Chigo Air Conditioner Error Codes


August 27, 2014 Chigo, Home

Chigo Air Conditioner Error CodesFAULT CODE FOR SPLIT-WALL MOUNTED TYPE ROOM AIR
CONDITIONER

LED code = DF

explain = display at on state


LAMP DISPLAY
code = flicker 1/1 SEC
explain =
FAILURE = defrost indication
The reason of fault and solution = Normal, the defrost state is removed, it will return to normal condition
automatically

LED
code = DF
explain = display at off state
LAMP DISPLAY
code = flicker 1/3 SEC
explain =
FAILURE = anti cold wind
The reason of fault and solution = 1.Normal (during heating mode )
2.It will be removed when the coil pipe temperature sensor reaches certain temperature.

LED
code = E2
explain = display at off state
LAMP DISPLAY
code = flicker 1/1 SEC
explain = display at on/off state
http://acerrorcode.com/chigo-air-conditioner-error-codes.html 1/11
2/25/2018 Chigo Air Conditioner Error Codes

FAILURE = room temp. sensor fault


The reason of fault and solution = 1.Check whether the resistance of the sensor is normal (the resistance is 5KΩ
in the normal temperature 25°), when it is abnormal the sensor should be replaced.
2.Check whether there is short circuit or open circuit in the wire of the sensor, and whether the plug is connected
well, whether there is welding off or rosin joint on the electric control board, if there is any, it should be
repaired.
3.When the 1 and 2 are both normal, then the components or integrated circuit is damaged, the electric control
board should be replaced.

LED
code = E3
explain = display at off state
LAMP DISPLAY
code = flicker 3/5 SEC
explain = display at on/off state
FAILURE = coil temp. sensor fault
The reason of fault and solution = 1 .Check whether the resistance of the sensor is normal (the resistance is 5KΩ
in the normal temperature 25°), when it is abnormal the sensor should be replaced.
2 .Check whether there is short circuit or open circuit in the wire of the sensor, and whether the plug is
connected well,
whether there is welding off or rosin joint on the electric control board, if there is any, it should be repaired.
3.When the 1 and 2 are both normal, then the components or integrated circuit is damaged, the electric control
board should be replaced.

LED
code = E4
explain = display at off state
LAMP DISPLAY
code = flicker 4/6 SEC
explain = display at off state
FAILURE = outdoor unit abnormal
The reason of fault and solution = 1.Check whether the winding resistance and operation current of the
compressor are normal.
2.Check whether the high and low pressure is normal when the unit is running.
3 .Check (whether the coil pipe sensor is normal) whether the contact of the
inserter on the circuit board is well, the coil pipe temperature sensor is fixed, the evaporation of the indoor unit
is well, the key is to check the evaporator temperature detected by the coil pipe temperature sensor has reached
the cooling or heating temperature.
4 .Check whether the surface of the condenser is too dirty, it should be cleaned when it is too dirty.
5 .Check whether the capacitance of the outdoor motor and the fan is damaged, it should be replaced when it is
damaged.
6 .If the above items are normal, the electric control board should be replaced.

LED
code = E5
explain = PG motor display at off state
LAMP DISPLAY
code = flicker 5/7 SEC
explain = display at off state
FAILURE = no feedback signal of indoor fan
The reason of fault and solution = 1.Check whether two sets of plugs on the outlet end of the motor have loosed
from the socket of the electric control board, insert it firmly when loosing.
2.Check whether the indoor motor has damaged, the motor should be replaced when it is damaged

http://acerrorcode.com/chigo-air-conditioner-error-codes.html 2/11
2/25/2018 Chigo Air Conditioner Error Codes

3.Check whether the controllable silicon and other components on the electric control board have damaged,
replace the controllable silicon or electric control board when they are damaged.

LED
code = E6
explain = PG motor display at off state
LAMP DISPLAY
code = flicker 6/8 SEC
explain = display at off state
FAILURE = no over zero signal
The reason of fault and solution = 1. Firstly check whether the indoor fan is normal.
2. Check whether the signal outputting from the integrated chip of the electric control board is normal, the
electric control board should be replaced when the signal is abnormal.

