CIRCUITO 5 ALUMBRADO CAMARA DE REFRESCOS 1 8 440 4.81 # 10 1X20 127 10 KA 0.052 0.00
RESISTENCIA DE CAMARA DE
CIRCUITO 6 1 2286 14.45 # 10 1X30 127 10 KA 0.040 1.59
REFRESCO
MINISPLIT
CIRCUITO 7 1 1430 9.03 # 10 2X20 220 10 KA 0.012 2.37
OFICINAS
CIRCUITO 11 ENFRIADOR DE HIELO 1 1286 14.06 #10 1X20 127 10 KA 0.025 3.29
CIRCUITO 13 CONTACTO DE CARNES FRIAS 1 1250 7.90 # 10 1PX30 127 10 KA 0.025 0.00
VENTILADOR 1
CIRCUITO 17 8 224 2.47 # 10 1X15 126 9 KA 0.017 #NAME?
VENTILADOR 1
CIRCUITO 18 8 224 2.45 # 10 1X15 127 10 KA 0.025 #NAME?
VENTILADOR 1
CIRCUITO 19 8 224 2.45 # 10 1X15 127 10 KA 0.035 #NAME?
VENTILADOR 1
CIRCUITO 20 8 224 2.45 # 10 1X15 127 10 KA 0.040 #NAME?
CIRCUITO 21 BOMBA SUMERGIBLE 1 1200 7.59 #12 1X15 127 10 KA 0.030 #NAME?
29742.5 214.01
CIRCUITO 6 BASCULA Y REBANADORA DE CARNES 2 1270 13.89 # 12 1X20 127 10 KA 0.020 2.62
CIRCUITO 7 ALUMBRADO DE BODEGA 2DA PLANTA 8 200 2.19 # 10 1X15 127 10 KA 0.038 2.58
5530.5 60.48
TABLERO SQUARE-D #3
CIRCUITO 5 ANUNCIO LUMINOSO 1 108 1.18 #12 1X20 127 10 KA 0.035 0.57
CIRCUITO 6 LUMINARIA PASILLO 4 660 7.22 #12 1X10 127 10 KA 0.030 1.48
4346 47.53
39619 322.02
ITM DE 3PX150A PLANTA ALTA 1 39619 1/0 3X150 220 20KA 0.04 1897.73
144578.01
920 227700
FACTOR DE DEMANDA 87%
CARGA TOTAL KW 39619.00
KVA TOTAL 44021.11
AMP. TOTAL 322.02
MINISPLIT
C4 20.83 # 10 3.61
OFICINAS
4500 METROS DE TUBERIA PVC PARED DELGADA 3/4 PULG. DE DIAM. (PARA EMPOTRAR
EN PARED)
5500 METROS DE TUBERIA PVC PARED DELGADA 2 PULG. DE DIAM. (PARA EMPOTRAR
EN PARED)
P=V*I
kw
8
8.47
KVA POR FASE
4.8959537572
FASES TIPO I.T.M.s`
3 COSTA SI
barra derivadora ponle u
donde estala galera
Nota: Para cumplir lo establecido en 250-51, los conductores de puesta a tierra de los equipos
podrían ser de mayor tamaño que lo especificado en esta Tabla.
arra derivadora ponle unas rayitas 1,2,3,4,5
onde estala galera