You are on page 1of 5

GENERATORS

Why generators fail


By William G Moore, PE, National Electric Coil

P
lanned outages for gas-turbine-based tized and optimized given the limited resources
peaking, cogeneration, and combined-cycle and shrinking budgets that plant managers are
plants are scheduled based on the inspec- forced to live with today. But be sure that the work
tion and maintenance needs of the gas tur- plan for your next outage gives the generators the
bine/generator as prescribed by the OEM (original respect they deserve. It doesn’t take much effort to
equipment manufacturer). Owners of machines in check them thoroughly and verify their safe work-
regular use often schedule two outages yearly— ing condition.
spring and fall, when the market for power is soft. The pictures presented here will help you iden-
Others opt for one major outage annually. For peak- tify the onset of problems that could compromise
ing turbines in limited use—say a couple of hun- safety and lead to a forced outage—including for-
dred hours per year of operation—the time between eign object damage, partial discharge, rotor wind-
overhauls may stretch from two to four years. ing distortion, overheating, contamination, fatigue
Outages typically focus on the engine; gen- and stress corrosion cracking, vibration, and loose
erators sometimes are taken for granted—until a wedges. Share this report with your key staff to
problem arises. It’s understandable that inspec- build awareness and knowledge of generator fail-
tion and maintenance activities must be priori- ure mechanisms. CCJ

Foreign object damage tenance. When inspecting for Partial discharge


damage, consider a combination
Problem: A generator operates of visual examination and final Problem: Partial discharge,
in a carefully controlled environ- crawl through, along with ultra- sometimes called corona, is quite
ment. Entrance of objects into sonic or magnetic particle tests common in air-cooled generators.
the machine can be disastrous. on rotating components. It is caused by a partial voltage
Such objects can come breakdown within the
from external sources generator coil insula-
or failure of internal tion, in gaps between
components. Once the coil and the sta-
inside the machine, tor core, or in the end
objects can gain ener- turns when the coils
gy from the spinning are in close proxim-
rotor and do exten- ity. Because it is not a
sive damage. Fig 1 complete breakdown
shows coil insulation of the insulation sys-
damage caused by a tem, it doesn’t cause a
fan bolt that corroded full electrical ground.
and flew off into the Over time, however,
winding. these discharges can
“eat” at the insula-
Prevention: Inspect, tion, causing its dete-
on a regular basis, all rioration until a full
Fig 1
internal parts that are ground does occur and
prone to failure or can the unit trips offline.
be dislodged—such as rotating Evidence of partial-discharge
fan blades, balance weights, and (PD) activity often is visible to the
pantleg washers. Damage to sta- eye, appearing as a white powder
tor core iron in Fig 2 was caused dusting the surface of the stator
by a balance weight that came off winding (Fig 3). Severe PD dam-
the rotor. age on the outside surface of a
Remember, too, there is always stator coil is shown in Fig 4. This
potential danger from items was attributed to a lack of semi-
left inside the generator during Fig 2 conductive coating on the surface
inspection, testing, and main- of the coil in the slot portion.
30 COMBINED CYCLE JOURNAL, First Quarter 2005
GENERATORS
Rotor winding distortion tion loss of life, shorting of turns,
and eventual ground faults. The
Problem: Air-cooled rotors some- tendency to overheat can result
times develop severe rotor wind- from problems in the original
ing distortion and displacement, design or abnormal operation.
which result in shorted turns or Darkened areas on the rotor sur-
an electrical ground. Distortion face in Fig 8 show typical areas of
can be caused by poor design of overheating caused by abnormal
the end-turn blocking supports operation.
or by top-turn elongation of the In other cases, short-term
rotor coils. Top-turn elongation overheating results from blocked
often is caused by an inadequate ventilation passages caused by
Fig 3 slip plane between the end turns shifting insulation components
and the retaining ring. Distortion or slot wedges.

Prevention: Make sure rotor


wedges with cooling vents are
securely in place to prevent their
migration and blockage of the
cooling passage. Slot liners and
fillers also should be locked in
place to prevent axial migration
and the blocking of ventilation
holes.
Fig 4 Fig 6
Always operate the unit within

Fig 8

Fig 5 Fig 7 the generator capability curve.


