You are on page 1of 54

PCS-985T

Transformer Relay
Instruction Manual Supplement

for Project ECKF110355

NR Electric Co., Ltd.


Supplement for Project ECKF110355

Preface
This document is the supplement of the corresponding general instruction manual of the
equipment mentioned on the cover. It is dedicated to the specific project, and cannot be used in
other projects. If there are some differences between this supplement and the corresponding
general instruction manual, user must refer to this supplement for the designated project.

Copyright

Version: 1.00 NR ELECTRIC CO., LTD.

69 Suyuan Avenue. Jiangning, Nanjing 211102, China

P/N: EN_ YJBH5093.0086.0001.110355 Tel: +86-25-87178185, Fax: +86-25-87178208

Website: www.nrelect.com, www.nari-relays.com

Copyright © NR 2013. All rights reserved Email: NR_TechSupport@nari-relays.com

We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination
to third parties is strictly forbidden except where expressly authorized.

The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.

We reserve the rights to make technical improvements without notice.

PCS-985T Transformer Relay i


Date: 2013-01-22
Supplement for Project ECKF110355

ii PCS-985T Transformer Relay.


Date: 2013-01-22
Supplement for Project ECKF110355

Table of Content
Preface........................................................................................................................ i
Table of Content....................................................................................................... iii
1 Information about this Application ...................................................................... 1
2 Introduction............................................................................................................ 3
2.1 Protective Functions Configuration ............................................................................................ 3

3 Operation Theory................................................................................................... 5
3.1 HV Side Phase Overcurrent Protection ..................................................................................... 5

3.2 HV Side Ground Overcurrent Protection.................................................................................... 6

4 Hardware .............................................................................................................. 13
4.1 Plug-in Module Terminal Definition........................................................................................... 13

5 Human Machine Interface ................................................................................... 17


5.1 Understand the LCD Display .................................................................................................... 17

6 Settings ................................................................................................................ 21
6.1 General Settings....................................................................................................................... 21

6.2 Implicit internal Settings ........................................................................................................... 24

6.3 Protection Settings ................................................................................................................... 26

6.4 Device Setup ............................................................................................................................ 42

7 Manual Version History ....................................................................................... 47

PCS-985T Transformer Relay iii


Date: 2013-01-22
Supplement for Project ECKF110355

iv PCS-985T Transformer Relay.


Date: 2013-01-22
1 Information about this Application

1 Information about this Application


The following table gives the information about the application of this supplement which must be
used with corresponding general instruction manual for the applied-specific project.

Project ECKF110355

SUBQ SUBQ00124177

Software version PCS-985T R1.00_ECKF110355

Corresponding general PCS-985T_X_Instruction Manual_EN_Domestic General_X_R1.00_


instruction manual version (EN_YJBH5093.0086.0001)

PCS-985T Transformer Relay 1


Date: 2013-01-22
1 Information about this Application

2 PCS-985T Transformer Relay.


Date: 2013-01-22
2 Introduction

2 Introduction

2.1 Protective Functions Configuration

According to the requirement of this project, following protective functions are configured with the
protection relay, and the functions which are not mentioned in this section are not equipped for
user’s protection relay.

Table 2.1-1 Protective functions in PCS-985T

Protective function

Transformer biased current differential protection 87T

Transformer unrestrained current differential protection 50/87UT

Restricted earth fault protection of HV side 64REF

Restricted earth fault protection of LV side A 64REF

Restricted earth fault protection of LV side B 64REF

Stub differential protection 87S

Overexcitation protection 24

Voltage controlled phase overcurrent protection of HV side 50/51P

Negative-sequence overcurrent protection of HV side 50/51Q

Voltage controlled phase overcurrent protections of each branch at


50/51P
LV side

Ground overcurrent protections of LV side A(B) 50/51G

Stub overcurrent protection 50/51P

Residual overvoltage alarm of LV side A(B) 59G

Overload alarm 49

Cooling initiation function 49

On-load tap change (OLTC) blocking function during overload 49

CT saturation detection

Inrush current detection

Overexcitation detection

Harmonic blocking function

VT circuit failure supervision VTS

CT circuit failure supervision CTS

PCS-985T Transformer Relay 3


Date: 2013-01-22
2 Introduction

NOTE! Please replace the Table 1.2-1 in the Section 1.2 of the general instruction

manual with the above table in this section.

4 PCS-985T Transformer Relay.


Date: 2013-01-22
3 Operation Theory

3 Operation Theory

3.1 HV Side Phase Overcurrent Protection

Voltage controlled overcurrent protection of HV side is replaced by negative-sequence


overcurrent protection of HV side, the operation principle of which is shown below.

3.1.1 Negative-Sequence Overcurrent Protection


Negative-sequence overcurrent protection is applied as backup protection of transformer, and two
stages are equipped. Negative-sequence current of HV side of transformer is adopted for the
protection calculation. Negative-sequence voltage is selectable to control negative-sequence
overcurrent protection to prevent maloperations during CT circuit failure.

 Logic

Two stages have similar logics and the logic of stage 1 is taken as an example shown below.

SIG U2>1V ≥1

SET [En_NegOV_Ctrl_NegOC_HVS]

SIG I2>[I_NegOC1_HVS]

BI [EBI_PPF_HVS] & &


[t_NegOC1_HVS] 0s
[Op_NegOC1_HVS]
SET [En_PPF_HVS]

SIG Flg_En_NegOC1_HVS

SIG FD_NegOC1_HVS

Figure 3.1-1 Logic diagram of stage 1 of negative-sequence overcurrent protection

Where

U2: the negative-sequence voltage of HV side.

[En_NegOV_Ctrl_NegOC_HVS]: the logic setting of enabling negative-sequence overcurrent


protection being controlled by negative sequence voltage.

I2: the negative sequence current of HV side.

[EBI_PPF_HVS]: the binary input of enabling the phase-to-phase fault backup protection of HV
side.

[En_PPF_HVS]: the logic setting of enabling the phase-to-phase fault backup protection of HV

Flg_En_NegOC1_Tr: the internal flag indicating that negative-sequence overcurrent stage 1 is


enabled by configuring the logic setting [TrpLog_NegOC1_HVS].

FD_NegOC1_HVS: the fault detector of stage 1 of negative-sequence overcurrent protection of

PCS-985T Transformer Relay 5


Date: 2013-01-22
3 Operation Theory

HV side picks up. The fault detector will pick up if negative-sequence current of HV side is greater
than the current setting.

[I_NegOC1_HVS]: current setting of stage 1 of negative-sequence overcurrent protection of HV


side.

[t_NegOC1_HVS]: time delay of stage 1 negative-sequence overcurrent protection of HV side.

[Op_NegOC1_HVS]: the operation flag of stage 1 negative-sequence overcurrent protection of


HV side.

3.2 HV Side Ground Overcurrent Protection

For the project, calculated residual current is fixedly used for the calculation of stage 1
definite-time ground overcurrent protection and neutral current is fixedly adopted for the
calculation of stage 2 definite-time ground overcurrent protection and inverse-time overcurrent
protection.

3.2.1 Definite-Time Ground Overcurrent Protection


Following functions of two-stage definite-time ground overcurrent protection relay can be selected
by configuring corresponding logic settings:

 Whether or not be controlled by directional element.

 Whether or not be controlled by residual voltage.

 Breaker(s) at what side or sides will be tripped.

Operation criterion of definite-time ground overcurrent protection

3I 0 _ Cal  [I_ROC1_Cal_HVS]
Equation 3.2-1
3I 0 _ NP  [I_ROC1_NP_HVS]
Where:

3I 0 _ Cal is the calculated residual current of HV side.

3I 0 _ NP is the neutral current of HV side.

[I_ROC1_Cal_HVS] is the setting of ground overcurrent protection with calculated residual current
of the HV side.

[I_ROC1_NP_HVS] is the setting of ground overcurrent protection with neutral current of the HV
side.

3.2.2 Inverse-Time Ground Overcurrent Protection


There are four inverse-time curves selectable for inverse-time overcurrent protection and they are

6 PCS-985T Transformer Relay.


Date: 2013-01-22
3 Operation Theory

“IEC Normal inverse”, “IEC Very inverse”, “IEC Extremely inverse” and “IEC Long-time inverse”.
The inverse-time operating time curve is as follows. Neutral current is adopted for the calculation.

K  Tp
t 
 I  Equation 3.2-2
   1
 I set 
Where:

I set is the operating current, i.e. [Ib_InvROC_NP_HVS].

Tp is time multiplier setting [TMS_InvROC_NP_HVS].

K is a constant.

 is a constant.

The user can select the operating characteristic from four inverse-time characteristic curves by

setting [Opt_InvROC_HVS], and parameters of available characteristics for selection are shown in

the following table.

Table 3.2-1 Inverse-time curve parameters

Time Characteristic K α

IEC Normal inverse 0.14 0.02

IEC Very inverse 13.5 1.0

IEC Extremely inverse 80 2.0

IEC Long-time inverse 120 1.0

3.2.3 Residual Voltage Control Element (RVCE)


 Operation criterion of RVCE

3U 0  [ V_ROV_VCE_HVS] Equation 3.2-3

Where:

3U 0 is the residual voltage of HV side.

[V_ROV_VCE_HVS] is the setting of residual overvoltage element for controlling the ground
overcurrent protection of the corresponding side.

 ROC being controlled by RVCE of local side

PCS-985T Transformer Relay 7


Date: 2013-01-22
3 Operation Theory

The logic setting [En_VCE.ROV_Ctrl_ROC1_Cal(NP)_HVS] is used to select whether some stage


ground overcurrent protection is controlled by residual voltage control element. For example
[En_VCE.ROV_Ctrl_ROC1_Cal(NP)_HVS], if this logic setting is set to 1, ground overcurrent
protection will be controlled by the RVCE of HV side. Otherwise it will not.

 Zero-sequence voltage used by RVCE

Residual voltage from broken-delta VT of HV side is fixed as the voltage used by residual voltage
control element.

3.2.4 Residual Directional Element (RDE)


The logic setting [Opt_Dir_ROC_HVS] is used to select the direction of every stage of ground
overcurrent protection. If this logic setting is set to 1, the direction is transformer and reach angle
is 225º. If this logic setting is set to 0, the direction is power system and reach angle is 75º. Figure
3.2-1 shows operating characteristic of directional protection where the hatched area is operation
zone.

