PI value less than 1 indicates the immediate need of reconditioning. Log sheet of drying
out of an induction motor:
1)Technical particulars of machine Rated voltage, rated frequency Rated KW, full load
current Connection diagram, number of windings
2)Technical particulars about connections for drying out 3)Check prior to starting the
drying
4)Ambient temperature
5)Initial values of insulation resistance 6)Time of start, date, hours
It is used primarily to detect low resistance paths to ground or between windings that result
from carbonization,deterioration, or the presence of moisture.
It will not indicate the actual quality of the insulation, but when conducted under controlled
conditions,
with the data compiled for a number of service intervals, trending data can be developed, and
definite conclusions can be drawn as to the insulation’s rate of deterioration.
(a) High and medium voltage insulation systems are usually designed to withstand large
potentials and large quantities of electricity. Because of this, special equipment must be used
to perform resistance tests. Ohm’s Law applies for all systems, and no matter how
high the applied voltage, or how “resistance” the insulating material, there will be a
measurable leakage current, and there will be a resultant resistance value.
Because of these conditions, leakage currents are usually stated in micro-amps (one millionth
of an amp) and resistance values in megohms (one million Ohms).Most hand-held meters are
not capable of reading these extremes accurately, and special equipment is used. Even if a
unit can read these extremes accurately, it must also be able to supply the necessary
quantities of electricity to charge the massive conductors and contacts found in a
transformer.
(b) An insulation resistance test is usually performed with a megger, an instrument that is not
only capable of reading high resistance values, but is also able to produce the necessary
currents and voltages to obtain the readings. Megger test potentials are usually applied at
500, 1,000, 2,500, and 5,000 volts DC.
(c)The following conditions should be observed when performing an insulation resistance
test:
Make sure that both the tank and core iron are solidly grounded.
Disconnect any systems that may be connected to the transformer winding, including high
and low voltage and neutral connections, lightning arrestors, fan systems, meters, and
potential transformers.
Potential transformers are often located on the lie sides of breakels or disconnects; when
the disconnect is opened, there will still be a path available to ground. Short circuit all
high and low voltage windings together at the bushings connections; jumpers should be
installed to ground, and no winding should be left floating.
The ground connection on grounded windings must be removed. If the ground cannot be
conveniently removed, the test cannot be performed on that winding. Such a winding must
be treated as part of the grounded circuit.
(a) The winding resistance can be measured with a low resistance ohmmeter, or with a
Kelvin bridge. Be sure to make good contact with the winding leads, and to wait 3 minutes
after initial contact before taking a reading. This delay is necessary due to the induction
created by the transformer windings. Because the windings will store energy, it is important
to shut off the test set and allow the energy to dissipate before removing the test leads.
(b) If the factory test values are available, or ifthe transformer cannot be disconnected, the
resistancevalues for each winding should be compared to thoseof the adjacent windings. A
difference of one percentindicates a potential problem.
(3) Contact resistance. Loose connections canresult in overheating and possible equipment,
failure.All high and low voltage and ground connections should be inspected, and if any
abnormal conditions are noted, the contact resistance should be measured to ensure that solid
contact is being made. This testingworks especially well in conjunction with infrared
scanning. If a connection shows hot on the IR scan, andits contact resistance cannot be
lowered by tightening,it should be replaced.