You are on page 1of 8

Smart Grid and Renewable Energy, 2011, 2, 359-366 359

doi:10.4236/sgre.2011.24041 Published Online November 2011 (http://www.SciRP.org/journal/sgre)

Online One-End Fault Location Algorithm for


Parallel Transmission Lines
Wanjing Xiu, Yuan Liao
Department of Electrical and Computer Engineering, University of Kentucky, Lexington, USA.
Email: yliao@engr.uky.edu

Received September 7th, 2011; revised October 10th, 2011; accepted October 18th, 2011.

ABSTRACT
Fault location and distance protection are essential smart grid technologies ensuring reliability of the power system.
This paper describes an accurate algorithm for locating faults on double-circuit transmission lines. The proposed ap-
proach is capable of identifying the faulted circuit of a parallel transmission line by checking the estimated fault loca-
tion and fault resistance. Voltage and current measurements from only one of the terminals of the faulty line are used.
No pre-fault data are required for the estimation. The lumped parameter line model considering shunt capacitance is
utilized for the derivation of the algorithm. It’s assumed that line parameters are known and transmission lines are fully
transposed. The method is applicable to all types of faults. It’s evinced by evaluation studies that the proposed algo-
rithm can correctly determine the faulted circuit in most cases. For exceptional cases, the current waveforms during the
fault can be used to help identify the faulted circuit. The proposed algorithm generates quite accurate fault location
estimates, and may be suitable for distance relaying.

Keywords: Distance Protection, Fault Location, Parallel Transmission Line

1. Introduction sound and faulted circuits together with the phase volt-
ages as the input signals, [4] provide fault location
To provide more reliable operations and higher power
methods for iteratively compensating the effects of line
transfer capability, double circuit transmission lines are
shunt capacitances for enhanced accuracy.
becoming more widely utilized in the power transmission
Measurement data at both ends of the faulty line are
systems. Since quick power system restoration and less
fed to two-terminal methods for locating faults in [6,7].
outage time are important to the power grid, especially
for the emerging smart grid, researchers developed vari- A method described in [6] decomposes the parallel
ous fault location algorithms for quick and accurate fault transmission line network into a differential component
location on power transmission lines. network and a common component network. Although
Most of the fault location approaches are based on very short data window is needed and any segment of the
voltage and current measurements acquired from one end data after fault can be utilized as the input for the method,
or several ends of the lines. In papers [1-4], data from this algorithm is not applicable to all kinds of parallel
only one terminal of the faulted line are used for finding transmission line systems. Reference [7] presents a fault
fault position on double-circuit lines. For double-circuit location method based on distributed line model. How-
transmission lines, the mutual coupling between the ad- ever, phasor measurements units (PMU) for synchro-
jacent lines can affect the fault location estimation con- nized data and continuous monitoring of the line under
siderably [5]. In order to solve this problem, authors of [1] normal operation are required.
made use of modal transformation technique to convert Multi-terminal methods implemented with signals
the coupled equations of transmission line into decoupled available from several buses are discussed in [8,9]. An
ones. As a result, the effects of mutual coupling as well approach proposed in [8] employs the magnitude of the
as pre-fault currents and charging currents have been differential currents at each terminal to locate the fault
eliminated. A fault location algorithm, independent of for multi-terminal two parallel transmission lines. Since
source impedances, fault resistance and remote infeed is fault location algorithms usually varies according to dif-
described in [2]. By using phase currents from both the ferent fault types, Funabashi and et al. developed their

