iSWAY-FC®

COMPACT PRESSURIZATION UNIT INTENDED FOR SMOKE AND


HEAT CONTROL SYSTEMS

Application:
The iSWAY-FC® series compact pressurization units are com-
prehensive technical solutions designated to overpressure pro-
tection of both vertical and horizontal escape routes in the va-
rious buildings in case of fire.

Functionality and reliability in aerodynamic, electrical and electronic aspects in accordance with:
Technical Approval ITB AT-15-9020/2015, confirmed by Certificate of Conformity ITB-2189/W and the national Declaration of
Conformity issued by SMAY Sp. z o. o. No. 282/2013

Note:
The manufacturer reserves the right to change, amend or update this data sheet at any time without notice.

Intended use and types of the units


The iSWAY-FC® series compact pressurization units (pressure differential kits in accordance with EN 12101-6) are comprehensive
technical solutions designated to overpressure protection of both vertical and horizontal escape routes in the various buildings in
case of fire. All iSWAY-FC® series units are equipped with predictive algorithm regulators which provide automatic adjustment of the
operating parameters to the dynamic changes of the ambient e.g. wind speed and direction, air temperature and internal parameters
e.g. different evacuation scenarios. Capacity of the air supply axial flow fan is continuously adjusted by means of the Danfoss frequency
inverter with the FIRE MODE function which shall be applied in smoke and heat control systems.

Correspondent iSWAY-FC® units can be equipped with dedicated automatics enabling to protect of certain spaces depending on the
local requirements in the building.

Due to the applied control system and wide range of accessories iSWAY-FC® series units can be used to protect number of spaces
with different cubature e.g. staircases, lift-shafts etc. Moreover due to the compact design and structure iSWAY-FC® series compact
pressurization units can be assembled almost anywhere inside the building e.g. technical floors, roof level or ground level.

Technically iSWAY-FC® series units are comprehensive technical solutions for overpressure protection against smokiness of escape
routes in buildings in case of fire. Thanks to a compact design and a wide range of versions this units can be installed almost anywhere
in the building, whereas varying performance of offered fans provides the required level of pressure gradient and normative velocity of
air outflow from the protected spaces.

Units from the iSWAY-FC® series are designed to produce the set value of overpressure within the space of staircase, shaft of rescue
elevator or in a system of separate elevator shafts (each with its own air supply point in reference to the fire floor. It is also possible the
use iSWAY-FC® units to control the pressure in the air supply duct.
Protected space pressure
measurement point

Reference pressure
measurement point

Protected space e.g. stairwell, lobby, Actual air leakage rate


lift shaft, corridor

Figure 1. Exemplary illustration of connection of iSWAY-FC® unit to the protected space

1 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems version 6.0.1
SMOKE
AND FIRE
ZONE

Protected space pressure


measurement point
Remote differential pressure
sensor P-MACF

Reference pressure
measurement point

Protected space e.g. stairwell, lobby, Actual air leakage


lift shaft, corridor rate

Figure. 2. Exemplary connection of iSWAY-FC®-D pressurization unit with remote differential pressure sensor and pressurized space

Protected space pressure


measurement point

Reference pressure
measurement point

Protected space Actual air leakage rate


MAC-D Min
e.g. stairwell, lobby, lift shaft,
Available static pressure Junction box PZ corridor
measurement point
Motorized volume control
damper SRC

Figure. 3. Exemplary connection of iSWAY-FC® pressurization unit with motorized volume control damper SRC
and regulator MAC-D-MIN and pressurized space

Note: Protected space is a space which is protected by means of an overpressure.

version 6.0.1 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems 2
Reference pressure
measurement point
Δp - differential pressure
measurement tubes iSWAY-FC

Pressure measurement
point in the stairwell

Corridor Stairwell

e.g. 50 Pa

Cables interconnecting TSS with


iSWAY-FC®

TSS

Fire brigades access level

x - For systems in line with EN 12101-6 and where units are located at upper storeys or on
the roof Twin-Air-Intake module shall be applied (alternative air intake)

Figure. 4. Multiple injection into the stairwell

Note:
1. Control-Signal Board (TSS) – shall be installed at the fire brigades access level near the building entrance,
2. Maximum length of the pressure differential measurement tubes shall not exceed 12 m,

Measurement taken with internal differential pressure sensor installed inside the unit’s casing through the pressure differential me-
asurement tubes. In case of communication loss with the pressure sensor regulator switches automatically into safe emergency
control mode (failure mode).

3 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems version 6.0.1
Reference pressure Pressure measurement point Reference pressure
measurement point inside the air supply duct measurement point
Δp - differential pressure
measurement tubes
iSWAY-FC
-D

P-MACF
Pressure measurement
point in the stairwell
Corridor Stairwell

e.g. 50 Pa

Cables interconnecting TSS


with iSWAY-FC®

TSS

Fire brigades access level

x - For systems in line with EN 12101-6 and where units are located at upper storeys or on
the roof Twin-Air-Intake module shall be applied (alternative air intake)

Figure. 5. Multiple injection into the stairwell – unit with remote differential pressure sensor

Note:
1. Control-Signal Board (TSS) – shall be installed at the fire brigades access level near the building entrance,
2. Maximum length of the pressure differential measurement tubes shall not exceed 12 m,
3. P-MACF remote differential pressure sensor connected with iSWAY-FC® unit with Local FireBus® communication loop,

In case when the unit is not located close to the protected space to avoid pressure difference measurement errors and delays remote
differential pressure sensor P-MACF is installed directly within the protected space and connected to iSWAY-FC® unit with Local Fire-
Bus® communication loop (more details on the protocol later in this data sheet).
In case of communication loss with the pressure sensor regulator switches automatically into safe emergency control mode (failure
mode) regulation based on pressure measurement inside the air supply duct.

version 6.0.1 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems 4
Reference pressure
measurement point
Δp - differential pressure
measurement tubes
iSWAY-FC

Pressure measurement
point in the stairwell

Corridor Stairwell

e.g.50 Pa

Cables interconnecting TSS


with iSWAY-FC®

TSS

Fire brigades access level

x - For systems in line with EN 12101-6 and where units are located at upper storeys or on
the roof Twin-Air-Intake module shall be applied (alternative air intake)

Figure. 6. Single point (concentrated) injection into the stairwell

Note:
1. Control-Signal Board (TSS) – shall be installed at the fire brigades access level near the building entrance,
2. Maximum length of the pressure differential measurement tubes shall not exceed 12 m,
3. Application of single injection system shall be every time validated taking into consideration building architecture and key
design objectives e.g. allowable pressure differences,

Single injection (concentrated) air supply does not require vertical air supply shaft and thus enable to save space which can be used for
lobbies pressurization or else increase available usable area in the building.
In case of communication loss with the differential pressure sensor regulator switches automatically into safe emergency control
mode (failure mode).

iSWAY-FC®-D unit with differential pressure sensor P-MACF and regulator MAC-FC for lobbies pressurization with constant capacity
air supply rate and compensative air supply for mechanically smoke extracted corridors and separate units operating stairwells and
lift shafts.

