You are on page 1of 31

Micrologic control units

2.0 A, 5.0 A, 6.0 A and 7.0 A


Low Voltage Products

User manual

We do more with electricity.


Micrologic control units
2.0 A, 5.0 A, 6.0 A and 7.0 A

Discovering your control unit 2


Identifying your control unit 2
Overview of functions 4
Setting your control unit 10
Selecting the type of neutral protection 10
Setting procedure 11
Setting the Micrologic 2.0 A control unit 12
Setting the Micrologic 5.0 A control unit 13
Setting the Micrologic 6.0 A control unit 14
Setting the Micrologic 7.0 A control unit 15
Fault and status indications 16
Resetting the fault indications
and checking battery status 16
Testing the earth-fault
and earth-leakage functions 17
Menus 18
Accessing the menus 18
Measuring phase currents 19
Displaying the maximum current values 20
Resetting the maximum current values 21
Viewing the settings 22
Technical appendix 24
Tripping curves 24
Changing the long-time rating plug 26
Zone selective interlocking (ZSI) 27
Digital display 28
Thermal memory 29

1 Micrologic A Schneider Electric


Discovering your Identifying your control unit
control unit Designations

All Compact NS800-3200 and Masterpact Micrologic 2.0 A: basic protection and ammeter
NT and NW circuit breakers are equipped

E51352A
E51384A
Micrologic 2.0 A
t
with a Micrologic control unit
that can be changed on site.
Control units are designed to protect
power circuits and connected loads. 100 %

40 %

menu

long time

0 Ir Isd I
Ir tr alarm
.8 (s) 4
8
.7 .9 12
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In at 6 Ir

instantaneous
Isd
3 4 5
2.5
2
1.5
x Ir
6

10
8 Long time + Instantaneous
setting

Micrologic 2.0 A
E51450A

Micrologic 5.0 A: selective protection and ammeter


E51385A

E51354A
Micrologic 5.0 A
t

X
Y
100 %

40 %

Z Ir

.6
.5
.7

.4

Isd 4
3
menu

long time
.8

x In
short time

5
.9

1
.95
tr
(s) 4 8 12

.98 1

tsd
(s)
2

.5
16
20
24
at 6 Ir

.4 .4 .3
Ii
6
alarm

instantaneous
8 10
0 Ir Isd Ii I

Long time + Short time + Instantaneous


2.5 6 .3 .2 4 12
2 8 .2 .1 3 15
1.5 10 .1 2 0 2 off
on I t

X: type of protection
x Ir x In
setting delay

c 2 for basic protection


c 5 for selective protection
c 6 for selective + earth-fault protection
c 7 for selective + earth-leakage protection
Micrologic 6.0 A: selective + earth-fault protection and
Y: version number ammeter
identification of the control-unit generation.
E51387A

Micrologic 6.0 A
t
E51395A
E51354A

t
"0" signifies the first generation.

Z: type of measurement 2
I t on
c A for "ammeter"
c P for "power meter" 100 %

2
I t off
c H for "harmonic meter" 40 %

c no indication: no measurements
menu

long time
Ir tr alarm
.8 (s) 4
8
.7 .9 12
.6
.5
.4
x In
1
.95 2
.98 1
.5
16
20
24
at 6 Ir
0 Ir Isd Ii I 0 Ig I
short time instantaneous
Isd tsd Ii
3
4 5 (s) .4 .4 . 3 6
8 10
2.5
2
1.5
x Ir
setting
10
6
8
.3
.2
on
.1 2 0
I t
delay
.2
.1
4
3
2
x In
12
15
off Long time + Short time Earth-fault protection
test
Ig
C
B
D E F

I
G
H
tg
(s)
.3
.2
.4 .4 .3

.1 2 0
.2
.1
+ Instantaneous
A
on I t off
ground fault

Micrologic 7.0 A: selective + earth-leakage protection and


ammeter
t
E51388A

E51354A

E51452A

Micrologic 7.0 A
t

100 %

40 %

menu

I∆n
long time
Ir

.6
.5
.7
.8
.9
tr
(s) 4
.95 2
.98 1
8
12
16
20
alarm

0 Ir Isd Ii I 0 I
.4 1 .5 24
x In at 6 Ir

short time instantaneous


Isd

2.5
2
3
4 5
6
8
tsd
(s)
.3
.2
.4 .4 .3

.1 2 0
.2
.1
Ii

4
3
6
8
10
12
15
Long time + Short time Earth-leakage protection
1.5 10 on I t off 2 off

+ Instantaneous
x Ir x In
setting delay
test

I∆n 5 7 ∆I 230 350


3
2 10
140
1 20 800
.5 30 60
earth leakage

2 Micrologic A Schneider Electric


Presentation

E51389A

E51390A
1 top fastener 1
2 bottom fastener
3 protective cover 10
4 cover opening point logic
7. 0A
Micro
5 lead-seal fixture for protective cover
6 long-time rating plug 31
7 screw for long-time rating plug 12
8 connection with circuit breaker 11
9 infrared link with communications interfaces 13 9
10 terminal block for external connections 100 %

