Grid Solutions

Multilin F650
Feeder Protection & Bay Controller
The Multilin™ F650 has been designed for the protection, control and automation of feeders or related
applications. The Multilin F650 provides high speed protection and control for feeder management and
Protection & Control
bay control applications, and comes with a large LCD and single line diagrams that can be built for • Time, instantaneous & directional phase, neutral,
bay monitoring and control for various feeder arrangements including ring-bus, double breaker or for ground and sensitive ground overcurrent
breaker and half. • 2nd Harmonic restraint
Designed with advanced communications options and detailed monitoring capabilities, the Multilin F650 • CT Supervision
provides advanced functionality, including high-performance protection, extensive control functions • Manual close with cold load pick up control,
and flexible configuration capabilities. The Multilin F650 can also be used for a variety of applications forward power and directional power units
other than feeder protection and control.
• Load encroachment supervision
• Wattmetric ground fault detection
Key Benefits • Positive and negative sequence based over/
• Comprehensive and flexible protection and control device for feeder applications under voltage elements
• Increased system uptime and improved system stability with load shedding and transfer schemes • Four-shot autorecloser with synchronism check
• Advanced automation capabilities for customized protection and control solutions • Trip circuit supervision, breaker control and
• Human Machine Interface (HMI) with graphical LCD, programmable buttons, and easy keys for breaker failure
selecting setting menus, and submenus • Frequency protection (rate of change and six
• Reduced replacement time with modular draw-out construction stages of under and over frequency)

• Reduced troubleshooting time and maintenance costs with IEEE® 1588 (PTP), IRIG-B and SNTP time • Broken conductor and locked rotor
synchronization (configuration of two different SNTP masters), event reports, waveform capture, and • Programmable digital inputs and outputs
data logger
• 6 Setting Groups
• Simplified system integration with communications supporting serial and Ethernet interfaces as well
as multiple protocols
• Embedded IEC® 61850 protocol (and support for edition 2), IEC 60870-5-103/104, IEC 62439/PRP/HSR, Monitoring & Metering
IEEE 802.1D/RSTP • Fault locator, fault and event recorder
• Proven interoperability and KEMA 61850 Edition 2 certified • Comprehensive breaker monitoring
• High resolution oscillography and data logger
Applications with programmable sampling rate
• Primary or back-up protection and control for feeders on solidly grounded, high impedance grounded • Metering: V, I, Hz, W, VA, PF
or resonant (Peterson Coil) grounded systems • Demand: Ia, Ib, Ic, Ig, Isg, I2, MW, MVA
• Bus blocking/interlocking schemes
• High-speed fault detection for arc flash
EnerVista Software
• Throw over schemes (bus transfer scheme applications)
• Simplified setup, configuration and
• Load shedding schemes based on voltage and frequency elements commissioning
• Distributed Generation (DG) interconnect protection, including active and passive anti-islanding • Strong document archive and
management system
• Simplified full featured monitoring and
data recording
• Seamless integration toolkit
F650 Feeder Protection & Bay Controller

Protection and Control Directional supervision is available for phase, Over/Under Frequency Protection
neutral, ground and sensitive ground currents.
The F650 provides high speed protection and The F650 offer six stages of overfrequency and
The neutral/ground directional elements
control for feeder management and bay control underfrequency elements to improve network
can be programmed to work under zero-
applications, including: (grid) stability using voltage or frequency based
sequence voltage, ground sensitive current or
loadshedding techniques. It also allows to
dual polarization.
Overcurrent Protection provide back up protection and trip breakers
directly when protecting feeders and other
Instantaneous and time over­current functions Over/Under Voltage Protection
frequency sensitive power equipment.
are available for phase, neutral, ground/sensitive
The F650 includes the following voltage elements:
ground and negative sequence currents. A
• Phase undervoltage/overvoltage elements
Frequency Rate of Change Protection
variety of time curves are provided including
IEEE/ANSI®, IEC A/B/C/long time inverse/short (each element has three individual phase Frequency rate of change (df/dt) elements
time inverse, GE IAC, I2t, definite time, rectifier undervoltage/overvoltage components) included in the F650 provide protection against
curve and four user-programmable curves. • Auxiliary undervoltage/overvoltageelement system disturbances through load shedding.

• Neutral overvoltage element


Directional Elements Wattmetric Zero-sequence Directional
Following are some of the key applications
Applications include ground fault protection
where voltage elements can be used:
in solidly grounded transmission networks,
• Source transfer schemes grounded/ungrounded/resistor-grounded/
• Load shedding schemes resonant-grounded distribution networks. The
wattmetric zero-sequence directional element
• Back up capacitor bank protection and
responds to power derived from zero-sequence
control
voltage and current in a direction specified by
• Backup motor protection to prevent the element characteristic angle. The angle
Flexible load encroachment characteristic in automatic restart can be set within all four quadrants and the
F650 can be set by adjusting the load angle and power can be active or reactive. Therefore, the
the reach.

Functional Block Diagram BUS

3 CTs 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 27X 3

50BF CLP 49 50PH 50PL 46 48 51PH/V 51PL/V 67P 32 32FP BROKEN


CONDUCTOR 32N 51N 50N 67N 60CTS
59X 3

3 3 3
50G/ 67G
51G 50G
51G

25 1
3 3 3 3
CT
50G/ 50IG 67SG
51SG 50SG
51G

BREAKER

METERING
52
TRANSIENT RECORDER
EVENT RECORDER
FAULT REPORT
79
TRIP CLOSE
3V0 CALCULATION
MONITORING

3
47 27P 59P VTFF 81U 81O 81R
59NH 3
3 3 3 1 6 6 3

LOAD 59NL 3
F650 Feeder Protection Relay and Bay Controller
ANSI Device Numbers & Functions
DEVICE FUNCTION DEVICE FUNCTION DEVICE FUNCTION
NUMBER NUMBER NUMBER
25 Synchrocheck 50G Ground Instantaneous Overcurrent 67N Neutral Directional Overcurrent
27/27X Bus/Line Undervoltage 50SG Sensitive Ground Instantaneous Overcurrent 67G Ground Directional Overcurrent
32 Sensitive Directional Power 50IG Isolated Ground Instantaneous Overcurrent 67SG Sensitive Ground Directional Overcurrent
32FP Forward Power 51N Neutral Time Overcurrent 79 Autorecloser
32N Wattmetric zero-sequence directional 51G Ground Time Overcurrent 81 U/O Under/Over Frequency Broken Conductor
46 Negative Sequence Time Overcurrent 51SG Sensitive Ground Time Overcurrent Detection
47 Negative Sequence Voltage 51PH/V Voltage Restraint Phase Time Overcurrent 81R Frequency Rate of Change
48 Blocked Rotor 51PL/V VTFF VT Fuse Failure Detection
49 Thermal Image - overload protection 59/59X Bus/Line Overvoltage Load Encroachment
50 BF Breaker Failure 59NH/NL Neutral Overvoltage - High/Low
50PH/PL Phase Instantaneous Overcurrent (High/Low) 67P Phase Directional Overcurrent
50N Neutral Instantaneous Overcurrent 60CTS CT supervision