For all rewinds, specify Class
Prevention: Special equipment of rotor end-turn coils is illustrat- F insulation and components.
is needed to detect PD activ- ed in Figs 6 and 7.
ity. Stator slot couplers can be Contamination
inserted under the stator wedge Prevention: Proper design of
to monitor magnitude and fre- the rotor coils, and bracing to Problem: Contamination from
quency of the discharges. It is support the coils under axial dirty oil or other chemicals can
important to trend PD activ- loads, are essential. Upgrading of wreak havoc on a turbine/genera-
ity over time because different the existing blocking design can tor. Gas purity is critical to the
machines have different base- provide improved coil support. efficient operation and cooling of
line values. In some instances, if only the top hydrogen-cooled generators. Oil
Doubling of PD levels over a turn is distorted, it can be placed leaking into the generator reduc-
period of six months is cause for back into its proper position. es hydrogen purity, sometimes
concern. The machine should be Rotors should be tested for to the point where the machine
opened up and inspected visu- turn-to-turn shorts with a flux trips offline. Dirt and dust are
ally. Special corona suppression probe at operating speed. more of a problem for air-cooled
treatments can be applied to Retaining-ring ground insula- machines; electrical grounds are
coil surfaces to minimize some tion should include a Teflon sur- relatively common.
types of PD activity. Fig 5 shows face so the coils can expand and
special cell- and corner-section contract with temperature. Prevention: Good maintenance
corona suppression treatment practices prevent contamination.
for a stator coil. Other types of Overheating For example, don’t forget to check
shielding arrangements can be these regularly: hydrogen dryers,
used as well, especially for phase- Problem: Overheating of the replacing the desiccant when
to-phase discharges. rotor or stator can lead to insula- needed; leak detectors, for signs
COMBINED CYCLE JOURNAL, First Quarter 2005 31
GENERATORS
of oil or water leakage; and filters particle, eddy current, and simple way insulation, plus the mixing
for air-cooled machines, cleaning dye penetrant testing. of the insulation particles with
when necessary. entrained oil, causes the greas-
Polarization Index tests pro- Retaining ring SCC ing. In companion Fig 13, dust-
vide a good indication of the rotor ing, caused by the relative move-
winding’s overall cleanliness. P r o b l e m : Stress corrosion ment between the stator-coil end
cracking occurs on non-magnet- turns and the support brack-
Fatigue cracks ic retaining rings—particularly et, shows up as a white powder
those made from 18Mn-5Cr alloy where the bracket and the end-
Problem: Many generator com- steel. The presence of high stress- turn surge ring meet.
ponents are susceptible to fatigue es (retaining rings usually are the Rotor vibration problems are
stresses that can initiate crack- most highly stressed component not usually catastrophic, but they
ing. To illustrate: Low-cycle on a generator), and moisture have been responsible for many
fatigue cracking caused by cyclic or chlorides, will initiate crack- forced outages. Most often, they
operation can occur in rotor-forg- ing and pitting in this materi- are caused by shorts, blocked
ing tooth tops and fluted areas, al. Laboratory tests have shown ventilation passages, electrical
slot wedges, and retaining rings. that when conditions are ideal for grounds, mechanical imbalance,
Keep in mind that the failure cracking, cracks can grow as fast wedge stick-slip, coil stick-slip,
of a forged component can com- as 0.001 inch per hour. loss of balance weights, overheat-
pletely destroy a generator and ing, and bearing wipe.
even cause loss of life. Fig 9 shows Prevention: SCC can be prevent-
cracks in the rotor winding attrib- ed by keeping the retaining rings Prevention: A “bump” test can
uted to low-cycle fatigue stresses dry. This can be difficult, especial- tell if stator windings are near
in the copper. ly on air-cooled generators, which, 120-Hz resonance, which would
Rotating fan blades are more unlike hydrogen-cooled machines, make them prone to vibration

Fig 9 Fig 11 Fig 12

are influenced by ambient air con-


ditions. Regular NDE, particular-
ly ultrasonic and dye penetrant
testing, can detect cracking early
as shown in Fig 11.
An alternative is to replace the
18Mn-5Cr retaining rings with
ones made of 18Mn-18Cr, a mate-
rial that is considerably less sus-
ceptible to SCC. However, this is
Fig 10 expensive. Fig 13

susceptible to high-cycle fatigue Vibration problems. For the rotor, good


cracking as shown in Fig 10. Here, vibration monitors and alert
the failure occurred in the blade Problem: Stator-winding end- operators are essential. Accurate
base area, not in a weld joint. turn vibration can wear away instrumentation signals impend-
coil insulation, precipitating a ing problems and knowledgeable
Prevention: Regular nondestruc- ground fault or it can cause coil operators can take appropriate
tive examination (NDE) helps you strand breakage, which results action to prevent damage.
find cracks early, before a failure in overheating. It is caused by
occurs and the component can double-frequency operating forc- Stator wedge looseness
be repaired or replaced. Inspec- es that loosen the end turns over
tion method depends on material, time. Fig 12 shows the tell-tale
and failure
accessibility of parts, and other greasing between coils indica- Problem: Wedges are essen-
criteria. Select from among ultra- tive of end-turn vibration. The tial for holding stator coils tight
sonic, wet fluorescent magnetic relative motion of coils wearing in their slots and for minimiz-
32 COMBINED CYCLE JOURNAL, First Quarter 2005
GENERATORS