5 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems version 6.0.1
Figure. 7. Simultaneous pressurization of the stairwell and fire-fighting lobbies (vestibules) with air compensative air transfer openings (from the
lobbies to the corridors or other smoke extracted spaces)

iSWAY-FC-D iSWAY-FC iSWAY-FC-D iSWAY-FC

KWP-z KWP-z
MAC-D MAC-D
MIN MIN

24 V guaranteed 24 V guaranteed

Corridor Fire-fighting lobby (vestibule) Stairwell Corridor Fire-fighting lobby (vestibule) Stairwell
available static pressure inside air supply duct
available static pressure inside air supply duct

KWP-o KWP-o
MAC-D MAC-D
MIN MIN
Free air release to the outside from the fire storey
Free air release to the outside from the fire storey

Reference pressure Pressure Reference Pressure


24 V guaranteed measurement pressure 2 m/s 24 V measurement
measurement point point in the lobby measurement guaranteed point in the lobby
45 Pa 50 Pa point

KWP-z KWP-z
MAC-D MAC-D
MIN MIN

24 V guaranteed 24 V guaranteed

KWP-z KWP-z
MAC-D MAC-D
MIN MIN

24 V guaranteed 24 V guaranteed

KWP-z KWP-z
MAC-D MAC-D
MIN MIN

24 V guaranteed 24 V guaranteed

KWP-o – fire damper (open), KWP-z – fire damper (closed)

x - For systems in line with EN 12101-6 and where units are located at upper storeys or on
the roof Twin-Air-Intake module shall be applied (alternative air intake)

Figure 8. Simultaneous pressurization of the stairwell and fire-fighting lobbies (vestibules) with electronic adjustable air transfers (from the lobbies to
the corridors or other smoke extracted spaces)

version 6.0.1 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems 6
Location in the building and design options
iSWAY-FC-D iSWAY-FC-R iSWAY-FC-D iSWAY-FC-R

KWP-z KWP-z

P-MACF Inside air Outside air P-MACF Inside air Outside air

available static pressure inside air supply duct

available static pressure inside air supply duct


temperature temperature temperature temperature
measurement measurement measurement measurement
Fire-fighting lobby point point Fire-fighting lobby point point
Corridor (vestibule) Stairwell Corridor (vestibule) Stairwell

KWP-o KWP-o

P-MACF P-MACF

Free air release to the outside from the fire storey


Free air release to the outside from the fire storey

iSWAY-FC iSWAY-FC
2 m/s
45 Pa 50 Pa

KWP-z KWP-z

P-MACF P-MACF

KWP-z KWP-z

P-MACF P-MACF
iSWAY-FC-R iSWAY-FC-R

KWP-z KWP-z

P-MACF Outside air P-MACF


Outside air
temperature Inside air temperature
measurement temperature measurement
point measurement point point

KWP-o – fire damper (open), KWP-z – fire damper (closed)

x - For systems in line with EN 12101-6 and where units are located at upper storeys or on
the roof Twin-Air-Intake module shall be applied (alternative air intake)

Figure 9. Simultaneous pressurization of the stairwell and fire-fighting lobbies (vestibules) with electronic adjustable air transfers (from the lobbies
to the corridors or other smoke extracted spaces). Stairwell pressurized with reversible flow pressurization system counteracting stack effect type
SAFETY WAY®.

Note:
1. Complex pressurization systems shall be fitted with Operating Conditions Monitoring Device (MSPU) with Control Board (TS) to
enable monitoring, visualization of the system and manual key-protected override switches. TS and MSPU are usually installed
in the BMS room,
2. Maximum length of the pressure differential measurement tubes shall not exceed 12 m,
3. Application of single injection system shall be every time validated taking into consideration building architecture and key
design objectives e.g. allowable pressure differences,
4. iSWAY-FC®D type pressurization unit can be interconnected with max. 32 P-MACF remote differential pressure sensors using
single FireBus® loop,
5. Each remote P-MACF sensor has to have Fire Alarm Signal (FAS) provided. Depending on the location of the fire pressurization
unit communicates with the sensor closest to the fire floor and neglect other readings in order to enable possibly fast
operation,
6. For fire-fighting lobbies (vestibules) equipped with electronic adjustable air transfers remote sensors P-MACF are replaced
with MAC-D-MIN regulators controlling volume control dampers located in the lobby and corridor. Proper functioning of such
system requires to receive Fire Alarm Signal (FAS) to trigger the system and enable measurement of pressure difference
between the lobby and reference (e.g. corridor),
7. iSWAY-FC® type units intended for pressurization of the lobbies with electronic adjustable air transfers or more than one lift
shaft pressurized by a single unit (individual pressure difference regulation) are by default fitted with factory automatics type
“D” and marked as iSWAY-FC®-D,
8. iSWAY-FC® type units intended for stairwell pressurization where reversible flow is required are by default fitted with factory
automatics type “R” and marked as iSWAY-FC®-R.

Use of P-MACF sensors and FireBus® loop communication protocol enable to save space and limit investment and operating costs by
reducing total length of the data transmission cables and capacities of the air supply fans – air supply rates are precisely controlled
and automatically adjusted to current needs. Application of electronic adjustable air transfers enables to save space and improve
aesthetics by reducing required size of air transfer openings (compensative air supply for smoke exhaust).

Failsafe mode In case of communication loss with the pressure sensor regulator switches automatically into safe emergency control
mode (failure mode) regulation based on pressure measurement inside the air supply duct. Desired pressure inside the air supply duct
shall be determined experimentally using the results of on-site measurements.

7 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems version 6.0.1
Exemplary locations of the units
Compact structure allows for installing units inside e.g. machinery rooms and outside the building e.g. roof level, ground level etc.
whereas wide range of applied fans enables to achieve desired pressure differences and directed airflow through the open doors.