2 GEGridSolutions.com
F650 Feeder Protection & Bay Controller

element may be used to sense either forward Autoreclosurer Advanced Automation


or reverse ground faults in either inductive,
This function is applicable to three-pole tripping The F650 incorporates advanced automation
capacitive or resistive networks. The inverse
schemes and single breaker applications. Four features including powerful programmable
time characteristic allows time coordination of
reclosing “shots“ are possible prior to locking logic, communication, and SCADA capabilities
elements across the network.
out, each with an independent time setting. that far surpass what is found in the average
Auto­reclosure outputs can be used to modify feeder relay. The F650 integrates seamlessly
Breaker Failure and Control
circuit protection settings between shots. with other Multilin relays for complete system
The breaker failure function determines if a
protection.
trip command sent to a breaker has not been Synchronism Check
executed within a selectable time delay. In the F650 Logic Configuration
One synchronism check element is available.
event of a breaker failure, the unit will issue an
The algorithm allows breaker close time F650 Logic Configuration is the powerful
additional signal to trip the breakers
compensation to optimize close conditions. programming logic engine that provides the
connected to the same busbar, potential
The element monitors maximum difference in ability of creating customized protection
sources of fault current.
voltage magnitudes and control schemes thereby minimizing the
The F650 incorporates 3 levels of current and need, and the associated costs, of auxiliary
( V), phase angles ( ), and frequencies
time, together with a trip without current components and wiring. Using F650 Logic
unit, and an internal arc detection unit. The ( f) as well as the dead source condition. Configuration, the F650 can be programmed
breaker failure unit has three levels: “Retrip” to provide required tripping logic along with
or “Supervision” used to generate a second Multiple Settings Groups
custom scheme logic for auto transfer schemes
trip signal to the corresponding breaker on Six separate groups of protection settings (Main-Tie-Main), load shedding based on
which the initial opening has been executed, may be stored in the F650 non-volatile frequency, voltage and communication, loop
“High Level”, and “Low Level” used to executing memory. The user can edit the active settings restoration schemes, other remedial action
complex protection schemes. The function can internally and externally via contact inputs and schemes and dynamic setting group changes.
be initiated/blocked via digital inputs as well as communications. F650 provides a comprehensive set of analog
communications. operands for two digital or analog inputs.
Broken Conductor
The relay also provides for control of one or two
F650 incorporates a broken or fallen conductor Inputs and Outputs
breakers from faceplate pushbuttons, remote
communications or contact inputs. A breaker detection function. The relay uses the ratio A choice of 16 to 64 inputs and 0 to 16
pole discrepancy is included in the breaker between the negative sequence current, I2, and outputs are available. The F650 also provides
control scheme. Breaker position is indicated by the positive sequence current I1. In normal and a comprehensive set of analog operands for
LEDs on the faceplate. balanced load situations, this ratio is zero, while two digital or analog inputs. Digital inputs may
in severe load fault conditions, an unbalance is be user defined with a separate debounce
Load Encroachment produced and this ratio increases. and chatter time. Programmable “quasi“
analog input levels allow the use of different
Feeders may experience very heavy load In order to avoid trips or pickup with very weak
voltage levels in the same model via setting
increases due to various contingency situations. loads, there is a current level threshold (I2/I1) to
the requested thresholds. EnerVista™ software
The Load Encroachment function in F650 inhibit the operation of the element when the
allows easy configuration of all the interlocking
provides the capability to manage such load three phase currents are below a fixed level.
and switching sequences. A graphic HMI
growth in feeders. The load encroachment
Locked Rotor interface provides access to monitoring,
element can be set for the feeder’s expected
metering and alarm panel screens.
maximum load, reducing the likelihood of false F650 incorporates a locked rotor element .
tripping for load conditions while maintaining Protection element 48 produces a trip when Virtual Inputs/Outputs
dependability to trip for legitimate faults. current (primary values) exceeds the set value.
Traditionally, protective relay logic has been
The load encroachment supervision in F650 is This current setting value is the product of the
relatively limited. Use virtual inputs and outputs
based on positive-sequence voltage and current set Full Load Current by the pickup setting.
in conjunction with the programmable logic
and applies a characteristic as shown in the capabilities of the F650 for unusual applications
figure above. It allows the user to set the phase involving interlocks, blocking, or supervisory
overcurrent elements below peak load current functions, to minimize the requirement for
to see end-offline phase faults in heavily loaded auxiliary components and wiring while making
feeder applications. more complex schemes possible.

The virtual inputs and outputs are digital signals


associated with the F650 internal logic. Virtual
inputs include signals generated remotely
via communications. The virtual outputs are
outputs of programmable logic equations used
to customize the device. Virtual outputs can also
serve as inputs to programmable logic equations.

GEGridSolutions.com 3
F650 Feeder Protection & Bay Controller

CAN BUS Remote I/O (CIO) Monitoring and Metering Trip Circuit Monitoring
The F650 can be ordered with up to two The F650 provides advanced monitoring and F650 can be used to monitor the integrity of
additional communication cards on the rear. metering that includes: both the breaker trip and closing coils and
Besides two identical ports, COM1 and COM2, circuits. The supervision inputs monitor both the
the cards may incorporate a port for CAN BUS Current Transformer Failure battery voltage level, while the outputs monitor
communications used to connect the Remote the continuity of the trip and/or closing circuits,
In event of abnormal behaviour of the CT or
CAN BUS I/O module (CIO Module). Use the by applying a small current through the circuits.
a loss of phase the F650 detects a change in
CIO Module to double the number of I/Os of
zero sequence current to initiaes a CT faillure
the F650, when the maximum number of I/Os Basic Metering
event and an output that can be used to block
available inside the relay (up to 64 inputs and Metered values include:
critical protection functions. This feature can
16 outputs) is not sufficient to meet the needs of
be inhibited either by zero sequence voltage, • Current: Ia, Ib, Ic, In, Ig, Isg
specific applications.
ground /sensitive ground current.
• Phase-to-phase and phase-to-ground
In addition to increasing the number of I/Os,
voltages for bus and line: Van, Vbn, Vcn, Vbb, Vab,
the CIO Module allows the F650 to monitor 2nd harmonic inhibit
Vbc, Vca
signals located at a remote location with only The F650 provides 2nd harmonic detecion that
• Active power (per-phase and total): Wa, Wb,
a connection between both devices, resulting in can be used to block sensitive elements, especially
Wc, W
significant savings in installation costs. during transformer energization. The setting can
be based on any phase, any two phases, all three • Reactive power (per-phase and total):
Transducer Inputs phases or an average of the 3 phases. VAra, VArb, VArc, VAr

dcmA inputs are available to monitor system • Total active and reactive energy: MWh, Mvarh
parameters such as temperature, vibration, VT Fuse Failure • Power factor (per-phase and total)
pressure, wind speed, and flow. Use the VT Fuse Failure feature to issue an alarm • Frequency
and/or to block voltage driven protection functions
Remote I/O • Demand
that can operate incorrectly due to an abrupt
The remote I/O feature provides a means of partial or total voltage loss. This loss is caused • Ia, Ib, Ic, Ig, Isg, Va, Vb, Vc and Vx signals are
sharing digital point state information between by the voltage transformers secondary circuit available locally and remotely and can be
F650s or other IEC 61850 compliant IEDs or protection fuse failure. Different methods are used stored in the oscillography record or data
controllers. The remote outputs interface to detect the different types of VT fuse failure. logger.
seamlessly to the remote inputs of other F650
devices via the IEC 61850 GSSE messaging. User
secure peer-to-peer communications to develop
complex schemes in distributed logic and I/Os.

