You are on page 1of 20

CABLE

FROM TO CABLE SIZE ARMOURIZATION


DIMTER

1 3x50+25 DB-T3GR1 SMDB-B3-T-GF non_armourd 28.1


2 3x50+25 DB-T3GR2 SMDB-B3-T-GF non_armourd 28.1
3 3x25+16 DB-T3GR3 SMDB-B3-T-GF non_armourd 23.9
4 3x25+16 DB-T3GR4 SMDB-B3-T-GF non_armourd 23.9
5 4X16+16 DB-T3GR5 SMDB-B3-T-GF non_armourd 0
6 4X16+16 ESCLATOR SMDB-B3-SERV non_armourd 0
7 4X16+16 ESCLATOR SMDB-B3-SERV non_armourd 0
totals

A=cable tray width 300 MM B=total cable diameter 158 MM


TOTAL EARTH EARTH
NO OF CABLE EARTH
INSULATION LEVEL CABLES CABLE COND
CABLES WEIGHT C.S.A
DIA DIA WEIGHT
CU/PVC/PVC 1 28.1
CU/PVC/PVC 1 28.1
CU/PVC/PVC 1 23.9
CU/PVC/PVC 1 23.9
CU/PVC/PVC 1 0
CU/PVC/PVC 1 0
CU/PVC/PVC 1 0
104 MM 16.22 KG/M 2.51 KG/M

filling ratio = B/A 35%


THE SELECTION OF CABLE TRAY WIDTH IS ACCOR
DIAMETER
CABLE
FROM TO CABLE SIZE
CODE
1 4x500
2 3x500+240 23 4x25
3 4x400 23 4x25
4 3x400+240 16 3x95+50
5 4x300 8 3x240+120
6 3x300+150 24 4x16
7 4x240
8 3x240+120
9 4x185
10 3x185+95
11 4x150
12 3x150+70
13 4x120
14 3x120+70
15 4x95
16 3x95+50
17 4x70
18 3x70+35
19 4x50
20 3x50+35
21 4x35
22 3x35+16
23 4x25
24 4x16
25 4x10
26 4x6
27 4x4

totals

A=cable tray width 300 MM B=total cable diameter


TOTAL CABLES DIAM
TOTAL CABLES WEIGHT
CABLE TRAY WEIGHT
TOTAL WEIGHT CABLES AND T

CABLE TRAY WIDTH = FILLING RATIO = TOTAL CABL

THE SELECTION OF CABLE TRAY WIDTH IS ACCORDIN


DIAMETERS *

SECTION: NO A-A

MAXIMUM
ALLOWED 60%
FILLING RATIO

CABLE COD FROM TO CABLE SIZE


10 3x185+95
8 3x240+120
24 4x16
24 4x16
24 4x16
22 3x35+16
22 3x35+16
22 3x35+16
22 3x35+16
22 3x35+16
23 4x25
TOTAL NO OF CABLES

TOTAL CABLES DIAM


TOTAL CABLES WEIGHT
CABLE TRAY WEIGHT
TOTAL WEIGHT CABLES AND T
Y WIDTH IS ACCORDING TO MULTIPLYING THE SUMMATION OF ALL CABLES
DIAMETERS *2 = (SUM D) X2
CABLE NO OF TOTAL
ARMOURIZATION INSULATION LEVEL
DIMTER CABLES CABLES DIA

non_armourd 23.9 CU/PVC/PVC 1 23.9


non_armourd 23.9 CU/PVC/PVC 1 23.9
non_armourd 36.1 CU/PVC/PVC 1 36.1
non_armourd 54.2 CU/PVC/PVC 1 54.2
non_armourd 20.3 CU/PVC/PVC 1 20.3
non_armourd CU/PVC/PVC 1
non_armourd CU/PVC/PVC 1
non_armourd CU/PVC/PVC 1
armoured CU/PVC/PVC 1
non_armourd CU/PVC/PVC 1
armoured CU/PVC/PVC 1
non_armourd CU/PVC/PVC
non_armourd CU/XLPE/PVC 1
non_armourd CU/XLPE/PVC
non_armourd CU/XLPE/PVC
non_armourd CU/XLPE/PVC 1
non_armourd CU/XLPE/PVC
non_armourd CU/XLPE/PVC
non_armourd CU/XLPE/PVC
non_armourd CU/XLPE/PVC
non_armourd CU/PVC/PVC
non_armourd CU/XLPE/PVC
non_armourd CU/XLPE/PVC
non_armourd CU/XLPE/PVC
non_armourd CU/XLPE/PVC
non_armourd CU/XLPE/PVC
non_armourd CU/XLPE/PVC
158 MM