Flexible differentia pressure measurement tube


e.g. PVC tube protected with electroinstallation tube
iSWAY-FC

3x400 V guaranteed power supply


general Fire Alarm Signal (FAS)

Static pressure
Stairwell measurement point inside
the protected space

Cables interconnecting TSS with


iSWAY-FC®

TSS

Fire brigades access level


x - For systems in line with EN 12101-6 and where units are located at upper storeys or on
the roof Twin-Air-Intake module shall be applied (alternative air intake)

Figure 10. Example of iSWAY-FC® unit top fed stairwell pressurization system with pressurization unit located on the roof

Note:
1. Control-Signal Board (TSS) – shall be installed at the fire brigades access level near the building entrance,
2. Complex pressurization systems shall be fitted with Operating Conditions Monitoring Device (MSPU) with Control Board (TS) to
enable monitoring, visualization of the system and manual key-protected override switches. TS and MSPU are usually installed
in the BMS room,
3. Maximum length of the pressure differential measurement tubes shall not exceed 12 m,
4. Application of single injection system shall be every time validated taking into consideration building architecture and key
design objectives e.g. allowable pressure differences.

version 6.0.1 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems 8
Stairwell

Static pressure
measurement point inside
the protected space

Reference
pressure
measurement Flexible differentia pressure
point measurement tube e.g. PVC tube
protected with electroinstallation tube

iSWAY-FC
TSS
KWP-o

Fire brigades access level


KWP-o – fire damper (open)
KWP-z – fire damper (closed) Cables interconnecting TSS with iSWAY-FC®

Figure. 11. Example of iSWAY-FC® unit based bottom fed stairwell pressurization system (with pressurization unit located in the machinery room)

Installation of the units


To provide maximum flexibility for the designers all iSWAY-FC® type units are delivered as a self-supporting structures with fan instal-
led on shock absorbers enabling to be installed in any position (horizontal, vertical) depending on the local requirements on the site.
However to guarantee comfort of the installers and maintenance crews it is recommended to define expected assembly position of the
unit (1 or 2) upon placing an order.
In case when defining final assembly position of the unit is unknown factory automatics will be installed as per default mounting po-
sition (1).

2 2 2 2
4 3 5

4 5
3
1 1 1 1
- Airflow direction – air supply unit- - Airflow direction – air exhaust unit - Assembly position

Figure 12. Example of the assembly position

After defining assembly position drain holes plugs o14 shall be removed from the bottom profiles of the unit’s casing. M8 Layout of
M8 mounting holes has been set in such a manner to enable any mounting position of the unit (see Scheme 12.). In case of vertical
assembly special supporting foot is required which is not available from the range of additional equipment offered by SMAY.

9 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems version 6.0.1
Measurement, monitoring and visualization 1 – seven segment display (three segments)
2 – general failure indicator (red)
For proper functioning of the iSWAY-FC® type unit it is indispen- 3 – two-position, key-protected switch (manual fan start)
sable to enable appropriate air intake, and provide all electrical 4 – smoke in the unit indicator (yellow)
connections (guaranteed power supply, data transmission ca- 5 – two-position, key-protected switch (locking the smoke
bles, fire alarm system inputs, connections between the unit detector or switching Twin-Air-Intake module)
and TSS or TS and MSPU). Moreover all pressure measurement smoke detector lock or Twin-Air-Intake module switch
tubes shall be unobstructed and properly connected (pressure 6 – membrane fan
difference between the protected space e.g. stairwell and re- 7 – EMC cable pass
ference e.g. corridor). If pressure regulation is carried out ba- 8 – Fire Alarm Signal indicator (yellow)
sing on the measurements taken inside the air supply duct it is 9 – board power supply indicator (green)
indispensable to connect appropriate pressure measurement 10 – two-position, key-protected switch (resetting fire alarm)
tubes and probes (duct pressure measurement probe shall be 11 – UNI cable pass
installed on the straight part of the air supply ductwork. 12 – wall bracket

Installed components of the control system P-MACF, MAC-D-


-MIN, MAC-LINK, T-MACF shall be interconnected with the Note
iSWAY-FC®-D(R) unit by means of Local FireBus® loop commu- Boards TSS-1 ÷TSS-3 can be used as a power
supplies 24VDC (power supplied from the iSWAY-
nication bus.
FC® unit).
In case when total number of P-MACF sensors doesn’t exceed 4
per unit power supply is provided through the FireBus®, other-
wise external power supply 24VDC shall be provided.
Operating Conditions Monitoring Device (MSPU)
For differential pressure sensors operating the lobbies it is in-
dispensable to address every sensor providing Fire Alarm Si- This device is an additional component which is recommended
gnal (FAS) to every sensor. In case of fire pressurization iSWAY- for complex pressurization systems and enables to control data
-FC® unit communicates with the sensor located in the lobby at transmission lines and monitor status and condition of the key
the fire floor. components of the SAFETY WAY® type pressurization system.
For buildings where total number of units doesn’t exceed 6 MSPU device shall be installed together with the TS Control Bo-
(without lobbies) manual control and monitoring are provided ard. MSPU device consists of the number of components enc-
with Control-Signal Board TSS in appropriate version TSS-1 ÷ losed in one steel casing painted in RAL3000. Key component
TSS-6 depending on number of units. of the MSPU is an industrial computer with touch screen fitted
in the front panel enabling to activate different features of the
For more complex pressurization systems where involving monitoring system. MSPU device is used to display operating
number of units it is recommended to apply Control Board (TS) parameters of the key components with individual graphics de-
together with Operating Conditions Monitoring Device (MSPU) veloped (including number of units, layout of protected spaces
located at the fire brigades access level possibly close to the and other components depending on the system’s structure). In
entrance (e.g. BMS room). general MSPU device enables to detect and locate any possible
failure of the system and reduce time required for periodic in-
Control-Signal Board (TSS) spections and maintenance of the pressurization system.

Control - Signal Board (TSS) is intended to enable basic manual


controls and monitoring of the proper functioning of the units.
Board is fitted with pressure difference value displays, key-pro-
tected manual override switches and indicators. Override swit-
ches are used to enable to start the unit, reset the failure, smo-
ke detector, Fire Alarm Signal (FAS) and, depending on system
structure, to control Twin-Air-Intake modules. Indicators show
information on fire alarm signal, major failure and detection of
the smoke inside the air supply unit.