Double the Number of I/O’s of F650

Up to 32 inputs + 16 outputs embedded

F650
MV Switchgear

Up to 64 inputs + 16 outputs

CIO
Circuit Breaker
CAN BUS to connect to a remote CAN BUS I/O module (CIO module)

4 GEGridSolutions.com
F650 Feeder Protection & Bay Controller

Example of Redundant HSR and PRP Architecture of communication networks by providing


redundancy and zero reconfiguration time in the
event of a failure. Failsafe communications systems
Data are crucial for industries and utilities with critical
Local HMI / SCADA EMS DMS Historian AMDS
Single Line PowerOn PowerOn PowerOn Proficy PowerOn applications where no recovery time is tolerated.
Reliance Reliance Fusion Historian Advantage

The F650 supports popular industry leading


standard protocols enabling easy, direct
integration into electrical SCADA and HMI systems.
The protocols supported by the F650 include:

• IEC 61850 (and support for edition 2)


• DNP 3.0
D400 D400 • Modbus RTU
• Modbus TCP/IP
• IEC 60870-5-103/104
• IEC 60870-5-103 and IEC 60870-5-104
• PRP & HSR (IEC 62439-3)
• RSTP (IEEE 802.1D)
• IEEE 1588 (PTP) for time synchronization
The F650 includes up to three communication
ports that operate simultaneously. Redundant
ports are also available for special applications.
F650 features an RS232 front port (COM2) and a
choice of rear RS485, plastic/glass fiber optics
8 Series F650 350 UR F650 350
(COM1 and COM2). Additionally, this module may
PRP Network HSR Ring incorporate a port for CAN bus communications,
used for the connection to the remote CAN
BUS I/O module. F650 COM3 features 10/100
Redundancy protocols (PRP and HSR) can be used for various networking architectures including BaseTX and 100 Base FX single or redundant
combined PRP/HSR topologies. Ethernet ports.

Security
Event Recording and Oscillography of faults and is available as default. The F650 Independent passwords for protection and
provides the estimated distance to the fault in control allow restricting access via keypad and
The F650 is capable of storing 1024 or 512
terms of the resistance and reactance of the display, or EnerVista software.
(depending on the selected model)time-tagged
circuit considering the fault type.
events (1 ms tagging), to help with trouble­
shooting. The trigger point, the channels, and Multi-Language
Communications
sampling rate of the oscillography files are user The F650 supports multiple languages. French,
programmable features. Up to five seconds at The F650 incorporates industry-leading Chinese, Russian language options are available
maximum sample rate can be stored. communication technologies making it one of on the local display, front panel, and EnerVista
the easiest and flexible feeder protection relay setup software, as well as the product instruction
Breaker Arcing Current (I2t) for use and integration into new and existing manual. Easily switch between English and an
infrastructures. additional user selectable language on the
The relay estimates the total interrupted
current as an accumulation of the RMS current The F650 provides optional Parallel Redundancy local display. The basic display supports English,
measured during the time period taken to open Protocol (PRP), High Availability Seamless Ring French, Spanish, Russian, Turkish and Chinese
the breaker after a trip. It calculates the per- (HSR) (IEC 62439-3) and also Rapid Spanning Tree languages.
phase wear on the breaker contacts to establish Protocol (RSTP) (IEEE 802.1D) to increase network
a threshold. When the breaker maintenance availability and reliability for critical applications. Interoperability With Embedded
threshold is exceeded the relay can be set to IEC 61850 Protocol
The basic concept of both protocols, PRP and HSR,
trigger an alarm. IEC 61850 is the international standard for
is to send identical frames over different paths
information exchange and interoperability
Fault Locator and discard one of the copies in reception, at
between intelligent devices within a substation.
best. If an error occurs or one of the paths goes
Fault Locator function provides an estimation Use the F650 with IEC 61850 to lower the costs
down, the frame travelling through that path will
of the fault location. Deploying proven single- and simplify the engineering, commissioning,
not reach its destination, but its copy remains
ended type algorithms, F650 is capable of operating, and maintenance associated with
intact and will reach the desired destination. This
providing accurate estimation of the location substation protection and control applications.
technology ensures high reliability and availability

GEGridSolutions.com 5
F650 Feeder Protection & Bay Controller

The F650 provides integration with 61850 software included with every F650 relay, to carry Viewpoint Monitoring
standard edition 2. IEC 61850 allows for the out postmortem event analysis to ensure proper
Viewpoint Monitoring is a simple-to-use and full-
seamless connection of IEDs from multiple protection system operation.
featured monitoring and data recording software
vendors. As a KEMA 61850 edition 2 certified
EnerVista Launchpad package for small systems. Viewpoint Monitoring
device, the F650 is in compliance with the
provides a complete HMI package with the
IEC 61850 standard, and seamless interoperability EnerVista Launchpad is a powerful software
following functionality:
with devices supporting this standard can be package that provides users with all of the
assured. In addition to device interoperability, setup and support tools needed for configuring • Plug-&-Play Device Monitoring
these protocols are designed to control the and maintaining Multilin products. The setup • System Single-Line Monitoring & Control
substation via a LAN instead of through discrete software within Launchpad allows configuring
• Annunciator Alarm Screens
wiring to an RTU. Peer-to-peer communication devices in real-time by communicating using
over Ethernet enables distributed control with • Trending Reports
serial, Ethernet, or modem connections, or offline
several IEDs and eliminates the need for an RTU by creating setting files to be sent to devices at • Automatic Event Retrieval
to remote SCADA master. High-speed message a later time. • Automatic Waveform Retrieval
transfer eliminates the need for large and costly
Included in Launchpad is a document archiving
hard-wired interconnection.
and management system that ensures critical
documentation is up-to-date and available when
EnerVista Software needed. Documents made available include:
The EnerVista™ Suite is an industry-leading • Manuals
set of software programs that simplifies every
• Application Notes
aspect of using the F65 relay. The EnerVista
suite provides all the tools to monitor the status • Guideform Specifications
of your the protected asset, maintain the relay, • Brochures
and integrate information measured by the • Wiring Diagrams
F650 into DCS or SCADA monitoring systems.
• FAQ’s
Convenient COMTRADE and Sequence of Events
viewers are an integral part of the 650 Setup • Service Bulletins

6 GEGridSolutions.com
F650 Feeder Protection & Bay Controller

User Interface

Display
Graphic 16x40 or text 4x20 LCD display
Fluorescent backlight to improve visibility

LEDs
Multicolor programmable LEDs with label panel
Local/Remote/Off pushbutton with LEDs

Keypad & Shuttle


Local/Remote/Off pushbutton withLEDs
Key control for easy navigation
Ergonomic programmable keys

Front Port
Electrically isolated front USB communication port

Dimensions
The F650 uses a “shuttle“ control for ease of use. A choice of text or graphic display, and up to five configurable keys are available for frequently performed
control functions. Up to 15 programmable LEDs are available. The F650 can incorporate (option “N” for the second position of the ordering code) a Graphical
display with IEC Symbols.