In addition, the logic setting [En_Dir_Ctrl_ROC1_Cal(NP)_HVS] is used to select whether the


corresponding ground overcurrent relay is controlled by directional element. If this logic setting is
set to 1, the corresponding ground overcurrent protection will be controlled by directional element.
Otherwise, it will not.

3I0

3U0 3U0
φRCA=255°
φRCA=75°

3I0

a) Direct to power system b) Direct to transformer

Figure 3.2-1 Operating characteristic of residual directional element

NOTE: The residual voltage and residual current used by directional relay are definitely

the calculated residual voltage and calculate residual current. The direction mentioned
above is based on the assumption that positive polarity of three-phase CT for calculating
residual current is at the side of busbar.

3.2.5 Influence of VT Circuit Failure on RVCE and RDE


The logic setting [Opt_VTS_Ctrl_ROC_HVS] is used to control performance of residual directional
element and residual voltage control element during VT circuit failure.

---When this logic setting is set to 1, if VT circuit failure of a side is detected, the residual voltage

8 PCS-985T Transformer Relay.


Date: 2013-01-22
3 Operation Theory

control element and residual directional element cannot operate to release the residual
overcurrent relay.

---When this logic setting is set to 0, if VT circuit failure of a side is detected and the operation
criterion of residual voltage control element or residual directional element are met, the
corresponding element can still operate to release the protection at local side.

3.2.6 Logic

3.2.6.1 Logic of Definite-Time Ground Overcurrent Protection

Ground overcurrent protection with calculated residual current and the ground overcurrent
protection with neutral current have the same logic diagram and here ground overcurrent
protection with calculated residual current is taken as an example to show the logic diagram.

SIG 3U0>[V_ROV_VCE_HVS] &

SIG Flg_VTS_HVS ≥1

&

Flg_RVCE
SET [Opt_VTS_Ctrl_ROC_HVS]
≥1

SET [En_VCE.ROV_Ctrl_ROC1_Cal_HVS]

SIG Flg_Direction_ROC_HVS &

SIG Flg_VTS_HVS ≥1

&

Flg_RDE
SET [Opt_VTS_Ctrl_ROC_HVS]
≥1
&
[t_ROC11_Cal_HVS] 0s
[Op_ROC11_Cal_HVS]
SET [En_Dir_Ctrl_ROC1_Cal_HVS]
[t_ROC12_Cal_HVS] 0s
[Op_ROC12_Cal_HVS]

SIG 3I0_Cal>[I_ROC1_Cal_HVS]

BI [EBI_EF_HVS] &

SET [En_EF_HVS]

SIG Flg_En_ROC1_Cal_HVS

SIG FD_ROC1_Cal_HVS

Figure 3.2-2 Logic diagram of definite-time ground overcurrent protection with calculated residual current

Where:

3U 0 : the residual voltage of HV side.

3I 0 _ Cal : the calculated residual current of HV side.

[V_ROV_VCE_HVS]: the voltage setting of residual voltage control element of HV side.

Flg_VTS_HVS: the internal flag indicating that VT circuit failure of HV side is detected.

[Opt_VTS_Ctrl_ROC_HVS]: the logic setting of selecting how HV side ground overcurrent

PCS-985T Transformer Relay 9


Date: 2013-01-22
3 Operation Theory

protection responses when VT circuit failure is detected.

[En_VCE.ROV_Ctrl_ROC1_Cal_HVS]: the logic setting of enabling residual voltage control


element to control ground overcurrent protection of HV side with calculated residual current.

[En_Dir_Ctrl_ROC1_Cal_HVS]: the logic setting of enabling directional element to control ground


overcurrent protection of HV with calculated residual current side.

Flg_RVCE: the internal flag indicating the residual voltage control element picks up.

Flg_RDE: the internal flag indicating the residual directional element picks up.

Flg_Direction_ROC_HVS: the internal flag indicating that residual directional element decides the
earth fault is in the protection direction of ground overcurrent protection of HV side.

[EBI_EF_HVS]: the binary input of enabling the earth fault backup protection of HV side.

[En_EF_HVS]: the logic setting of enabling earth fault protection of HV side.

Flg_En_ROC1_Cal_HVS: the internal flag indicating that ground overcurrent protection of HV side
with calculated residual current is enabled by configuring the logic settings
[TrpLog_ROC11_Cal_HVS] and [TrpLog_ROC12_Cal_HVS].

FD_ROC1_Cal_HVS: the pickup of fault detector of ground overcurrent protection of HV side with
calculated residual current.

[t_ROC11_Cal_HVS], [t_ROC12_Cal_HVS]: two time delays of delay 1 and delay 2 of ground


overcurrent protection of HV side with calculated residual current respectively.

[Op_ROC11_Cal_HVS], [Op_ROC12_Cal_HVS]: two operation flags of delay 1 and delay 2 of


ground overcurrent protection of HV side with calculated residual current respectively.

3.2.6.2 Logic of Inverse-Time Ground Overcurrent Protection

IDMT
SIG 3I0_NP >[I_InvROC_NP_HVS] & &
[tmin_InvROC_NP_HVS] 0s
SIG Flg_InvROC_NP_HVS

BI [EBI_EF_HVS] & &


[Op_InvROC_NP_HVS]
SET [En_EF_HVS]

SIG FD_InvROC_NP_HVS

Figure 3.2-3 Logic diagram of inverse-time ground overcurrent protection with neutral current

Where:

3I 0 _ NP : the neutral current of HV side.

[I_InvROC_NP_HVS]: the picking up current setting of inverse-time ground overcurrent protection


of HV side with neutral current.

10 PCS-985T Transformer Relay.


Date: 2013-01-22
3 Operation Theory

FD_InvROC_NP_HVS: the pickup of fault detector of inverse-time ground overcurrent protection


of HV side with neutral current.

[tmin_InvROC_NP_HVS]: the minimum time delay of inverse-time overcurrent protection of HV


side with neutral current.

[Op_InvROC_NP_HVS]: the operation flag of inverse-time ground overcurrent protection of HV


side with neutral current.

PCS-985T Transformer Relay 11


Date: 2013-01-22
3 Operation Theory

12 PCS-985T Transformer Relay.


Date: 2013-01-22
4 Hardware

4 Hardware
Pin definitions of signal output modules NR1526A at slot 10 and NR1541A at slot 11 are
somewhat different to those in the corresponding general manual, and the detailed definition for
the project is shown below.

4.1 Plug-in Module Terminal Definition

NR1526A
Slot 10
NR1526A

BO_Diff 1002 1001 BO_Diff

BO_PPF_HVS 1004 1003 BO_PPF_HVS


BO_ROC_Cal/REF_ BO_ROC_Cal/REF_
1006 1005
HVS HVS
BO_EF_NP_HVS 1008 1007 BO_EF_NP_HVS

COM 1010 1009 COM

BO_OvExc 1012 1011 BO_OvExc

BO_ROC/REF_Br1 1014 1013 BO_ROC/REF_Br1

BO_ROC/REF_Br2 1016 1015 BO_ROC/REF_Br2

BO_Bak_Br11 1018 1017 BO_Bak_Br11

COM 1020 1019 COM

BO_Bak_Br12 1022 1021 BO_Bak_Br12

BO_Bak_Br21 1024 1023 BO_Bak_Br21

BO_Bak_Br22 1026 1025 BO_Bak_Br22

BO_Resv1 1028 1027 BO_Resv1

COM 1030 1029 COM

Figure 4.1-1 Pin definition of signal output module NR1526A at slot 10

The pin description of NR1526A at slot 10 is shown respectively.

Pin No. Symbol Description


1009 COM Common terminal
1009-1001 BO_Diff The signal output of operation of transformer differential protection
The signal output of operation of phase-to-phase fault protection of
1009-1003 BO_PPF_HVS
HV side
The signal output of operation of ground overcurrent protection
BO_ROC_Cal/REF_H
1009-1005 of HV side with calculated residual current or restricted earth
VS
fault protection of HV side
The signal output of operation of ground overcurrent protection
1009-1007 BO_ROC_NP_HVS
of HV side with neutral current
1019 COM Common terminal
1019-1011 BO_OvExc The signal output of over excitation alarm

PCS-985T Transformer Relay 13


Date: 2013-01-22
4 Hardware

Pin No. Symbol Description


The signal output of operation of ground overcurrent protection of LV
1019-1013 BO_ROC/REF_Br1
side A or REF protection of LV side A
The signal output of operation of ground overcurrent protection of LV
1019-1015 BO_ROC/REF_Br2
side A or REF protection of LV side B
1019-1017 BO_Bak_Br11 The signal output of backup protection of branch A1 at LV side
1029 COM Common terminal
1029-1021 BO_Bak_Br12 The signal output of backup protection of branch A2 at LV side
1029-1023 BO_Bak_Br21 The signal output of backup protection of branch B1 at LV side
1029-1025 BO_Bak_Br22 The signal output of backup protection of branch B2 at LV side
1029-1027 BO_Resv1 The reserved signal output 1 for future application
1010 COM Common terminal
1010-1002 BO_Diff The signal output of operation of transformer differential protection
The signal output of operation of phase-to-phase fault protection of
1010-1004 BO_PPF_HVS
HV side
The signal output of operation of ground overcurrent protection
BO_ROC_Cal/REF_H
1010-1006 of HV side with calculated residual current or restricted earth
VS
fault protection of HV side
The signal output of operation of ground overcurrent protection
1010-1008 BO_ROC_NP_HVS
of HV side with neutral current
1020 COM Common terminal
1020-1012 BO_OvExc The signal output of over excitation alarm
The signal output of operation of ground overcurrent protection of LV
1020-1014 BO_ROC/REF_Br1
side A or REF protection of LV side A
The signal output of operation of ground overcurrent protection of LV
1020-1016 BO_ROC/REF_Br2
side A or REF protection of LV side B
1020-1018 BO_Bak_Br11 The signal output of backup protection of branch A1 at LV side
1030 COM Common terminal
1030-1022 BO_Bak_Br12 The signal output of backup protection of branch A2 at LV side
1030-1024 BO_Bak_Br21 The signal output of backup protection of branch B1 at LV side
1030-1026 BO_Bak_Br22 The signal output of backup protection of branch B2 at LV side
1030-1028 BO_Resv1 The reserved signal output 1 for future application

14 PCS-985T Transformer Relay.


Date: 2013-01-22
4 Hardware

NR1541A
Slot 11
NR1541A

1102 1101
RLY01 BO_Diff
1104 1103

1106 1105
RLY02 BO_PPF_HVS
1108 1107

1110 1109
BO_ROC_Cal/REF_H
RLY03
VS
1112 1111

RLY04 1114 1113 BO_ROC_NP_HVS

RLY05 1116 1115 BO_OvExc

RLY06 1118 1117 BO_ROC/REF_Br1

RLY07 1120 1119 BO_ROC/REF_Br2

RLY08 1122 1121 BO_Bak_Br11

RLY09 1124 1123 BO_Bak_Br12

RLY10 1126 1125 BO_Bak_Br21

RLY11 1128 1127 BO_Bak_Br22

RLY12 1130 1129 BO_Resv1

Figure 4.1-2 Pin definition of signal output module NR1541A at slot 11

The pin description of NR1541A at slot 11 is shown below.

