP-E-CAL-VT-0001 REV NO : A
CONTRACT NO : PLS150234-E PAGE 2 OF 6 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
33kV CABLE FEEDER
Date: 14.09.16 Date: 14.09.16 Date: 14.09.16 Date: 14.09.16

VOLTAGE TRANSFORMER CALCULATION

VT Core Duty : Instrument + Protection Relays


VT Ratio : 33kV : 110kV : 110kV
√3 √3 √3
Class : 0.5/3P
VA : 40VA/35VA

CL 0.5 Winding

Total VA connected to voltage transformer:

Device Burden (VA)


i. Multifunction Power Meter SCHNEIDER ELECTRIC ION6200 0.05 VA
ii. Combined KW/KVAR transducer TAIK S3-WRD-3 0.2 VA
iii. Synchronising circuit 10 VA

Total 10.25 VA

CL 3P Winding

Total VA connected to voltage transformer:

Device Burden (VA)


i. Directional overcurrent earth fault relay (7SJ622) 0.1 VA
VA
VA
Total 0.1 VA

VA's required for CL0.5 and CL 3P Winding are 10.25VA and 0.1VA respectively.

Hence 40VA for CL.0.5 winding and 35VA for CL.3P winding is more than sufficient
DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-SAP-E-CAL-VT-0001 REV NO : A
CONTRACT NO : PLS150234-E PAGE 3 OF 6 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
33/11kV TRANSFORMER FEEDER
Date: 14.09.16 Date: 14.09.16 Date: 14.09.16 Date: 14.09.16

VOLTAGE TRANSFORMER CALCULATION

VT Core Duty : Instrument


VT Ratio : 33kV : 110kV
√3 √3
Class : 0.5
VA : 50VA

CL 0.5 Winding

Total VA connected to voltage transformer:

Device Burden (VA)


i. Multifunction Power Meter SCHNEIDER ELECTRIC ION6200 0.05 VA
ii. Combined KW/KVAR transducer TAIK S3-WRD-3 0.2 VA

Total 0.25 VA

VA's required for CL0.5 Winding is 0.25VA respectively.

Hence 50VA per winding is more than sufficient.


DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-SAP-E-CAL-VT-0001 REV NO : A
CONTRACT NO : PLS150234-E PAGE 4 OF 6 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
33kV BUS VT
Date: 14.09.16 Date: 14.09.16 Date: 14.09.16 Date: 14.09.16

VOLTAGE TRANSFORMER CALCULATION

VT Core Duty : Instrument


VT Ratio : 33kV : 110kV
√3 √3
Class : 0.5
VA : 50VA

CL 0.5 Winding

Total VA connected to voltage transformer:

Device Burden (VA)


i. Voltmeter GOSSEN 2.5 VA
ii. Voltage Transducer TAIK S3-VSD 1.5 VA
iii. Synchronising circuit 10 VA
iv. Underfrequency Relay SEL751-A 0.1 VA

Total 14.1 VA

VA's required for CL0.5 Winding is 14.1VA respectively.

Hence 50VA per winding is more than sufficient.


DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-SAP-E-CAL-VT-0001 REV NO : 1
CONTRACT NO : PLS150234-E PAGE 5 OF 6 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
11kV TRANSFORMER INCOMER
Date: 14.09.16 Date: 14.09.16 Date: 14.09.16 Date: 14.09.16

VOLTAGE TRANSFORMER CALCULATION

VT Core Duty : Instrument


VT Ratio : 11kV : 110kV
√3 √3
Class : 0.5
VA : 100VA

CL 0.5 Winding

Total VA connected to voltage transformer:

Device Burden (VA)


i. Multifunction Power Meter SCHNEIDER ELECTRIC ION6200 0.05 VA
ii. Combined KW/KVAR transducer TAIK S3-WRD-3 0.2 VA

Total 0.25 VA

VA's required for CL0.5 Winding are 0.25VA respectively.

Hence 100VA per winding is more than sufficient.


DEPARTMENT ENGINEERING & DESIGN
DOCUMENT PLS150234-SAP-E-CAL-VT-0001 REV NO : 1
CONTRACT NO : PLS150234-E PAGE 6 OF 6 PAGES

PROJECT: SUPPLY, ERECTION AND COMMISSIONING OF Prepared Checked Verified Approved


LOAGAN SALAM 33/11kV SUBSTATION, LAWAS
SUBSTATION: 33/11kV LOAGAN SALAM SUBSTATION LIYANA K.P.TEO H.D.TAN K.J.LIM
11kV BUS VT
Date: 14.09.16 Date: 14.09.16 Date: 14.09.16 Date: 14.09.16

VOLTAGE TRANSFORMER CALCULATION

VT Core Duty : Instrument+Protection


VT Ratio : 11kV : 110kV
√3 √3
Class : 0.5
VA : 100VA

CL0.5

Total VA connected to voltage transformer:

Device Burden (VA)


i. Voltmeter GOSSEN 2.5 VA
ii. Voltage Transducer TAIK-S3-VSD 1.5 VA
iii. Underfrequency Relay SEL751-A 0.1 VA

Total 4.1 VA

VA's required for CL0.5 Winding are 4.1VA.

Hence 100VA per winding is more than sufficient.