SIDE VIEW FRONT VIEW CUTOUT

210 ( 8,27 )

28 172,8 237 186 ( 7,32 )

19

4x 7 ( ,27 )
263 ( 10,36 )

190,5 ( 7,5 )
260,7

266,3

NOTE: All dimensions are shown in mm (inches)

GEGridSolutions.com 7
F650 Feeder Protection & Bay Controller

Dimensions

8 GEGridSolutions.com
F650 Feeder Protection & Bay Controller

Technical Specifications
PROTECTION PROTECTION Minimum voltage threshold:
3 to 300 in steps of 1V
PHASE/NEUTRAL AND GROUND TIMED OVERCURRENT ISOLATED GROUND INSTANTANEOUS OVERCURRENT (50IG) Logic: Any/two/all phases logic selectable by
(51PH/51PL/51N/51G) Current Input: Fundamental Phasor (without harmonics)
Current: Fundamental Phasor (w/o harmonics) or RMS setting
Rated current : For connection to 1 or 5 A CTs. Voltage Input: Fundamental Phasor (without harmonics) Supervised by breaker:
Pickup level : 0.05 to 160.00 A in steps of 0.01 A Current Pickup level: 0.005 to 0.400 A in steps of 0.001 A Selectable by setting
Reset Dropout level: 97% to 98% of the pickup level Voltage Pickup level: 2 to 70 V in steps of 1 V Timing accuracy: ±3.5% of operation time or 50 ms.
Accuracy: ±0.5% of the reading ±10 mA from 0.05 Dropout level : 97 to 98% of the pickup level (whichever is greater)
to10A Pickup level: for voltage 2 to 70 V in steps of 1 V
±1.5% of the reading for values higher Dropout Level: 97-98% of the pickup level PROTECTION
than 10A Level Accuracy: ±1.5% of the reading ± 1 mA from 0.005 AUXILIARY OVERVOLTAGE (59X)
OPERATION CURVES to 16 A
IEEE extremely/very/moderately inverse Trip delay: 0.00 to 900.00 s. in steps of 0.01 s. Pickup level: 3 to 300 in steps of 1 V
IEC Curve A/B/C/Long-Time Time to instantaneous 0.00 to 900.00 s. in steps of 0.01 s. Reset dropout level: 97% to 98% of the pickup level
Inverse/ Short-Time Inverse Operate time: <50 ms at 3 x Pickup at 50 Hz, typically Accuracy: ±1% of the reading, from 10 to 208 V
ANSI extremely/very/normally/moderately Timing accuracy: at 0 ms time delay (no intentional Timing accuracy: ±3.5% of operation time or 50 ms
inverseI2t delay): 50ms at non-zero time delay: (whichever is greater)
IAC extremely / very / moderately inverse ±3% of operate time or 50 ms (which AUXILIARY UNDERVOLTAGE (27X)
Definite time ever is greater) Pickup level: 3 to 300 in steps of 1 V
Rectifier curve Snapshot Events: Selectable by setting Reset dropout level: 97% to 98% of the pickup level
User curve FlexCurve™ A/B/C/D Accuracy: ±1% of the reading, from 10 to 208 V
PHASE DIRECTIONAL UNITS (67P) Operation curves:
Reset time type: Instantaneous or time delayed according
to IEEE Directionality: Forward and reverse selectable by setting Fixed time or inverse curve
Snapshot events: Selectable by setting Polarizing: Quadrature Voltage: Timing accuracy: ±3.5% of operation time or 50 ms
Timer accuracy: From 1.03 times the pickup, ±3% of ABC seq: Phase A (VBC), Phase B (VCA), (whichever is greater)
operation time or 50 ms. (whichever is Phase C (VAB)
ACB seq: Phase A (VCB), Phase B (VAC), FREQUENCY (81U ,81O)
greater)
Phase C (VBA) Pickup level: 20 to 65 Hz in steps of 0.01 Hz
Voltage restraint: Selectable by setting Reset dropout level: 30 mHz higher/lower than the
Polarizing voltage threshold: 0 to 300 Vac in steps of 1 V
NEGATIVE SEQUENCE (46) Current Sensitivity Threshold: 50 mA pickup level
Current: Fundamental phasor (without harmonics) Characteristic angle: -90º to +90º in steps of 1º Accuracy: 0.05 Hz
Pickup level: 0.05 to 160.00 A in steps of 0.01 A Block Logic: Permission or Block selectable by setting Operation time trip delay: 0.00 to 900.00 s. in steps
Reset level: 98% of the pickup level Angle accuracy: ±2º for I>0.1 A and V>5 Vac of 0.01 s
Accuracy: ±0.5% of the reading ±10 mA from 0.05 to Operate time: <30ms, typically Reset time delay: 0.00 to 900.00 s. in steps of 0.01 s
10A Timer accuracy: ±3.5% of operation time or 100 ms.
NEUTRAL AND GROUND DIRECTIONAL UNIT (67N/67G) (whichever is greater)
±1.5% of the reading for higher values
Operation curves: Directionality: Forward and reverse selectable by setting
Polarizing: Voltage, current, dual NEUTRAL OVERVOLTAGE (59NH/59NL)
IEEE extremely/very/moderately inverse Voltage: Fundamental phasor of the neutral
IEC Curve A/B/C/Long-Time Inverse/Short- Polarizing Voltage: VN (measured or calculated, selected
by setting) voltage
Time Inverse Pickup level: 3 to 300 in steps of 1 V
Ansi extremely/very/normally/moderately Polarizing Current: Isg (measured from 5th current
inverse transformer) Reset level: 97% of the pickup level
I2t Operating Current: Ig (measured from 4th current Accuracy: ±1% of the reading, from 10 to 208 V
IAC extremely / very / moderately inverse transformer) Trip delay: 0.00 to 900.00 s. in steps of 0.01 s
Definite time Polarizing Voltage threshold: 0 to 300 Vac in steps of 1 V Reset time: 0.00 to 900.00 s. in steps of 0.01 s
Rectifier curve Polarizing Current threshold: 0.005 A Timing accuracy: ±3.5% of operation time or 50 ms.
User curve FlexCurve™ A/B/C/D Characteristic angle: -90º to +90º in steps of 1º (whichever is greater)
Reset time type: Instantaneous or time delayed according Block Logic: Permission or Block selectable by setting
to IEEE NEGATIVE SEQUENCE OVERVOLTAGE (47)
Timing: Operate at > 1.03 times the pickup Angle accuracy: ±2º for I>0.1 A and V>5 Vac Pickup level: 3 to 300 in steps of 1 V
±3% of operate time or 50 ms. (whichever Operate time: <30ms, typically Reset dropout level: 97%to 98%of the pickup level
is greater) SENSITIVE GROUND DIRECTIONAL UNIT (67SG) Accuracy: ±1% of the reading, from 10 to 208 V
SENSITIVE GROUND TIMED OVERCURRENT (51SG) Trip delay: 0.00 to 900.00 s. in steps of 0.01 s