Copyright © 2011 SciRes. SGRE


360 Online One-End Fault Location Algorithm for Parallel Transmission Lines

P Q
method, in which for all types of faults, the equations 2
used for pinpointing the fault location are the same [9].
EG R 1 EH
Although two-terminal and multi-terminal methods
usually produce more accurate results, one-terminal ap- x 1–x

proaches still have advantages such as simplicity and no Rf


need for communication with remote end.
E
In recent years, some special methods for finding fault
positions on parallel transmission lines are presented in Figure 1. Circuit diagram used for developing the new al-
[10,11]. As we know, most of the fault location algo- gorithm.
rithms for double circuit lines require measurements
from at least one of the local terminals. One of the ad- parameter model is more computationally demanding. For
vantages of [10] is that only voltage measurements from the interests of computational efficiency, the nominal-PI
one or two buses, which can be far from the faulted sec- model is utilized. Only voltage and current measurements
tion, are needed. Due to this reason, the new approach at terminal P are used for estimating the fault location.
can be taken as a method in case there is no data-re- Positive, negative and zero sequence circuits of the
cording device near the faulted line. Authors of [11] ap- system are depicted in Figure 2(a), Figure 2(b) and
ply Artificial Neural Networks (ANNs) to fault analysis Figure 2(c), respectively. Suppose a fault with a fault
for fault detection, fault classification and fault location. resistance of R f occurs on circuit 1 at location R. The
For different aims of fault analysis, the particular Neu- following notations are defined for deriving the algorithm:
ral-network structure is selected with the help of a soft- V0 p , V1 p , V2 p zero, positive and negative sequence
ware tool named SARENEUR. voltages at terminal P, respectively;
Generally speaking, the existing fault location methods V0 q ,V1q , V2 q zero, positive and negative sequence
are suitable for off-line analysis. This paper aims to pre- voltages at terminal Q, respectively;
sent a method for online applications, which is capable of V0 r1 , V0 r 2 zero sequence voltages at bus R and F, re-
identifying the faulted circuit and locating the faults as spectively;
well. In other words, the proposed method does not need V1r , V2 r positive and negative sequence voltages at bus
to know which circuit of the parallel line is faulted. In R, respectively;
this paper, in order to enhance the accuracy of the esti- I 0 p1 , I1 p1 , I 2 p1 zero, positive and negative sequence
mates, shunt capacitances of long lines are considered in currents through circuit 1 at terminal P, respectively;
the power system model utilized in [2]. It is assumed that I 0 p 2 , I1 p 2 , I 2 p 2 zero, positive and negative sequence
the network data, including source impedances and currents through circuit 2 at terminal P, respectively;
transmission line parameters, are known. It is also as- I 0 q1 , I1q1 , I 2 q1 zero, positive and negative sequence
sumed that power lines are fully transposed, and the currents through circuit 1 at terminal Q, respectively;
positive- and negative-sequence line impedances are I 0 q 2 , I1q 2 , I 2 q 2 zero, positive and negative sequence
equal. Compared to [4], the proposed method in this pa- currents through circuit 2 at terminal Q, respectively;
per solves one equation to directly obtain the fault loca- V0 se , V1se , V2 se zero, positive and negative sequence
tion without the need to iteratively compensate the line voltages at fault location E, respectively;
shunt capacitances. Therefore, the proposed method may Z 0 s1 , Z1s1 , Z 2 s1 total zero, positive and negative se-
be suitable for online distance protection. quence series impedances of circuit 1 respectively and
Section 2 presents the proposed fault location ap- Z1s1  Z 2 s1 ;
proaches with boundary condition for each type of fault. Z 0 s 2 , Z1s 2 , Z 2 s 2 total zero, positive and negative se-
An online protection method for parallel transmission quence series impedances of circuit 2 respectively and
lines is discussed in detail as well. Simulation studies Z1s 2  Z 2 s 2 ;
based on Electro-Magnetic Transients Program (EMTP) Y01 , Y11 , Y21 total zero, positive and negative sequence
under diverse fault conditions are reported in Section 3 shunt admittances of circuit 1 respectively and Y11  Y21 ;
[12], followed by the conclusion. Y02 , Y12 , Y22 total zero, positive and negative sequence
shunt admittances of circuit 2 respectively and Y12  Y22 ;
2. Fault Location Algorithm for Parallel Z 0m total zero sequence mutual impedance between
Transmission Lines circuit 1 and circuit 2;
The system diagram adopted for deriving the new fault Y0m total zero sequence mutual admittance between
location algorithm is shown in Figure 1. Although the circuit 1 and circuit 2;
distributed parameter line model is more accurate for x fault distance from terminal P in per unit;
modeling lines than the nominal-PI model, the distributed R f fault resistance in ohms;

