You are on page 1of 79

Surge Arrester Theory & Applications

Jorge Luiz De Franco


REP – Lima – November 18th – 20th, 2013

November 15, 2013


High Voltage Technical Seminar
Surge Arrester Theory & Applications
• Purpose of Surge Arresters in Electrical Systems
• Overvoltage Conditions – Short Review
• Interaction of Surge Arresters with the Systems
• Insulation Coordination using Deterministic Method - Short Review
• Proper selection of Surge Arresters for protection of the Electrical
System
– Selection of Surge Arrester by it’s Electrical Characteristics
– Selection and Evaluation of Insulation Withstand Levels for proper
Equipment Protection
– Evaluation of the Insulation Coordination

page 2 / November 15, 2013


Purpose of Surge Arresters in Electrical Systems

• Arresters are used to protect electrical


equipment and power systems against
transient overvoltages (lightning and
switching) by reducing their electrical
Voltage with SA
stress to values lower than the withstand
voltage of the equipment / power Full Wave
Withstand Voltage
systems.
• This protects the equipment / power
system from damage and / or failures in
the insulation of the equipment / power
Voltage on the Insulation
systems after the overvoltage condition’s without SA – Flashover
occurrence. Occurrence
Overvoltage Conditions – Short Review

• Definition – IEC 60.071-1 – Edition 8.0 / 2006:


– Any voltage between one phase conductor and earth or across a
longitudinal insulation having a peak value exceeding the peak of
the highest voltage of the system divided by 3 or between phase
conductors having a peak value exceeding the peak of the highest
voltage of the system.

• Classification: According to their shape and duration, voltage and


overvoltages are divided in the following classes:
– Continuous
– Temporary Overvoltage
– Transient Overvoltage

page 4 / November 15, 2013


Overvoltage Conditions – Short Review
• Temporary Overvoltage:
– An oscillatory phase-to-ground or
phase-to-phase overvoltage of
relatively long duration. May be
undamped or weakly damped and
in some cases its frequency may
be several times smaller or higher
than power frequency.
– Temporary overvoltages usually
originate from Switching
Operations, Faults (Short Circuit),
Load Rejection, Ferroresonance
Effects or Ferranti Effect.
Overvoltage Conditions – Short Review

• Transient Overvoltages:
– Short Duration Overvoltage of few milliseconds or less, oscillatory or
non-oscillatory, usually highly damped.
• Slow-Front Overvoltage (usually associated with switching)
• Fast-Front Overvoltage (usually associated with lightning)
• Very Fast-Front Overvoltage (GIS and very fast events)
• Combined Overvoltage

page 6 / November 15, 2013


Overvoltage Conditions – Short Review

Continuous (Power Frequency) Temporary Transient (Slow, Fast and Very Fast Fronts)

Combined
Purpose of Surge Arresters in Electrical Systems

page 8 / November 15, 2013


Interaction of Surge Arresters with the Systems

U0 Expected overvoltage (kV)


Z0 Surge impedance (Ω)
UPR Residual voltage of the surge arrester (kV)
ZC Charge impedance (Ω)
Interaction of Surge Arresters with the Systems

Applying Thevenin´s Theorem:

ZC Z0  ZC
UTH  2 U0  ZTH 
Z0  ZC Z0  ZC
UTH  ZTH  I d  U PR  f  I d   0
Interaction of Surge Arresters with the Systems

UTH  ZTH  I d  U PR  f  I d   0

Z0  ZC
 I d  U PR  f  I d   0
ZC
2 U0  
Z 0  ZC Z 0  ZC

Considering the arrester installed at the end of the line:


ZC → ∞ (open circuit)

UTH  2 U 0 ZTH  Z 0
Interaction of Surge Arresters with the Systems

2 U 0  Z0  I d  U PR  f  I d   0

2 U 0  Z0  I d  U PR  f  I d 
Interaction of Surge Arresters with the Systems:
Protection with Silicon Carbide Arresters

Overvoltage Characteristic:

U0 (kV) 10 245 500 715 800 695 620 555 442

T (µs) 0,10 0,16 0,30 0,60 1,00 3,00 6,00 10,00 30,00

Surge Impedance of the System: 450 Ω


Interaction of Surge Arresters with the Systems:
Protection with Silicon Carbide Arresters

Voltage versus time Sparkover Voltage:

Udisr 1400 1200 1080 1030 960 940 940 960 980 1000
(kV)

Tdisr 0,16 0,30 0,60 1,00 3,00 6,00 10,00 30,00 100 1000
(µs)

Residual Voltage versus Discharge Current Characteristic:

UPR (kV) 320 650 900 1000 1080 1110 1140 1150

Id (kA) 0,2 0,4 0,6 0,8 1,0 1,2 1,4 1,6


Interaction of Surge Arresters with the Systems:
Protection with Silicon Carbide Arresters

Z0 . Id + UPR 2U0

UPR (Id) Z0 . Id Sparkover Voltage


Interaction of Surge Arresters with the Systems:
Protection with Silicon Carbide Arresters

Z0 . Id + UPR 2U0

UPR (Id) Z0 . Id Sparkover Voltage


Interaction of Surge Arresters with the Systems:
Protection with Silicon Carbide Arresters

2000

1800

1600
Overvoltage
1400
without SA
1200

1000
Overvoltage
800
with SA
600

400

200

0
0.10 1.00 10.00 100.00
Interaction of Surge Arresters with the Systems:
Protection with Zinc Oxide Arresters

Overvoltage Characteristic:

U0 (kV) 10 245 500 715 800 695 620 555 442

T (µs) 0,10 0,16 0,30 0,60 1,00 3,00 6,00 10,00 30,00

Surge Impedance of the System: 450 Ω

Residual Voltage versus Discharge Current Characteristic:

UPR (kV) 320 650 900 1000 1080 1110 1140 1150

Id (kA) 0,2 0,4 0,6 0,8 1,0 1,2 1,4 1,6


Interaction of Surge Arresters with the Systems:
Protection with Zinc Oxide Arresters

Z0 . Id + UPR 2U0

UPR (Id) Z0 . Id
Interaction of Surge Arresters with the Systems:
Protection with Zinc Oxide Arresters

2000

1800

1600
Overvoltage
1400
without SA
1200

1000
Overvoltage
800
with SA
600

400

200

0
0.10 1.00 10.00 100.00
Purpose of Surge Arresters in Electrical Systems

• Arresters are used to protect equipment and power systems against


transient overvoltages (lightning and switching) by reducing their
magnitudes to established values lower than the withstand voltages of
the equipment / power systems protected in way to avoid damages and
failures in the insulation of the equipment / power systems after the
overvoltage’s occurrence.

• Maximum magnitudes of the transient overvoltages on the terminals of


the equipment protected are calculated taking into account the Surge
Arrester’s protective levels and the distance effect (electrical distance)
among the arrester and the protected equipment.

page 21 / November 15, 2013


Function of Surge Arresters in Electrical Systems:
Arrester Protective Level

page 22 / November 15, 2013


Function of Surge Arresters in Electrical Systems:
Effect of Electrical Distance

Distance → VT

800

Lightning overvoltage (kVcr)


700
600
500
400
300
200
100
0
0 5 10 15 20 25 30 35 40 45 50

Distance (m)
LIWV Lightning Overvoltage LIWV / 1.2

page 23 / November 15, 2013


Insulation Coordination using Deterministic Method
- Short Review
• Insulation Coordination:
– As per IEC 60.071-1 / 2006 insulation coordination consists in the
selection of insulation strength consistent with expected overvoltages to
obtain an acceptable risk of failure.
Insulation Coordination using Deterministic Method
- Short Review

• Protective Margin:

CWV LIWV SIWV


PM 1  PM 2  PM 3 
FWPL  V1 LIPL  V2 SIPL

CWV Chopped Wave Voltage of the equipment


FWPL Front of Wave Protective Level of the arresters
LIWV Lightning Impulse Withstand Voltage of the equipment
LIPL Lightning Impulse Protective Level of the arrester
SWIV Switching Impulse Withstand Voltage of the equipment
SIPL Switching Impulse Protective Level of the arrester

V Additional voltage due to the electrical distance between the


arrester and the protected equipment

page 25 / November 15, 2013


Insulation Coordination using Deterministic Method
- Short Review

LIWV - BIL
PM ≥ 1,20
VMAX
LIPL SA
SIWV - BSL
PM ≥ 1,15
VMAX
SIPL SA

VMAX t   VRES t   V t 
Insulation Coordination using Deterministic Method
- Short Review
• To reduce the electrical distance among surge arresters and the
protected equipment in special power transformers, place the surge
arresters as closer as possible to the protected equipment
– Possibility of increasing the Protective Margin (MP)
– Possibility of reducing the Insulation Withstand Voltage

• Arrester as an integral part of the Protected Equipment


Arrester as an integral part of the Protected
Equipment – Power Transformers
Arrester as an integral part of the Protected
Equipment – Power Transformers

CHESF – Brazil 230 kV System


Arrester as an integral part of the Protected
Equipment – Power Transformers

Cazaquistan 220kV System


Surge Arrester Applications

Substations Distribution Networks Transmission Lines


Proper Selection of Surge Arresters for the
Protection of Electrical Systems
• Selection of the Arrester’s Characteristics
– Steady State Condition – MCOV and Rated Voltage
– Protective Characteristics – Residual Voltage Levels
– Energy Requirements
– Environmental Conditions
– Short-circuit requirements
– Mechanical requirements

• Selection and Evaluation of the Insulation Withstand Levels for proper


Equipment Protection

• Evaluation of the Insulation Coordination

page 32 / November 15, 2013


Selection of Surge Arrester Characteristics

Lightning and switching


overvoltages
Contamination and
environmental condition

Voltage

U rw
Temporary
overvoltages

Up
Continuous operating
voltage

Uc

t1
Time
Selection of Surge Arrester Characteristics

page 34 / November 15, 2013


Selection of Surge Arrester Characteristics -
Arrester Rated Voltage
• Condition 1 - Selection of Ur based on the Maximum Continuous
Operating Voltage (MCOV)
– Highest System Voltage

U max
Ur1  K 
3

U rated
K
MCOV

page 35 / November 15, 2013


Selection of Surge Arrester Characteristics -
Arrester Rated Voltage
• Condition 2 - Selection of Ur based the Amplitudes of the Temporary
Overvoltages (TOV) and their Duration
– Temporary Overvoltage versus Time Capability for Surge Arrester

1.30
Prior Energy 600C - 4,50 kJ/kV
1.25 No prior Energy - 60C
TOV
Ur2 
Prior Energy 60C - 2,25 kJ/kV
1.20

1.15
K2
U/Ur

1.10

1.05

1.00 TOV
0.95 K2 
0.90 U rated
0.10 1.00 10.00 100.00 1000.00
Time (s)

page 36 / November 15, 2013


Selection of Surge Arrester Characteristics -
Arrester Rated Voltage
• For same arrester design, it is
possible to reduce the surge
arrester’s protective levels by
reducing the arrester’s rated
voltage.
URATED

TOV SA TOV 2
TOV 1
MCOV
VMAX
Selection of Surge Arrester Characteristics -
Arrester Rated Voltage – Example
• System Voltage (Phase-to-Phase)
– Rated Voltage: 220 kV
– Highest Voltage of the System: 245 kV
– Case 1 - Grounded System: TOV = 198 kV (1.4 pu) at 1 s
– Case 2 - High Impedance System: TOV = 219 kV (1.55 pu) at 1 s
– Case 3 - Ungrounded System: TOV = 245 kV (1.73 pu) at 1 s
– Case 4 - General Case: TOV = 184 kV (1.3 pu) at 10 s