Polarization By: Voltage Reset delay: 0.00 to 900.00 s. in steps of 0.01 s
Current: Fundamental Phasor (w/o harmonics)or RMS Polarization Voltage: 0 to 300 Vac in steps of 1V Timing accuracy: ±3.5% of operation time or 50 ms.
Rated current : For connection to 1 or 5 A CTs Directionality: Forward and reverse selectable (whichever is greater)
Pickup level: 0.005 to 16.00 A in steps of 0.001 A by setting
Reset dropout level: 97% to 98% of the pickup level Characteristic angle:-90º to +90º in steps of 1º FORWARD POWER (32FP)
Accuracy: ±1.5% of the reading ± 1 mA Angle accuracy: ±3º from 0.1 A and 5 Vac Current, Voltage: Fundamental phasor (primary values)
Response time: <30ms typically Pickup level (two steps)
from 0.005 to 16 A 0-10000 MW (primary values) in steps
Operation curves: THERMAL MODEL (49) of 0.01 MW
IEEE extremely / very / moderately inverse Current: Fundamental phasor (without harmonics) Reset dropout level: 97%to 98% of the pickup level
IEC A/B/C/long-time inverse/short time Rated current: Valid for connection to 1 or 5 A CTs Accuracy for primary magnitudes
inverse curve Pickup level: 0.05 to 160.00 A in steps of 0.01 A ±3% in the complete range.
IAC extremely / very / normally / Dropout level: 97% to 98% of the pickup
moderately inverse Reset type: Instantaneous
Accuracy: ±0.5% of the reading ±10 mA from 0.05 to 10 A Trip delay (two steps):
ANSI extremely / very / normally / ±1.5% of the reading for higher values
moderately inverse I2t 0.00 to 900.00 s in steps of 0.01 s
Timer accuracy: ±3.5% of the operating time or 50 ms. Timing accuracy: ±3.5% of operation time or 50 ms.
Definite time (whichever is greater)
Rectifier curve (whichever is greater)
FlexCurve™ A/B/C/D user curve Heating constant: Between 3 and 600 minutes
Cooling constant :1 to 6 times the heating constant SENSITIVE DIRECTIONAL POWER (32)
Reset time: Instantaneous or time delayed according Current, Voltage: Fundamental phasor (primary values)
to IEEE BREAKER FAILURE (50BF) Pickup level (two steps):
Timing accuracy: Operate at > 1.03 times the pickup ±3% Current: Fundamental phasor (without harmonics) -10000.00 to 10000.00 MW (primary
of operate time or 50 ms. (whichever is Rated current: Valid for connection to 1 or 5 A CTs
greater) values) in steps of 0.01
PHASE/NEUTRAL AND GROUND INSTANTANEOUS Pickup level for supervision: Characteristic angle (two steps):
0.05 to 160.00 A in steps of 0.01 A 0.00 to 359.99 in steps of 0.01º
OVERCURRENT (50PH/50PL/50N/50G) Pickup level high level: Accuracy for primary magnitudes:
Current: Fundamental Phasor (w/o harmonics) or RMS 0.05 to 160.00 A in steps of 0.01 A ±3% of complete range
Rated current : For connection to 1 or 5 A CTs. Pickup level low level: Trip delay (two steps):
Pickup level: 0.05 to 160.0 A in steps of 0.01 0.05 to 160.00 A in steps of 0.01 A 0.00 to 900.00s in steps of 0.01s
Reset dropuout level: 97% to 98% of the pickup level Pickup level internal arcing: Timing accuracy: ±3.5% of operation time or 50ms
0.05 to 160.00 A in steps of 0.01 A (whichever is greater)
Accuracy: ±0.5% of the reading ±10mA from 0.05 Reset dropout level: 97% to 98% of pickup level
to 10A Accuracy: ±0.5% of the reading ±10 mA from 0.05 to 10A CT SUPERVISION FAILURE (60CTS)
±1.5% of the reading for higher values ±1.5% of the reading for higher values Inputs: Neutral Current IN
Overreach < 2% Timer accuracy : ±3.5% of the operating time or 50 ms Neutral Voltage VN (from three-phase VTs)
Trip Delay: 0.00 to 900.00 s. in steps of 0.01 s. (whichever is greater) Ground Current Ig
Sensitive Ground Current Isg
Operate time: <30 ms at 3 x Pickup at 50 Hz, typically PHASE OVERVOLTAGE (59P) Time Delay: 0.00 to 600.00 s in steps of 0.01 s
Reset time delay: 0.00 to 900.00 s. in steps of 0.01 s. Voltage: Fundamental phasor (without harmonics 3I0 Level Accuracy: ±0.5% of the reading ± 10 mA
Timing accuracy: at 0ms time delay (no intentional delay): of phase-to phase voltages from 0.05 to 10 A (for ground)
50 ms Pickup level: 3 to 300 in steps of 1 V ±1.5% of the reading ± 1 mA
at non-zero time delay: ± 3% of operate Reset dropout level: 97% to 98% of the pickup level from 0.005 to 5 A (for sensitive
time or 50ms (whichever is greater) Accuracy: ±1% of the reading, from 10 to 208 V ground
Operate time : 0.00 to 900.00 s. in steps of 0.01s 3V0 Level Accuracy: ±1% of reading from 10 to 208 V
SENSITIVE GROUND INSTANTANEOUS Reset time: 0.00 to 900.00 s. in steps of 0.01s Ground current accuracy:±0.5% of the reading ± 10 mA
OVERCURRENT (50SG) Timer accuracy: ±3.5% of operation time or 50 ms from 0.05 to 10 A
(whichever is greater) Sensitive Ground current Accuracy:
Current: Fundamental Phasor (w/o harmonics) or RMS ±1.5% of the reading ± 1 mA from 0.005 to 5 A
Rated current: For connection to 1 or 5 A CTs. PHASE UNDERVOLTAGE (27P)
Pickup level: 0.005 to 16.0 A in steps of 0.001 A. Voltage: Fundamental phasor of phase-to-ground
Reset dropout level: 97% to 98% of the pickup level or phase-to phase voltages (selectable by
Accuracy: ±1.5% of the reading 1 mA from 0.005 to 16A setting)
Overreach: < 2% Pickup level: 3 to 300 in steps of 1 V
Trip Delay: 0.00 to 900.00 s. in steps of 0.01 s. Reset dropout level: 102% to 103% of the pickup level
Operate Time: < 30 ms at 3 x Pickup at 50 Hz
Reset time: 0.00 to 900.00 s. in steps of 0.01 s. Accuracy: ±1% of the reading, from 10V to 208 V
Timing accuracy: at 0ms time delay (no intentional delay): Operation curves:
50 ms at non-zero time delay: ± 3% of Fixed time or inverse curve
operate time or 50ms (whichever is greater) Reset type: Instantaneous