TSS dimensions:
1. TSS-1 – 205x340 x 188 mm
2. TSS-2 – 305x340 x 188 mm
3. TSS-3 – 305x340 x 188 mm
Picture 1. General view of the Operating Conditions Monitoring Device
MSPU
1
Dimensions of the MSPU: 500 x 650 x 250 mm

8 2
Control board (TS)
9 3
10 4 Control Board (TS) is always installed in the building along with
MSPU at the fire brigades access level. In the front panel of the
5 board light indicators of board power supply, Fire Alarm Signal
11 6 (FAS) and general failure are fitted. Board is also fitted with ove-
rall switch enabling manual activation of the units which starts
12 7
all units simultaneously. Since each unit can be individually
stopped from the TS board it is also possible to start selected
Figure 13. General view of the Control Signal Board TSS-1 units or group of units. For each unit board also enables to re-

version 6.0.1 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems 10
set fire alarm signal resulting in deactivation of the unit. All • P-MACF +/-600 – measuring range: -600 ÷ 600 Pa –
units after being triggered with fire alarm signal work indepen- pressure difference between protected space and the refe-
dently and require manual stop. This manual switch can be also rence or inside the air supply duct – for iSWAY-FC®-D(R).
used to deactivate the unit. For security reasons this switch is
key-protected. For each unit board is fitted with additional swi- Remote differential pressure sensors are used in pressure
tch to lock the smoke sensor providing control signal for the differential systems in below cases:
Twin-Air-Intake module. This switch has two different functions • In case when iSWAY-FC® type units and pressurized spaces
depending on if the unit is equipped with Twin-Air-Intake mo- are apart and thus length of the pressure measurement
dule. In such case once smoke is detected inside the unit air tubes exceeds 12 m. Then P-MACF sensor is connected
intake openings are automatically switched. Alternatively for to iSWAY-FC®-D unit with Local FireBus® communication
units without Twin-Air-Intake module detection of smoke in- loop. In case of the communication loss iSWAY-FC®-D unit
side the unit results in automatic stop of the unit. Smoke de- goes to the fail-safe mode when pressure difference regu-
tection signal can be neglected using this switch and the unit lation is provided using internal P-MACF sensor of the unit
remains active. Information on smoke detection inside the unit or else fixed setting of the regulator,
is displayed on the MSPU device located near the board.
Dimensions of the P-MACF: 180x122x90mm

Picture 2. General view of the Control Board TS-12


Picture 3. General view of the differential pressure sensor P-MACF

Dimensions of the TS:


• In case pressurized lobbies when electronic adjustable air
Name Dimensions DxHxS [mm] transfers are not applied each lobby is fitted with indepen-
TS-1; TS-6 300 x 340 x 188 dent P-MACF sensor. All lobbies sensors are connected to
an appropriate iSWAY-FC®-D pressurization unit with Local
TS-7; TS-16 600 x 522 x 269
FireBus® communication loop. For each sensor power sup-
TS-17; TS-32 600 x 722 x 269 ply 24VDC, Fire Alarm Signal (FAS) input and pressure me-
TS-33; TS-36 800 x 922 x 321 asurement tubes shall be provided. The maximum number
of sensors within single Local FireBus® loop is 32 including
one sensor installed inside the unit . In case of fire sen-
sor located at the fire floor receives fire alarm signal which
Remote differential pressure sensor (P-MACF) enables to use this particular device to control pressure
difference between the lobby and the reference or inside
P-MACF is a digital pressure differential transducer fitted with the air supply duct.
one differential pressure sensor and connector providing power
supply and data transmission over two Local FireBus® chan-
nels. Built in, internal microprocessor system performs line- In case of communication loss with the pressure
arity correction while taking into account, inter alia, operating sensor regulator switches automatically into safe
temperature, and characteristics entered at the time of calibra- emergency control mode (failure mode) regulation
based on pressure measurement inside the air
tion. High accuracy and stability of measurement is ensured by supply duct. Setting of the duct pressure is defined
the use of sophisticated calibration equipment and long-term basing on the measurements taken during normal
aging process of the elements of the device. The converter is operation of the pressurization system
designed to measure air pressure with small degree of conta- (e.g. calibration).
mination.

Depending on desired function and measuring range two dif- Digital pressure regulator (MAC-D-MIN)
ferent variants of the sensors P-MAC and P-MACF can be di-
stinguished: In case when fire-fighting lobbies are equipped with electro-
• P-MAC +/-250 – measuring range: -250 ÷ 250 Pa – nic adjustable air transfers to provide compensative air supply
pressure difference between protected space and the refe- for smoke extracted corridors MAC-D-MIN regulators shall be
rence – for iSWAY-FC®, applied. Such regulators with integrated pressure sensor are
• P-MAC +/-600 – measuring range: -600 ÷ 600 Pa – intended to control position of motorized volume control dam-
pressure difference between protected space and the refe- pers installed in the air supply and air transfer ducts. Likewise
rence or inside the air supply duct – for iSWAY-FC®, P-MACF sensors MAC-D-MIN regulators are fitted with pressu-
• P-MACF +/-250 – measuring range: -250 ÷ 250 Pa – re measurement tubes terminals to measure pressure diffe-
pressure difference between protected space and the refe- rence between the protected fire-fighting lobby and corridor
rence – for iSWAY-FC®-D(R), and are connected to iSWAY-FC®-D unit with Local FireBus®

11 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems version 6.0.1
communication loop. For each regulator power supply 24VDC I/O adapter (MAC-LINK)
and Fire Alarm Signal (FAS) input shall be provided. The maxi-
mum number of regulators within single Local FireBus® loop is I/O adapters type MAC-LINK are intended to enable extend ba-
31. In case of fire regulator located at the fire floor receives fire sic functions of the pressurization systems. This adapters use
alarm signal which enables to use this particular device to con- existing and available architecture of the FireBus® communica-
trol pressure difference between the lobby and the reference or tion loop. MAC-LINK adapters are continuously monitored and
inside the air supply duct. thus any failure is immediately detected. Depending on actual
needs adapters can be fitted with desired number of inputs and
Dimensions MAC-D-MIN - 180 x250 x 90 mm outputs.

Family of the MAC-LINK adapters can be divided into three ba-


sic groups listed below:
• MAC-LINK adapter with maximum 4 inputs and 4 outputs,
• MAC-LINK-I adapter with 8 inputs,
• MAC-LINK-O adapter with 8 outputs.

Maximum number of MAC-LINK adapters installed in single


Local FireBus® loop is 8.
.