Copyright © 2011 SciRes. SGRE


Online One-End Fault Location Algorithm for Parallel Transmission Lines 361

V1 p V1q From the positive sequence network shown in Figure


I1 p 2 Z1s 2 I 1q 2 2(a), the following equations are obtained based on the
1
measurements at terminal P:
1
Y12 Y12
2 2  x 
V1r  V1 p  xZ1s1  I1 p1  Y11V1 p 
 2 
I 1 p1 xZ 1s1 V1r (1  x) Z1s1 I 1q1 (1)
R
 1 x 
x x 1 x 1 x  V1q  1  x  Z1s1  I1q1  Y11V1q 
Y11 Y11 Y11 Y11  2 
2 2 2 2
R f _ seq  1 
V1q  V1 p  Z1s 2  I1 p 2  Y12V1 p  (2)
V1 se  2 
(a)  x x
V1r  R f _ seq   I1 p1  Y11V1 p  Y11V1r
V2 p V2 q  2 2
(3)
1 x 1 x 
I2 p2 Z 1s 2 I 2q2  I1q1  Y11V1q  Y11V1r   V1se
1 1
2 2 
Y12 Y12
2 2 Eliminating V1q and I1q1 from Equations (1), (2)
and (3), it yields
I 2 p1 xZ 1s 1 V2 r (1  x ) Z 1s1 I 2 q1
R
1 x  1  x 
x x 1 x V1se  R f _ seq     I1 p1  Y11V1 p 
Y11 Y11 Y11 Y11 
2 2 2 2  1 x  2 
(4)
R f _ seq k  1  1 1  
 1  I1 p 2  Y12V1 p    Y11   V1r  ,
1 x   2
V 2 se 2 R f _ seq  
(b)
where
V0 p x x 1 x 1 x
V0 q
Z1s 2
2
Y 02
2
Y 02
2
Y02
2
Y02 k1  . (5)
xZ0s 2 F (1 x)Z0s 2 Z1s1
I 0 p2 V0r 2 I0q 2 Similarly, for negative sequence network, the follow-
xZ0m (1 x)Z0m ing equation is derived:
x x 1 x 1 x
Y0 m Y0 m Y0m
2 2 2
Y0m
2  1  x 
V2 se  R f _ seq     I 2 p1  Y11V2 p 
I 0 p1 xZ0s1 V0r1
R
(1 x)Z0s1 I0q1  1 x  2 
k  1 
x x 1 x 1 x  1  I 2 p 2  Y12V2 p  (6)
2
Y01
2
Y 01
2
Y01
2
Y01 1 x  2 
Rf _ seq
1 1  
  Y11   V2 r 
V0se 2
 R f _ seq  
(c)
For zero sequence circuit, the following four equations
Figure 2. (a) Positive sequence circuit of the system. (b)
hold according to Figure 2(c):
Negative sequence circuit of the system. (c) Zero sequence
circuit of the system.  x 
V0 r1  V0 p  xZ 0 s1  I 0 p1  Y01V0 p 
R f _ seq fault resistance shown in sequence circuits in  2 
ohms.  x 
 xZ 0 m  I 0 p 2  Y02V0 p 
 2 
2.1. Sequence Equations (7)
 1 x 
Known phase voltages and currents at terminal P, we can  V0 q  1  x  Z 0 s1  I 0 q1  Y01V0q 
 2 
obtain the symmetrical components from phase compo-
 1 x 
nents by employing the symmetrical component theory  1  x  Z 0 m  I 0 q 2  Y02V0 q 
[13].  2 