11 housing for battery 30 40 %


7
12 digital display
13 three-phase bargraph and ammeter 29
alarm

menu long
time tr 8 12
(s) 4 16
Ir .8 .9
.7 2 20
.95
1 24
.6 .98 .5 6 Ir
.5 at

Adjustment dials .4 x In
1

5
6
14 long-time current setting Ir
15 long-time tripping delay tr 3 4
16 short-time pickup Isd
17 short-time tripping delay tsd 8
2
18 instantaneous pick-up Isd
19 instantaneous pick-up Ii
20 earth-fault pick-up Ig Micrologic 7.0 A Micrologic 2.0 A
21 earth-fault tripping delay tg
E51391A

E51394A
22 earth-leakage pick-up I∆n 24 25 26 27 28
23 earth-leakage tripping delay ∆t Ir
.7
long time
.8
.9
tr
(s) 4
8
12
alarm
7
.6 .95 2 16
14 .5
.4 1
.98 1
.5
20
24
Indications Micrologic 7.0 A
15
x In
instantaneous
at 6 Ir

Isd
3 4 5
31 2.5 6

24 LED indicating long-time tripping 18 2


1.5 10
8

x Ir
25 LED indicating short-time tripping setting

26 LED indicating earth-fault 12


or earth-leakage tripping 33
27 LED indicating auto-protection tripping
28 LED indicating an overload
13
Navigation 100 % Micrologic 5.0 A
E51393A

29 navigation button to change menus 40 % 28


30 navigation button to view menu contents long time
Ir .8 tr 8
alarm
7
31 button for fault-trip reset and battery test 14 .6
.7 .9 (s) 4
.95 2
12
16
.5 .98 1 20
.4 1 .5 24
x In at 6 Ir

29 menu 30 15 short time instantaneous


Isd tsd Ii
3 4 5 (s) . 4 .4 .3 6 8 10
6 .3 .2 12
Test 16 2.5
2 8 .2 .1
4
3 15

14
Ir
.7
long time
.8
.9
tr
(s) 4
8
12
alarm 28 1.5
x Ir
10
on
.1 2 0
I t
2
x In
off

.6
.5
.95 2
.98 1
16
20
17 setting delay

32 test button for earth-fault and earth-leakage 15 .4


x In
1 .5 24
at 6 Ir 7
protection Isd
short time
tsd
instantaneous 19 33
3 4 5 (s).4 .4 .3 Ii
6
8
10
.3 .2
33 test connector 16
2.5
2
6
8 .2 .1
4
3
12
15 19
10
.1 2 0
1.5 on I t off 2 off
x Ir x In
17 I∆n
(A)
setting
∆I
(ms)
delay

230
test
32
5 350
3 7
2 10

22 1
.5 30
20
140

60
800 33 Micrologic 6.0 A
earth leakage
E51392A

23 15 long time
Ir
.7
.8
.9
tr
(s) 4
8
12
alarm 28
.6 .95 2 16
14 .5 .98 1
.4
x In
1 .5
20
24
at 6 Ir
7
17 Isd
short time
tsd Ii
instantaneous

3
4
5 (s) .4 .4 .3 6
8
10
2.5 .3 .2
16 2
6
8 .2 .1
4
3
12
15 19
1.5 10 .1 2 0 2 off
x Ir on I t off x In
21 Ig
setting
tg
delay
test
32
D
E
F (s) .4 .4 .3
C G .3 .2
20 B H .2
.1 2 0
.1
33
A I
on I t off
ground fault

3 Micrologic A Schneider Electric


Discovering your Overview of functions
control unit Current protection

Protection settings
Depending on the type of installation, it is possible to set the tripping curve of your
control unit using the parameters presented below.
Micrologic 2.0 A

E51358A
t
1

0 Ir Isd I
1. current setting Ir (long time)
2. tripping delay tr (long time) for 6 x Ir
3. pick-up Isd (instantaneous)

Micrologic 5.0 A, 6.0 A, Micrologic 6.0 A Micrologic 7.0 A


7.0 A
t t t
E51359A

E51386A

E51396A
1
2
I t on 2
I t on
2
2
I t off 2
1 I t off 1
3
4 2 2
5

0 Ir Isd Ii I 0 Ig I 0 I∆n I
1. current setting Ir 1. pick-up Ig (earth fault) 1. pick-up I∆n
(long time) 2. tripping delay tg (earth leakage)
2. tripping delay tr (earth fault) 2. tripping delay ∆t
(long time) for 6 x Ir (earth leakage)
3. pick-up Isd (short time)
4. tripping delay tsd
(short time)
5. pick-up Ii
(instantaneous)

Long-time protection
The long-time protection function protects cables (phases and neutral)
against overloads. This function is based on true rms measurements.

Thermal memory
The thermal memory continuously accounts for the amount of heat in the cables,
both before and after tripping, whatever the value of the current (presence of
an overload or not). The thermal memory optimises the long-time protection
function of the circuit breaker by taking into account the temperature rise in the
cables. The thermal memory assumes a cable cooling time of approximately
15 minutes.