Picture 4. Regulator MAC-D-MIN for motorized volume control dam-


pers (for pressure differential systems)

Junction box (PZ)

Junction box is used to connect volume control damper’s ac-


tuators with the regulators MAC-D-MIN. Four different types
of junction boxes can be distinguished – PZ1 ÷PZ4. Number
in the designation of the box correspond to number of Belimo
Picture 7. MAC-LINK digital I/O adapter
NMQ24A-SR connected. Each junction box is power supplied
with 24VDC (power consumption depends on the total number
of actuators connected). Construction
Casing

Body of the unit is made as of aluminum profiles with steel


sheet profiles insulated with polyisocyanurate (PIR) foam. To
enable access for servicing and maintenance side panels are
removable.

Fan – Frequency Inverter

Fan powered by a frequency inverter supplies air into the pro-


Picture 5. Junction box PZ tected space. In order to enable sharp changes of air supply
rate all fans are fitted with breaking resistors taking energy out
of the system while decreasing fan’s capacity.
Temperature sensor (T-MACF)
Shut-off damper
For SAFETY WAY® pressurization system where reversible air-
flow within the stairwell is produced it’s direction is automati- In order to separate protected space from the outside (cold,
cally set basing on measured air temperature inside the stair- dust and other pollutants) during normal use of the building all
well and outside. This measurements are taken with T-MACF iSWAY-FC® type units are fitted with thermally insulated, mo-
remote temperature sensors located by default at the top and torized dampers installed at the air intake side. Shut-off dam-
bottom of the stairwell and transmitting signals to the MAC- per’s actuator is equipped with the return spring to increase
-FCR regulator installed in the iSWAY-FC(R)® unit through the overall system reliability. In case of power failure (e.g. caused
Local FireBus® communication loop. E by cable damage), the shut-off damper switches to the fully
open position assumed to be safe.

Duct smoke detector

All iSWAY-FC® type units by default are fitted with duct smoke
detectors installed inside the unit’s casing. Depending on the
programmed action upon smoke detection unit can be auto-
matically switched off or else smoke detection alarm can be
indicated.

Picture 6. Temperature sensor T-MACF


(for pressure differential systems)

version 6.0.1 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems 12
Pressure measurement tubes connection terminals 6 14 7 8 10 1 19 4 3 2 5

Pressure measurement tubes terminals are in the boxes


installed directly on the unit’s casing and marked as (+) for 11
12

pressure in the protected space and (-) for the reference. 13

Regulator MAC-FC(R)
20

MAC-FC(R) regulator is microprocessor electronic device inten-


ded for precise control of the pressure difference in accordance 19 18 17 16 15 9

with the requirements listed in EN 12101-6 standard. It ensures


full compliance with the requirements of the paragraph 5.4.2.5.
Figure 14. Structure and key components of the iSWAY-FC® unit
“Variable supply fans or dampers controlled by pressure sen-
sors shall not be used unless the system can achieve over 90
1. Casing (steel sheet insulated with PIR foam)
% of the new air supply requirements within 3 s of a door being
2. Infrared heater AF (option)
opened or closed.”
3. Airflow measurement probe
MAC-FC(R) regulator adjusts automatically capacity of the fan
4. Fan
by means of the frequency inverter depending on an actual va-
5. Breaking resistor
lue of pressure difference. Setting is automatically set depen-
6. Shut-off damper (air intake)
ding on the status of its outputs and displayed interconnected
7. Maintenance panel (servicing)
device.
8. Smoke detector
9. Frequency inverter
Main switch
10. Control cabinet
11. Reference pressure measurement terminal (-)
The main switch is used to disconnect power supply of the unit
12. Protected space pressure measurement terminal (+)
for maintenance or in case of an unpredicted emergency.
13. Main switch 14. Shut-off damper’s actuator
15. Cable tray
Power Supply - Control Cabinet (SzA-FCZ)
16. Thermostat (option)
17. Differential pressure sensor
SzA-FCZ cabinet is a component that power supplies iSWAY-
18. Regulator
-FC® unit’s components and controls the adjustable volume
19. Ventilation grille
control dampers using the information from MAC-FC(R) regu-
20. Terminals of control cables and FireBus® communication
lator. On the cabinet’s casing "Power supply control 3x400VAC
loop
and 24VDC" information is displayed whereas inside the cabi-
net 24VDC power supply equipment is installed. Additionally all
power supply outputs for system’s components are protected.

Differential pressure sensor P-MAC or P-MACF Principle of operation


P-MAC and P-MACF are digital pressure differential transdu- Control objective is precise control of pressure difference be-
cers fitted with one differential pressure sensor and connector tween the protected space e.g. stairwell, lobby, lift shaft and
providing power supply and data transmission over Local Fire- the reference (overpressure within protected space). The inver-
Bus® channels. Built in, internal microprocessor system per- ter supplied from the power network sends a control signal to
forms linearity correction while taking into account, inter alia, the fan motor alternating voltage with frequency inverter in the
operating temperature, and characteristics entered at the time range 0 to 50 Hz. This enables precise control of the motor rota-
of calibration. High accuracy and stability of measurement is tional speed i.e. fan capacity. The inverter receives a control si-
ensured by the use of sophisticated calibration equipment and gnal from the regulator, which corresponds to the frequency of
long-term aging process of the elements of the device. The co- 0 to 50 Hz. Control strategy is based on precise regulation of ac-
nverter is designed to measure air pressure with small degree tual pressure difference measured continuously with P-MAC(F)
of contamination. sensor e.g. 50 Pa. Control objective is in general reached with
automatically adjusted capacity of the air supply fan taking into
Two different variants of the sensors P-MAC and P-MACF were account actual leakage of the protected space (including door
described in paragraph: Measurement, monitoring and visuali- open/closed). It is assumed that overpressure of 50 Pa is con-
zation. sidered as sufficient to hold back smoke and thus keep escape
routes smoke free in case of fire. In case when total leakage of
Anti-Frost System the protected space is exceeds assumed value e.g. more doors
open simultaneously pressure drop within the protected space
If required iSWAY-FC® type units can be fitted with an infrared may occur.
heater in order to prevent shut-off damper from freezing (cold
outside condition). In this case all seals of the in the shut-off The most innovative feature of the MAC-FC(R) regulator is ap-
damper are made from special material which remains flexible plication of neural network based predictive algorithm which
at low temperatures. Infrared heater is activated depending on eliminates fixed control system settings popular for instance
the air temperature inside the unit by means of the thermostat. for PID controllers. Control system can adapt to changes in
In order to increase heat absorption and direct heat transfer the control object and learn. This ensures higher reliability and
internal surfaces of the unit operate as screen and damper is flexibility of the control system and adaptation to unforeseen
painted in black. scenarios e.g. broken window, blocked escape doors etc.

