Discharge Current Data - Manufacturer

Hours Minutes Seconds


Cell Type Rated Ah
10 8 5 3 2 1.5 1 30 20 15 10 5 1 30 5 1

830 83 102 156 217 272 313 370 464 501 550 606 636 761 830 1010 1108

Capacity Rating Factor (Kt) � �=�� � − ((� ��−�� 𝟏) (� �−� 𝟏))/((� �−� 𝟏))REFERENCE: IEEE
RECOMMENDED
PRACTICE FOR SIZING
NICKEL-CADMIUM
BATTERIES FOR
Discharge Time t1 Time t2 from Ampere for Ampere for Factor Kt1 Factor Kt2 Factor Kt for STATIONARY
Time t from data data time t1 (A) time t2 (A) for time t1 for time t2 time t APPLICATION

10.000 10.0 1.000 83.000 1.000 10.000 830.000 10.000

1.000 1.0 1.000 761.000 1.000 1.091 830.000 1.091

(IEEE Std 1115-2000)