GEGridSolutions.com 9
F650 Feeder Protection & Bay Controller

Technical Specifications
SECOND HARMONIC INHIBIT BREAKER FAILURE (50BF) SNAPSHOT EVENTS
Operating Parameter: Current 2nd harmonic per phase Current: Fundamental phasor (without harmonics) Capacity: 512 scrolling events for models with rear
or average ethernet communication board 2 options;
Pickup Level: 0.1 to 40.0% in steps of 0.1% Rated current: Valid for connection to 1 or 5 A CTs G,H,J,K L,M,N
Dropout Level: 98% of pickup Pickup level for supervision: 479 scrolling events for models with
Level accuracy: 2% or 10mA 0.05 to 160.00 A in steps of 0.01 A rear ethernet communication board 2
Minimum Current: 0.05 to 15.00 A in steps of 0.01 options;B,C,D,E
Time Delay: 0.00 to 600.00 s in steps of 0.01 Pickup level for high level: Labeling time tag: 1 ms using an internal clock of 100 µs
Time Delay Accuracy: ±3% of expected time or 1,5 0.05 to 160.00 A in steps of 0.01 A Accuracy: 1 ms (using the IRIG-B synchronization
cycle, whichever is greater Pickup level for low level: input)
Time accuracy: 3% or 1.5 cycles Trigger: By pickup or dropout or operate of any
Snapshot Events: Selectable by settings 0.05 to 160.00 A in steps of 0.01 A element
Pickup level for internal arcing: By change of state in a Digital
BROKEN CONDUCTOR (I2/I1) input/output change of state
Pickup level: 20.0-100.0% (I2/I1 ratio) in steps of 0.1% 0.05 to 160.00 A in steps of 0.01 A
By virtual inputs and control events
Reset dropout level: 97%to 98%of the pickup level Reset level: 97% to 98% of pickup level Storage: Permanent in non volatile memory
Trip delay: 0.00 to 900.00 s in steps of 0.01 s Accuracy: ±0.5% of the reading ± 10 mA from 0.05 (flash) without battery
Timing accuracy: ±3.5% of operation time or 30 ms. to 10 A
(whichever is greater)
Minimum phase current threshold: I2/I1 current inhibi- ±1.5% of the reading for higher values CONTROL EVENTS
tion level: 0.000-1.000 in steps of 0.001 Reset type: Instantaneous Capacity: 128 events programmable through PLC
Labeling time tag: 1 ms using an internal clock of 100 µs
FREQUENCY RATE OF CHANGE Timing accuracy: ±3.5% of the operating time or 30 ms. Accuracy: 1 ms (using the IRIG-B synchronization
df/dt trend: Increasing, decreasing, bi-directional (whichever is greater) input)
df/dt pickup level: 0.10 to 10.00 Hz/s in steps of 0.01 Trigger: By any digital signal programmable
df/dt level accuracy: 80 mHz/s or 3.5%, whichever is through PLC
greater BREAKER MAINTENANCE Alarm: Possibility to display the event as an
Overvoltage supervision: 0.00 to 110.00 % in steps Kl2t BKR Ph A, B, C Cnt: alarm on the alarms panel. Information
of 0.0 0.00 to 9999.99 in steps of 0.01 (KA)2s available always through
95% settling time for df/dt: < 24 cycles Communications for all models and
Operate time: BKR Openings Cnt: 0 to 9999 in steps of 1 also in HMI for models with graphical
at 2 × pickup : 12 cycles BKR Closings Cnt: 0 to 9999 in steps of 1 display (M in ordering code).
at 3 × pickup : 8 cycles BREAKER SETTINGS Storage: Permanent in non volatile memory
at 5 × pickup : 6 cycles Switchgear number: 1 to16 (flash) without battery
Frequency Rate min.: 20.00 to 80.00 Hz in steps of 0.01
Frequency Rate max.: 20.00 to 80.00 Hz in steps of 0.01 Maximum KI2t: 0.00 to 9999.99 in steps of 0.01 (KA)2s
DEMAND
Frequency Rate delay: 0.00 to 60.00 s in steps of 0.01 KI2t integ. Time: 0.03 : 0.25 s in steps of 0.01s Channels: 9
Snapshot Events: Selectable by setting Maximum openings: 0 to 9999 in steps of 1 Parameters: Ia(kA RMS), Ib(kA RMS), Ic(kA RMS),
Maximum Openings in an hour: 1 to 60 in steps of 1 Ig(kA RMS), Isg(kA RMS), I2 (KA),
PROTECTION P(MW), Q (MVAr) and S (MVA)
LOAD ENCROACHMENT SWITCHGEAR Current and Power Method:
Responds to: Positive-sequence quantities Switchgear number: 1 to16 Thermal Exponential, block
Minimum voltage: 0.00 to 300.00 V in steps of 0.01 interval, Rolling demand
Switchgear: 1 to16 (configurable) Metering Measurements: Each channel shows the
Reach (sec. Ω ): 0.02 to 250.00 Ω in steps of 0.01
MAXIMUM NUMBER OF STARTS: present and maximum measured
Impedance accuracy: ±3% (depending on ordering code) value, with date and time for the
Angle: 5 to 50° in steps of 1 Metering algorithm: Fundamental maximum recorded value.
Angle accuracy: ±3° Tripping Time ±250 ms or 5% whichever is Samples: 5, 10, 15, 20, 30, 60 minutes.
Pickup delay: 0 to 65.535 s in steps of 0.001 Accuracy: ±1%
Accuracy: greater
Reset delay: 0 to 65.535 s in steps of 0.001 DATA LOGGER
Time accuracy: ±3.5% or ±60 ms, whichever is greater Full load Amps: 0.5 to 10.0 A in steps of 0.1 Channels: 1 to 16
Operate time: < 60 ms at 50 Hz Breaker Supervision: Selectable by setting Parameters: Any of the analog Metering actual values
Snapshot Events: Selectable by setting Min. Stop time: 0.0 to 900.0 s in steps of 0.1 Samples: 1 second, 1, 5, 10, 15, 20, 30, 60
Number of starts: 0 to 10 in steps of 1 minutes.
CONTROL Capacity: Fixed, (32768 measures)
Time to restart: 0 to 100 minutes in steps of 1
AUTORECLOSE (79) Reset Counter: Selectable by setting
METERING
Schemes: Three-phase pole tripping schemes Snapshot Events: Selectable by Setting
Operate time: <45 ms at 50Hz, typically CURRENT
No. of reclosing shots: Up to 4 reclose attempts Accuracy: ±0.5% of the reading ± 10 mA
before lockout DIGITAL COUNTERS: (depending on ordering code)
from 0.1 to 10 A (for phases and
Dead time: Independent dead time setting before Number of Counters: 8 ground)
each shot adjustable between 0 and 900 s Counting: Preset, Compare ±1.5% of the reading ± 1 mA from
in steps of 0.01 s Programmability: reset, up/down, set to pre-set, 0.005 to 5 A (for sensitive ground)
Reclaim time: 0.00 to 900.00 s in steps of 0.01 s freeze/reset, freeze/count ±1.5% of the reading for higher
METERING values
Condition permission: Selectable by setting MONITORING
VOLTAGE
Hold time: 0.00 to 900.00 s in steps of 0.01 s TRIP/CLOSE COIL MONITORS Accuracy: ±1% reading, from 10 to 208 V
Reset time: 0.00 to 900.00 s in steps of 0.01 s Detect open trip and close circuits POWER
Snapshot Events: Selectable by setting OSCILLOGRAPHY Active: ±2,5% of the reading from power
Possibility to modify protection settings after each shot Records: Up to 20 oscillography records. factor ±0.8 to 1
Samples: Programmable to 4, 8, 16, 32 or 64 Reactive: ±2,5% of the reading from power
SYNCHRONISM CHECK (25) samples per cycle factor ±0.2 to 0
Dead/live levels for line and bus: Trigger position: Apparent: ±2,5% of the reading
0.00 to 300.00 in steps of 0.01 V 5% to 95% of total length ENERGY
Trigger: Programmable via programmable logic Watts- hour (positive and negative)
Maximum voltage difference: Data: 5 current channels and 4 voltage
2.00 to 300.00 V in steps of 0.01 V Accuracy: 2,5%
channels Range: ±0 to 2147 MWh
Maximum angle difference: Up to 16 digital channels selectable Parameters: three-phase
2.0º to 80.0º in steps of 0.1º from the available internal states Updating Time: 100 ms
Maximum frequency slip: programmable through PLC Var-hour (positive and negative)
10 to 5000 mHz in steps of 10 mHz Storage: Permanent in non volatile memory Accuracy: 2,5%
(flash) without battery In non-volatile Range: ±0 to 2147 MVArh
Synchronism time: 0.01 to 600.00 s in steps of 0.01 s memory (flash) without battery Updating Time: 100 ms
Angle accuracy: 3º Format: International Standard COMTRADE
ASCII - IEEE C37.111-1999. POWER FACTOR
Dead Source function: None Accuracy: 0.02
(DL-DB) Dead Line - Dead Bus FREQUENCY
FAULT LOCATOR
(LL-DB) Live Line-Dead Bus Accuracy: ±50 mHz
Method: Single-ended Accuracy angle: 2º
(DL-LB) Dead Line – Live Bus
Positive sequence module:
Snapshot Events: Selectable by setting 0.01 to 250.00 Ohm in steps of 0.01 INPUTS
Ohms
FUSE FAILURE Positive sequence angle: CURRENT INPUTS
25 to 90º in steps of 1º Rated current: Appropriate for 1 or 5 A
Activation by Algorithm based onpositive sequence of volt- LoadRelay Burden: < 0.04 Ohm
age and current Zero sequence module:
0.01 to 750.00 Ohms in steps of 0.01 Overload: 20 A permanent
Activation by V2/V1 ratio 500 A during 1 second
Ohm
Zero sequence angle: Current Withstand:
25 to 90º in steps of 1º Continuous at 20 A
Line length: 0.0 to 2000.0 in steps of 0.1 (miles or 1 second at 500 A for phases
km) and ground
Display fault on HMI: 1 second at 50 A for sensitive
Possibility to show the fault report on ground
the display
Accuracy: 5% (typical)