Tests carried out for iSWAY-FC® unit demonstrated that use of


MAC-FC(R) regulator is enables to generate and control the no-
minal value of pressure difference and automatically adapt to
changes introduced according to test procedure (range of fan

13 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems version 6.0.1
capacity min / max, and the range of leakage values min / max). Operation modes
The iSWAY-FC® type unit was tested at I.F.I. Institute for Indu-
strial Aerodynamics in Aachen, Germany in accordance with the Control system is designed in a manner to produce and control
current test procedure constituting part of the revised Europe- pressure difference or else airflow as described below:
an standard revEN 12101-6. • Door closed conditions: set value of pressure difference
between the protected space and the reference is produced
Tests were carried out for the biggest unit considered to be the e.g. 50 Pa +/- 20% (design pressure difference and toleran-
“worst case scenario” and thus representative for the whole ce may vary depending on system architecture and design
family of kits fitted with 15 kW fan and max. capacity 50 500 objectives to be met),
m3/h and for the lowest air leakage rate of 200 m3/h. All tests • Door open conditions: set value of directed airflow through
results were positive and have proven that tested kit meets all the open door between protected and unprotected spaces
the requirements in terms of response time, precise control, is produced e.g. min. 1.0 m/s (means of escape) or 2.0 m/s
reliability, durability and immunity to oscillations. (means of fire-fighting).

Note: all laboratory tests of the representative unit


were carried out in full control range (up to 50 Hz) Please note: to achieve airflow criterion (door
and all settings of the control system remained the open conditions) proper air release from the fire
same through all the tests in order to validate and storey shall be provided.
confirm self-adaptation features.

In most cases opening the door results in sharp pressure drop


whereas closing the door will result in significant pressure
Reliability of the device – test jump. Those differential pressures changes are more visible in
In order to guarantee the highest available safety level automa- small and airtight spaces e.g. lobbies. Control system of the
tic self-test function was introduced. By default every 24-hours pressurization unit shall be capable to stabilize pressure dif-
shut-off damper and fan are activated (damper is opened and ference within 3 seconds after opening or closing the door to
fan is started at the very low capacity) by MAC-FC regulator. enable safe evacuation and support fire-fighting.
During this test it is checked whether shut-off damper reaches
fully open position and fan-inverter set functions properly. Re- The control system in accordance with the principle "we do not
sults of such test are stored in the regulator’s memory. In case only realize fire scenarios, but save human lives" should reali-
any abnormality is detected general failure signal is transmit- ze control task in all conditions, regardless of the number of
ted immediately. open / partially closed doors, broken windows, etc.

Please note: air leakage of the protected space


may change rapidly e.g. stairwell with external
windows or smoothly door closer operation and
thus pressurization system shall be capable to
compensate negative influence of an unpredicted
processes.

Communication and control


In order to enable communication and control of the iSWAY-FC®
units based pressurization system dedicated FireBus® protocol
was developed and implemented. For any SAFETY WAY® type
pressurization system 2 FireBus® loops can be distinguished:

• Global FireBus® interconnects in the loop MAC-FC(R)


iSWAY-FC®(-D)(-R) regulators with TSS or TS (depending
on system configuration). The tasks:
• the transfer of Fire Alarm Signal (FAS) information be-
tween the devices,
• monitoring the status of different pressurization system
components and transmitting them to the TSS or MSPU,
• transmitting control signals sent from TSS or TS swit-
ches to proper devices.
• Local FireBus® interconnects in the loop MAC-FC(R)
iSWAY-FC®(-D)(-R) regulators with remote P-MACF diffe-
rential pressure sensors, MAC-D-MIN regulators, T-MAC
temperature sensors and MAC-LINK cards. The tasks:
• communication between regulators MAC-FC, tempe-
rature sensors T-MACF, regulators MAC-D-MIN and
MAC-LINK cards, with which it interoperates.

Figure 15. Official summary of the performance parameters of tested Local and Global FireBus® communication protocols have a
iSWAY-FC® unit loop topology which enables to increase its reliability and im-
munity to single damages of the data transmission lines (in
such case required component can be accessed through the
alternative branch of the loop).

version 6.0.1 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems 14
Dimensions and weight

W1

W2

C
187
A
D1

D2
B

Figure 16. External dimensions of the iSWAY-FC® type unit

Table 1. Dimensions of the iSWAY-FC® unit and connecting elements


External dimensions of the casing
A B C D1 D2 W1=W2
[mm] [mm] [mm] [mm] [mm] [mm]
0 1520 1070 870 435 435 770 x 770
Size of
1 1620 1320 1100 550 550 1000 x 1000
the casing
2 1720 1520 1300 650 650 1200 x 1200

Table 2. Performance and electrical parameters of the iSWAY-FC® units


Performance and electrical parameters of the iSWAY-FC® units
Electrical pro-
Availa- Electrical pro-
Power sup- Active Apparent tection within Recommended power
Capacity ble static tection within Weight
Typ ply power power the switchbo- supply cables
pressure the unit
ard.
[m3/h] [Pa] [V] [kW] [kVA] Typ [A] Typ [kg]
0.3 3000 900 3x400 3,38 3,45 FWC-10A10F gG 16 A NHXH FE180/E90 5x2,5 330
0.12 12000 430 3x400 5,47 5,57 FWC-16A10F gG 20 A NHXH FE180/E90 5x4 340
1.17 17000 380 3x400 5,26 5,36 FWC-16A10F gG 20 A NHXH FE180/E90 5x4 530
1.20 20000 390 3x400 6,96 7,10 FWC-16A10F gG 20 A NHXH FE180/E90 5x4 540
1.24 24000 360 3x400 9,22 9,40 FWC-20A10F gG 25 A NHXH FE180/E90 5x6 550
2.31 31000 400 3x400 9,22 9,40 FWC-20A10F gG 25 A NHXH FE180/E90 5x6 735
2.39 39000 420 3x400 13,00 13,26 FWC-32A10F gG 40 A NHXH FE180/E90 5x10 755
2.47 47000 300 3x400 17,40 17,75 FWC-40A10F gG 50 A NHXH FE180/E90 5x16 770

15 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems version 6.0.1
Performance curves
iSWAY-FC(-D)

1800

1600

1400

1200 - Airflow direction – air supply unit


- Airflow direction – air exhaust unit

1000

Figure 18. Basic version of the iSWAY-FC® unit to be installed horizon-


800 tally fitted with flexible connectors on the air intake/supply sides (duct
assembly version)
600