Long-time current setting Ir and standard tripping delay tr


Micrologic control unit 2.0 A and 5.0 A
current setting Ir = In x …(*) 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
tripping between other ranges or disable by changing rating plug
1.05 and 1.20 x Ir
time delay (s) tr at 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
accuracy: tr at 6 x Ir 0.5 1 2 4 8 12 16 20 24
0 to -20 % tr at 7.2 x Ir 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

* In: circuit breaker rating

Setting accuracy of the Ir setting may be enhanced by using a different long-time


rating plug.
See the technical appendix "Changing the long-time rating plug".

4 Micrologic A Schneider Electric


For the characteristics and external wiring Short-time protection
of the zone selective interlocking function, c the short-time protection function protects the distribution system against
impedant short-circuits
see the technical appendix on c the short-time tripping delay can be used to ensure discrimination with a
"Zone selective interlocking". downstream circuit breaker
c this function carries out true rms measurements.
The portable test kit can be used to test
c the I2t ON and I2t OFF options enhance discrimination with downstream
the wiring between circuit breakers protection devices
for the zone selective interlocking function. c use of I2t curves with short-time protection:
v I2t OFF selected: the protection function implements a constant time curve;
v I2t ON selected: the protection function implements an I2t inverse-time
curve up to 10 Ir. Above 10 Ir, the time curve is constant.

c zone selective interlocking (ZSI)


The short-time and earth-fault protection functions enable time discrimination
by delaying the upstream devices to provide the downstream devices the time
required to clear the fault. Zone selective interlocking can be used to obtain total
discrimination between circuit breakers using external wiring.

Short-time pick-up Isd and tripping delay tsd


Micrologic control unit 2.0 A, 5.0 A, 6.0 A and 7.0 A
pick-up Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10
accuracy ± 10 %
time delay settings I2t OFF 0 0.1 0.2 0.3 0.4
(ms) at 10 Ir I2t ON 0.1 0.2 0.3 0.4
I2t ON or tsd (max resettable time) 20 80 140 230 350
I2t OFF tsd (max break time) 80 140 200 320 500

Instantaneous protection
c the instantaneous-protection function protects the distribution system
against solid short-circuits. Contrary to the short-time protection function,
the tripping delay for instantaneous protection is not adjustable.
The tripping order is sent to the circuit breaker as soon as current exceeds
the set value, with a fixed time delay of 20 milliseconds.
c this function carries out true rms measurements.

Instantaneous pick-up Isd


Micrologic control unit 2.0 A
pick-up Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10
accuracy ± 10 %

Instantaneous pick-up Ii
Micrologic control unit 5.0 A, 6.0 A and 7.0 A
pick-up li = In x … (*) 2 3 4 6 8 10 12 15 OFF
accuracy ± 10 %

* In: circuit-breaker rating

5 Micrologic A Schneider Electric


Discovering your Overview of functions
control unit Current protection

Protection of the fourth pole on four-pole circuit breakers


Protection of the neutral conductor depends on the distribution system.
There are three possibilities.

Type of neutral Description.


Neutral unprotected The distribution system does not require protection
of the neutral conductor.
Neutral protection The cross-sectional area of the neutral conductor
at 0.5 In is half that of the phase conductors.
c the long-time current setting Ir for the neutral is equal
to half the setting value
c the short-time pick-up Isd for the neutral is equal
to half the setting value
c the instantaneous pick-up Isd (Micrologic 2.0 A)
for the neutral is equal to half the setting value
c the instantaneous pick-up Ii (Micrologic 5.0 A / 6.0 A /
7.0 A) for the neutral is equal to the setting value.
Neutral protection The cross-sectional area of the neutral conductor is equal
at In to that of the phase conductors.
c the long-time current setting Ir for the neutral is equal
to the setting value
c the short-time pick-up Isd for the neutral is equal to
the setting value
c the instantaneous pick-ups Isd and Ii for the neutral
are equal to the setting value.

Earth-fault protection on Micrologic 6.0 A


c an earth fault in the protection conductors can provoke local temperature rise
at the site of the fault or in the conductors.
The purpose of the earth-fault protection function is to eliminate this type of fault.
c there are two types of earth-fault protection.

Type Description
Residual c the function determines the zero-phase sequence
current, i.e. the vectorial sum of the phase and neutral
currents
c it detects faults downstream of the circuit breaker.
Source Ground Return c using a special external sensor, this function
directly measures the fault current returning
to the transformer via the earth cable
c it detects faults both upstream and downstream
of the circuit breaker
c the maximum distance between the sensor
and the circuit breaker is ten metres.

c earth-fault and neutral protection are independent and can therefore be


combined.

Earth-fault pick-up Ig and tripping delay tg


The pick-up and tripping-delay values can be set independently and are identical
for both the residual and "source ground return" earth-fault protection functions.