B=total cable diameter 158 MM filling ratio = B/A 53%


TOTAL CABLES DIAM 158 MM
TOTAL CABLES WEIGHT 18.73 KG/M
CABLE TRAY WEIGHT Err:504
L WEIGHT CABLES AND TRAYS Err:504

LING RATIO = TOTAL CABLE DIA = TRAY WIDTH

T.C.W/M 59.3
C.T.W/M 10
T.W/M 69.3

DTH IS ACCORDING TO MULTIPLYING THE SUMMATION OF ALL CABLES


DIAMETERS *2=(SUM D)X2

FILLING
REQ TRAY
FILLING RATIO RATIO
/TRUNK 97.26 CM ASPER REQUIRED
50% AFTER
WIDTH IN CM
SELECTION

REQ TRAY/
NEAREST ACTUAL
TRUNK 972.60 MM WIDTH
### TEST
WIDTH IN MM

ARMOURIZATION CABLE DIMTER INSULATION LEVEL NO OF CABLDIAMETER app


non_armourd 57.6 CU/PVC/PVC 3 172.8
non_armourd 64 CU/PVC/PVC 1 64
non_armourd 25.6 CU/PVC/PVC 1 25.6
non_armourd 25.6 CU/PVC/PVC 1 25.6
non_armourd 25.6 CU/PVC/PVC 1 25.6
non_armourd 28.7 CU/PVC/PVC 1 28.7
non_armourd 28.7 CU/PVC/PVC 1 28.7
non_armourd 28.7 CU/PVC/PVC 1 28.7
non_armourd 28.7 CU/PVC/PVC 1 28.7
non_armourd 28.7 CU/PVC/PVC 1 28.7
non_armourd 29.2 CU/PVC/PVC 1 29.2
555.60

TOTAL CABLES DIAM 556 MM


TOTAL CABLES WEIGHT 46.41 KG/M
CABLE TRAY WEIGHT Err:504
L WEIGHT CABLES AND TRAYS Err:504
OF ALL CABLES

EARTH
CABLE EARTH EARTH
COND EARTH CODE data base for cables
WEIGHT C.S.A CABLE DIA
WEIGHT

1.295 (1X4) 4.2 0.05 13 s.n C.S.A


1.295 (1X240) 24.7 2.457 1 1 4x500
3.69 2 3x500+240
9.06 3 4x400
0.88 4 3x400+240
5 4x300
6 3x300+150
7 4x240
8 3x240+120
9 4x185
10 3x185+95
11 4x150
12 3x150+70
13 4x120
14 3x120+70
15 4x95
16 3x95+50
17 4x70
18 3x70+35
19 4x50
20 3x50+35
21 4x35
22 3x35+16
23 4x25
24 4x16
25 4x10
26 4x6
16.22 KG/M 2.51 KG/M 27 4x4
LL CABLES

61%

UN ACCEPTED RATIO

CABLE WEIGEARTH COND WEIGHT


21 0.967
9 1.24
0.9 0.177
0.9 0.177
0.9 0.177
1.6 0.177
1.6 0.177
1.6 0.177
1.6 0.177
1.6 0.177
1.3 0.177
42.61 3.80
data base for cables non-armourd armoured