Copyright © 2011 SciRes. SGRE


362 Online One-End Fault Location Algorithm for Parallel Transmission Lines

x 2.2.1. Single Line to Ground Faults


V0 r 2  V0 p  xZ 0 s 2 ( I 0 p 2  Y02V0 p )
2 Phase A to ground (AG) faults are taken as an instance
 x  for deriving the new algorithm. For AG faults, the
 xZ 0 m  I 0 p1  Y01V0 p  boundary condition is given as
 2 
(8) V0 se  V1se  V2 se  0. (13)
 1 x 
 V0 q  1  x  Z 0 s 2  I 0 q 2  Y02V0q 
 2  Substituting Equations (4), (6), (11) into (13) leads to
 1 x   1 
 1  x  Z 0 m  I 0 q1  Y01V0 q  A1  A2 x  A3 x 2  R f _ seq   A4  A5 x  A6 x 2  , (14)
 2   1  x 
x x x where A1 , A2 , A3 , A4 , A5 , A6 are constants defined in Ap-
I 0 p 2  Y02V0 p  Y02V0 r 2  Y0 m V0 r 2  V0 r1  pendix I.
2 2 2
Rearranging Equation (14), it becomes
 1 x 1 x
   I0q 2  Y02V0 q  Y02V0 r 2 (9) B4 x3  B3 x 2  B2 x  B1
 2 2 R f _ seq  , (15)
1 x B8 x3  B7 x 2  B6 x  B5

 Y0 m V0 r 2  V0 r1  
2  where B1 , B2 , B3 , B4 , B5 , B6 , B7 , B8 are constants defined
in Appendix I.
 x x Since R f _ seq is the sequence fault resistance in ohms,
V0 r1  R f _ seq   I 0 p1  Y01V0 p  Y01V0 r1
 2 2 it is a real number, or equivalently
x R f _ seq  R f _ seq ,
 Y0 m V0 r1  V0 r 2   I 0 q1 (16)
2 (10)
1 x 1 x where the bar over a variable represents the its complex
 Y01V0 q  Y01V0 r1 conjugate.
2 2
Substituting (15) into (16) results in
1 x 
 Y0 m V0 r1  V0 r 2    V0 se f1  x   C7 x 6  C6 x 5  C5 x 4  C4 x3  C3 x 2  C2 x  C1 (17)
2 
Eliminating V0q , I 0 q1 and I 0 q 2 from Equations (7), f1  x   0, (18)
(8), (9) and (10), it follows
where C1 , C2 , C3 , C4 , C5 , C6 , C7 are constants defined in
 1  x  Appendix I.
V0 se  R f _ seq     I 0 p1  Y01V0 p  By applying the Newton-Raphson method to function
 1  x  2 
f1  x  as follows, fault location x can be estimated
k  x 
 0  I 0 p 2  Y02V0 p  accurately.
1 x  2 
 df 
1 2 
(11) x   f1  xk    xk   (19)
  Y01  Y0 m  k0Y0 m   V0 r1  dx 

2 R f _ seq  xk 1  xk  x (20)
1 
  k0Y02  Y0 m  k0Y0 m  V0 r 2  , where
2  xk is the estimate of x at the kth iteration;
where x is the difference between two successive estima-
tions;
Z0 s 2  Z0m
k0  . (12) k is the iteration number starting from 1.
Z 0 s1  Z 0 m An initial value of x1  0.5 for fault location can be
adopted for the iterative approach. The iteration can be
2.2. Boundary Conditions
terminated when the desired tolerance for x is reached.
In this section, boundary conditions for single line to After x is obtained, Equation (15) can be utilized to
ground (LG), line to line (LL), line to line to ground compute the value for R f _ seq . Due to the calculated
(LLG) and balanced three-phase (LLL) faults are de- R f _ seq from Equation (15) may have negligible imagi-
scribed respectively with details. Newton-Raphson me- nary part, the real part of R f _ seq is taken as the final
thod is applied to estimate the fault location after the estimate for sequence fault resistance.
final equations are acquired. It’s worth noting that R f _ seq is the fault resistance