Micrologic control unit 6.0 A


pick-up Ig = In x … (*) A B C D E F G H I
accuracy In ≤ 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
± 10 % 400 A < In ≤ 1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
In > 1200 A 500 A 640 A 720 A 800 A 880 A 960 A 1040 A 1120 A 1200 A
time delay settings I2t OFF 0 0.1 0.2 0.3 0.4
(ms) at 10 In (*) I2t ON 0.1 0.2 0.3 0.4
I2t ON or tg (max resettable time) 20 80 140 230 350
I2t OFF tg (max break time) 80 140 200 320 500

* In: circuit-breaker rating

6 Micrologic A Schneider Electric


Current protection and alarms

Earth-leakage protection on Micrologic 7.0 A


c the earth-leakage protection function primarily protects people against indirect
contact because an earth-leakage current can provoke an increase in the potential
of the exposed conductive parts. The earth-leakage pick-up value I∆n is displayed
directly in amperes and the tripping delay follows a constant-time curve
c an external rectangular sensor is required for this function
c this function is inoperative if the long-time rating plug is not installed
c d protected against nuisance tripping.
c k DC-component withstand class A up to 10 A.

Pick-up value I∆n and tripping delay ∆t


Micrologic control unit 7.0 A
pick-up I∆n 0.5 1 2 3 5 7 10 20 30
accuracy
0 to - 20 %
time delay settings
(ms) ∆t (max resettable time) 60 140 230 350 800
∆t (max break time) 140 200 320 500 1000

Overload LED
E51398A

long time
Ir tr alarm
.8 (s) 4
8
.7 .9 12
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In at 6 Ir

short time instantaneous


Isd
4
tsd
(s) .4 .4 .3
Ii
6 8 10
100 %
3 5
2.5 6 .3 .2 4 12
2 8 .2 .1 3 15
1.5 10 .1 2 0 2 off
x Ir on I t x In
setting delay
test
I∆n ∆t
(A)
3
5
7
(ms) 230 350 40 %
2 10
140
1 20
800
.5 30 60
earth leakage

This LED signals that the long-time current setting Ir has been overrun.

The auto-protection function (excessive Fault indications


temperature or short-circuit higher than
Signals tripping due to an Signals tripping due
circuit-breaker capacity) opens the circuit
overrun of the long-time to an overrun of the
breaker and turns on the Ap LED. current setting Ir. short-time pick-up Isd
or the instantaneous
Caution. pick-up Isd / Ii.
If the circuit breaker remains closed and
E51399A

E51400A

Micrologic 7.0 A Micrologic 7.0 A


the Ap LED remains on, contact the
Schneider after-sales support department.

Caution.
The battery maintains the fault indications.
If there are no indications, check the
battery.

Signals tripping due to an Signals tripping due to


overrun of the earth-fault the auto-protection
pick-up Ig or the earth- function of the control
leakage pick-up I∆n. unit.
E51401A

E51402A

Micrologic 7.0 A Micrologic 7.0 A

7 Micrologic A Schneider Electric


Discovering your Overview of functions
control unit Ammeter measurements

If no information is displayed on the screen, c all Micrologic control units measure the true rms value of currents
c the most heavily loaded phase is continuously displayed on the digital screen
see the technical appendix "Digital display".
c using the navigation buttons, it is possible to display successively the I1, I2, I3,
neutral IN, Ig, I∆N and stored-current (maximeter) values
c the percent load on each phase is displayed. A bargraph displays the currents
measured on phases 1, 2 and 3 as a percentage of the long-time current setting Ir.

E60371A
1.125 x Ir
100 % 1 x Ir
0.8 x Ir
0.6 x Ir
40 % 0.4 x Ir

8 Micrologic A Schneider Electric


9 Micrologic A Schneider Electric
Setting your control unit Selecting the type
of neutral protection

On four-pole circuit breakers, it is possible to select the type of neutral protection


for the fourth pole:
c neutral unprotected (4P 3D);
c neutral protection at 0.5 In (3D + N/2);
c neutral protection at In (4P 4D).

E51383A
/2
3D+N
4P 4D
4P 3D

10 Micrologic A Schneider Electric


Setting procedure

Setting procedure
1. Open the protective cover.

E51411A
E51410A
7.0 A 7.0 A
logic logic
Micro Micro
Ir=
A

100 % 100 % 2. Select the desired


40 % 40 % setting.
The set value is
menu

1
menu
automatically displayed
2 on the digital screen in
absolute value with the
relevant units.
c Current in amperes
(A and kA);
c Tripping delays in
seconds.
E51412A

3. If no information is displayed, see the technical


appendix "Digital display". If no further action is taken,
Microlo
gic 7.0
A
after a few seconds, the display returns to the main
menu for current measurements.

4. Close the protective cover and, if necessary, install


a lead seal to protect the settings.
100 %

40 %

menu

See the user manual for the portable Using the portable test kit
test kit To test the control unit, connect the portable test kit via the test connector.
E51410A

E51413A

7.0 A 7.0 A
logic logic
Micro Micro

100 % 100 %

40 % 40 %

menu

1 menu

11 Micrologic A Schneider Electric


Setting your control unit Setting the Micrologic 2.0 A
control unit

The rating of the circuit breaker Set the threshold values


in this example is 2000 A.