Pin No. Symbol Description


1101-1102 BO_Diff_1 The signal output 1 of operation of transformer differential protection
1103-1104 BO_Diff_2 The signal output 2 of operation of transformer differential protection
The signal output 1 of operation of phase-to-phase fault protection of
1105-1106 BO_PPF_HVS_1
HV side
The signal output 2 of operation of phase-to-phase fault protection of
1107-1108 BO_PPF_HVS_2
HV side
The signal output 1 of operation of ground overcurrent
BO_ROC_Cal/REF_H
1109-1110 protection of HV side with calculated residual current or
VS_1
restricted earth fault protection of HV side
The signal output 2 of operation of ground overcurrent
BO_ROC_Cal/REF_H
1111-1112 protection HV side with calculated residual current of or
VS_2
restricted earth fault protection of HV side
The signal output of operation of ground overcurrent protection
1113-1114 BO_ROC_NP_HVS
of HV side with neutral current
1115-1116 BO_OvExc The signal output of operation of overexciation
The signal output of operation of ground overcurrent protection or
1117-1118 BO_ROC/REF_Br1
restricted earth fault protection of LV side A.
The signal output of operation of ground overcurrent protection or
1119-1120 BO_ROC/REF_Br2
restricted earth fault protection of LV side B

PCS-985T Transformer Relay 15


Date: 2013-01-22
4 Hardware

Pin No. Symbol Description


The signal output of operation of backup protection of branch A1 at LV
1121-1122 BO_Bak_Br11
side.
The signal output of operation of backup protection of branch A2 at LV
1123-1124 BO_Bak_Br12
side.
The signal output of operation of backup protection of branch B1 at LV
1125-1126 BO_Bak_Br21
side.
The signal output of operation of backup protection of branch B2 at LV
1127-1128 BO_Bak_Br22
side.
1129-1130 BO_Resv1 The reserved signal output 1 for future application

16 PCS-985T Transformer Relay.


Date: 2013-01-22
5 Human Machine Interface

5 Human Machine Interface

5.1 Understand the LCD Display

5.1.1 Display When Tripping


All operation messages for the project are listed in the following table.

Table 5.1-1 Operation report list

No. Item Description

1 ManTrigDFR Oscillography function is triggered manually.

2 AlmTrigDFR Oscillography function is triggered by alarm signals.

3 FD.Pkp Any one fault detector picks up.

4 Op_InstDiff Unrestrained instantaneous differential protection operates.

5 Op_PcntDiff Biased differential protection operates.

HV side unrestrained instantaneous restricted earth fault (REF)


6 Op_InstREF_HVS
protection operates.

7 Op_PcntREF_HVS HV side biased REF protection operates.

8 Op_InstREF_Br1 Unrestrained instantaneous REF protection of LV side A operates.

9 Op_PcntREF_Br1 Biased REF protection of LV side A operates.

10 Op_InstREF_Br2 Unrestrained instantaneous REF protection of LV side B operates.

11 Op_PcntREF_Br2 Biased REF protection of LV side B operates.

Stage 1 of negative-sequence overcurrent protection of HV side


12 Op_NegOC1_HVS
operates.

Stage 2 of negative-sequence overcurrent protection of HV side


13 Op_NegOC2_HVS
operates.

14 Op_InstOC_HVS Instant overcurrent protection of HV side operates.

15 Op_DefOvExc Definite time overexcitation protection operates

16 Op_InvOvExc Inverse time overexcitation protection operates.

Delay 1 of HV side ground overcurrent protection with calculated residual


17 Op_ROC11_Cal_HVS
current operates.

Delay 2 of HV side ground overcurrent protection with calculated residual


18 Op_ROC12_Cal_HVS
current operates.

Delay 1 of HV side ground overcurrent protection with neutral current


19 Op_ROC11_NP_HVS
operates.

Delay 2 of HV side ground overcurrent protection with neutral current


20 Op_ROC22_NP_HVS
operates.

PCS-985T Transformer Relay 17


Date: 2013-01-22
5 Human Machine Interface

No. Item Description

Inverse time ground overcurrent protection with neutral current of HV


21 Op_InvROC_NP_HVS
side operates

22 Op_ROV11_HVS Delay 1 of stage 1 of HV side residual overvoltage protection operates

23 Op_ROV12_HVS Delay 2 of stage 1 of HV side residual overvoltage protection operates

Stage 1 of definite-time overcurrent protection of LV side branch A1


24 Op_OC1_Br11
operates.

Stage 2 of definite-time overcurrent protection of LV side branch A1


25 Op_OC2_Br11
operates.

26 Op_InstOC_Br11 Instant overcurrent protection of LV side branch A1 operates.

Stage 1 of definite-time overcurrent protection of LV side branch A2


27 Op_OC1_Br12
operates.

Stage 2 of definite-time overcurrent protection of LV side branch A2


28 Op_OC2_Br12
operates.

29 Op_InstOC_Br12 Instant overcurrent protection of LV side branch A2 operates.

Stage 1 of definite-time overcurrent protection of LV side branch A3


30 Op_OC1_Br13
operates.

Stage 2 of definite-time overcurrent protection of LV side branch A3


31 Op_OC2_Br13
operates.

32 Op_InstOC_Br13 Instant overcurrent protection of LV side branch A3 operates.

Stage 1 of definite-time overcurrent protection of LV side branch A4


33 Op_OC1_Br14
operates.

Stage 2 of definite-time overcurrent protection of LV side branch A4


34 Op_OC2_Br14
operates.

35 Op_InstOC_Br14 Instant overcurrent protection of LV side branch A4 operates.

36 Op_OC1_Br1 Stage 1 of definite-time overcurrent protection of LV side A operates.

37 Op_OC2_Br1 Stage 2 of definite-time overcurrent protection of LV side A operates.

38 Op_InstOC_Br1 Instant overcurrent protection of LV side A operates.

Stage 1 of definite-time overcurrent protection of LV side branch B1


39 Op_OC1_Br21
operates.

Stage 2 of definite-time overcurrent protection of LV side branch B1


40 Op_OC2_Br21
operates.

41 Op_InstOC_Br21 Instant overcurrent protection of LV side branch B1 operates.

Stage 1 of definite-time overcurrent protection of LV side branch B2


42 Op_OC1_Br22
operates.

Stage 2 of definite-time overcurrent protection of LV side branch B2


43 Op_OC2_Br22
operates.

44 Op_InstOC_Br22 Instant overcurrent protection of LV side branch B2 operates.

45 Op_OC1_Br23 Stage 1 of definite-time overcurrent protection of LV side branch B3

18 PCS-985T Transformer Relay.


Date: 2013-01-22
5 Human Machine Interface

No. Item Description

operates.

Stage 2 of definite-time overcurrent protection of LV side branch B3


46 Op_OC2_Br23
operates.

47 Op_InstOC_Br23 Instant overcurrent protection of LV side branch B3 operates.

Stage 1 of definite-time overcurrent protection of LV side branch B4


48 Op_OC1_Br24
operates.

Stage 2 of definite-time overcurrent protection of LV side branch B4


49 Op_OC2_Br24
operates.

50 Op_InstOC_Br24 Instant overcurrent protection of LV side branch B4 operates.

51 Op_OC1_Br2 Stage 1 of definite-time overcurrent protection of LV side B operates.

52 Op_OC2_Br2 Stage 2 of definite-time overcurrent protection of LV side B operates.

53 Op_InstOC_Br2 Instant overcurrent protection of LV side B operates.

54 Op_ROC1_Br1 Stage 1 of ground overcurrent protection of LV side A operates.

55 Op_ROC2_Br1 Stage 2 of ground overcurrent protection of LV side A operates.

56 Op_ROC1_Br2 Stage 1 of ground overcurrent protection of LV side B operates.

57 Op_ROC2_Br2 Stage 2 of ground overcurrent protection of LV side B operates.

58 TrpOutp1 Group 1 of tripping output contacts operate.

59 TrpOutp2 Group 2 of tripping output contacts operate.

60 TrpOutp3 Group 3 of tripping output contacts operate.

61 TrpOutp4 Group 4 of tripping output contacts operate.

62 TrpOutp5 Group 5 of tripping output contacts operate.

63 TrpOutp6 Group 6 of tripping output contacts operate.

64 TrpOutp7 Group 7 of tripping output contacts operate.

65 TrpOutp8 Group 8 of tripping output contacts operate.

66 TrpOutp9 Group 9 of tripping output contacts operate.

67 TrpOutp10 Group 10 of tripping output contacts operate.

68 TrpOutp11 Group 11 of tripping output contacts operate.

69 TrpOutp12 Group 12 of tripping output contacts operate.

70 TrpOutp13 Group 13 of tripping output contacts operate.

71 TrpOutp14 Group 14 of tripping output contacts operate.

72 TrpOutp15 Group 15 of tripping output contacts operate.

73 TrpOutp16 Group 16 of tripping output contacts operate.

PCS-985T Transformer Relay 19


Date: 2013-01-22
5 Human Machine Interface

20 PCS-985T Transformer Relay.


Date: 2013-01-22
6 Settings

6 Settings

6.1 General Settings

6.1.1 System Settings


Table 6.1-1 System settings list

No. Setting Item Range Description

1 Active_Grp 1~30 Current setting group.

2 Opt_SysFreq 0: 50Hz; 1:60Hz Select system working frequency.

Name of the protected primary equipment, such as


3 PrimaryEquip_Name Max 16 characters
transformer, line, etc.

 Setting path

Access path in menu is:

Main Menu -> Settings -> General Settings -> System Settings

6.1.2 Enable Settings

 Settings list

Table 6.1-2 Enable settings list

No. Setting item Range Description

Logic setting used to enable (1) or disable (0) transformer


1 En_Diff 0/1
differential protection

Logic setting used to enable (1) or disable (0) phase-to-phase


2 En_PPF_HVS 0/1
backup protection of HV side

Logic setting used to enable (1) or disable (0) earth fault


3 En_EF_HVS 0/1
protection of HV side

Logic setting used to enable (1) or disable (0) overexcitation


4 En_OvExc 0/1
protection

Logic setting used to enable (1) or disable (0) restricted earth


5 En_REF_HVS 0/1
fault protection of HV side

The logic setting used to enable (1) or disable (0) backup


6 En_Bak_Br11 0/1
protection of LV side branch A1

The logic setting used to enable (1) or disable (0) backup


7 En_Bak_Br12 0/1
protection of LV side branch A2

Logic setting used to enable (1) or disable (0) backup


8 En_Bak_Br13 0/1
protection of LV side branch A3

PCS-985T Transformer Relay 21


Date: 2013-01-22
6 Settings

No. Setting item Range Description

Logic setting used to enable (1) or disable (0) backup


9 En_Bak_Br14 0/1
protection of LV side branch A4

Logic setting used to enable (1) or disable (0) backup


10 En_Bak_Br1 0/1
protection of LV side A

Logic setting used to enable (1) or disable (0) backup


11 En_Bak_Br21 0/1
protection of LV side branch B1

Logic setting used to enable (1) or disable (0) backup


12 En_Bak_Br22 0/1
protection of LV side branch B2

Logic setting used to enable (1) or disable (0) backup


13 En_Bak_Br23 0/1
protection of LV side branch B3

Logic setting used to enable (1) or disable (0) backup


14 En_Bak_Br24 0/1
protection of LV side branch B4

Logic setting used to enable (1) or disable (0) backup


15 En_Bak_Br2 0/1
protection of LV side B

Logic setting used to enable (1) or disable (0) earth fault


16 En_EF_Br1 0/1
protection of LV side A

Logic setting used to enable (1) or disable (0) earth fault


17 En_EF_Br2 0/1
protection of LV side B

Logic setting used to enable (1) or disable (0) restricted earth


18 En_REF_Br1 0/1
fault protection of LV side A

Logic setting used to enable (1) or disable (0) restricted earth


19 En_REF_Br2 0/1
fault protection of LV side B

Logic setting used to enable (1) or disable (0) stub differential


20 En_StubDiff_HVS 0/1
protection of HV side

Logic setting used to enable (1) or disable (0) stub overcurrent


21 En_StubOC_HVS 0/1
protection of HV side

Logic setting used to enable (1) or disable (0) VT neutral line


22 En_VTNS 0/1
failure supervision

Logic setting used to enable (1) or disable (0) debugging


23 En_TestMode 0/1
operation through PCS-PC software.

 Setting path

Access path in menu is:

Main Menu -> Settings -> General Settings -> Enable Settings

6.1.3 Transformer System Settings

 Settings list

22 PCS-985T Transformer Relay.


Date: 2013-01-22
6 Settings

Table 6.1-3 Transformer system settings list

No. Setting Item Range Step Unit Description

1 Sn 0.01~600 0.01 MVA Capacity of the transformer

2 U1n_HVS 0.01~2000 0.01 kV Rated primary voltage of HV side

3 U1n_Br1 0.01~600 0.01 kV Rated primary voltage of LV side A

4 U1n_Br2 0.01~600 0.01 kV Rated primary voltage of LV side B

5 U1n_VT_HVS 0.01~2000 0.01 kV Rated primary voltage of VT of HV side

6 U2n_VT_HVS 0.01~200 0.01 V Rated secondary voltage of VT of HV side

7 U2n_DeltVT_HVS 0.01~330 0.01 V Rated secondary voltage of broken-delta VT of HV side

8 U1n_VT_Br1 0.01~600 0.01 kV Rated primary voltage of VT of LV side A

9 U2n_VT_Br1 0.01~200 0.01 V Rated secondary voltage of VT of LV side A

10 U1n_VT_Br2 0.01~600 0.01 kV Rated primary voltage of VT of LV side B

11 U2n_VT_Br2 0.01~200 0.01 V Rated secondary voltage of VT of LV side B

12 I1n_CT_HVS 0~60000 1 A Rated primary current of CT of HV side

13 I2n_CT_HVS 1 or 5 A Rated secondary current of CT of HV side

14 I1n_BushCT_HVS 0~60000 1 A Rated primary current of bushing CT of HV side

15 I2n_BushCT_HVS 1 or 5 A Rated secondary current of bushing CT of HV side

16 I1n_CT_Br11 0~60000 1 A Rated primary current of CT of LV side branch A1

17 I2n_CT_Br11 1 or 5 A Rated secondary current of CT of LV side branch A1

18 I1n_CT_Br12 0~60000 1 A Rated primary current of CT of LV side branch A2

19 I2n_CT_Br12 1 or 5 A Rated secondary current of CT of LV side branch A2

20 I1n_CT_Br13 0~60000 1 A Rated primary current of CT of LV side branch A3

21 I2n_CT_Br13 1 or 5 A Rated secondary current of CT of LV side branch A3

22 I1n_CT_Br14 0~60000 1 A Rated primary current of CT of LV side branch A4

23 I2n_CT_Br14 1 or 5 A Rated secondary current of CT of LV side branch A4

24 I1n_BushCT_Br1 0~60000 1 A Rated primary current of bushing CT of LV side A

25 I2n_BushCT_Br1 1 or 5 A Rated secondary current of bushing CT of LV side A

26 I1n_CT_Br21 0~60000 1 A Rated primary current of CT of LV side branch B1

27 I2n_CT_Br21 1 or 5 A Rated secondary current of CT of LV side branch B1

28 I1n_CT_Br22 0~60000 1 A Rated primary current of CT of LV side branch B2

29 I2n_CT_Br22 1 or 5 A Rated secondary current of CT of LV side branch B2

30 I1n_CT_Br23 0~60000 1 A Rated primary current of CT of LV side branch B3

31 I2n_CT_Br23 1 or 5 A Rated secondary current of CT of LV side branch B3

32 I1n_CT_Br24 0~60000 1 A Rated primary current of CT of LV side branch B4

33 I2n_CT_Br24 1 or 5 A Rated secondary current of CT of LV side branch B4

34 I1n_BushCT_Br2 0~60000 1 A Rated primary current of bushing CT of LV side B

PCS-985T Transformer Relay 23


Date: 2013-01-22
6 Settings

No. Setting Item Range Step Unit Description

35 I2n_BushCT_Br2 1 or 5 A Rated secondary current of bushing CT of LV side B

36 I1n_CT_NP_HVS 0~60000 1 A Rated primary current of neutral CT of HV side

37 I2n_CT_NP_HVS 1 or 5 A Rated secondary current of neutral CT of HV side

38 I1n_CT_Gap_HVS 0~60000 1 A Rated primary current of gap neutral CT of HV side

39 I2n_CT_Gap_HVS 1 or 5 A Rated secondary current of gap neutral CT of HV side

40 I1n_CT_NP_Br1 0~60000 1 A Rated primary current of neutral CT of LV side A

41 I2n_CT_NP_Br1 1 or 5 A Rated secondary current of neutral CT of LV side A

42 I1n_CT_NP_Br2 0~60000 1 A Rated primary current of neutral CT of LV side B

43 I2n_CT_NP_Br2 1 or 5 A Rated secondary current of neutral CT of LV side B

logic settings “1” - enable, “0” – disable

44 Yyy12_Conn 0/1 Connection group of transformer is Y/Y/Y-12

45 Ddd12_Conn 0/1 Connection group of transformer is Δ/Δ/Δ-12

46 Dyy11_Conn 0/1 Connection group of transformer is Δ/Y/Y-11

47 Ydd11_Conn 0/1 Connection group of transformer is Y/Δ/Δ-11

48 Dyy1_Conn 0/1 Connection group of transformer is Δ/Y/Y-1

49 Ydd1_Conn 0/1 Connection group of transformer is Y/Δ/Δ-1

 Setting path

Access path in menu is:

Main Menu -> Settings -> General Settings -> Tr Sys Settings

6.2 Implicit internal Settings

These settings can not be seen on LCD of device and only can be viewed and configured on PC
through PCS-PC software. These settings are usually configured in factory or configured by field
commission engineer according to the design drawing and project requirement.

