Energypac Fashions Ltd.

Monipur, Hpotapara, Gazipur sadar, Gazipur.


Electrical audit Report
Conducted by EFL Own Team

Sl NC Issue Description Location Corrective Action Plan Respective Authority Completed BY


No
01 Electrical LT-BBT Riser Electrical Need to set As per Energypac Engineering Ltd. (BBT EEL
Switchgear Neutral Neutral Room, Ground standard Section)
Not Set as Standard Not Set as Proper Floor
Size
02 Electrical LT-BBT Riser ECC Electrical Need to set As per Energypac Engineering Ltd. (BBT EEL
Switchgear ECC Not Not Set as Proper Room, Ground standard Section)
Set as Standard Size Floor
03 TAP off Box internal TAP Off Box 1st floor to 5th Need to set As per Energypac Engineering Ltd. (BBT EEL
wiring Not Set as internal wiring Not Floor standard Section
Standard Set as Proper Size
of cable, like
Phase, neutral 7
ECC
04 TAB front Door Not TAB front Door not 1st floor to 5th Need to cut front door Energypac Engineering Ltd. (BBT EEL
Close. Properly closed Floor as per size of breaker Section
due to Breaker knob.
knob not operate
properly
05 System earthing Substation Utility area Need to install as per Energypac Engineering Ltd. Will Done EFL
Undersize Earthing not done standard of BNBC (Transformer) (already take one
as per standard. quotation)
06 Generator earthing Generator Utility area Need to install as per Energypac Power Generation Ltd. Will Done EFL
Undersize Earthing not done standard of BNBC (already take one
as per standard. quotation)
Energypac Fashions Ltd.
Electrical audit Report

Sl NC Issue Description Location Corrective Action Plan Respective Authority Completed BY


No
07 Electrical as Built Factory need to Factory-2 Need to make SLD EFL EFL
drawing Not found develop as built
electrical drawing
08 Ventilation at Need to make a All electrical Will set a exhaust fan of EFL EFL
electrical duct room Proper duck room each room
(Thermographic Ventilation
Spot Category -2) system
09 Danger Sign Need a danger All electrical We will set a sign of EFL EFL
sign in front of all duck room Danger in front of DB
DB MDB and MDB and electrical duct
electrical duct room
room
10 Multiple Looping At There is a 5th floor Fusing We will remove all EFL EFL
TAB Multiple Looping area looping within one week
at TAB.