E60365A
long time
alarm
In = 2000 A
E51366A

Ir .8
.7 .9
.6 .95 Ir = 0.7 x In = 1400 A
.5 .98
.4 1 Isd = 3 x Ir = 4200 A
x In
instantaneous
Isd
3 4 5
2.5 6
2 8
1.5 10
x Ir
1 setting

In = 2000 A
A
2000
In =

See pages 4 and 5 for information


E51368A

t
on the available settings Ir

Isd

0 I

Set the tripping delay


E60366A

long time tr = 1 second


tr alarm
(s)
8
4 12
2 16
1 20
.5 24
at 6 Ir
E51370A

tr

0 I

12 Micrologic A Schneider Electric


Setting the Micrologic 5.0 A
control unit

The rating of the circuit breaker Set the threshold values


in this example is 2000 A.

E60367A
long time In = 2000 A
E51366A

Ir alarm
.8 .9
.7 Ir = 0.7 x In = 1400 A
.6 .95
.5 .98
.4 1
Isd = 2 x Ir = 2800 A
x In
short time instantaneous Ii = 3 x In = 6000 A
Isd 4 5 Ii
3 6 8 10
2.5 6 4 12
2 8 3 15
1.5 10 2 off
x Ir x In
1 setting

In = 2000 A
A
2000
In =

See pages 4 and 5 for information


Set the tripping delay
on the available settings
E60368A

long time tr = 1 second


Thresholds tr alarm
(s) 8 12
4
I2t ON curve I2t OFF curve 2 16
1 20
E51373A

E51372A

t
Ir
t
Ir .5 24 tsd = 0.2 seconds
at 6 Ir

short time
tsd
(s) .4 .4 .3
.3 .2 I2t on I2t off
Isd Isd
.2 .1
.1 2 0
on I t
Ii Ii
delay

0 I 0 I

Tripping delays
I2t ON curve I2t OFF curve
E51376A

E51375A

t t

tr tr

tsd tsd

0 I 0 I

13 Micrologic A Schneider Electric


Setting your control unit Setting the Micrologic 6.0 A
control unit

The rating of the circuit breaker Set the threshold values


in this example is 2000 A.

E51414A
long time
alarm
In = 2000 A
E51366A

Ir .8
.7 .9
.6 .95
.5 .98
.4
x In
1 Ir = 0.7 x In = 1400 A
short time instantaneous
Isd Ii
3 4 5 6 8 10 Isd = 2 x Ir = 2800 A
2.5 6 4 12
2 8 3 15
1.5 10 2 x In off
x Ir Ii = 3 x In = 6000 A
1 setting
test
Ig
D E F
C G
B Ig = 640 A
In = 2000 A B H
A
A I
2000
In =

ground fault

See pages 4 to 6 for information


Set the tripping delay
on the available settings.
E60372A

long time
Thresholds tr alarm
(s) 4
8
12 tr = 1 second
I2t ON curve I2t OFF curve 2 16
1 20
E51373A

E51372A

t t .5 24
Ir Ir at 6 Ir

short time
tsd
(s) .4 .4 .3 tsd = 0.2 seconds
.3 .2
Isd Isd .1
.2
.1 2 0 I2t on I2t off
on I t off
Ii Ii delay
test
tg
0 I 0 I (s)
.4 .4 .3
.3 .2
E51416A

E51415A

t t
.2 .1 tg = 0.2 seconds
.1 2 0
on I t off
ground fault

Ig Ig

0 I 0 I

Tripping delays
I2t ON curve I2t OFF curve
E51376A

E51375A

t t

tr tr

tsd tsd

0 I 0 I
E51418A

t
E51419A

tg tg

0 I 0 I

14 Micrologic A Schneider Electric


Setting the Micrologic 7.0 A
control unit

The rating of the circuit breaker Set the threshold values


in this example is 2000 A.

E51420A
long time
Ir alarm
E51366A

.8 .9
.7
.95
In = 2000 A
.6
.5 .98
.4 1
Ir = 0.7 x In = 1400 A
x In
short time instantaneous Isd = 2 x Ir = 2800 A
Isd Ii
3 4 5 6 8 10 Ii = 3 x In = 6000 A
2.5 6 4 12
2 8 3
1.5 10 2
15
off
I∆n = 1 A
x Ir x In
1 setting
test
I∆n
(A) 3 5 7
2 10
1 20
In = 2000 A .5 30
A
2000
In =

ground fault

See pages 4 to 7 for information


Set the tripping delay
on the available settings.
E60373A

long time
Thresholds tr alarm tr = 1 second
(s) 4 8 12
I2t ON curve I2t OFF curve 2 16
1 20
E51373A

E51372A

t t .5 24
Ir Ir at 6 Ir

short time
tsd tsd = 0.2 seconds
.4 .4 .3
(s)

.3 .2
Isd Isd .2 .1
.1 2 0
on I t off
I2t on I2t off
Ii Ii delay
test
∆t
(ms) 230
0 I 0 I 350
140
E51421A

t
800
60 ∆t = 140 milliseconds
ground fault

I∆n

0 I

Tripping delays
I2t ON curve I2t OFF curve
E51375A
E51376A

t t

tr tr

tsd tsd

0 I 0 I

t
E51423A

∆t

0 I

15 Micrologic A Schneider Electric


Fault and status Resetting the fault indications
indications and checking battery status

The procedure for closing the circuit Resetting the fault indications
c determine why the circuit breaker tripped.
breaker following a fault trip is presented
The fault indication is maintained until it is reset on the control unit.
in the circuit-breaker user manual. v press the fault-trip reset button.