• For a first evaluation:

U rated
K  1.25
MCOV

page 38 / November 15, 2013


Selection of Surge Arrester Characteristics -
Arrester Rated Voltage – Example
• System Voltage (Phase-to-Phase)
– Rated Voltage: 220 kV
– Highest Voltage of the System: 245 kV

Um
Ur1  K1  MCOVmin  1,25 
3

245
Ur1  1,25   176,8kV
3

page 39 / November 15, 2013


Selection of Surge Arrester Characteristics -
Arrester Rated Voltage – Example
• System Voltage (Phase-to-Phase)
– Rated Voltage: 220 kV
– Highest Voltage of the System: 245 kV
– Case 1 - Grounded System: TOV = 198 kV (1.4 pu) at 1 s

TOV
Ur2 
K2

198
Ur2   172,2kV
1.15

page 40 / November 15, 2013


Selection of Surge Arrester Characteristics -
Arrester Rated Voltage – Example
• System Voltage (Phase-to-Phase)
– Rated Voltage: 220 kV
– Highest Voltage of the System: 245 kV
– Case 2 - High Impedance System: TOV = 219 kV (1.55 pu) at 1 s

TOV
Ur2 
K2

219
Ur2   190.4kV
1.15

page 41 / November 15, 2013


Selection of Surge Arrester Characteristics -
Arrester Rated Voltage – Example
• System Voltage (Phase-to-Phase)
– Rated Voltage: 220 kV
– Highest Voltage of the System: 245 kV
– Case 3 - Ungrounded System: TOV = 245 kV (1.73 pu) at 1 s

TOV
Ur2 
K2

245
Ur2   213.0kV
1.15

page 42 / November 15, 2013


Selection of Surge Arrester Characteristics -
Arrester Rated Voltage – Example
• System Voltage (Phase-to-Phase)
– Rated Voltage: 220 kV
– Highest Voltage of the System: 245 kV
– Case 4 - General Case: TOV = 184 kV (1.3 pu) at 10 s

TOV
Ur2 
K2

184
Ur2   170.4kV
1.08

page 43 / November 15, 2013


Selection of Surge Arrester Characteristics -
Arrester Rated Voltage – Example
• Summary of the Results:

• System Voltage (Phase-to-Phase)


– Rated Voltage: 220 kV
– Highest Voltage of the System: 245 kV
– Case 1 - Ur1 = 176.8 kV / Ur2 = 172.2 kV ▬ Ur ≥ 177 kV
– Case 2 - Ur1 = 176.8 kV / Ur2 = 190.4 kV ▬ Ur ≥ 190 kV
– Case 3 - Ur1 = 176.8 kV / Ur2 = 213.0 kV ▬ Ur ≥ 213 kV
– Case 4 - Ur1 = 176.8 kV / Ur2 = 170.4 kV ▬ Ur ≥ 177 kV

page 44 / November 15, 2013


Selection of Surge Arrester Characteristics -
Arrester Classification
• ANSI IEEE Std. 62.11
– Intermediate Class Arrester: 5 kA
– Station Class Arrester: 10 kA / 15 kA / 20 kA

• IEC 60.099-4
– Transmission Line Discharge Class: 1 - 5
• Nominal Discharge Current 10 kA: Class 1, 2 & 3
• Nominal Discharge Current 20 kA: Class 4 & 5

page 45 / November 15, 2013


Selection of Surge Arrester Characteristics -
Energy Requirements

• To define Surge Arrester Energy Capability


– ANSI IEEE Std. C62.11: Station or Intermediate Class
– IEC 60.099-4: Transmission Line Discharge Class

