Bouyancy Check

Column Marking BW21 (BW19 similar)

Ground Water Table approximate at RL 105.6 m

Basement 2 at RL 100.0 m

Basement Slab Thickness 0.45 m

Water Bouyancy Pressure 59.4 kN/m2

Tributary Area of Column = 6.5 x 4.5 = 29.25 m2

Uplift due to water = 29.25 x 59.4


= 1736 kN

Dead weight on pile (exclude pilecap) = 2475 kN

Net Loading = 739 kN (No Uplift)

Bouyancy Check

Column Marking BW20

Ground Water Table approximate at RL 105.60 m

Basement 2 at RL 100.550 m

Basement Slab Thickness 0.45 m

Water Bouyancy Pressure 54.0 kN/m2

Tributary Area of Column = 8.5 x 3 = 25.5 m2

Uplift due to water = 25.5 x 54.0


= 1376 kN

Dead weight on pile (exclude pilecap) = 1185 kN

Net Loading = -191 kN (Uplift Force)


< PE's -46T, OK
Bouyancy Check

Column Marking BW3 (BW2 similar)

Ground Water Table approximate at RL 105.60 m

Basement 2 at RL 100.335 m

Basement Slab Thickness 0.45 m

Water Bouyancy Pressure 56.1 kN/m2

Tributary Area of Column = 8.5 x 3 = 25.5 m2

Uplift due to water = 25.5 x 56.1


= 1430 kN

Dead weight on pile (exclude pilecap) = 1185 kN

Net Loading = -245 kN (Uplift Force)


< PE's -65T , OK

Bouyancy Check

Column Marking BW4 (BW1, BW5 to BW15 similar)

Ground Water Table approximate at RL 105.60 m

Basement 2 at RL 102.575 m

Basement Slab Thickness 0.45 m

Water Bouyancy Pressure 34.1 kN/m2

Tributary Area of Column = 6.5 x 3.3 = 21.45 m2

Uplift due to water = 21.45 x 34.1


= 731 kN

Dead weight on pile (exclude pilecap) = 912 kN

Net Loading = 181 kN (No Uplift)


Bouyancy Check

Column Marking BW17

Ground Water Table approximate at RL 105.60 m

Basement 2 at RL 101.125 m

Basement Slab Thickness 0.45 m

Water Bouyancy Pressure 48.3 kN/m2

Tributary Area of Column = 6.75 x 3 = 20.25 m2

Uplift due to water = 20.25 x 48.3


= 978 kN

Dead weight on pile (exclude pilecap) = 984 kN

Net Loading = 6 kN (No Uplift)

Bouyancy Check

Column Marking BW18

Ground Water Table approximate at RL 105.60 m

Basement 2 at RL 100.84 m

Basement Slab Thickness 0.45 m

Water Bouyancy Pressure 51.1 kN/m2

Tributary Area of Column = 8.5 x 3 = 25.5 m2

Uplift due to water = 25.5 x 51.1


= 1303 kN

Dead weight on pile (exclude pilecap) = 1185 kN

Net Loading = -118 kN (Uplift Force)


approx to PE's -10T , OK

Dead weigth on pile (include pilecap) = 1195 kN

Net Loading = -109 kN approx to PE's -10T , OK