You are on page 1of 4

B ) PANTRY EXTRACT FAN - PEF / R1

HYDRAULIC PRESSURE LOSS CALCULATION


PROJECT SOHAR AROMATICS DATE
BUILDING ADMINISTRATION PREPARED BY
SERVICE PANTRY EXTRACT FAN
DRG.NO
FAN REF PEF/R1

SECTION SIZE ITEM FLOW Qty / TOTAL


LENGTH LOSS
mm lps No./m pa
1-2 150 x 150 DIFFUSER 50 1 no. 33.00
150 x 150 DUCT 50 0.6m 0.53
150 x 150 ELBOW 50 2nos. 1.60
150 x 150 DUCT 50 4.0m 3.56
150 x 150 TAPER 50 1 no. 0.53
300 x 100 TEE 100 1 no. 0.95
250 x 250 DUCT 150 1.0m 0.36
2-3 250 x 250 45 ELBOW 150 1 no. 0.43
250 x 250 DUCT 150 1.0m 0.36
250 x 250 45 ELBOW 150 3 nos. 0.15
250 x 250 DUCT 150 1.5m 0.54
3-4 250 x 250 ELBOW 150 3 nos. 3.30
250 x 250 DUCT 150 10.0m 3.57
250 x 250 TEE 150 1 no. 0.29
4-5 200 x 100 TEE 100 1 no. 0.72
300 x 300 DUCT 250 6.0m 2.14
300 x 300 ELBOW 250 2 nos. 2.21
5-6 300 x 300 DUCT 250 1.0m 0.36
300 x 300 VCD 250 1 no. 10.00
_ TRANSITION 250 1 no. 0.58
300 x 300 DUCT 250 1.0m 0.36
300 x 300 VCD 250 1 no. 10.00
300 x 300 MESH 250 1 no. 6.00

SUB TOTAL 81.53 Pa


SAFETY 20% 16.31 Pa

GRAND TOTAL 97.84 Pa

FAN (PEF/R1) - TWIN TYPE, DUCT MOUNTED, WEATHER PROOF


DUTY - 250 LPS @ 98.0 Pa
C ) PANTRY EXTRACT FAN - PEF / R2

HYDRAULIC PRESSURE LOSS CALCULATION


PROJECT SOHAR AROMATICS DATE
BUILDING ADMINISTRATION PREPARED BY
SERVICE PANTRY EXTRACT FAN
DRG.NO
FAN REF PEF/R2

SECTION SIZE ITEM FLOW Qty / TOTAL


LENGTH LOSS
mm lps No./m pa
1-2 225 x 225 DIFFUSER 75 1 no. 21.00
225 x 225 DUCT 75 0.6m 0.10
225 x 225 TEE 75 2 nos. 0.20
400 x 200 DUCT 150 2.8m 2.90
400 x 100 ELBOW 150 1 no. 2.53
400 x 100 DUCT 150 8.0m 8.31
400 x 100 TAPER 150 1 no. 0.83
2-3 400 x 200 DUCT 250 4.0m 3.02
400 x 200 TAPER 250 0.5m 0.38
300 x 300 DUCT 250 6.5m 2.41
300 x 100 TEE 100 1 no. 0.71
3-4 300 x 300 DUCT 350 7.1m 4.35
300 x 300 ELBOW 350 1 no. 1.97
4-5 300 x 300 DUCT 350 1.0m 0.61
300 x 300 VCD 350 1 no. 10.00
_ TRANSITION 350 2 nos. 0.98
300 x 300 DUCT 350 1.0m 0.61
300 x 300 BDD 350 1 no. 10.00
300 x 300 ELBOW 350 1 no. 1.97
300 x 300 MESH 350 1 no. 6.00