6.2.1 Internal Configuration Settings

 Settings list

Table 6.2-1 Internal configuration settings list

No. Setting item Range Description

1 Cfg_Polar_CT 0~7FFF CT polarity definition

Logic setting of selecting three-phase current channel for CT of


2 Cfg_CT_HVS1 0~14
HV side 1

Logic setting of selecting three-phase current channel for CT of


3 Cfg_CT_HVS2 0~14
HV side 2

24 PCS-985T Transformer Relay.


Date: 2013-01-22
6 Settings

No. Setting item Range Description

Logic setting of selecting three-phase current channel for


4 Cfg_BushCT_HVS 0~14
bushing CT of HV side

Logic setting of selecting three-phase current channel for CT of


5 Cfg_CT_Br11 0~14
LV side branch A1

Logic setting of selecting three-phase current channel for CT of


6 Cfg_CT_Br12 0~14
LV side branch A2

Logic setting of selecting three-phase current channel for CT of


7 Cfg_CT_Br13 0~14
LV side branch A3

Logic setting of selecting three-phase current channel for CT of


8 Cfg_CT_Br14 0~14
LV side branch A4

Logic setting of selecting three-phase current channel for


9 Cfg_BushCT_Br1 0~14
bushing CT of LV side A

Logic setting of selecting three-phase current channel for CT of


10 Cfg_CT_Br21 0~14
LV side branch B1

Logic setting of selecting three-phase current channel for CT of


11 Cfg_CT_Br22 0~14
LV side branch B2

Logic setting of selecting three-phase current channel for CT of


12 Cfg_CT_Br23 0~14
LV side branch B3

Logic setting of selecting three-phase current channel for CT of


13 Cfg_CT_Br24 0~14
LV side branch B4

Logic setting of selecting three-phase current channel for


14 Cfg_BushCT_Br2 0~14
bushing CT of LV side B

Logic setting of selecting zero-sequence current channel for


15 Cfg_CT_NP_HVS 0~8
neutral point zero-sequence CT of HV side

Logic setting of selecting zero-sequence current channel for gap


16 Cfg_CT_Gap_HVS 0~8
zero-sequence CT of HV side

Logic setting of selecting zero-sequence current channel for


17 Cfg_CT_NP_Br1 0~8
neutral point zero-sequence CT of LV side A

Logic setting of selecting zero-sequence current channel for


18 Cfg_CT_NP_Br2 0~8
neutral point zero-sequence CT of LV side B

Logic setting of selecting CTs for transformer differential


19 Cfg_CT_Diff 0~F
protection

Logic setting of selecting CTs for overcurrent protection of HV


20 Cfg_CT_OC_HVS 0~3
side

21 Cfg_CT_Abnor_HVS 0~3 Logic setting of selecting CTs for abnormal protection of HV side

Logic setting of selecting CTs for restricted earth fault protection


22 Cfg_CT_REF_HVS 0~7
of HV side

PCS-985T Transformer Relay 25


Date: 2013-01-22
6 Settings

No. Setting item Range Description

Logic setting of selecting CTs for restricted earth fault protection


23 Cfg_CT_REF_Br1 0~7
of LV side A

Logic setting of selecting CTs for restricted earth fault protection


24 Cfg_CT_REF_Br2 0~7
of LV side B

Configuration setting of selecting which tripping outputs will


25 Cfg_Ext_TrpOutp 0~1FFFF
delay drop off

26 t_Ext_TrpOutp 0~0.45s The pulse width of tripping output to delay drop off

6.2.2 Label Settings

 Settings list

Table 6.2-2 Label settings list

No. Setting item Description

1 Name_Trp1 Label setting of tripping output 1

2 Name_Trp2 Label setting of tripping output 2

3 Name_Trp3 Label setting of tripping output 3

4 Name_Trp4 Label setting of tripping output 4

5 Name_Trp5 Label setting of tripping output 5

6 Name_Trp6 Label setting of tripping output 6

7 Name_Trp7 Label setting of tripping output 7

8 Name_Trp8 Label setting of tripping output 8

9 Name_Trp9 Label setting of tripping output 9

10 Name_Trp10 Label setting of tripping output 10

11 Name_Trp11 Label setting of tripping output 11

12 Name_Trp12 Label setting of tripping output 12

13 Name_Trp13 Label setting of tripping output 13

14 Name_Trp14 Label setting of tripping output 14

15 Name_Trp15 Label setting of tripping output 15

16 Name_Trp16 Label setting of tripping output 16

6.3 Protection Settings

6.3.1 Transformer Differential Protection Settings


 Settings list

26 PCS-985T Transformer Relay.


Date: 2013-01-22
6 Settings

Table 6.3-1 Transformer differential protection settings list

No. Setting Item Range Step Unit Description

Pickup current setting of biased differential protection


1 I_Pkp_PcntDiff 0.1~1.5 0.01 A
of transformer

Current setting of unrestrained instantaneous


2 I_InstDiff 2~14 0.01 A
differential protection of transformer

Current setting of transformer differential current


3 I_Alm_Diff 0.05~1 0.01 A
abnormality alarm

The first slope of sensitive biased differential


4 Slope1_PcntDiff 0.05~0.5 0.01
protection

The second slope of sensitive biased differential


5 Slope2_PcntDiff 0.5~0.8 0.01
protection

6 k_Harm_PcntDiff 0.1~0.35 0.01 Restraint coefficient of second harmonic

Tripping output logic setting of differential protection


7 TrpLog_Diff 0000~1FFFF
of transformer

logic settings “1” - enable, “0” - disable

Logic setting of enabling unrestrained instantaneous


8 En_InstDiff 0/1
differential protection of transformer

Logic setting of enabling biased differential protection


9 En_PcntDiff 0/1
of transformer

Logic setting for selecting the restraint blocking


principle.
10 Opt_Inrush_Ident 0/1
“0”: discrimination by harmonics
“1”: discrimination by waveform distortion

Logic setting of selecting whether biased differential


protection being controlled during CT circuit failure
“1”: the transformer biased current differential
11 Opt_CTS_Blk_PcntDiff 0/1
protection will be blocked and alarm will be issued.
“0”: alarm will be issued but transformer biased
current differential protection will not be blocked

 Setting path

Access path in menu is:

Main Menu -> Settings -> Tr Diff Prot Settings -> Tr Diff Prot Settings

6.3.2 HV Side Restricted Earth Fault Protection Settings


 Settings list

PCS-985T Transformer Relay 27


Date: 2013-01-22
6 Settings

Table 6.3-2 HV side restricted earth fault (REF) protection settings list

No. Setting Item Range Step Unit Description

1 I_Pkp_PcntREF_HVS 0.1~1.5 0.01 A Pickup current setting of biased REF protection of HV side

Current setting of unrestrained instantaneous REF


2 I_InstREF_HVS 2~14 0.01 A
protection of HV side

Current setting for HV side REF protection operates to


3 I_Alm_REF_HVS 0.05~1 0.01 A
alarm

4 Slope_PcntREF_HVS 0.3~0.8 0.01 Restraint coefficient of HV side biased REF protection

5 TrpLog_REF_HVS 0000~1FFFF Tripping output logic setting of HV side REF protection

logic settings “1” - enable, “0” – disable

Logic setting of enabling unrestrained instantaneous REF


6 En_InstREF_HVS 0/1
protection of HV side

7 En_PcntREF_HVS 0/1 Logic setting of enabling biased REF protection of HV side

 Setting path

Access path in menu is:

Main Menu -> Settings -> HVS Prot Settings -> HVS REF Prot Settings

6.3.3 HV Side Phase-to-phase Backup Protection Settings

 Settings list

Table 6.3-3 HV side phase-to-phase backup protection settings list

No. Setting Item Range Step Unit Description

Current setting of instaneous overcurrent


1 I_InstOC_HVS 0.05~100 0.01 A
protection of HV side

Time delay of instaneous overcurrent protection


2 t_InstOC_HVS 0~10 0.01 s
of HV side

Tripping output logic setting of instaneous


3 TrpLog_InstOC_HVS 0000~1FFFF
overcurrent protection of HV side

Current setting of stage 1 of negative-sequence


4 I_NegOC1_HVS 0.05~100 0.01 A
overcurrent protection of HV side

Time delay of stage 1 of negative-sequence


5 t_NegOC1_HVS 0~10 0.01 s
overcurrent protection of HV side

Tripping output logic setting of stage 1 of


6 TrpLog_NegOC1_HVS 0000~1FFFF negative-sequence overcurrent protection of HV
side

Current setting of stage 2 of negative-sequence


7 I_NegOC2_HVS 0.05~100 0.01 A
overcurrent protection of HV side

8 t_NegOC2_HVS 0~10 0.01 s Time delay of stage 2 of negative-sequence

28 PCS-985T Transformer Relay.


Date: 2013-01-22
6 Settings

No. Setting Item Range Step Unit Description

overcurrent protection of HV side

Tripping output logic setting of stage 2 of


9 TrpLog_NegOC2_HVS 0000~1FFFF negative-sequence overcurrent protection of HV
side

Current setting of overload alarm element of HV


10 I_Alm_OvLd_HVS 0.05~20 0.01 A
side

Time delay of overload alarm element of HV


11 t_Alm_OvLd_HVS 0~10 0.01 s
side

Current setting of stage 1 of overload cooling


12 I_InitCool1_OvLd_HVS 0.05~20 0.01 A
initiation element of HV side

Time delay of stage 1 of overload cooling


13 t_InitCool1_OvLd_HVS 0~25 0.01 s
initiation element of HV side

Current setting of stage 2 of overload cooling


14 I_InitCool2_OvLd_HVS 0.05~20 0.01 A
initiation element of HV side

Time delay of stage 2 of overload cooling


15 t_InitCool2_OvLd_HVS 0~25 0.01 s
initiation element of HV side

Current setting of overload block on-load tap


16 I_OvLd_Blk_OLTC_HVS 0.05~20 0.01 A
changing element of HV side

Time delay of overload block on-load tap


17 t_OvLd_Blk_OLTC_HVS 0~10 0.01 s
changing element of HV side

logic settings “1” - enable, “0” - disable

Logic setting of enabling stage 1 of overcurrent


18 En_NegOV_Ctrl_NegOC_HVS 0/1 protection of HV side being controlled by
voltage control elements

Logic setting of enabling overload alarm


19 En_OvLd_HVS 0/1
element of HV side

Logic setting of enabling stage 1 of overload


20 En_InitCool1_OvLd_HVS 0/1
cooling initiation element of HV side

Logic setting of enabling stage 2 of overload


21 En_InitCool2_OvLd_HVS 0/1
cooling initiation element of HV side

Logic setting of enabling overload block on-load


22 En_OvLd_Blk_OLTC_HVS 0/1
tap changing element of HV side

 Setting path

Access path in menu is:

Main Menu -> Settings -> HVS Prot Settings -> HVS PPF Prot Settings

6.3.4 HV Side Earth Fault Protection Settings


 Settings list

PCS-985T Transformer Relay 29


Date: 2013-01-22
6 Settings

Table 6.3-4 HV side earth fault protection settings list

No. Setting Item Range Step Unit Description

Voltage setting of residual overvoltage


1 V_ROV_VCE_HVS 2~100 0.01 V element for controlling ground overcurrent
protection of HV side

Current setting of definite-time ground


2 I_ROC1_Cal_HVS 0.1~100 0.01 A overcurrent protection of HV side with
calculated residual current

Time delay 1 of definite-time ground


3 t_ROC11_Cal_HVS 0~10 0.01 s overcurrent protection of HV side with
calculated residual current

Tripping output logic setting of delay 1 of


definite-time ground overcurrent
4 TrpLog_ROC11_Cal_HVS 0000~1FFFF
protection of HV side with calculated
residual current

Time delay 2 of definite-time ground


5 t_ROC12_Cal_HVS 0~10 0.01 s overcurrent protection of HV side with
calculated residual current

Tripping output logic setting of delay 2 of


definite-time ground overcurrent
6 TrpLog_ROC12_Cal_HVS 0000~1FFFF
protection of HV side with calculated
residual current

Current setting of stage 2 of definite-time


7 I_ROC1_NP_HVS 0.1~100 0.01 A ground overcurrent protection of HV side
with neutral current

Time delay 1 of stage 2 of definite-time


8 t_ROC11_NP_HVS 0~10 0.01 s ground overcurrent protection of HV side
with neutral current