Copyright © 2011 SciRes. SGRE


Online One-End Fault Location Algorithm for Parallel Transmission Lines 363

demonstrated in the sequence circuits while R f is the tions developed under BC faults can be used for LLL
actual fault resistance for each type of fault. Under AG faults to estimate fault location x and sequence fault
fault, R f is the resistance between phase A and the resistance R f _ seq . R f is equal to R f _ seq during bal-
ground. In this case, R f  R f _ seq . anced three-phase faults.
The following procedure is utilized to determine which One distinctive feature of the developed algorithm is
circuit of the parallel lines is faulted. First of all, we as- its capability to identify which circuit of the parallel line
sume the fault occurs on circuit 1. Then, the proposed is faulted utilizing the following procedure. We will first
algorithm is employed to calculate the estimated x and assume that the fault falls on circuit 1 and applies the
R f . If x is out of range from 0 to 1 or R f is less than developed method. If the obtained fault location estimate
0, it means the assumption is incorrect. Then, we run the is within zero and one and fault resistance estimate is
algorithm again by assuming circuit 2 is the faulty circuit. larger than zero, it indicates that the assumption is cor-
Study results show that for various fault locations and rect. Otherwise, we will apply the developed method
resistances, this approach can successfully distinguish the assuming that the fault occurs on circuit 2 to obtain a
sound and faulty circuits. new pair of estimates. The evaluation studies presented
in Section 3 illustrate this process.
2.2.2. Line to Line Faults
Take phase B to phase C (BC) faults as an example. 3. Evaluation Studies
Phase B is connected to phase C though a fault resistance
of R f . The boundary condition for BC faults is de- In this section, the EMTP package has been adopted to
scribed as simulate a double-circuit line system under diverse fault
conditions based on the distributed parameter line model
V1se  V2 se . (21) [12]. A 50 Hz power system shown in Figure 3 is mod-
Substituting (4) and (6) into (21), similar function as eled for the study. The simulated power system consists
(17) can be acquired: of two generators at the two ends and a 200-mile parallel
f 2  x   D7 x 6  D6 x 5  D5 x 4  D4 x3 transmission line. One of the circuits is suffering from
(22) the fault. Generator information and line parameters are
 D3 x 2  D2 x  D1 presented in Tables 1, 2 and 3. In this study, base values
f2  x   0
of 500 kV and 100 MVA are chosen for the per unit sys-
(23)
tem. In the studies, all the simulated faults are placed on
where D1 , D2 , D3 , D4 , D5 , D6 , D7 are constants, which circuit 1.
will not be provided with details in this paper.
By employing the Newton-Raphson approach to func- 1 2
tion f 2  x  , fault location x can be well estimated and 2
therefore R f _ seq can be obtained as well. For BC faults, G2
G1
R f  2  R f _ seq . 1

2.2.3. Line to Line to Ground Faults


For line to line to ground faults, a phase B to phase C to
ground (BCG) fault is discussed in details. In this case, Figure 3. Schematic diagram of studied power system.
both phase B and phase C are grounded through a resis-
Table 1. Source impedance.
tance R f . For BCG faults, boundary condition is written
as Voltagea Positive Sequence Zero Sequence
Generator
(kV) Impedance (p.u.) Impedance (p.u.)
V1se  V2 se . (24)
G1 565.69 20  0.319 + j19.7544 0.2872 + j8.4968
Since the boundary condition for BCG faults and BC G2 565.69 0 0.4745 + j 28.6908 0.6829 + j23.9267
faults are the same, we have identical equations for cal-
a. Line to neutral voltage.
culating fault location x and sequence fault resistance
R f _ seq . R f  R f _ seq under BCG faults. Table 2. Transmission line parameters for both circuits.
2.2.4. Balanced Three-Phase Faults
Positive Zero Positive Zero
For LLL faults, boundary condition is given as Sequence Sequence Sequence Sequence
V1se  V2 se  0. (25) Impedance Impedance Admittance Admittance
(Ω/mile) (Ω/mile) (S/mile) (S/mile)
Because the boundary condition for LLL faults satis-
0.061 + j0.3513 0.268 + j1.0371 j4.66 × 10–6 j2.7018 × 10–6
fies the boundary condition for BC faults, the same equa-