SUB TOTAL 78.88 Pa


SAFETY 20% 15.78 Pa

GRAND TOTAL 94.65 Pa

FAN (PEF/R2) - TWIN TYPE, DUCT MOUNTED, WEATHER PROOF


DUTY - 350 LPS @ 95.0 Pa
D ) TOILET EXTRACT FAN - TEF / R1

HYDRAULIC PRESSURE LOSS CALCULATION


PROJECT SOHAR AROMATICS DATE
BUILDING ADMINISTRATION PREPARED BY
SERVICE TOILET EXTRACT FAN
DRG.NO
FAN REF TEF/R1
SECTION SIZE ITEM FLOW Qty / TOTAL
LENGTH LOSS
mm lps No./m pa
1-2 225 x 225 DIFFUSER 80 1 no. 30.00
225 x 225 DUCT 80 0.6m 0.10
225 x 225 TEE 80 3 nos. 0.30
300 x 200 DUCT 160 1.0m 0.72
300 x 200 ELBOW 160 1 no. 1.65
300 x 200 DUCT 160 5.5m 3.94
300 x 200 TEE 160 2 nos. 1.15
500 x 300 TAPER 320 1 no. 0.57
500 x 300 ELBOW 650 3 nos. 8.19
2-3 500 x 300 DUCT 650 6.0m 3.37
500 x 300 DUCT 650 4.9m 2.75
500 x 300 TAPER 650 1 no. 0.45
550 x 300 TEE 585 1 no. 0.49
550 x 550 DUCT 1275 1.9m 0.68
550 x 550 ELBOW 1275 1 no. 2.38
3-4 550 x 550 DUCT 1275 1.0m 0.36
550 x 550 VCD 1275 1 no. 15.00
_ TRANS 1275 2 nos. 2.00
550 x 550 DUCT 1275 1.0m 0.36
550 x 550 BDD 1275 1 no. 15.00
550 x 550 MESH 1275 1 no. 10.00

SUB TOTAL 99.45 Pa


SAFETY 20% 19.89 Pa

GRAND TOTAL 119.34 Pa

FAN (TEF/R1) - TWIN TYPE, DUCT MOUNTED, WEATHER PROOF


DUTY - 1275 LPS @ 120.0 Pa
E ) TOILET EXTRACT FAN - TEF / R2

HYDRAULIC PRESSURE LOSS CALCULATION


PROJECT SOHAR AROMATICS DATE
BUILDING ADMINISTRATION PREPARED BY
SERVICE TOILET EXTRACT FAN
DRG.NO
FAN REF TEF/R2

SECTION SIZE ITEM FLOW Qty / TOTAL


LENGTH LOSS
mm lps No./m pa
1-2 225 x 225 DIFFUSER 112.5 1 no. 40.00
225 x 225 DUCT 112.5 0.6m 0.23
255 x 225 TEE 112.5 1 no. 0.31
300 x 150 DUCT 112.5 3.2m 1.95
300 x 150 TEE 112.5 2 no. 0.49
2-3 300 x 300 DUCT 337.5 4.0m 2.51
300 x 300 ELBOW 337.5 1 no. 1.97
300 x 300 DUCT 337.5 1.2m 0.75
300 x 300 TAPER 337.5 1 no. 0.50
3-4 300 x 200 TEE 282.0 2 nos. 1.00
400 x 400 DUCT 713.5 1.8m 1.06
400 x 400 ELBOW 713.5 1 no. 2.72
4-5 400 x 400 DUCT 713.5 4.9m 2.90
400 x 400 TAPER 713.5 1 no. 0.47
500 x 300 TEE 666.5 1 no. 0.49
550 x 550 DUCT 1360.0 1.9m 0.92
5-6 550 x 550 ELBOW 1360.0 1 no. 3.19
550 x 550 DUCT 1360.0 1.0m 0.48
550 x 550 VCD 1360.0 1 no. 15.00
_ TRANSITION 1360.0 2 nos. 2.00
550 x 550 DUCT 1360.0 1.0m 0.59
550 x 550 BDD 1360.0 1 no. 15.00
550 x 550 ELBOW 1360.0 1 no. 3.19
550 x 550 MESH 1360.0 1 no. 10.00

SUB TOTAL 107.71 Pa


SAFETY 20% 21.54 Pa

GRAND TOTAL 129.25 Pa

FAN (TEF/R2) - TWIN TYPE, DUCT MOUNTED, WEATHER PROOF


DUTY - 1360 LPS @ 130.0 Pa