Tripping output logic setting of delay 1 of


stage 2 of definite-time ground
9 TrpLog_ROC11_NP_HVS 0000~1FFFF
overcurrent protection of HV side with
neutral current

Time delay 2 of stage 2 of definite-time


10 t_ROC12_NP_HVS 0~10 0.01 s ground overcurrent protection of HV side
with neutral current

Tripping output logic setting of delay 2 of


stage 2 of definite-time ground
11 TrpLog_ROC12_NP_HVS 0000~1FFFF
overcurrent protection of HV side with
neutral current

Operating current of inverse-time ground


12 Ib_InvROC_NP_HVS 0.5~20 0.01 A
overcurrent protection of HV side with

30 PCS-985T Transformer Relay.


Date: 2013-01-22
6 Settings

No. Setting Item Range Step Unit Description

neutral current

Time multiplier setting of inverse-time


13 TMS_InvROC_NP_HVS 0.05~10 0.01 ground overcurrent protection with neutral
current

Minimum time delay of inverse-time


14 tmin_InvROC_NP_HVS 0~10 0.01 s ground overcurrent protection of HV side
with neutral current

Logic setting of selecting time


characteristic curve of inverse-time
overcurrent protection of HV side with
neutral current
15 Opt_InvROC_NP_HVS 0~3
0: IEC Normal inverse
1: IEC Very inverse
2: IEC Extremely inverse
3: IEC Long-time inverse

Tripping output logic setting of


16 TrpLog_InvROC_NP_HVS 0000~1FFFF inverse-time ground overcurrent
protection of HV side with neutral current

logic settings “1” - enable, “0” - disable

Logic setting of enabling definite-time


ground overcurrent protection with
17 En_VCE.ROV_Ctrl_ROC1_Cal_HVS 0/1 calculated residual current being
controlled by residual voltage control
element

Logic setting of enabling definite-time


ground overcurrent protection of HV side
18 En_VCE.ROV_Ctrl_ROC1_NP_HVS 0/1
with neutral current being controlled by
residual voltage control element

Logic setting of enabling of definite-time


ground overcurrent protection of HV side
19 En_Hm_Ctrl_ROC1_NP_HVS 0/1
with neutral current being controlled by
harmonic

Logic setting of enabling definite-time


ground overcurrent protection of HV side
20 En_Dir_Ctrl_ROC1_Cal_HVS 0/1
with calculated residual current being
controlled by residual directional element.

Logic setting of enabling definite-time


ground overcurrent protection of HV side
21 En_Dir_Ctrl_ROC1_NP_HVS 0/1
with neutral current being controlled by
residual directional element

PCS-985T Transformer Relay 31


Date: 2013-01-22
6 Settings

No. Setting Item Range Step Unit Description

Logic setting of selecting the direction of


ground overcurrent protection of HV side
“1”: the direction is transformer and reach
22 Opt_Dir_ROC_HVS 0/1
angle is 225º.
“0”: the direction is power system and
reach angle is 75º.

Logic setting of selecting how ground


overcurrent protection of HV side
responses when VT circuit fails.

“1”: when VT circuit failure at one side is


detected, directional relay and voltage
control element at the same side will be
disabled but overcurrent relay on the
23 Opt_VTS_Ctrl_ROC_HVS 0/1 same side can still be controlled by
voltage control elements of other side if
corresponding logic setting is set as “1”.

“0”: when VT circuit failure at one side is


detected, the overcurrent relay will
become an overcurrent relay without
directional element and voltage control
element.

 Setting path

Access path in menu is:

Main Menu -> Settings -> HVS Prot Settings -> HVS EF Prot Settings

6.3.5 Overexcitation Protection Settings


 Settings list

Table 6.3-5 Overexcitation protection settings list

No. Setting Item Range Step Unit Description

Overexcitation multiple setting for definite time


1 k_DefOvExc1 1~2 0.01
overexcitation protection operates to trip

2 t_DefOvExc1 0.1~3000 0.1 s Time delay of definite time overexcitation protection

Tripping output logic setting of definite time


3 TrpLog_DefOvExc1 0000~1FFFF
overexcitation protection

Overexcitation multiple setting for definite time


4 k_Alm_DefOvExc 1~2 0.01
overexcitation operates to alarm

Time delay for definite time overexcitation operates to


5 t_Alm_DefOvExc 0.1~25 0.1 s
alarm

32 PCS-985T Transformer Relay.


Date: 2013-01-22
6 Settings

No. Setting Item Range Step Unit Description

Upper limit overexcitation multiple setting of inverse


6 k0_InvOvExc 1~2 0.01
time overexcitation protection: n0

Time delay corresponds to upper limit overexcitation


7 t0_InvOvExc 1~3000 0.1 s
multiple: t0

Overexcitation multiple corresponds to the point n1 of


8 k1_InvOvExc 1~2 0.01
inverse time overexcitation curve

Time delay corresponds to the point n1 of inverse time


9 t1_InvOvExc 1~3000 0.1 s
overexcitation curve

Overexcitation multiple corresponds to the point n2 of


10 k2_InvOvExc 1~2 0.01
inverse time overexcitation curve

Time delay corresponds to the point n2 of inverse time


11 t2_InvOvExc 1~3000 0.1 s
overexcitation curve

Overexcitation multiple corresponds to the point n3 of


12 k3_InvOvExc 1~2 0.01
inverse time overexcitation curve

Time delay corresponds to the point n3 of inverse time


13 t3_InvOvExc 1~3000 0.1 s
overexcitation curve

Overexcitation multiple corresponds to the point n4 of


14 k4_InvOvExc 1~2 0.01
inverse time overexcitation curve

Time delay corresponds to the point n4 of inverse time


15 t4_InvOvExc 1~3000 0.1 s
overexcitation curve

Overexcitation multiple corresponds to the point n5 of


16 k5_InvOvExc 1~2 0.01
inverse time overexcitation curve

Time delay corresponds to the point n5 of inverse time


17 t5_InvOvExc 1~3000 0.1 s
overexcitation curve

Overexcitation multiple corresponds to the point n6 of


18 k6_InvOvExc 1~2 0.01
inverse time overexcitation curve

Time delay corresponds to the point n6 of inverse time


19 t6_InvOvExc 1~3000 0.1 s
overexcitation curve

Lower limit overexcitation multiple setting of inverse


20 k7_InvOvExc 1~2 0.01
time overexcitation protection: n7

Time delay corresponds to lower limit overexcitation


21 t7_InvOvExc 1~3000 0.1 s
multiple setting: t7

Tripping output logic setting of inverse time


22 TrpLog_InvOvExc 0000~1FFFF
overexcitation protection

 Setting path

Access path in menu is:

Main Menu -> Settings -> HVS Prot Settings -> OvExc Prot Settings

PCS-985T Transformer Relay 33


Date: 2013-01-22
6 Settings

6.3.6 Settings of Backup Protection of Each Branch of LV Side A


In this section, x=1~4 corresponds to LV side branch A1~A4 respectively
 Settings list

Table 6.3-6 LV side branch A1/A2/A3/A4 backup protection settings list

No. Setting Item Range Step Unit Description

Setting of negative-sequence voltage controlled


1 V_NegOV_VCE_Br1x 1~20 0.01 V
element of LV side branch Ax

Setting of phase-to-phase undervoltage controlled


2 Vpp_UV_VCE_Br1x 10~100 0.01 V
element of LV side branch Ax

Current setting of instant overcurrent protection of LV


3 I_InstOC_Br1x 0.1~100 0.01 A
side branch Ax

Time delay of instant overcurrent protection of LV side


4 t_InstOC_Br1x 0~10 0.01 s
branch Ax

Tripping output logic setting of instant overcurrent


5 TrpLog_InstOC_Br1x 0000~1FFFF
protection of LV side branch Ax

Current setting of stage 1 of overcurrent protection of


6 I_OC1_Br1x 0.1~100 0.01 A
LV side branch Ax

Time delay of stage 1 of overcurrent protection of LV


7 t_OC1_Br1x 0~10 0.01 s
side branch Ax

Tripping output logic setting of stage 1 of overcurrent


8 TrpLog_OC1_Br1x 0000~1FFFF
protection of LV side branch Ax

Current setting of stage 2 of overcurrent protection of


9 I_OC2_Br1x 0.1~100 0.01 A
LV side branch Ax

Time delay of stage 2 of overcurrent protection of LV


10 t_OC2_Br1x 0~10 0.01 s
side branch Ax

Tripping output logic setting of stage 2 of overcurrent


11 TrpLog_OC2_Br1x 0000~1FFFF
protection of LV side branch Ax

logic settings “1” - enable, “0” - disable

Logic setting of enabling stage 1 of overcurrent


12 En_VCE_Ctrl_OC1_Br1x 0/1 protection of LV side branch Ax being controlled by
voltage controlled element

Logic setting of enabling stage 2 of overcurrent


13 En_VCE_Ctrl_OC2_Br1x 0/1 protection of LV side branch Ax being controlled by
voltage controlled element

Logic setting of enabling accelerating tripping of stage


14 En_OC2_SOTF_Br1x 0/1
2 of overcurrent protection of LV side branch Ax

Protection performance option if VT circuit fails.


15 Opt_VTS_Ctrl_OC_Br1x 0/1 “1”: when VT circuit failure is detected, voltage
controlled element of corresponding side will be

34 PCS-985T Transformer Relay.


Date: 2013-01-22
6 Settings

No. Setting Item Range Step Unit Description

disabled.
“0”: when VT circuit failure of one side is detected, the
overcurrent element of LV side branch Ax will not be
controlled by voltage controlled element.