LED
code = E7
explain = display at off state
LAMP DISPLAY
code = flicker 7/9 SEC
explain = display at off state
FAILURE = outdoor feedback fault
The reason of fault and solution = 1.Check whether the winding resistance and operation current of the
compressor are normal
2.Check whether the high and low pressure is normal when the unit is running.
3.Check whether the indoor and outdoor wiring is right; when it is wrong, connect them again according to the
circuit diagram
4.Check whether the contact of the inserter on the circuit board and the connection are well, otherwise repair.
5.Check whether the signal feedback wire is disconnected, replace or connect the feedback signal wire.
6.Check whether the supply power is phase-lacking or phase opposition.
7.Check whether the AC electromagnetic contactor is well.

LED
code = E8
explain = display at off state
LAMP DISPLAY
code = flicker 8/10 SEC
explain = display at off state
FAILURE = frost protection/over heat protection
The reason of fault and solution = 1 .Check whether the filter of the indoor unit is dirty or blocked, and clean if it
is dirty.
2.Check whether the indoor fan is running normally, and replace the motor if it is abnormal.
3.Check whether indoor pipe temperature sensor is normal, and replace the sensor if it is abnormal.
4 .Check whether the system pressure is normal, if abnormal, should check whether there is leakage, and fill the
refrigerant again.

The malfunction oindoor and outdoor unit


The common malfunction code analysis and solutions

The fault code = F1


The fault content = The communication fault
The reason of fault and its solutions = 1.The communication wire is broken off. Please check whether the wire is
disentwined ;
2.Please check whether the electrical control board is damaged. It should be replaced when it is damaged;
http://acerrorcode.com/chigo-air-conditioner-error-codes.html 3/11
2/25/2018 Chigo Air Conditioner Error Codes

3.Please check whether the power ground wire is reliable;


4.Please check whether the unit is abnormal caused by the external interference. If it is, then find the interfering
sources, and remove them.

The fault code = F2


The fault content = The indoor temperature sensor fault
The reason of fault and its solutions = 1.Check whether the resistance of sensor is normal, otherwise replace it;
2.Check whether the sensor wire is short circuit or open circuit, and whether the plug is well contacted, whether
there is welding off or rosin joint on the electric control board, repair it if there is any above;
3.When the 1 and 2 are both normal, then the component or integrated circuit is damaged, the electric control
board should be replaced.

The fault code = F3


The fault content = The indoor coil temperature sensor fault
The reason of fault and its solutions = 1. Check whether the resistance of sensor is normal, otherwise replace it;
2. Check whether the sensor wire is short circuit or open circuit, and whether the plug is well contacted, whether
there is welding off or rosin joint on the electric control board ,repair it if there is any above;
3. When the 1 and 2 are both normal, then the component or integrated circuit is damaged, the electric control
board should be replaced.

The fault code = F4


The fault content = Indoor PG motor fault (tap motor hasn’t so breakdown )
The reason of fault and its solutions = 1.Check whether the contact of the plug of the motor wire and socket is
well. Please make sure it is well contacted;
2.Check whether the indoor motor has damaged, the motor should be replaced when it is damaged;
3 .Check whether the controllable silicon and other components on the electric control board have damaged,
replace the controllable silicon or electric control board when they are damaged;
4.Check whether the indoor fan is unobstructed when running, please fix the indoor fan again when it is
obstructed.

The fault code = F5


The fault content = IPM protection
The reason of fault and its solutions = 1.Check whether the supply voltage is out of ranging from 150 to
270V(overvoltage and undervoltage protection); Measuring the actual current, if the current is greater than
the rated current of 2A,it is over-temperature protection; If the above are normal, that is IPM module internal
circuit fault protection, so please replace the IPM module.

