ANNEX C [Clause 4.2.4(b)] AREA REQUIRED FOR TRANSFORMER ROOM AND SUBSTATION FOR DIFFERENT CAPACITIES C-1 The requirement for area for transformer room and substation for different capacities of transformers is given below for guidance: Sl Capacity of Total Transformer Total Substation Area (In Coming, Suggested Minimum No. Transformers) Room Area, HV, MV Panels, Transformer Roof but" Face Width KVA Minimum, m Without Generators), Minimum m @ @) (Oy ) 1x 160 140 90 90 2x 160 280 118 135 1250 150 1 90 2% 250 300 121 13S 1x 400 165 93 90 2400 33.0 125 135 3400 495 167 180 2500 360 130 145 3x50 540 m 19.0 2630 360 132 145 3x630 540 176 19.0 2x 800 390 135 45 3x 800 580 181 140 2 1000 390 149 145 3x 1000 580 197 199 NoTEs |The above dimensions are overall area requised for substation excluding generating Set. 2 The clear height required for substation equipment shal be misimum of 3.0 m below the soffit ofthe bear. ANNEX D [Clause 4.2.4G)] ADDITIONAL AREA REQUIRED FOR GENERATOR IN ELECTRIC SUBSTATION Del The requirement of additional area for generator in electric substation for different capacities of generators is given below for guidance: SINo, Capacity Area Clear Height below the Soffit of the Beam KW a m @ 2) @ o a 25 56 36 ii) 48 36 36 iit) 100 65 36 iv) 150 n 46 vy) 248, 100 46 vi) 350 100 46 vii) 480 100 46 vit) 600 10 46 ix) 300 120 46 x) 1.000 120 46 xi) 1250 120 46 xii) 1600 150 46 NOTE — "The area ad height rice for generating set room given in the above table are for geeral guidance only and may be finally fixed accondng to actual requirement PART 8 BUILDING SERVICES — SECTION 2 ELECTRICAL AND ALLIED INSTALLATIONS 6