 Setting path

Access path in menu is:

Main Menu -> Settings -> LVS Prot Settings -> Br1x Bak Prot Settings

6.3.7 Settings of Backup Protection of Each Branch of LV Side B


In this section, x=1~4 corresponds to LV side branch B1~B4 respectively
 Settings list

Table 6.3-7 LV side branch B1/B2/B3/B4 backup protection settings list

No. Setting Item Range Step Unit Description

Setting of negative-sequence voltage controlled


1 V_NegOV_VCE_Br2x 1~20 0.01 V
element of LV side branch Bx

Setting of phase-to-phase undervoltage controlled


2 Vpp_UV_VCE_Br2x 10~100 0.01 V
element of LV side branch Bx

Current setting of instant overcurrent protection of LV


3 I_InstOC_Br2x 0.1~100 0.01 A
side branch Bx

Time delay of instant overcurrent protection of LV side


4 t_InstOC_Br2x 0~10 0.01 s
branch Bx

Tripping output logic setting of instant overcurrent


5 TrpLog_InstOC_Br2x 0000~1FFFF
protection of LV side branch Bx

Current setting of stage 1 of overcurrent protection of


6 I_OC1_Br2x 0.1~100 0.01 A
LV side branch Bx

Time delay of stage 1 of overcurrent protection of LV


7 t_OC1_Br2x 0~10 0.01 s
side branch Bx

Tripping output logic setting of stage 1 of overcurrent


8 TrpLog_OC1_Br2x 0000~1FFFF
protection of LV side branch Bx

Current setting of stage 2 of overcurrent protection of


9 I_OC2_Br2x 0.1~100 0.01 A
LV side branch Bx

Time delay of stage 2 of overcurrent protection of LV


10 t_OC2_Br2x 0~10 0.01 s
side branch Bx

Tripping output logic setting of stage 2 of overcurrent


11 TrpLog_OC2_Br2x 0000~1FFFF
protection of LV side branch Bx

logic settings “1” - enable, “0” - disable

12 En_VCE_Ctrl_OC1_Br2x 0/1 Logic setting of enabling stage 1 of overcurrent

PCS-985T Transformer Relay 35


Date: 2013-01-22
6 Settings

No. Setting Item Range Step Unit Description

protection of LV side branch Bx being controlled by


voltage controlled element

Logic setting of enabling stage 2 of overcurrent


13 En_VCE_Ctrl_OC2_Br2x 0/1 protection of LV side branch Bx being controlled by
voltage controlled element

Logic setting of enabling accelerating tripping of stage


14 En_OC2_SOTF_Br2x 0/1
2 of overcurrent protection of LV side branch Bx

Protection performance option if VT circuit fails.


“1”: when VT circuit failure is detected, voltage
controlled element of corresponding side will be
15 Opt_VTS_Ctrl_OC_Br2x 0/1 disabled.
“0”: when VT circuit failure of one side is detected, the
overcurrent element of LV side branch Bx will not be
controlled by voltage controlled element.

 Setting path

Access path in menu is:

Main Menu -> Settings -> LVS Prot Settings -> Br2x Bak Prot Settings

6.3.8 Settings of Backup Protection of LV Side A


The current used in LV side A backup protection is derived from the LV side A bushing CT.
 Settings list

Table 6.3-8 LV side A backup protection settings list

No. Setting Item Range Step Unit Description

Setting of negative-sequence voltage controlled


1 V_NegOV_VCE_Br1 1~20 0.01 V
element of LV side A

Setting of phase-to-phase undervoltage controlled


2 Vpp_UV_VCE_Br1 10~100 0.01 V
element of LV side A

Current setting of instant overcurrent protection of LV


3 I_InstOC_Br1 0.1~100 0.01 A
side A

Time delay of instant overcurrent protection of LV side


4 t_InstOC_Br1 0~10 0.01 s
A

Tripping output logic setting of instant overcurrent


5 TrpLog_InstOC_Br1 0000~1FFFF
protection of LV side A

Current setting of stage 1 of overcurrent protection of


6 I_OC1_Br1 0.1~100 0.01 A
LV side A

Time delay of stage 1 of overcurrent protection of LV


7 t_OC1_Br1 0~10 0.01 s
side A

36 PCS-985T Transformer Relay.


Date: 2013-01-22
6 Settings

No. Setting Item Range Step Unit Description

Tripping output logic setting of stage 1 of overcurrent


8 TrpLog_OC1_Br1 0000~1FFFF
protection of LV side A

Current setting of stage 2 of overcurrent protection of


9 I_OC2_Br1 0.1~100 0.01 A
LV side A

Time delay of stage 2 of overcurrent protection of LV


10 t_OC2_Br1 0~10 0.01 s
side A

Tripping output logic setting of stage 2 of overcurrent


11 TrpLog_OC2_Br1 0000~1FFFF
protection of LV side A

logic settings “1” - enable, “0” - disable

Logic setting of enabling stage 1 of overcurrent


12 En_VCE_Ctrl_OC1_Br1 0/1 protection of LV side A being controlled by voltage
controlled element

Logic setting of enabling stage 2 of overcurrent


13 En_VCE_Ctrl_OC2_Br1 0/1 protection of LV side A being controlled by voltage
controlled element

Protection performance option if VT circuit fails.


“1”: when VT circuit failure is detected, voltage
controlled element of LV side A will be disabled.
14 Opt_VTS_Ctrl_OC_Br1 0/1
“0”: when VT circuit failure of one side is detected, the
overcurrent element of LV side A will not be controlled
by voltage controlled element.

 Setting path

Access path in menu is:

Main Menu -> Settings -> LVS Prot Settings -> Br1 Bak Prot Settings

6.3.9 Settings of Backup Protection of LV Side B


The current used in LV side B backup protection is derived from the LV side B bushing CT.
 Settings list

Table 6.3-9 LV side B backup protection settings list

No. Setting Item Range Step Unit Description

Setting of negative-sequence voltage controlled


1 V_NegOV_VCE_Br2 1~20 0.01 V
element of LV side B

Setting of phase-to-phase undervoltage controlled


2 Vpp_UV_VCE_Br2 10~100 0.01 V
element of LV side B

Current setting of instant overcurrent protection of LV


3 I_InstOC_Br2 0.1~100 0.01 A
side B

4 t_InstOC_Br2 0~10 0.01 s Time delay of instant overcurrent protection of LV side

PCS-985T Transformer Relay 37


Date: 2013-01-22
6 Settings

No. Setting Item Range Step Unit Description

Tripping output logic setting of instant overcurrent


5 TrpLog_InstOC_Br2 0000~1FFFF
protection of LV side B

Current setting of stage 1 of overcurrent protection of


6 I_OC1_Br2 0.1~100 0.01 A
LV side B

Time delay of stage 1 of overcurrent protection of LV


7 t_OC1_Br2 0~10 0.01 s
side B

Tripping output logic setting of stage 1 of overcurrent


8 TrpLog_OC1_Br2 0000~1FFFF
protection of LV side B

Current setting of stage 2 of overcurrent protection of


9 I_OC2_Br2 0.1~100 0.01 A
LV side B

Time delay of stage 2 of overcurrent protection of LV


10 t_OC2_Br2 0~10 0.01 s
side B

Tripping output logic setting of stage 2 of overcurrent


11 TrpLog_OC2_Br2 0000~1FFFF
protection of LV side B

logic settings “1” - enable, “0” - disable

Logic setting of enabling stage 1 of overcurrent


12 En_VCE_Ctrl_OC1_Br2 0/1 protection of LV side B being controlled by voltage
controlled element

Logic setting of enabling stage 2 of overcurrent


13 En_VCE_Ctrl_OC2_Br2 0/1 protection of LV side B being controlled by voltage
controlled element

Protection performance option if VT circuit fails.


“1”: when VT circuit failure is detected, voltage
controlled element of LV side B will be disabled.
14 Opt_VTS_Ctrl_OC_Br2 0/1
“0”: when VT circuit failure of one side is detected, the
overcurrent element of LV side B will not be controlled
by voltage controlled element.

 Setting Path

Access path in menu is:

Main Menu -> Settings -> LVS Prot Settings -> Br2 Bak Prot Settings

6.3.10 Settings of Earth Fault Protection of LV Side A


 Settings list

Table 6.3-10 LV side A earth fault protection settings list

No. Setting Item Range Step Unit Description

1 I_ROC1_Br1 0.1~100 0.01 A Current setting of stage 1 of ground overcurrent

38 PCS-985T Transformer Relay.


Date: 2013-01-22
6 Settings

No. Setting Item Range Step Unit Description

protection of LV side A

Time delay of stage 1 of ground overcurrent protection


2 t_ROC1_Br1 0~10 0.01 s
of LV side A

Tripping output logic setting of stage 1 of ground


3 TrpLog_ROC1_Br1 0000~1FFFF
overcurrent protection of LV side A

Current setting of stage 2 of ground overcurrent


4 I_ROC2_Br1 0.1~100 0.01 A
protection of LV side A

Time delay of stage 2 of ground overcurrent protection


5 t_ROC2_Br1 0~10 0.01 s
of LV side A

Tripping output logic setting of stage 2 of ground


6 TrpLog_ROC2_Br1 0000~1FFFF
overcurrent protection of LV side A

Voltage setting of residual overvoltage alarm element


7 V_Alm_ROV_Br1 5~100 0.01 V
of LV side A

Time delay of residual overvoltage alarm element of


8 t_Alm_ROV_Br1 0~10 0.01 s
LV side A

logic settings “1” - enable, “0” - disable

Logic setting of enabling residual overvoltage alarm


9 En_Alm_ROV_Br1 0/1
element of LV side A

 Setting path

Access path in menu is:

Main Menu -> Settings -> LVS Prot Settings -> Br1 EF Prot Settings

6.3.11 Settings of Earth Fault Protection of LV Side B


 Settings list

Table 6.3-11 LV side B earth fault protection settings list

No. Setting Item Range Step Unit Description

Current setting of stage 1 of ground overcurrent


1 I_ROC1_Br2 0.1~100 0.01 A
protection of LV side B

Time delay of stage 1 of ground overcurrent protection


2 t_ROC1_Br2 0~10 0.01 s
of LV side B

Tripping output logic setting of stage 1 of ground


3 TrpLog_ROC1_Br2 0000~1FFFF
overcurrent protection of LV side B

Current setting of stage 2 of ground overcurrent


4 I_ROC2_Br2 0.1~100 0.01 A
protection of LV side B

Time delay of stage 2 of ground overcurrent protection


5 t_ROC2_Br2 0~10 0.01 s
of LV side B

PCS-985T Transformer Relay 39


Date: 2013-01-22
6 Settings

No. Setting Item Range Step Unit Description

Tripping output logic setting of stage 2 of ground


6 TrpLog_ROC2_Br2 0000~1FFFF
overcurrent protection of LV side B

Voltage setting of residual overvoltage alarm element


7 V_Alm_ROV_Br2 5~100 0.01 V
of LV side B

Time delay of residual overvoltage alarm element of LV


8 t_Alm_ROV_Br2 0~10 0.01 s
side B

logic settings “1” - enable, “0” - disable

Logic setting of enabling residual overvoltage alarm


9 En_Alm_ROV_Br2 0/1
element of LV side B

 Setting path

Access path in menu is:

Main Menu -> Settings -> LVS Prot Settings -> Br2 EF Prot Settings

6.3.12 Settings of Restricted Earth Fault Protection of LV Side A


 Settings list

Table 6.3-12 LV side A restricted earth fault protection settings list

No. Setting Item Range Step Unit Description

Pickup current setting of biased REF protection of LV


1 I_Pkp_PcntREF_Br1 0.1~1.5 0.01 A
side A

Current setting of unrestrained instantaneous REF


2 I_InstREF_Br1 2~14 0.01 A
protection of LV side A

Current setting for LV side A REF protection operates to


3 I_Alm_REF_Br1 0.05~1 0.01 A
alarm

4 Slope_PcntREF_Br1 0.3~0.8 0.01 Restraint coefficient of LV side A biased REF protection

5 TrpLog_REF_Br1 0000~1FFFF Tripping output logic setting of LV side A REF protection

logic settings “1” - enable, “0” - disable

Logic setting of enabling unrestrained instantaneous


6 En_InstREF_Br1 0/1
REF protection of LV side A

Logic setting of enabling biased REF protection of LV


7 En_PcntREF_Br1 0/1
side A

 Setting explanation

Please refer to Section 6.3.2 for details.