E51439A
Micrologic 7.0 A

v check the parameter settings of the control unit.

Checking the battery


E51440A

Micrologic 7.0 A

Press the battery-test button (same as the fault-trip reset button) to display
the battery status.
E51441A

Battery fully charged


Battery half charged
Change the battery

If no information is displayed, either:


c no battery is installed in the control unit, or;
c an auxiliary power supply is required.
See the technical appendix "Digital display".

If the battery needs to be changed, please Changing the control-unit battery


use the one with Schneider catalogue
1. Remove the battery 2. Remove the battery.
number 33593 (characteristics given on the cover.
battery compartment cover).
E51443A
E51442A

100 %

40 %

3. Insert a new battery. 4. Put the cover back in


Check the polarity. place. Press the battery-
test button to check the
new battery.
E51444A

E51445A

100 %

40 %

16 Micrologic A Schneider Electric


Testing the earth-fault and earth-
leakage functions

Charge and close the circuit breaker.


Using a screwdriver, press the test button for earth-fault and earth-leakage
protection. The circuit breaker should open.

E51410A

E51456A
7.0 A 7.0 A
logic logic
Micro Micro

100 % 100 %

40 % 40 %

menu menu

1
2

If the circuit breaker does not open, contact the Schneider after-sales
support department.

17 Micrologic A Schneider Electric


Menus Accessing the menus

Symbols used: Three menus may be accessed on Micrologic control units, providing the following
information:
E51404A

c phase current measurements I1, I2, I3, neutral IN, earth-fault current Ig on the
Micrologic 6.0 A control unit and earth-leakage current I∆n on the Micrologic 7.0 A
control unit;
c maximeter current values for phases I1, I2, I3, neutral IN, the maximum earth-
Briefly press a key. fault current Ig on the Micrologic 6.0 A control unit and the maximum earth-leakage
current I∆n on the Micrologic 7.0 A control unit;
c protection settings and tripping delays.
E51405A

1. Measurements 2. Maximeter 3. Settings

E51406A

E51407A

E51408A
Press and hold a key. Max
Ir=
A A A

It is possible at any time to stop consulting


a current measurement, a maximum
current value recorded by the maximeter or
the setting values. After a few seconds, the
Micrologic control unit automatically returns 100 % 100 % 100 %
to the main menu displaying the current
value of the most heavily loaded phase. 40 % 40 % 40 %
menu menu menu

The protection settings can be displayed


directly on the digital display.

Press the "menu" button Press the "menu" button Press the "menu" button
to access the maximum to access the protection to return to the current
current values measured settings and tripping measurements.
by the maximeter. delays.

4. The system returns


to the main
"Measurements" menu.
E51409A

100 %

40 %

18 Micrologic A Schneider Electric


Measuring phase currents

Current values may be read in the Display of current I1. Display of current I2.
"Measurements" menu, which is also the

E51425A

E51426A
main menu.
A A
If no particular action is taken, the system
displays the current value of the most
heavily loaded phase.
"Measurements" menu
Phase 1 is the most heavily loaded. 100 % 100 %
E51409A

40 % 40 %
A

Press the "arrow" button Press the "arrow" button


100 % to go on to current I2. to go on to current I3.

40 % Display of current I3. Display of current IN.


E51427A

E51429A

A A

100 % 100 %

40 % 40 %

Press the "arrow" button Press the "arrow" button


to go on to current IN if to go on to the earth-fault
the circuit breaker is current Ig or the earth-
connected to the neutral. leakage current I∆n.

Display of current Ig The system returns to


(Micrologic 6.0 A) or the display of current I1.
current I∆n
(Micrologic 7.0 A).
E51428A

E51409A

A A

100 % 100 %

40 % 40 %

Press the "arrow" button


to return to current I1.

19 Micrologic A Schneider Electric


Menus Displaying the maximum
current values

Maximum current values may be read in Display of the Display of the


maximum I1 current. maximum I2 current.
the "Maximeter" menu.

E51430A

E51431A
MAX MAX
If no particular action is taken, the system A A
returns to the main menu.

"Maximeter" menu.
E51407A

100 % 100 %
Max

A
40 % 40 %

100 % Press the "arrow" button Press the "arrow" button


to go on to the maximum to go on to the maximum
I2 current. I3 current.
40 %
menu Display of the Display of the
maximum I3 current. maximum IN current.
E51432A

E51434A

MAX MAX

A A

100 % 100 %

40 % 40 %

Press the "arrow" button Press the "arrow" button


to go on to the maximum to go on to the maximum
IN current if the circuit earth-fault current Ig
breaker is connected to (Micrologic 6.0 A) or the
the neutral. maximum earth-leakage
current I∆n
(Micrologic 7.0 A)

Display of the maximum The system returns to


Ig current or the the display of the
maximum I∆n current. maximum I1 current.
E51433A

E51435A

MAX MAX

A A

100 % 100 %

40 % 40 %

Press the "arrow" button


to return to the maximum
I1 current.