400

200
0,3 0,12 1,17 1,20 1,24 2,31 2,39 2.47

0
0 5000 10000 15000 20000 25000 30000 35000 40000 45000 50000 55000 60000

Stand-by air intake damper

iSWAY-FC -R
minimum 12 meters

1200

1000

800
Available static pressure [Pa]

600 Stand-by air intake damper

Air flow direction

400

200

1.17 1.20 1.24 2.31 2.39 2.47


0
Figure 19. iSWAY-FC® unit fitted with additional Twin-Air-Intake modu-
0 5000 10000 15000 20000 25000 30000 35000 40000 45000 50000 55000 60000 le (e.g. roof top assembly)
Flow [m³/h]

Figure 17. Performance curves of an iSWAY-FC® fans

Available structures of the unit


The basic version of the iSWAY-FC® unit is a compact structure
intended (Fig. 18.) intended to be installed outside e.g. roof or
ground level or inside e.g. machinery room. For units instal-
led on the roof or technical floors Twin-Air-Intake module is
recommended (Fig. 19.).

Other versions of an iSWAY-FC® units are unit with air intake


(Fig. 20.) and vertical assembly unit with adjustable air intake
module (Fig. 21.).

In order to achieve desired air intake rate of the pressurization


fan, for units installed within the ductwork, it is recommend to
provide straight duct section at least 1 m long before the fan
on the air intake side. Figure 20. iSWAY-FC® with additional air intake module

version 6.0.1 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems 16
1479

232

2190
387 max

Figure 21. Vertical assembly version of the smallest „0” iSWAY-FC® unit (adjustable air intake closed)

66

325
2510
387 max

Figure 22. Vertical assembly version of the smallest „0” iSWAY-FC® unit (adjustable air intake open)

17 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems version 6.0.1
Examples of electrical and data transmission connections

1P1 1P2

BLE24 BLE24

Key:
C1

ADAPTIVE

p - Control-Signal Board (TSS-1)


SAP
iSWAY-FC X.XX TSS-1
E2 A1
3x400V
- Motorized shut-off damper

- Differential pressure
D2 p measurement probes – tubes ø6 mm

BLE24 - Actuator Belimo BLE24

TSS-1

B1
1x230V
16W

MONITORING ROOM
e.g. BMS room

Figure 23. Block diagram of connections between TSS-1 Control-Signal Board and one iSWAY-FC® unit

1P1 1P2 2P1 2P2

BLE24 BLE24 BLE24 BLE24

C1 C1
ADAPTIVE ADAPTIVE

SAP
iSWAY-FC X.XX p SAP
iSWAY-FC X.XX p
E2 E2
1 A1 2 A1
3x400V 3x400V
D2 D2

Key:

- Control-Signal Board (TSS-2)


TSS-2

TSS-2 - Motorized shut-off damper

B1
BLE24 - Actuator Belimo BLE24-BELIMO
1x230V
16W
p - Differential pressure measurement probes
MONITORING ROOM – tubes ø5 mm
e.g. BMS room

WIRING
Figure 24. Block diagram of connections between TSS-2 Control-Signal Board and two iSWAY-FC® units
Marking on
Connections of automation components Tye of the cable
the diagram
Guaranteed power supply cable
A1 TABELA 2
3x400V for iSWAY-FC
Guaranteed power supply 1x230VAC MSPU,
version 6.0.1 B1 NHXH
iSWAY-FC® – compact FE180/PH90
pressurization 3x1,5for smoke and heat control systems
unit intended 18
TS, TSS
1P1 1P2 2P1 2P2 3P1 3P2

BLE24 BLE24 BLE24 BLE24 BLE24 BLE24

C1 C1 C1
ADAPTIVE ADAPTIVE ADAPTIVE

SAP
iSWAY-FC X.XX p SAP
iSWAY-FC X.XX p SAP
iSWAY-FC X.XX p
E2 E2 E2
1 A1 2 A1 3 A1
3x400V 3x400V 3x400V
D2 D2 D2

Key:

- Control-Signal Board (TSS-3)


TSS-3

TSS-3 - Motorized shut-off damper

B1
1x230V BLE24 - Actuator Belimo BLE24
16W
p - Differential pressure measurement probes – tubes ø5 mm
MONITORING ROOM
e.g. BMS room

Figure 25. Block diagram of connections between TSS-3 Control-Signal Board and three iSWAY-FC® units

19 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems version 6.0.1
Fire-fighting lobby with electronically Staircase Lift lobby Rescue lift shaft
controlled air transfer

Roof level

inside outside

inside outside

Level +29

Inside Outside
temperature temperature
measurement measurement

Level +28

Inside
temperature
Outside
temperature
Level ...
measurement measurement

inside outside

inside outside number


Control and monitoring
Level +1 room e.g. BMS

Level 0

EXEMPLARY WIRING Sizes of automation


Marking
Key components
Connections of automation components Type of the cable Name
in the diagram Dimensions DxHxS [mm]

Guaranteed power supply


TABLE 2 Operating Conditions
3x400V for iSWAY-FC® type unit Temperature sensor T-MAC
Monitoring Device (MSPU)
Guaranteed power supply
1x230VAC for TSS, TS and MSPU
Junction box PZ
Power supply and control
24VDC for Twin-Air-Intake module Control Board (TS - Y)
Adjustable volume control
Guaranteed power supply
where Y – number of iSWAY-FC® units dampers regulator (MAC-D-MIN)
24VDC for P-MACF and MAC-D-MIN
Guaranteed power supply Motorized air damper
24VDC for PZ (1 – 2 actuators)
Guaranteed power supply Actuator Belimo NMQ24A-SR
24VDC for PZ (3 actuators)
Guaranteed power supply Actuator Belimo BLE24
24VDC for PZ (4 actuators)
Differential pressure measurement probes –
Control and monitoring
of the actuator NMQ24A-SR tubes Ö 6 mm
Local FireBus® loop
Differential pressure sensor (P-MACF)
Global FireBus® loop
FireBus® magisterial line

Fire Alarm Signal (NC)

Fire Alarm Signal (NC)


Operation confirmation (NO)
General failure (NC)

Connection between MAC-D-MIN and PZ

Figure 26. Exemplary block diagram of the expanded SAFETY WAY® pressure differential system (air release must be additionally provided)

version 6.0.1 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems 20
Installation guidelines Described set of two alternative intakes operating automatical-
ly and enabling to switch to an alternative air intake is offered
Each iSWAY-FC® type unit shall be installed (units, air intakes, by SMAY company as a Twin-Air-Intake Module. Such module
cable trays etc.) in such manner to avoid any collisions with consists of two motorized volume control dampers with strictly
other installations and enable free access to the removable in- defined air tightness in accordance with EN 1751 and protected
spection panels (maintenance and servicing). In order to enable from the negative influence of ambient conditions. By default
easy access to the unit minimum distance from the fixed ele- sizes of the air intake dampers are compatible with sizes of
ments e.g. walls shall be maintained.. flexible connectors of the iSWAY-FC® units (easy assembly and
connections).