10 GEGridSolutions.com
F650 Feeder Protection & Bay Controller

Technical Specifications
VOLTAGE INPUTS ETHERNET PORT: MECHANICAL CHARACTERISTICS
VAC inputs do not need varistors, as the impulse test is Type: Metallic package in 1/2 19" rack 6 units high
applied to 100% of the transformers Model B: 10/100BaseTX self-negotiable
Metering range: From 2 to 275 Vac Protection class IP52 (according to IEC 529)
Model C: 10/100BaseTX + 100Base FX with
LoadRelay Burden: 0.05 VA at 120 Vac (50 or 60 Hz) ST connectors
Voltage withstand: 260 Vac permanent Model D: 10/100BaseTX + Double CONTROL
Continuous at 275 V to neutral 100BaseFX with ST connectors Graphical display: English, Spanish, French and Chinese
420 Vac during 1 min/hr at 420 to (physical media redundancy) Basic display: English, Spanish, French, Chinese and Cyrilic
neutral Model E: Redundant 10/100BaseTX
Model G: 1588, 10/100 Base TX* + 100 Base TX PACKAGING
DIGITAL INPUTS Model H: 1588, 10/100 Base TX* + 100 Base FX
Voltage Threshold: Programmable from 20 up to Model J: PRP, 1588, 10/100 Base TX* + Approximate weight:
230Vdc in steps of 1 V Redundant 100 Base FX Net: 11 lbs (5 kg)
Impedance: > 100 kOhm Model K: PRP, HSR , RSTP, 1588, 10/100 Base TX* Ship: 13.2 lbs (6 kg)
Load for voltage + Redundant 100 Base FX
supervision inputs: 2 mA + V/100 kOhm Model L: PRP, 1588, 10/100 Base TX +
Maximum error: ±10% setting or ± 5 V ENVIRONMENTAL
Redundant 100 Base TX
Acknowledgement time: < 1 ms Model M: PRP, HSR , RSTP, 1588, 10/100 Base TX Temperature:
Debounce time: 1 to 50 ms in steps of 1 ms + Redundant 100 Base TX Storage: -40 to +80° C
PROTOCOLS: ModBus TCP/IP Operation: -10 to +60 degrees C (-20 degrees C
REMOTE INPUTS DNP over TCP/IP and UDP/IP for models with copper communication ports)
No of input points: 32, configured from 64 incoming IEC 60870-5-104 Humidity: Up to 95% without condensing
bit pairs IEC 61850
No of remote devices: 16 IEEE1588 (PTP) APPROVALS
Default states on loss of comms: On, Off, Latest/on, IEC 62439-3 Clause 4 (PRP) CE: Conforms to EN/IEC 60255, 61010
Latest/off IEC 62439-3 Clause 5 (HSR) UL: UL508 Certicfied under E234610
IEEE 802.1D (RSTP) KEMA: 61850 edition 2 Certified
ANALOG INPUTS (dcmA) Http, ftp, tftp (allow the use of a stan- EAC : Machines and Equipment TR CU 010/2011
Current inputs: 0 to -1; 0 to +1; -1 to +1; 0 to 5; 0 dard Internet browser) Lloyd´s Register: Marine certification (Only available for
to 10; 0 to 20, 4 to 20 NOTES: models with Environmental protection
Conversion range: -1 to 20 dcmA In Models C and D, the 10/100BaseTX port is selected by an option “M”)
Accuracy: +/-0.2% of full scale internal switch. Two indicating LEDs for transmission and
Type: Passive reception are included.
Models B,C, D and E supports IEC 61850 Edition 1. *Specifications subject to change without notice.
Models G, H, J, K, L and M supports IEC 61850 Edition 2.
IRIG-B TIME SYNCHRONIZATION INPUT
Type: Demodulated input (no carrier) TYPE TESTS
Formats: B000(*) B001, B002 and B003(*)
Level: TTL REFERENCE
CATEGORY TEST TEST LEVEL
Load: 1.5 mA STANDARD
(*) Signal combinations recognized in accordance with IRIG Dielectric IEC60255-27 2 KV / 2.3 KV
Standard 200-95 voltage
withstand
REAL TIME CLOCK SAFETY Impulse voltage IEC60255-27 5 KV
withstand
Accuracy: Typical 20 ppm
Backup energy: More than 1 week Insulation IEC60255-27 500 V (test
resistance level)
POWER SUPPLY Electrostatic IEC60255-26/ Level 4
Discharge IEC6100-4-2
Options: Immunity
F range LO, LOR: DC: 24 to 48 V Radiated RF IEC60255-26/ Level 3
H range HI, HIR: DC: 110 to 250 V Electromagnetic IEC6100-4-3
AC: 120 to 230 V Field Immunity
Power: 25 VA nominal, maximum 45 VA
Voltage loss hold-up time: Electrical Fast IEC60255-26/ Zone A
Transient IEC6100-4-4
High Range (HI): 200 ms typical, worst Immunity
case 100 ms without unit reset
Surge Immunity IEC60255-26/ Zone A
Low Range (LO): 24 Vdc 30ms; 48Vdc IEC6100-4-5
100ms
Conducted RF IEC60255-26/ Level 3
Immunity IEC6100-4-6
OUTPUTS
Power magnetic IEC60255-26/ Level 5
TRIPPING CONTACTS/OUTPUT RELAYS Immunity IEC6100-4-8
Permanent current Carry continous 16 A EMC Power IEC60255-26/ Zone A
Closing current Make and Carry for 1 second 60 A Frequency IEC6100-4-16
during 1 second Immunity
Opening current 0.3 A with L/R = 40 ms at 125 Vdc Damped IEC60255-26/ 2.5 KV
0.25 A with L/R = 40 ms at 250 Vdc Oscillatory IEC6100-4-18 Common
Wave Immunity Mode
1 KV Diff.
REMOTE OUTPUTS Mode
Standard output points 32 Voltage Dips & IEC60255-26/ Levels
User output points 32 Interruptions IEC61000-4-11/ based on
COMMUNICATIONS IEC61000-4-29 IEC61000-4-11
& IEC61000-
FRONT PORT (COM2): 4-29
Type: RS232 Ripple on DC IEC60255-26/ 15% Rated
Baude Rate: 300, 600, 1200, 2400, 4800, 9600, IEC61000-4-17 DC value
38400, 57600 and 115200 bauds Radiated & IEC60255-26/ Class A
Default baud rate: 19200 bauds Conducted CISPR11/
Protocol: ModBus® RTU / DNP 3.0 Emissions CISPR22
ASYNCHRONOUS REAR PORTS: Sinusoidal IEC60255-21-1 Class 1
Vibration
Two COM1, COM2 (rear COM2 multiplexed with front
port) MECHANICAL Shock & Bump IEC60255-21-2 Class 1
Type: Depending on model Seismic IEC60255-21-3 Class 2
Two RS485 ports Enclosure IEC60255-26/ IP52
Two 1mm-plastic F.O. ports Protection IEC6100-4-2
Two multimode glass F.O. ports Cold test IEC60068-2-1 -40˚C 16 hrs
with ST connectors. (storage)
PROTOCOLS: IEC 60870-5-103 on COM1 Cold test IEC60068-2-1 -20˚C 16 hrs
DNP on COM1 & COM2 (operational)
Serial Modbus on COM1 & COM2 Dry heat test IEC60068-2-2 85˚C 16 hrs
(storage)
CAN PORT: Dry heat test IEC60068-2-2 60˚C 16 hrs
CLIMATIC (operational)
Type: Cable or Multimode glass F.O. port
with ST connectors Change of IEC60068-2-14 5 cycles (3+3)
Fiber Wave length: 1300 nm Temperature -20˚C/60˚C
Isolation: 2kV Damp Heat IEC60068-2-30 6 cycles
Humidity Cyclic (12+12) 55˚C
@ 93% R.H.
Damp Heat IEC60068-2-78 40˚C @ 93%
steady state R.H.