20 Micrologic A Schneider Electric


Resetting the maximum current
values

Maximum current values can be reset Select the maximum Reset. Select another value
current value to be to reset or return to
using the "Maximeter" menu.
reset (e.g. I2 max.). the main menu.

If no particular action is taken, the system

E51436A

E51437A

E51438A
returns to the main menu. MAX MAX MAX

A A A

"Maximeter" menu.
E51407A

Max

A
100 % 100 % 100 %

40 % 40 % 40 %

100 %

40 %
Press the "arrow" button Press and hold the Press the "arrow" button
menu as many times as "arrow" button down for as many times as
required to select I2 max. three to four seconds. required to select another
The current value flashes maximum value to reset
during the reset, then or return to the main
changes to the present menu.
value (the new
maximum).

21 Micrologic A Schneider Electric


Menus Viewing the settings

Micrologic control unit

2.0 A 5.0 A 6.0 A 7.0 A


E60374A

Long-time current setting Ir menu Select the "Settings"


menu.
The Ir value is the first Ir=
displayed. A

Long-time tripping delay tr Press the "arrow" button


to go on to the tr value. tr=
s

Short-time pick-up Isd Press the "arrow" button


to go on to the
short-time Isd value. Isd=
A

Short-time tripping delay tsd Press the "arrow" button


to go on to the tsd tsd=
value. s

Instantaneous pick-up Isd Press the "arrow" button


to go on to the
instantaneous Isd Isd=
value. A

Or

Instantaneous pick-up Ii the instantaneous Ii


value.
Ii= A

Earth-fault pick-up Ig Press the "arrow" button


to go on to the Ig value.

Ig= A

Or

Earth-leakage pick-up I∆n the I∆n value.


I∆n=

Earth-fault tripping delay tg Press the "arrow" button


to go on to the tg value.
s
tg=
Or

Earth-leakage tripping delay ∆t the ∆t value.


∆t=
s

Press the "arrow" button


to return to the
beginning of the menu. Ir=
A

22 Micrologic A Schneider Electric


23 Micrologic A Schneider Electric
Technical appendix Tripping curves

Long-time and instantaneous protection (Micrologic 2.0 A)

E60369A
10 000
5 000 Ir = 0.4…1 x In

2 000
1 000
500

200
100 tr = 0.5…24 s
50

20
10
5
t(s)
2
Isd = 1.5…10 x Ir
1
.5

.2
.1
.05

.02
.01
.005

.002
.001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir

Long-time, short-time and instantaneous protection


(Micrologic 5.0 A, 6.0 A and 7.0 A)
E60370A

10 000
5 000 Ir = 0.4…1 x In

2 000
1 000
500 tr = 0.5…24 s

200
100
50

20
10
5
t(s) Isd = 1.5…10 x Ir
2
1
I2t ON
.5 0.4 0.4
0.3 0.3
.2 0.2 0.2
0.1 0. 1
.1 I2t OFF
0 0
.05
Ii = 2…15 x In . OFF (1)
.02
.01
.005

.002
.001
.5 .7 1 2 3 4 5 7 10 20 3 5 7 10 20 30
x Ir x In

24 Micrologic A Schneider Electric


Earth-fault protection (Micrologic 6.0 A)

E46266A
10 000
5 000

2 000
Ig = A…J x In (1)
1 000 1200 A max.
500

200
100
50

20
10
5
t(s) I2t ON
2
1
.5 0.4 0.4
0.3 0.3
.2 0.2 0.2
2 0.1 0.1
.1 It OFF
0 0
.05

.02
.01
.005

.002
.001
.05.07 .1 .2 .3 .4 .5 .7 1 2 3 5 7 10 200 300
I / In

25 Micrologic A Schneider Electric


Technical appendix Changing the long-time
rating plug

Select the long-time rating plug


A number of setting ranges for the long-time current setting are available on
Micrologic A control units by changing the long-time rating plug.
The available rating plugs are listed below.

Part number Setting range for the Ir value


33542 standard 0.4 to 1 x Ir
33543 low setting 0.4 to 0.8 x Ir
33544 high setting 0.8 to 1 x Ir
33545 without long-time protection

Caution.
Change the long-time rating plug
Following any modifications to the long-
Proceed in the following manner.
time rating plug, all control-unit protection
parameters must be checked. 1. Open the circuit breaker.
2. Open the protective 3. Completely remove
cover of the control unit. the long-time rating plug screw.
E51378A

E51379A
7.0 A 7.0 A
logic logic
Micro Micro

100 % 100 %

40 % 40 %

menu menu

Caution. 4. Snap out the rating 5. Clip in the new rating plug.
If no long-time rating plug is installed, the plug.
E51381A
E51380A

control unit continues to operate under the


following downgraded conditions: 7.0 A logic
7.0 A
logic Micro
Micro

c the long-time current setting Ir is 0.4;


c the long-time tripping delay tr
corresponds to the value indicated by the
adjustment dial; 100 % 100 %

c the earth-leakage protection function is 40 % 40 %

disabled.
menu menu

alarm alarm

time 8 12 long
time tr 8 12
long tr 4
(s) 4 16 .8 .9
(s) 16
Ir .8 .9 Ir 2
.7 2 20 .7 .95 20
.95 1
.6 1 24 .6 .98 24
.98 .5 @ 6 Ir .5 @ 6 Ir
.5 .5 1
1 .4 x In
.4 x In

6. Refit the screw for the 7. Check and/or modify the


long-time rating plug. control-unit settings.