 Setting path

Access path in menu is:

Main Menu -> Settings -> LVS Prot Settings -> Br1 REF Prot Settings

40 PCS-985T Transformer Relay.


Date: 2013-01-22
6 Settings

6.3.13 Settings of Restricted Earth Fault Protection of LV side B


 Settings list

Table 6.3-13 LV side B restricted earth fault protection settings list

No. Setting Item Range Step Unit Description

Pickup current setting of biased REF protection of LV


1 I_Pkp_PcntREF_Br2 0.1~1.5 0.01 A
side B

Current setting of unrestrained instantaneous REF


2 I_InstREF_Br2 2~14 0.01 A
protection of LV side B

Current setting for LV side B REF protection operates to


3 I_Alm_REF_Br2 0.05~1 0.01 A
alarm

4 Slope_PcntREF_Br2 0.3~0.8 0.01 Restraint coefficient of LV side B biased REF protection

5 TrpLog_REF_Br2 0000~1FFFF Tripping output logic setting of LV side B REF protection

logic settings “1” - enable, “0” - disable

Logic setting of enabling unrestrained instantaneous


6 En_InstREF_Br2 0/1
REF protection of LV side B

Logic setting of enabling biased REF protection of LV


7 En_PcntREF_Br2 0/1
side B

 Setting explanation

Please refer to Section 6.3.2 for details.

 Setting path

Access path in menu is:

Main Menu -> Settings -> LVS Prot Settings -> Br2 REF Prot Settings

6.3.14 Stub Differential Protection Settings

 Settings list

Table 6.3-14 Stub differential protection settings list

No. Setting Item Range Step Unit Description

Pickup current setting of stub biased differential


1 I_Pkp_StubDiff 0.1~1.5 0.01 A
protection

Current setting of stub differential current abnormality


2 I_Alm_StubDiff 0.05~1 0.01 A
alarm

Restraint coefficient of stub biased differential


3 Slope_StubDiff 0.3~0.8 0.01
protection

Tripping output logic setting of stub biased differential


4 TrpLog_StubDiff 0000~1FFFF
protection

logic settings “1” - enable, “0” - disable

PCS-985T Transformer Relay 41


Date: 2013-01-22
6 Settings

No. Setting Item Range Step Unit Description

5 En_StubDiff 0/1 Logic setting of enabling stub differential protection

Logic setting of selecting whether stub biased


differential protection being controlled during CT
circuit failure
6 Opt_CTS_Blk_StubDiff 0/1 “1”: the stub biased current differential protection will
be blocked and alarm will be issued.
“0”: alarm will be issued but stub biased current
differential protection will not be blocked

 Setting path

Access path in menu is:

Main Menu -> Settings -> Stub Prot Settings -> Stub Diff Prot Settings

6.3.15 Stub Overcurrent Protection Settings

 Settings list

Table 6.3-15 Stub overcurrent protection settings list

No. Setting Item Range Step Unit Description

Current setting of instaneous overcurrent protection of


1 I_InstOC_Stub 0.05~100 0.01 A
stub

Time delay of instaneous overcurrent protection of


2 t_InstOC_Stub 0~10 0.01 s
stub

Tripping output logic setting of instaneous overcurrent


3 TrpLog_InstOC_Stub 0000~1FFFF
protection of stub

Current setting of stage 1 of overcurrent protection of


4 I_OC1_Stub 0.05~100 0.01 A
stub

5 t_OC1_Stub 0~10 0.01 s Time delay of stage 1 of overcurrent protection of stub

Tripping output logic setting of stage 1 of overcurrent


6 TrpLog_OC1_Stub 0000~1FFFF
protection of stub

 Setting path

Access path in menu is:

Main Menu -> Settings -> Stub Prot Settings -> Stub OC Prot Settings

6.4 Device Setup

6.4.1 Device Settings


 Settings list

42 PCS-985T Transformer Relay.


Date: 2013-01-22
6 Settings

Table 6.4-1 Device settings list

No. Setting Item Range Description

Select encoding format of header (HDR) file


1 HDR_EncodedMode GB18030, UTF-8 COMTRADE recording file. Default value is
“UTF-8”.

Select the caption language sent to SAS via


IEC103 protocol. Default value is 0.
2 Opt_Caption_103 0~2 0: Current language;
1: Fixed Chinese
2: Fixed English

3 Un_BinaryInput 24V, 48V, 110V, 220V Voltage level of binary input

 Setting explanation

1. [HDR_EncodedMode]

The setting is to select encoding format of header file .Default value of [HDR_EncodeMode] is
1(i.e. UTF-8 code) and please set it to 0(i.e. GB18030) according to the special requirement.

2. [Opt_Caption_103]

The setting is to select the caption language of IEC103 protocol. Please set it to “1” (i.e. Fixed
Chinese) if the SAS is supplied by a Chinese manufacturer.

0: Current language, i.e. the caption language changes with device LCD language.

1: Fixed Chinese, i.e. Chinese is fixedly selected as the caption language.

2: Fixed English, i.e. English is fixedly selected as the caption language.

3. [Un_BinaryInput]

The setting is used to set the voltage level of binary input module. 24V and 48V can be selected
when low-voltage BI module is equipped and 110V or 220V can be selected when high voltage
BI module is equipped.

 Setting path

Access path in menu is:

Main menu -> Settings -> Device Setup -> Device Settings

6.4.2 Communication Settings


 Settings list

Table 6.4-2 Communication settings list

No. Settings item Range Description

000.000.000.000~
1 IP_LAN1 IP address of Ethernet port 1.
255.255.255.255

PCS-985T Transformer Relay 43


Date: 2013-01-22
6 Settings

No. Settings item Range Description

000.000.000.000~
2 Mask_LAN1 Subnet mask of Ethernet port1.
255.255.255.255

000.000.000.000~
3 IP_LAN2 IP address of Ethernet Ethernet port 2.
255.255.255.255

000.000.000.000~
4 Mask_LAN2 Subnet mask of Ethernet port 2.
255.255.255.255

5 En_LAN2 0: disable, 1: enable Enable/disable the IP address of Ethernet port 2.

6 IP_LAN3 0: disable, 1: enable IP address of Ethernet port 3.

000.000.000.000~
7 Mask_LAN3 Subnet mask of Ethernet port 3.
255.255.255.255

8 En_LAN3 0: disable, 1: enable Enable/disable the IP address of Ethernet port 3.

9 IP_LAN4 0: disable, 1: enable IP address of Ethernet port 4.

000.000.000.000~
10 Mask_LAN4 Subnet mask of Ethernet port 4.
255.255.255.255

11 En_LAN4 0: disable, 1: enable Enable/disable the IP address of Ethernet port 4.

000.000.000.000~
12 Gateway Gateway of router
255.255.255.255

Enable/disable sending message in broadcast


13 En_Broadcast 0: disable, 1: enable
mode via network. (IEC103).

Communication address between the protective


14 Addr_RS485A 0~255 device with the SCADA or RTU via RS-485 serial
port 1.

4800,9600,19200,
15 Baud_RS485A Baud rate of rear RS-485 serial port 1.
38400,57600,115200 bps

Communication protocol of rear RS-485 serial port


1.
0: IEC60870-5-103
16 Protocol_RS485A 0~9
1: Modbus
2: Reserved
Others: Not available

Communication address between the protective


17 Addr_RS485B 0~255 device with the SCADA or RTU via RS-485 serial
port 2.

4800,9600,19200,
18 Baud_RS485B Baud rate of rear RS-485 serial port 2.
38400,57600,115200 bps

44 PCS-985T Transformer Relay.


Date: 2013-01-22
6 Settings

No. Settings item Range Description

Communication protocol of rear RS-485 serial port


2.
0: IEC60870-5-103
19 Protocol_RS485B 0~9
1: Modbus
2: Reserved
Others: Not available

4800,9600,
20 Baud_Printer 19200,38400, 51600, Baud rate of printer port
115200 bps

0: disable
21 En_AutoPrint Enable/disable automatic printing function
1: enable

Conventional
SAS Select the mode of time synchronization of
22 Opt_TimeSyn
Advanced equipment.
NoTimeSyn

The address of the external SNTP clock


000.000.000.000~
23 IP_Server_SNTP synchronization server sending SNTP message to
255.255.255.255
the equipment.

The local time zone also referred to as the hour


24 OffsetHour_UTC -12~12hrs
offset hour from UTC .

25 OffsetMinute_UTC 0~60min The offset minute of local time from UTC.

0: Tripping reports will not be uploaded via


communication port;
26 En_Maintenance 0/1
1: Tripping reports will not be uploaded via
communication port.

 Setting path

Access path in menu is:

Main Menu -> Settings -> Device Setup -> Comm Settings

PCS-985T Transformer Relay 45


Date: 2013-01-22
6 Settings

46 PCS-985T Transformer Relay.


Date: 2013-01-22
7 Manual Version History

7 Manual Version History


In the latest version of the instruction manual, several descriptions on existing features have been
modified.

Manual version and modification history records

Manual
Software
Version Date Description of change
Version
Source New
PCS-985T
1.00 2013-01-22 Form the original manual.
R1.00_ECKF110355

PCS-985T Transformer Relay 47


Date: 2013-01-22
7 Manual Version History

48 PCS-985T Transformer Relay.


Date: 2013-01-22

You might also like