The fault code = F6


The fault content = The outdoor sensor fault
The reason of fault and its solutions = 1. Check whether the resistance of sensor is normal, otherwise replace it;
2. Check whether the sensor wire is short circuit or open circuit, and whether the plug is well contacted, whether
there is welding off or rosin joint on the electric control board, repair it if there is any above;
3. When the 1 and 2 are both normal ,then the component or integrated circuit is damaged, the electric control
board should be replaced.

ADVERTISEMENT

The fault code = F7


The fault content = The outdoor coil temperature sensor fault (Including the mid-point of tube. inspiratory gas)
The reason of fault and its solutions = 1. Check whether the resistance of sensor is normal, otherwise replace it;
2.Check whether the sensor wire is short circuit or open circuit, and whether the plug is well contacted, whether
there is welding off or rosin joint on the electric control board, repair it if there is any above;
3.When the 1 and 2 are both normal, then the component or integrated circuit is damaged, the electric control
board should be replaced
http://acerrorcode.com/chigo-air-conditioner-error-codes.html 4/11
2/25/2018 Chigo Air Conditioner Error Codes

The fault code = F9


The fault content = Exhaust gas sensor failure
The reason of fault and its solutions = 1. Check whether the resistance of sensor is normal, otherwise replace it;
2. Check whether the sensor wire is short circuit or open circuit, and whether the plug is well contacted, whether
there is welding off or rosin joint on the electric control board, repair it if there is any above;
3. When the 1 and 2 are both normal, then the component or integrated circuit is damaged, the electric control
board should be replaced.

The fault code = FA


The fault content = The communication fault between the wire controller and the indoor PCB
The reason of fault and its solutions = 1. check whether the wire controller’s connecting wire is short circuit or
loose, please make it connect well;
2. Check the connecting line.wire controller.PCB whether they are loose or have a bad contact. Please make
them have a good contact.

The fault code = FC


The fault content = outdoor unit driving fault, starting compressor failure
The reason of fault and its solutions = 1. Turn on the power again, and then check whether the operation of the
compressor is normal;
2. Check whether the connection of the compressor is correct or reliable, otherwise repair it;
3. Check whether the components on the electric control board have been damaged, if they are damaged, the
components or the electric control board should be replaced.;
4. Check whether the connecting wires are disentwined between the Intelligent Power Module board and the
main board, otherwise make the wires connect firmly .

The fault code = FF


The fault content = The outdoor DC motor fault
The reason of fault and its solutions = 1. Check the resistance value of the DC motor port. If it is short circuit,
please change the DC motor;
2. Check the voltage value of the DC motor port VCC(15Vdc), Vdm(340Vdc),please change the PCB board if
the voltage values are abnormal;
3. if all the voltage values of the DC motor port are normal,the Vsp voltage (0~5v) is also ok ,it shows that the
inner PCB board of the DC motor is damaged, then change the DC motor.

The fault code = FH


The fault content = The indoor unit EEPROM error
The reason of fault and its solutions = 1. Check whether there are false weld and bad contact etc between the
EEPROM chip block and the electronic control board ;
2. Check whether the EEPROM chip pin is broken foot and the direction of installation is in line with the
EEPROM block;
3. When the procedure of EEPROM chip and itself have fault it will appear the code FH. That is the need to
replace the EEPROM chip.

The fault code = dF


The fault content = The indoor unit EEPROM error
The reason of fault and its solutions = 1. Check whether there are false weld and bad contact etc
between the EEPROM chip block and the electronic control board ;
2. Check whether the EEPROM chip pin is broken foot and the direction of installation is in line with the
EEPROM block;
3. When the procedure of EEPROM chip and itself have fault it will appear the code FH. That is the need to
replace the EEPROM chip.

The fault code = dI


The fault content = Mode conflict

http://acerrorcode.com/chigo-air-conditioner-error-codes.html 5/11
2/25/2018 Chigo Air Conditioner Error Codes

The reason of fault and its solutions = When the running mode for No.1 indoor unit is different from No.2
indoor unit, the dF is displayed.