armoured non_armourd CU/PVC/PVC CU/PVC/STA/PVC


87.7 77.6 CU/XLPE/PVC CU/STA/XLPE/PVC
57.3 73.3
80 70.1
67.8 66
72.9 63.3
62.2 60
66.8 57
57.1 54.2
60.5 50.7 ARMOURING NO_OF_CABLES
51.2 48.2 non_armourd 1
55.1 45.9 armoured 2
46.3 43.5 3
50.6 41.2 4
42.1 39.5 5
46.6 37.8 6
38 36.1 7
40.7 32.9 8
33.1 31.4 9
37.1 29.3
28.7 28.1
32.1 26.6
25.6 25
29.2 23.9 ACCEPTED RATIO
22 20.3 UN ACCEPTED RATIO
18.9 17.9
18 16
16 14.8
data base for cables WEIGHT CABLE TRAY WEIGHT

s.n C.S.A armoured non_armourd type Width Thick


(b) (t)
1 4x500 22885 21085 C1 50 1.0
2 3x500+240 19515 19205 C2 100 1.0
3 4x400 17515 16500 C3 200 1.0
4 3x400+240 15505 15270 C4 300 1.0
5 4x300 13835 12915 C8 400 1.5
6 3x300+150 12205 11290 C9 500 1.5
7 4x240 11285 10330 C10 600 1.5
8 3x240+120 10000 9060 800 2
9 4x185 8930 7960
10 3x185+95 7865 7025
11 4x150 7195 6400
12 3x150+70 6355 5580
13 4x120 5710 5205
14 3x120+70 5365 4675
15 4x95 4815 4175
16 3x95+50 4280 3690
17 4x70 3335 3065
18 3x70+35 2960 2725
19 4x50 2415 2225
20 3x50+35 2160 2115
21 4x35 1775 1700
22 3x35+16 1615 1505
23 4x25 1385 1295
24 4x16 975 880
25 4x10 720 635
26 4x6 555 425
27 4x4 450 335

armoured 3
non_armourd 4
BLE TRAY WEIGHT WEIGH

Weight s.n C.S.A DIA


Kg/mt
1.50 1 (1X240) 2457 24.7
1.80 2 (1X185) 1852 21.5
2.50 3 (1X150) 1500 19.4
3.00 4 (1X120) 1240 17.4
6.50 5 (1X95) 967 15.7
7.00 6 (1X70) 711 13.5
8.00 7 (1X50) 514 11.8
10 8 (1X35) 371 9.9
9 (1X25) 278 8.8
10 (1X16) 177 7.1
11 (1X10) 117 6.1
12 (1X6) 71 4.7
13 (1X4) 50 4.2
FROM TO CABLE SIZE

1 3x240+120 DB-T3GR1 SMDB-B3-T-GF


2 3x25+16 DB-T3GR2 SMDB-B3-T-GF
3 3x25+16 DB-T3GR3 SMDB-B3-T-GF
4 3x95+50 DB-T3GR4 SMDB-B3-T-GF
5 4x16+16 DB-T3GR5 SMDB-B3-T-GF
totals

A=cable tray width 400 MM B=total cable diameter

0.5266666667

FROM TO

DB-S3B1
DB-S3GR
DB-S33
SMDB-B3-SERV

MCC-B3-R1-01
DS-for esclator
DS-for esclator
DB-S3B2
DS for WF-03
DB-EXT-02
TOTAL EARTH
NO OF CABLE EARTH
ARMOURIZATION INSULATION LEVEL CABLES CABLE
CABLES WEIGHT C.S.A
DIA DIA
non_armourd CU/PVC/PVC 1 54.2
non_armourd CU/PVC/PVC 1 23.9
non_armourd CU/PVC/PVC 1 23.9
non_armourd CU/PVC/PVC 1 36.1
non_armourd CU/PVC/PVC 1 20.3
158 MM 16.22 KG/M

B=total cable diameter filling ratio = B/A 40%

CABLE SIZE
EARTH
COND
WEIGHT

2.51 KG/M
cable type application approx. meter length

1 pair 18 awg DI /DO 15000


2 pair 16 awg AI/AO 8000

CONNECTION
BETWEEN
communcation cable CONTROLLER TILL 2000
belden 9841 MASTER
CONTROLLER

CONTROLLER WILL BE IP based