Copyright © 2011 SciRes. SGRE


364 Online One-End Fault Location Algorithm for Parallel Transmission Lines

Table 3. Mutual coupling between circuit 1 and circuit 2. Table 4. Fault location results assuming faults occurring on
circuit 1.
Zero Sequence Mutual Zero Sequence Mutual
Impedance (Ω/mile) Admittance (S/mile) Fault Actual fault Estimated fault
Fault
resistance location location x
0.23 + j 0.6308 j1.6242 × 10–6 type
(Ω) (per unit) (per unit)
0.2 0.200
0.5 0.498
Transient waveforms generated from EMTP are proc-
0.8 0.790
essed to obtain the voltage and current phasors. Fault 1
0.9 0.886
location estimates are acquired by implementing the new 0.95 0.934
algorithms in Matlab. Table 4 presents the results under 0.98 0.962
various fault conditions when assuming faults occurring
on circuit 1. In the table, x is defined as the distance in 0.2 0.200
per unit from the fault point on the faulty circuit to bus 1. 0.5 0.500
0.8 0.797
The first three columns of Table 4 list the actual fault LG 100
0.9 0.897
type, fault resistance and fault location, respectively. 0.95 0.946
Fault location estimates are given in the fourth column in 0.98 0.976
per unit. Evaluation studies indicate that all of the simu-
lated faults are on circuit 1 and quite accurate estimates 0.2 0.201
for fault location are generated by the algorithms. 0.5 0.504
As indicated in Section 2, the developed algorithm is 0.8 0.804
300
0.9 0.904
capable of identifying which circuit of the parallel line is
0.95 0.954
faulted. For instances, let us assume that the fault occurs
0.98 0.982
on circuit 2, the fault location estimates are obtained as
shown in Table 5. “N/A” indicates that an estimate of 0.2 0.200
fault location within zero and one cannot be found. It is 0.5 0.499
evinced that either the fault location estimate is out of the 1
0.8 0.795
range from zero to one or the fault resistance estimate is 0.9 0.892
less than zero and thus indicates that the fault does not 0.95 0.941
0.98 0.970
occur on circuit 2, but occurs on circuit 1.
LL
Sometimes, the algorithm can produce a valid solution 0.2 0.200
if the fault is assumed to be on the actually healthy cir- 0.5 0.499
cuit. For example, for an AG fault occurring on circuit 1 0.8 0.795
10
at m  0.2 with R f  1 ohm, if we assume the fault is 0.9 0.893
on circuit 2, the proposed algorithm yields the estimate 0.95 0.942
pair m  0.572 and R f  0.125 ohm, which is a valid 0.98 0.971
solution. Under such circumstances, we cannot tell which
0.2 0.200
circuit is the faulty one. More research is needed to find 0.5 0.499
out under which fault conditions this phenomenon will 0.8 0.795
1
occur. Under such circumstances, the current waveforms 0.9 0.892
are utilized to identify the faulty circuit because the 0.95 0.941
faulty circuit has larger currents than the healthy circuit 0.98 0.970
due to the fault.
0.2 0.200
The method proposed in this paper generally yields
0.5 0.501
higher accuracy than the method described in [2] for LL, 0.8 0.801
LLG and LLL faults. For LG faults, the new method is LLG 100
0.9 0.900
more accurate if the fault resistance is larger than 100 0.95 0.950
ohms, but is not as accurate as the one in [2] for fault 0.98 0.980
cases with smaller resistances. So for LG faults with
small estimated fault resistances, the method in [2] can 0.2 0.201
0.5 0.503
be applied.
0.8 0.805
300
4. Conclusions 0.9 0.905
0.95 0.954
A novel fault location algorithm considering shunt ca- 0.98 0.984