• Lightning Requirements

• Switching Requirements
– Closing and Re-closing of Long Lines
– Switching of Capacitor Banks and Cables
– Switching of reactors

page 46 / November 15, 2013


Selection of Surge Arrester Characteristics -
Energy Requirements
• Two aspects to be considered:
– The mechanical integrity of the ZnO disks
• Intrinsic energy absorption capability

page 47 / November 15, 2013


Selection of Surge Arrester Characteristics -
Energy Requirements
• Two aspects to be considered:
– Thermal stability for the complete arrester
• Thermal energy absorption capability

page 48 / November 15, 2013


Selection of Surge Arrester Characteristics -
Energy Requirements

page 49 / November 15, 2013


Selection of Surge Arrester Characteristics -
Energy Requirements
• Reevaluate the real conditions for the surge arresters regarding the
energy requirements during the occurrence of transient overvoltages.

• Detailed studies have shown that in some cases is possible to reduce


the energy absorption capability required for the surge arresters,
reducing costs and optinmizing the cost – benefit relationship.

• Surge arresters must be defined based on the energy absorption


capability required instead of the transmission line discharge class.

page 50 / November 15, 2013


Selection of Surge Arrester Characteristics -
Energy Requirements

page 51 / November 15, 2013


Selection of Surge Arrester Characteristics -
Protective Levels / Residual Voltages
• To obtain the Surge Arrester Protective Levels
– ANSI IEEE Std. C62.11
• Normalized lightning impulse discharge voltage
• Normalized switching impulse discharge voltage
• Normalized front-of-wave discharge voltage

– IEC 60.099-4
• Steep Current Residual Voltage: 1 µs / Nominal Discharge Current - In
• Lightning Impulse Residual Voltage: 8/20 µs / 0.5.In, In, and 2.In
• Switching Impulse Residual Voltage: 30/60 µs / Discharge Current
based on TLD Class and Nominal Discharge Current

page 52 / November 15, 2013


Selection of Surge Arrester Characteristics -
Protective Levels / Residual Voltages
– IEC 60.099-4
• Steep current residual voltage: 1 µs / Nominal discharge current

page 53 / November 15, 2013


Selection of Surge Arrester Characteristics -
Protective Levels / Residual Voltages
– IEC 60.099-4
• Lightning impulse residual voltage: 8/20 µs / 0.5.In, In e 2.In

page 54 / November 15, 2013


Selection of Surge Arrester Characteristics -
Protective Levels / Residual Voltages
– IEC 60.099-4
• Lightning impulse residual voltage: 8/20 µs / 0.5.In, In e 2.In

page 55 / November 15, 2013


Selection of Surge Arrester Characteristics -
Protective Levels / Residual Voltages
– IEC 60.099-4
• Switching impulse residual voltage: 30/60 µs / dicharges currents
values based on the TLD & nominal discharge current of the arrester

page 56 / November 15, 2013


Selection of Surge Arrester Characteristics -
Protective Levels / Residual Voltages

page 57 / November 15, 2013


Selection of Surge Arrester Characteristics -
Other Parameters to be Selected

• Environmental Conditions (Especially for Polymeric Arresters)

• Contamination Issues

• Short-Circuit Capability
– At Low Current
– At High Current

• Mechanical considerations

page 58 / November 15, 2013


Proper Selection of Surge Arresters for the
Protection of Electrical Systems
• Selection of the Arrester’s Characteristics
– Steady State Condition – MCOV and Rated Voltage
– Protective Characteristics – Residual Voltage Levels
– Energy Requirements
– Environmental Conditions
– Short-circuit requirements
– Mechanical requirements

• Selection and Evaluation of the Insulation Withstand Levels for proper


Equipment Protection

• Evaluation of the Insulation Coordination

page 59 / November 15, 2013


Selection and Evaluation of the Insulation Withstand
Levels for proper Equipment Protection