26 Micrologic A Schneider Electric


Zone selective interlocking (ZSI)
E51397A

Operating principle
c A fault occurs at point A.
Downstream device no. 2 clears the fault and sends a signal to upstream device
no. 1, which maintains the short-time tripping delay tsd or the earth-fault tripping
delay tg to which it is set.
c A fault occurs at point B.
Upstream device no. 1 detects the fault. In the absence of a signal from a
downstream device, the upstream device immediately trips without taking into
1 B account its tripping-delay settings. If it is connected to a device even further
upstream, it sends a signal to that device, which delays tripping according to its tsd
or tg setting.

Note :
On a circuit breaker likely to receive a ZSI signal, the tsd and tg tripping delays must not
2 be set to zero, as this would make discrimination impossible.
A

Connections between control units


A logic signal (0 or 5 volts) can be used for zone selective interlocking between the
upstream and downstream circuit breakers.
c Micrologic 5.0 A, 6.0 A, 7.0 A.
c Micrologic 5.0 P, 6.0 P, 7.0 P.
c Micrologic 5.0 H, 6.0 H, 7.0 H.

Caution. Wiring
If the protection function is not used on c maximum impedance: 2.7 Ω / 300 metres
circuit breakers equipped for ZSI c capacity of connectors: 0.4 to 2.5 mm2
protection, a jumper must be installed to c maximum cross-sectional area of wires (including insulation): 3.5 mm2
short terminals Z3, Z4 and Z5. c wires: single or multicore
c maximum length: 3000 metres
If the jumper is not installed, the short-time c limits to device interconnection:
and earth-fault tripping delays are set v the common ZSI - OUT - SOURCE (Z1) and the output ZSI - OUT (Z2)
to zero, whatever the position of the can be connected to a maximum of 10 inputs;
adjustment dial. v a maximum of 100 devices may be connected to an input ZSI IN CR (Z4) or GF
(Z5)
c connections are made from the output ZSI - OUT (Z2) on the downstream device
to the input(s) ZSI - IN - ST (Z4) and/or GF (Z5) on the upstream device.

Terminals Z1 to Z5 correspond to the


E60375A

identical indications on the circuit-breaker and/or


terminal blocks. Z1 Z2 Z3 Z4 Z5

Terminal block
for external
connections

Upstream
circuit breaker

and/or
Z1 Z2 Z3 Z4 Z5

Terminal block
for external
connections

Z1 Z2 Z3 Z4 Z5

Terminal block
for external
connections

Downstream
circuit breaker

27 Micrologic A Schneider Electric


Technical appendix Digital display

For information on connecting an external c display of measurements operates without an external power supply.
The digital display goes off if the current drops below 0.2 x In (In = rated current).
power supply, see the electrical diagrams
c display back-lighting is disabled in the following situations:
in the circuit-breaker user manual. v current less than 1 x In on one phase;
v current less than 0.4 x In on two phases;
v current less than 0.2 x In on three phases.
c the maximeter does not operate for currents under 0.2 x In.

These three functions may be maintained by adding an external power supply.


Even if an external power supply is installed, the long-time, short-time,
instantaneous and earth protection functions will not use it.

28 Micrologic A Schneider Electric


Thermal memory

Thermal memory
The thermal memory is a means to simulate temperature rise and cooling caused
by changes in the flow of current in the conductors.

These changes may be caused by:


c repetitive motor starting;
c loads fluctuating near the protection settings;
c repeated circuit-breaker closing on a fault.

Control units without a thermal memory (contrary to bimetal strip thermal


protection) do not react to the above types of overloads because they do not last
long enough to cause tripping. However, each overload produces a temperature
rise and the cumulative effect can lead to dangerous overheating.

Control units with a thermal memory record the temperature rise caused by each
overload. Even very short overloads produce a temperature rise that is stored in
the memory.
This information stored in the thermal memory reduces the tripping time.

Micrologic control units and thermal memory


All Micrologic control units are equipped as standard with a thermal memory
c for all protection functions, prior to tripping, the temperature-rise and cooling time
constants are equal and depend on the tripping delay in question:
v if the tripping delay is short, the time constant is low;
v if the tripping delay is long, the time constant is high.

c for long-time protection, following tripping, the cooling curve is simulated by the
control unit. Closing of the circuit breaker prior to the end of the time constant
(approximately 15 minutes) reduces the tripping time indicated in the tripping
curves.

29 Micrologic A Schneider Electric


Schneider Electric Industries SA As standards, specifications and designs develop from time, always ask for confirmation of the
information given in this publication.
5, rue Nadar
92506 Rueil-Malmaison Cedex
France This document has been printed on ecological paper.
Tel: +33 (0)1 41 29 82 00
Fax:+33 (0)1 47 51 80 20 Designed by: HeadLines
Printed by:
http://www.schneiderelectric.com

04443724AA-A 11-99

You might also like