Copyright © 2011 SciRes. SGRE


Online One-End Fault Location Algorithm for Parallel Transmission Lines 365

0.2 0.200 online protection. By examining the estimated fault loca-


0.5 0.499
0.8 0.795
tion and fault resistance obtained under a certain assump-
1 tion, the new method can distinguish the sound and
0.9 0.892
0.95 0.941 faulted circuits in most cases. Besides, the new approach,
0.98 0.970 which is applicable to both symmetrical and unsymmet-
LLL
0.2 0.200 rical faults, is independent of source impendence and
0.5 0.499 fault resistance. Simulation studies have demonstrated
0.8 0.795 that the algorithm produces quite accurate estimates for
10
0.9 0.894
0.95 0.943 all kinds of faults.
0.98 0.972
REFERENCES
Table 5. Fault location results assuming faults occurring on
circuit 2. [1] T. Kawady and J. Stenzel, “A Practical Fault Location
Approach for Double Circuit Transmission Lines Using
Actual Estimated Estimated Single End Data,” IEEE Transactions on Power Delivery,
Fault
Fault fault fault fault Vol. 18, No. 4, 2003, pp. 1166-1173.
resistance
type location location x resistance doi:10.1109/TPWRD.2003.817503
(Ω)
(per unit) (per unit) Rf (Ω)
[2] Y. Liao and S. Elangovan, “Digital Distance Relaying
0.2 0.354 –240.959 Algorithm for First-Zone Protection for Parallel Trans-
0.5 0.762 –141.080 mission Lines,” IEE Proceedings-Part C: Generation,
0.8 0.983 –24.77 Transmission and Distribution, Vol. 145, No. 5, 1998, pp.
LG 300 531-536.
0.9 N/A N/A
0.95 N/A N/A
[3] Y. Ahn, M. Choi, S. Kang and S. Lee, “An Accurate
Fault Location Algorithm for Double-Circuit Transmis-
0.98 N/A N/A sion Systems,” IEEE Power Engineering Society Summer
Meeting, Seattle, 16-20 July 2000, pp. 1344-1349.
0.2 N/A N/A [4] J. Izykowski, E. Rosolowski and M. M. Saha, “Locating
0.5 N/A N/A Faults in Parallel Transmission Lines under Availability
0.8 N/A N/A of Complete Measurements at One End,” IEE Proceed-
LL 10 ings-Generation, Transmission and Distribution, Vol.
0.9 N/A N/A
151, No. 2, 2004, pp. 268-273.
0.95 N/A N/A doi:10.1049/ip-gtd:20040163
0.98 N/A N/A [5] Power System Relaying Committee, “Guide for Deter-
mining Fault Location on AC Transmission and Distribu-
0.2 0.478 –195.525 tion Lines,” IEEE C37.114, 2005, pp. 1-36.
0.5 0.884 –69.383 [6] G. Song, J. Suonan, Q. Xu, P. Chen and Y. Ge, “Parallel
Transmission Lines Fault Location Algorithm Based on
0.8 N/A N/A
LLG 300 Differential Component Net,” IEEE Transactions on
0.9 N/A N/A Power Delivery, Vol. 20, No. 4, 2005, pp. 2396-2406.
0.95 N/A N/A doi:10.1109/TPWRD.2005.852364
0.98 N/A N/A [7] C. S. Chen, C. W. Liu and J. A. Jiang, “A New Adaptive
PMU Based Protection Scheme for Transposed/Untrans-
0.2 N/A N/A
posed Parallel Transmission Lines,” IEEE Transactions
on Power Delivery, Vol. 17, No. 2, 2002, pp. 395-404.
0.5 N/A N/A doi:10.1109/61.997906
0.8 N/A N/A
LLL 10 [8] T. Nagasawa, M. Abe, N. Otsuzuki, T. Emura, Y. Jikihara
0.9 N/A N/A and M. Takeuchi, “Development of a New Fault Location
0.95 N/A N/A Algorithm for Multi-Terminal Two Parallel Transmission
0.98 N/A N/A Lines,” IEEE Transactions on Power Delivery, Vol. 7,
No. 3, 1992, pp. 1516-1532. doi:10.1109/61.141872
[9] T. Funabashi, H. Otoguro, Y. Mizuma, L. Dube and A.
pacitance has been discussed in this paper. Only voltage
Ametani, “Digital Fault Location for Parallel Double-
and current measurements at one of the terminals are Circuit Multi-Terminal Transmission Lines,” IEEE Trans-
needed. No pre-fault data is required in the approach. actions on Power Delivery, Vol. 15, No. 2, 2000, pp. 531-
Lumped parameter line model is used instead of the dis- 537. doi:10.1109/61.852980
tributed line model for the interests of computational [10] N. Kang and Y. Liao, “Fault Location for Double-Circuit
efficiency. The proposed algorithm may be utilized for Lines Utilizing Sparse Voltage Measurements,” Power &