GEGridSolutions.com 11
Ordering
F650 * * * F * G * * * * * * * * Description
DISPLAY B Basic Display (see note 2)
M Graphic Display with Standard Symbols (see note 2)
N Graphic Display with IEC Symbols (see note 2)
REAR SERIAL F None
COMMUNICATIONS BOARD 1 A Redundant RS485
P Redundant plastic fiber optic
G Redundant glass fiber optic
X Redundant RS485 + fiber remote CAN bus I/O
Y Redundant plastic fiber optic + fiber remote CAN bus I/O
Z Redundant glass fiber optic + fiber remote CAN bus I/O
C Cable remote CAN bus I/O
M RS485 + cable remote CAN bus I/O
REAR ETHERNET B 10/100 Base TX
COMMUNICATIONS BOARD 2 C 10/100 Base TX + 100 Base FX
D 10/100 Base TX + Redundant 100 Base FX
E Redundant 10/100 Base TX
G 1588, 10/100 Base TX* + 100 Base TX
H 1588, 10/100 Base TX* + 100 Base FX
J PRP, 1588, 10/100 Base TX* + Redundant 100 Base FX (See note3)
K PRP, HSR , RSTP, 1588, 10/100 Base TX* + Redundant 100 Base FX (See note3)
L PRP, 1588, 10/100 Base TX* + Redundant 100 Base TX (See note3)
M PRP, HSR , RSTP, 1588, 10/100 Base TX* + Redundant 100 Base TX (See note3)
I/O BOARD IN SLOT F 1 16 Digital Inputs + 8 Outputs
2 8 Digital Inputs + 8 Outputs + 2 Trip / Close circuit supervision circuits
4 32 Digital Inputs
5 16 Digital Inputs + 8 Analog Inputs
I/O BOARD IN SLOT G 0 None
1 16 Inputs + 8 Outputs
2 8 Digital Inputs + 8 Outputs + 2 Trip / Close circuit supervision circuits
4 32 Digital Inputs (See Note 1)
5 16 Digital Inputs + 8 Analog Inputs (See Note 1)
AUXILIARY VOLTAGE LO 24-48 Vdc (range 19.2 – 57.6)
HI 110-250 Vdc (range 88 – 300),120-230 Vac (range 96 – 250)
LOR Redundant L
HIR Redundant H
LANGUAGE C Chinese/English (See Note 2, 4)
E English/English
F French/English
P Russian/English (See Note 2)
S Spanish/English
T Turkish/English
PROTOCOL None Modbus® RTU, TCP/IP, DNP 3.0 Level 2, IEC 60870-5-104
3 IEC 60870-5-103, Modbus RTU, TCP/IP
6 IEC 61850 Edition 2, Modbus RTU & TCP/IP, DNP 3.0 Level 2, IEC 60870-5-104
ENVIRONMENTAL PROTECTION Without Harsh (Chemical) Environment Conformal Coating
H Harsh (Chemical) Environment Conformal Coating
M Marine Range (Lloyd´s certification) (See Note 5)
ENHANCED DISPLAY E Enhanced Display with Front USB port

(*) Notes:
Communication port marked with “*” is intended only for maintenance purposes in models with Rear Ethernet Communication Board options G,H,J,K,L or M,
1. The number selected for option G must be equal or higher than the number selected for option F for models including boards 4 and 5.
2. Display options with language selection:
Graphic display (M & N): available for English, French, Spanish and Chinese languages. For chinese only IEC symbols option is available (N in ordering code).
Basic display (B): available for English, French, Spanish, Russian, Turkish and Chinese languages
3. Advanced features require new CPU:
• G & H: IEEE 1588 Precision Time Protocol (PTP), 61850 Edition 2.0.
• J & L: Parallel Redundancy Port (PRP,) IEEE 1588 Precision Time Protocol (PTP), 61850 Edition 2.0.
• K & M: High-Availability Seamless Redundancy (HSR), Rapid Spanning Tree Protocol (RSTP), Parallel Redundancy Port (PRP), IEEE 1588 Precision Time Protocol (PTP), 61850 Edition 2.0.
4. Chinesse language is not available in models with Rear Ethernet communication board options G, H, J, K, L or M.
5. Marine Range option of Enviromental Protection section is only available with REAR ETHERNET COMMUNICATIONS BOARD 2 options G,H,J,K,L or M

Related Products / Accessories GE Grid Solutions


MultiSync 100 - GPS Clock MultiSync100-P Toll Free: +1 877-605-6777
CIO Remote CAN Bus I/O Module CIO-H-X-J-X-XXX Direct: +1 678-844-6777

GEGridSolutions.com
IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark
of Schneider Automation. ANSI is a registered trademark of American National Standards Institute,
Incorporated.
GE, the GE monogram, Multilin, EnerVista and MultiSync are trademarks of General Electric Company.

GE reserves the right to make changes to specifications of products described at any time without notice
and without obligation to notify any person of such changes.