Fig 14 Fig 16

ing vibration from steady-state tion. Such wear leads to


related excitation forces. When shorts, core hot spots, and
wedges loosen, coils can vibrate, eventually, core-to-core or
wearing ground-wall and turn Fig 15 coil-to-core failure. Note
insulation. Such wear leads to that in Fig 15, arc damage
ground failure or turn-to-turn age into the machine you can pro- on lamination surfaces was not
shorts. Note that when a wedge long wedge tightness and insula- visible until after the core was
becomes completely dislodged, tion life. A typical stator wedge unstacked.
damage to both the winding and and top spring are shown in Fig
core can be extensive. 14. Wedge has gauge holes for Prevention: Though some engi-
measuring ripple-spring deflec- neers doubt that retorquing can
Prevention: Proper design and tion. tighten the core, inspection of
installation minimize the poten- through-bolt tightness is rec-
tial for wedge movement and Stator core damage ommended at regular intervals.
vibration. Top, bottom, and side Regular EL CID (for electromag-
ripple springs preload the coil Problem: Stator-core looseness netic core imperfection detection)
and maintain compression under can occur over time as pre-ten- tests or loop test inspections of
all normal operating conditions. sioned through bolts relax. A loose the stator core also can verify its
Conduct periodic checks during core is conducive to coil and lami- continued integrity. The knife
regular maintenance activities to nation damage. If laminations test illustrated in Fig 16 is a sim-
verify wedge tightness. Be aware vibrate relative to one another, ple way to check for stator core
too, that by preventing oil seep- they can wear surface insula- looseness.

HRSG Data Set


2005 Edition Now Available!
Robust database of combined-cycle plants identifying over
7000 major components — GT, ST, and HRSG — in 89 countries
Provides specific data to identify fellow HRSG and GT
users, or pr ospective customers. International entries include:
Owner Plant Name Location MW Rating
EPC Fuel Status HRSG OEM
GT OEM GT Model ST OEM NOx Control . . . and more

Contact info also provided for North American listings:


Contact name! Address! Phone! Fax!

Delivered on CD, in a large flatfile dbf format that can be


imported into your database software for maximum effectiveness
Published by the HRSG User's Group and Utility Data Institute
For details visit www.HRSGusers.org
Request a brochure from info@ HRSGusers.org
Or call 1-406-582-8655
COMBINED CYCLE JOURNAL, First Quarter 2005 33
COMBINED
CYCLEJournal
Gas turbines • HRSGs • Steam turbines • Auxiliaries
• Engineering solutions for gas-turbine-based powerplants •
• Plus, analysis and perspective of critical business and regulatory issues •
You qualify for a FREE subscription to the COMBINED CYCLE Journal if you have engi-
neering, supervisory, management, or executive responsibility for the design, construction, opera-
tion, and/or maintenance of combined-cycle and simple-cycle electric generating facilities or gas-
turbine-based industrial cogeneration plants.
® YES, start my FREE subscription to the COMBINED CYCLE Journal
® No, I do not want to receive this professional journal

Signature ___________________________________ Date _________________________________

ALL QUESTIONS MUST BE ANSWERED TO QUALIFY FOR A FREE SUBSCRIPTION


Name __________________________________ Title ___________________________________
Company _______________________________ E-mail _________________________________
Address ________________________________ Address is: ® Home; ® Business
City ____________________________________ State_____________ Zip __________________
Phone __________________________________ Fax ___________________________________
1. Type of company or organization (check ONLY one): 2. Primary job function (check ONLY one):
® A – Electric generator (regulated utility or unregulated ® A – Plant management (including O&M)
IPP, merchant, etc.) ® B – Construction management
® B – Industrial generator (pulp and paper, refinery, etc.) ® C – Engineering management
® C – Institutional/commercial generator ® D – Engineering, plant O&M, plant services
® D – Engineer/constructor, consultant ® E – Other (specify) ____________________
® E – Equipment manufacturer/plant services provider
® F – Regulatory agency, law firm, financial services
® G – Other (specify) ____________________________
You may receive renewal reminders via e-mail. If you do not want to receive other business-related third-party e-mail
offers from the publisher—including messages from supporting user groups—please check here ®

Please also start subscriptions for these other qualified personnel at this address:
Name ________________________________ Title ____________________________ E-mail____________________________

Name ________________________________ Title ____________________________ E-mail ____________________________

Name ________________________________ Title ____________________________ E-mail ____________________________

FAX to 702-869-6867

You might also like