Copyright © 2011 SciRes. SGRE


366 Online One-End Fault Location Algorithm for Parallel Transmission Lines

Energy Society General Meeting, Calgary, 26-30 July doi:10.1109/TPWRD.2005.855482


2009, pp. 1-7. [12] Leuven EMTP Centre, “Alternative Transient Program,”
[11] J. Gracia, A. J. Mazon and I. Zamora, “Best ANN Struc- User Manual and Rule Book, Leuven, 1987.
tures for Fault Location in Single- and Double-Circuit [13] J. Grainger and W. Stevenson, “Power System Analysis,”
Transmission Lines,” IEEE Transactions on Power Deliv- McGraw-Hill Inc., New York, 1994.
ery, Vol. 20, No. 4, 2005, pp. 2389-2395.

Appendix I B1   A1 (A.7)
A1  V0 p  V1 p  V2 p (A.1) B2  A1  A2 (A.8)
B3  A2  A3
A2    Z 0 s1 I 0 p1  Z 0 m I 0 p 2  Z1s1  I1 p1  I 2 p1  
(A.9)
(A.2)
B4  A3 (A.10)
 Z 0 s1Y01  Z 0 mY02  V0 p  Z1s1Y11 V1 p  V2 p   (A.3)
1
A3  B5   A4
2  (A.11)

 1 1  B6   A5 (A.12)
A4   I 0 p1  Y01V0 p  k0 I 0 p 2  k0Y02V0 p 
 2 2  B7  A5  A6 (A.13)
  I1 p1  I 2 p1   Y11 V1 p  V2 p 
1
(A.4) B8  A6 (A.14)
2
C1  B1 B5  B1B5
 k1  I1 p 2  I 2 p 2   k1Y12 V1 p  V2 p 
1 (A.15)
2
C2  B2 B5  B2 B5  B1 B6  B1 B6 (A.16)
Y01  Y0 m  k0Y0 m   Z 0 s1 I 0 p1  Z 0 m I 0 p 2 
1
A5 
2 C3  B3 B5  B3 B5  B2 B6  B2 B6  B1 B7  B1 B7 (A.17)
  k0Y02  Y0 m  k0Y0 m   Z 0 s 2 I 0 p 2  Z 0 m I 0 p1   (A.5) C4  B4 B5  B4 B5  B3 B6  B3 B6
(A.18)
 Y11 Z1s1  I1 p1  I 2 p1   B2 B7  B2 B7  B1 B8  B1 B8
1
2
C5  B4 B6  B4 B6  B3 B7
1 (A.19)
A6  V0 p  k0Y02  Y0 m  k0Y0 m  Z 0 s 2Y02  Z 0 mY01   B3 B7  B2 B8  B2 B8
4
 Y01  Y0 m  k0Y0 m  Z 0 s1Y01  Z 0 mY02   (A.6) C6  B4 B7  B4 B7  B3 B8  B3 B8 (A.20)

 Y112 Z1s1 V1 p  V2 p 


1
C7  B4 B8  B4 B8 (A.21)
4

Copyright © 2011 SciRes. SGRE

You might also like