IEC 60071-1 / 2006

page 62 / November 15, 2013


Selection and Evaluation of the Insulation Withstand
Levels for proper Equipment Protection

ANSI IEEE Std. 1313.1 / 1996

page 63 / November 15, 2013


Proper Selection of Surge Arresters for the
Protection of Electrical Systems
• Selection of the Arrester’s Characteristics
– Steady State Condition – MCOV and Rated Voltage
– Protective Characteristics – Residual Voltage Levels
– Energy Requirements
– Environmental Conditions
– Short-circuit requirements
– Mechanical requirements

• Selection and Evaluation of the Insulation Withstand Levels for proper


Equipment Protection

• Evaluation of the Insulation Coordination

page 64 / November 15, 2013


Evaluation of the Insulation Coordination

page 65 / November 15, 2013


Evaluation of the Insulation Coordination

• Methods for evaluating the Distance Effect


– Simplified Method
– IEC Method: IEC 60.099-5
– ANSI IEEE Std. Method: ANSI C62.22
– Computational Simulation Method: Usually more realistic, but the
final results depend strongly on the models and the parameters
used.

page 66 / November 15, 2013


Evaluation of the Insulation Coordination
Distance effect - Computational simulation method
• The following models shall be considered:
– Incoming surge entrances in the substation
– Transmission line model (last towers)
– Bus bar model (representation of bus bar and connections)
– Models for the equipments of the substation

page 67 / November 15, 2013


Evaluation of the Insulation Coordination
Distance effect - Computational simulation method
• Models for the equipments of the substation:

page 68 / November 15, 2013


Evaluation of the Insulation Coordination
Distance effect - Computational simulation method
• Surge Arrester models
– Frequency dependence behavior shall be considered – IEEE model

page 69 / November 15, 2013


Evaluation of the Insulation Coordination
Distance effect - Computational simulation method
• Example: Arrester before the equipment to be protected

page 70 / November 15, 2013


Evaluation of the Insulation Coordination
Distance effect - Computational simulation method
• Example: Arrester before the equipment to be protected

page 71 / November 15, 2013


Evaluation of the Insulation Coordination
Distance effect - Computational simulation method
• Example: Arrester before the equipment to be protected

600

500

400

300

200

100

0
0,01 0,1 1 10 100

page 72 / November 15, 2013


Evaluation of the Insulation Coordination
Distance effect - Computational simulation method
• Example: Arrester before the equipment to be protected

page 73 / November 15, 2013


Evaluation of the Insulation Coordination
Distance effect - Computational simulation method
• Example: Arrester after the equipment to be protected

page 74 / November 15, 2013


Evaluation of the Insulation Coordination
Distance effect - Computational simulation method
• Example: Arrester after the equipment to be protected

page 75 / November 15, 2013


Evaluation of the Insulation Coordination
Distance effect - Computational simulation method
• Example: Arrester after the equipment to be protected

page 76 / November 15, 2013


Evaluation of the Insulation Coordination
Distance effect - Computational simulation method
• Example: Arrester position regarding to the equipment to be protected

page 77 / November 15, 2013


Evaluation of the Insulation Coordination
Distance effect - Computational simulation method
• Example: Effect of the Arresters in the entrance of the substation

page 78 / November 15, 2013


Evaluation of the Insulation Coordination
Distance effect - Computational simulation method
• Example: Effect of the Arresters in the entrance of the substation

page 79 / November 15, 2013


Proper Selection of Surge Arresters for the
Protection of Electrical Systems

VMAX t   VRES t   V t 
LIWV - BIL
MP ≥ 1,20
VMAX
LIPL SA
SIWL - BSL
MP ≥ 1,15
VMAX
SIPL SA

TOV capability
TOV SA
TOV system
1.3 – 2.0 pu
MCOV MCOV SA
1.0 pu VMAX
Thank You For Your Attention!

November 15, 2013

You might also like