The fault code = P1


The fault content = Indoor coil temperature
over-temperature protection for heating (thermal overload), outdoor coil temperature overheating protection for
cooling (cooling overload)
The reason of fault and its solutions = 1. Check whether the ambient temperature is over the range of air-
conditioning running temperature ;
2. Check whether the indoor coil temperature is higher than or equal to 63 degrees when heating and check
whether the outdoor coil temperature is higher than or equal to 65 degrees when cooling, it will appear
protection if the value is over the above;
3. Check whether the parameters of indoor and outdoor coil temperature sensors are normal, if abnormal, please
replace the sensors;
4. If the above are normal, check whether the main control board output parameters are normal, if abnormal,
please replace the main control board.

The fault code = P2


The fault content = The outdoor unit inverter module protection fault
The reason of fault and its solutions = 1. Check whether the connection of the compressor is reliable, otherwise
connect firmly again;
2. Check whether the fixation between the IPM module and the radiator is firm.;
3. Check whether the compressor is well, otherwise replace it;
4. Check whether the IPM module is abnormal, otherwise replace it.

The fault code = P3


The fault content = Over current of outdoor unit
The reason of fault and its solutions = 1. Check whether the ambient temperature exceeds the operation range for
the air conditioner;
2. Check whether the current detection circuit is abnormal, the electric control should be replaced when it is
abnormal.

The fault code = P4


The fault content = discharge temperature of compressor is too high, the outside ambient temperature over-
temperature, switch off the compressor shell temperature, module temperature over-temperature
The reason of fault and its solutions = 1. Check whether the pressure is normal when the unit is running, if it is
abnormal, you should detect the leakage and then welding and adding refrigerant;
2. Check whether the ambient temperature is too high or too low, when the temperature is more than -20 degrees
and less 55 degrees, it can disappear automatically;
3. Check whether temperature switch of compressor is damage, it should be replaced if it is damaged.

The fault code = P7


The fault content = The outdoor unit DC generatrix voltage is abnormal
The reason of fault and its solutions = 1. Check whether the supply voltage is out of ranging from 150 to 270V;
2. Check the voltage detection circuit of the IPM base board is abnormal, if it is abnormal, the IPM base board
or the electric control board should be replaced.

The fault code = P8


The fault content = lack refrigerant or reverse valve fault
The reason of fault and its solutions = 1. Check whether the high and low pressure valves have been opened,
otherwise open the valves;
2. Check whether the indoor coil pipe temperature sensor is normal, if it is abnormal, the sensor should be
replaced;
3. Check whether the indoor coil temperature sensor hung in the air, please plug it in a correct position if the
indoor coil temperature sensor hung in the air;
http://acerrorcode.com/chigo-air-conditioner-error-codes.html 6/11
2/25/2018 Chigo Air Conditioner Error Codes

4. Check the system pressure is abnormal, if it is abnormal, you should detect leakage and the welding and
adding the refrigerant.;
5. Please change the outdoor PCB board , if all above are normal.

The fault code = PA


The fault content = protection when indoor pipe temperature is too low (Anti-icing)
The reason of fault and its solutions = 1. Check whether the ambient temperature is over the range of air-
conditioning running temperature;
2. Check the indoor coil temperature is less than or equal to -1 degrees, if more than this value it will be the
protection of;
3. Check whether the indoor coil temperature sensor parameters are normal, if abnormal it is the replacement of
the sensor;
4. If the above are normal, check whether the main control board output parameters are normal, if abnormal
,please replace the main control board.

The fault code = PC


The fault content = Outdoor ambient temperature over-temperature protection (including high and low)
The reason of fault and its solutions = 1. Check whether the outdoor ambient temperature is too high or too low,
when the ambient temperature is lower than (T> -20, T <55), this fault automatically discharges;
2. Check whether the outdoor temperature sensor’s ring temperature parameters are normal, if abnormal ,please
replace the sensor;
3. If the above are normal, check whether the main control board’s output parameters are normal, f abnormal
,please replace the main control board.