0,9 xB B
Multiblade air damper SRC-Z-U

Size of the
Service
casing B [mm] H [mm]
Side iSWAY-FC
0 770 770
1 1000 1005
2 1200 1205

B+200 300
Figure 27. Minimum distance of iSWAY-FC® unit from the fixed ele- B+60
200
B
ments (e.g. walls)

Twin Air-Intake module (alternative air inta-


ke in case of smoke contamination)

H+60
H
actuator
Air intake shall be provided for drawing air in from outside the
building in such a way that it is not contaminated with smoke
electric box
from a fire within the building. Air intake (intake) should always cable
gland

be positioned away from any potential fire hazards. In order to actuator’s box
damper
avoid contamination by the rising smoke, it is recommended to
locate air intakes at the ground level or close to it (but well away
Figure 28. Dimensions of the Twin-Air-Intake module
from the basement smoke vents). If it is not possible, air intakes
should be positioned at the roof level. It is essential that the air
supply used for pressurization is never in danger of contamina-
tion by smoke. If the air intake is located at the roof level it is
obligatory to provide smoke detector inside the air supply duc- Identification of the unit
twork to cause automatic shutdown of the air supply fan. For
the needs of the fire brigades manual override switch operating
the air supply fan shall be provided.

Where air intakes are positioned at roof level there shall be


two air intakes (Twin-Air-Intake module), spaced apart and fa-
cing different directions in such a manner that they could not
be directly downwind of the same source of smoke. Each inlet
shall be independently capable of providing the full air require-
ments of the system. Each inlet shall be protected by an in-
dependently operated smoke control damper system in such
a way that if one damper closes due to smoke contamination,
the other inlet will supply the air requirements of the system
without interruption.

The discharge point of a smoke ventilation duct shall be a mi- Figure 29. iSWAY-FC® rating plate
nimum of 1 m above the air intake and 5 m horizontally from
it. Manual override switch to reopen the closed damper and to Each iSWAY-FC® type unit is fitted with individual rating plate
close the open damper shall be provided for fire brigade use. indicating parameters that enable precise identification of the
Manual override switches of pressure differential system sho- unit.
uld be located in the following locations:
a) machinery room or machinery room of the pressure differen- Type – specifies the device's technical specifications,
tial system (if separated), and e.g. FC 1.20
b) near the entrance to the building, at the site agreed with local S/N – serial number
authorities having jurisdiction. Year – production year
V – capacity of the fan at available static pressure Δp
These switches after activating should be locked in the "on" po- P – electric power of the unit [kW]
sition, and should be designed so that their return to the "off" ΔP - available static pressure [Pa]
position is made by authorized personnel (e.g., by staff or by
using code lock).

21 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems version 6.0.1
Accessories and ordering instructions
Upon placing an order for iSWAY-FC® type unit following information shall be provided:

iSWAY - FC-<A>-<W>.<V><P>-<X>-<T>/<ADD>-<VER> <U>

Where:
A control system
none: standard control system
D - intended for local FireBus® loop
R - reversible flow fans (counteracting stack effect)
W size of the casing [mm]:
0 unit’s version 2012: 1500 x 1050 x 850; unit’s version 2015: 1520 x 1070 x 870
1 unit’s version 2012: 1600 x 1300 x 1080; unit’s version 2015: 1620 x 1320 x 1100
2 unit’s version 2012: 1700 x 1500 x 1280; unit’s version 2015: 1720 x 1520 x 1300
V capacity of the fan at 300 Pa
3 - capacity 3000 m3/h (for W = 0)
12 - capacity12000 m3/h (for W = 0)
17 - capacity 17000 m3/h (for W = 1)
20 - capacity 20000 m3/h (for W = 1)
24 - capacity 24000 m3/h (for W = 1)
31 - capacity 31000 m3/h (for W = 2)
39 - capacity 39000 m3/h (for W = 2)
47 - capacity 47000 m3/h (for W = 2)
P differential pressure sensor range
none = -250;250Pa
HP - 600;600Pa
X service side
none: right side
L - left side
T operating temperatures range
none: from -5 to +55 °C
AF - from -25 to +55 °C – fitted with Anti Frost system
ADD accessories:
KE - flexible connector on the intake side
CP - air intake
UP - Twin-Air-Intake module
DA - automatic roof (for W=0, VER-2012)
SS - installation on welded feet – horizontal assembly
BF - installation on Big Foot - horizontal assembly
KM - fixation with angle bars – horizontal assembly
RS - installation on welded frame – horizontal assembly
SW - installation on self-aligned foot – vertical assembly with top air intake
(VER-2012)
PSW - installation on platform and self-aligned foot (VER-2012)
VER unit’s version
2012 - version 2012 (casing thermally insulated with mineral wool and separate power supply equipment)
2015 - version 2015 (casing thermally insulated with PIR foam and integrated power supply equipment)
U location of the device
none inside the building
Z outside the building

version 6.0.1 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems 22
Exemplary order code:
iSWAY – FC – D – 1.20 – AF / KE, KM – 2015

Note:
Upon placing an order where TSS-1, TSS-2, TSS-3, TS, MSPU, T-MACF, MAC-LINK, P-MACF,MAC-D-MIN, PZ are included it is
indispensable to define number of each component listed above e.g.

Example:
TSS-1 - 1 pcs.
T-MACF - 8 pcs.
P-MACF -250÷ 250 – 16 pcs.

By default iSWAY-FC® units are fitted with flexible connectors on the air intake side to be installed on welded feet (SS) or fixed with
angle bars (KM). All other components shall be ordered separately. Unit’s casing is painted in RAL color 9010 (white).

Note:
In case when pressurization system consists of more than 6 iSWAY-FC® type units it is recommended to provide control,
visualization and monitoring of such pressurization system by means of Control Board (TS) and Operating Conditions Monitoring
Device (MSPU) which enable easy integration of all components.

23 iSWAY-FC® – compact pressurization unit intended for smoke and heat control systems version 6.0.1