The fault code = PE


The fault content = EEPROM reading error (outdoor unit)
The reason of fault and its solutions = 1. Check whether there are false weld and bad contact etc between the
EEPROM chip block and the electronic control board ;
2. Check whether the EEPROM chip pin is broken foot and the direction of installation is in line with the
EEPROM block;
3. When the procedure of EEPROM chip and itself have fault it will appear the code PE. At this time there is the
need toreplace the EEPROM chip.

ADVERTISEMENT

9 Responses to Chigo Air Conditioner Error Codes

1. marvin says:
May 6, 2015 at 3:05 am

Need to know wath ff meas????

Reply

2. Iliasse Nurmamade says:


October 11, 2015 at 5:21 am

http://acerrorcode.com/chigo-air-conditioner-error-codes.html 7/11
2/25/2018 Chigo Air Conditioner Error Codes

I think is good and help much, i will test.

Reply

3. winson says:
November 13, 2015 at 12:45 pm

Goodday, I do have a chigo split unit inside unit gives me C2

Reply

4. Luis says:
December 6, 2015 at 3:09 am

Feliz noche tengo una unidad chigo de casete 36000 me parpadea 9 veces ella prende estabiliza presión y
al minuto dispara la unidad condensadora

Reply

5. Doran Yount says:


June 14, 2016 at 5:16 pm

I have a Chigo Model # KF35C2A-W the compressor tries to start but shuts down within a few seconds. I
get an FC code in the LED window inside. I’ve checked all connections and they appear to be fine. The
main outside power board seems fine. I get 7 flash’s from the read light on the outside board then it stays
on and back to 7 flash’s again.
Any help would be appreciated.
Please reply here for everyone else but send me an email. Thank you.
Takunchances@Yahoo.com

Reply

6. SAW SIS AUNG says:


August 11, 2016 at 12:11 pm

After service indoor display C3 show code what wrong explain me about that.Chigo 1.5 Hp Please help
me.,
leave a message

Reply

7. hemin says:
August 15, 2016 at 9:25 pm

i have chigo show me error 5 30000 btu

Reply

8. A.S.Etesami says:
September 30, 2016 at 7:02 pm

I have a Chigo CFA-50CO


IT runs well after starting but after 10 or 15 minutes it turns off Automatically without any alarm. no over
current fault and no activated timer, i checked the temp and pressure sensors and they are working
properly…

http://acerrorcode.com/chigo-air-conditioner-error-codes.html 8/11
2/25/2018 Chigo Air Conditioner Error Codes

Reply

9. Aimee says:
December 5, 2016 at 8:25 am

I have a Chigo home air conditioning unit & it’s displaying PF and no cold air is coming out – just
blowing like a fan – does anyone know what this means or if there is a way to fix it without getting a
technician out?

Reply

Leave a Reply
Your email address will not be published. Required fields are marked *

Comment

Name *

Email *

Post Comment

Search

Custom Search Search

Categories
Acson
Actron
Airwell
Akai
Amana
AmeriCool
Amvent
Aux
Baxi
Beko
Bryant
Carrier
Challenge
Chigo
Chunlan
Climatemaster
Comfortaire
Comfortmaker
http://acerrorcode.com/chigo-air-conditioner-error-codes.html 9/11
2/25/2018 Chigo Air Conditioner Error Codes

Cooper&Hunter
Daikin
Danby
Day & Night
Delonghi
Derby
Dimplex
Dometic
Ductlessair
Edgestar
Fedders
Friedrich
Frigidaire
Fujitsu
Fujitsu General
Galanz
Garrison
GE
Goodman
Gree
Haier
Hitachi
Home
Hyundai
Insignia
Keeprite
Kelvinator
Klimaire
Koppel
Lennox
LG
Lloyd
Maxon
McQuay
Midea
Mitsubishi
Mitsubishi Electric
Mitsubishi Heavy
Mr. Slim
Mrcool
Onida
Panasonic
Pridiom
Ramsond
Rheem
Rittal
Ruud
Samsung
Sanyo
Sharp
Shinco
SoleusAir
Sunpentown
TCL
http://acerrorcode.com/chigo-air-conditioner-error-codes.html 10/11