Signal Conditioners Introduction
With the variety of process control systems available, it is often necessary to convert an input signal into a format that the
system will accept. Signal conditioners take signals from an assortment of field instruments such as thermocouples and RTDs,
and convert those signals into any of several standard instrument signals (1 V to 5 V, 4 mA to 20 mA, etc.). Signal conditioners
are also beneficial to the accurate transfer of these signals, isolation, and the elimination of ground loops.

Signal Conditioners
Operating principle
The key to process control is accuracy both in measurement and in signal
conditioning. The biggest and most overlooked threat to effective process control
is the presence of ground loops. Whenever analog data is transferred through long
cable runs, there is a high probability that ground loop problems will occur.
A ground loop exists when multiple earth ground connections are made in a system.
A difference in potential between the grounds generates an extraneous current flow
in the signal conductor.
The result is commonly known as noise. In its mildest form, noise in the signal line causes measurement offsets, incorrect
sensor readings, and general signal corruption. In its most severe form, however, noise contamination can deteriorate
communication to a point where control of the process is lost. Isolation between the ground circuits is essential to the
prevention of ground loop currents and, therefore, the elimination of noise. Signal conditioners provide the necessary isolation
as well as amplification, filtering, and linearity corrections.

K-System 566
 Broad product range
 3-port galvanically isolated barriers
 SIL rated for safety instrumented systems
 Limit detection
 Logic functions: pushbutton programmable
 Fault detection and alarming
 Loop-powered and analog isolators
11/2010
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
565
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K-System Signal Conditioners
K-System

K-System
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs

11/2010
Accessories

908837 (US) / 208599 (EU)


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


566 Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Signal Conditioners Introduction

System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 568


Digital Inputs
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 577

K-System
Product Data Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 579

Digital Outputs
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 603

Product Data Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 604

Analog Inputs

Digital Inputs
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 609

Product Data Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 612

Analog Outputs
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 647

Digital Outputs
Product Data Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 648

Accessories
Selection Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 655

Accessory Data Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 657

Analog Inputs
Analog Outputs
11/2010

Accessories
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 567
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description Signal Conditioners

Introduction KF module housings


The K-System consists of wide range of signal conditioners Used for high channel density S1
S2

suitable for mounting on 35 mm DIN rail. K-System is easy to • 20 mm housing


S3

specify, integrate and expand and has become synonymous • Highest packing density on the market
with safety and reliability. Our extensive line of signal 7

conditioner for safety location applications contains over • As low as 5 mm per channel 1
1
K-System

60 different models, each containing industry leading features


and benefits.
Digital Inputs

Figure 3 20 mm housing (KF module)

Used for applications with high


functionality
• Logic controls determine and monitor
Figure 1 K-System on Power Rail speed, direction of rotation, slip, flow
rates and time
Digital Outputs

1 2 3 4 5 6
KFD2-WAC2-
1.D
• Analog controls monitor transmitter
Housing types signals, strain gauges, temperature OUT
ERR

1 2
PWR

and load cells ESC

Depending on the functionality and application, K-System has


different housing widths. Whether it is the 12.5 mm • Configured using PACTware™ or by RS 232
OK

KC modules or the well-proven 20 mm KF modules, the push button 7


13
8
14
9
15
10
16
11
17
12
18
19 20 21 22 23 24
electrical and mechanical characteristics of the K-System are • Universal power supply
maintained. This collection of modules provides a wide range
of interface barriers that can be combined on Power Rail.
Analog Inputs

KC module housing
Figure 4 40 mm housing (KF module)
Used for high signal integrity
• Compact housing, only 12.5 mm wide
• Single loop integrity
• Power loss only 0.8 W per device 1
3
2
4
Analog Outputs

KCD2-SR-
1.LB

PWR

OUT/CHK

S1
S2
S3
S4
I II

5 6
7 8
9 10
11/2010
Accessories

908837 (US) / 208599 (EU)

Figure 2 12.5 mm housing (KC module)


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


568 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Signal Conditioners System Description

Supply voltage Mounting on Power Rail


K-System signal conditioners are available with different As shown in the figure, the isolation modules are snapped
supply voltages. The most widely used rating is 24 V DC; onto the Universal Power Rail in a vertical downward
however, 115 V AC and 230 V AC are also available for movement.
applications when DC power is not available.
The universal supply units carry the complete range from

K-System
20 V DC to 90 V DC and 48 V AC to 230 V AC on the same
input terminals. The supported supply voltage for each barrier
is identified on the side plate.

Mounting
The K-System is mounted on a 35 mm DIN rail acc. to
EN 60715. To reduce wiring and installation costs, Power Rail
is the optimum solution.
Low heat dissipation allows vertical or horizontal mounting.

Digital Inputs
Power Rail
The Power Rail is a plastic insert into a standard DIN rail and
contains two leads that deliver power to the modules. Power
is sent through the rail by a power feed module that delivers Figure 6 Proper K-System mounting
24 V DC at 4 A. The module uses a 5 A fuse to protect the
barriers. The Power Rail virtually eliminates the risk of wiring CORRECT: Device snapped on vertically.
faults and facilitates easy expansion. Power Rail is available

Digital Outputs
in two versions:
• UPR-03: 3-lead version supplies two leads for power and
one lead for error signal
• UPR-05: 5-lead version supplies two leads for power, one
lead for error signal and two leads for serial data
exchange.

Analog Inputs
Analog Outputs
Figure 5 Universal Power Rail UPR-05 Figure 7 Improper K-System mounting

INCORRECT: Device snapped on from the side.


11/2010

Accessories
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 569
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description Signal Conditioners

Power connection to K-System Redundant Supply with Power Feed Modules


Two power supplies or a redundant power supply with two
Conventional power supply without power feed modules offers a high degree of safety and
Power Rail reliability. If a power supply is damaged or a fuse opens in a
power feed module, the redundant power supply continues to
Conventional power supplies create complicated and energize the isolator modules through their Power Rail
expensive wiring systems. After all signal conditioners are connection.
K-System

connected, there is a significant amount of wiring and more


wiring must be added for features such as lead breakage and Power Feed Power Feed
short-circuit monitoring. Module 1 Module 2

Power
1 2 3 1 2 3 1 2 3 1 2 3
4 5 6 4 5 6 4 5 6 4 5 6 Rail
1 2 3 1 2 3 1 2 3 1 2 3
4 5 6 4 5 6 4 5 6 4 5 6
DIN Rail
Digital Inputs

7 8 9 7 8 9 7 8 9 7 8 9
10 11 12 10 11 12 10 11 12 10 11 12
13 14 15 13 14 15

7 8 9 7 8 9 7 8 9 7 8 9
10 11 12 10 11 12 10 11 12 10 11 12
Digital Outputs

24 V DC 24 V DC
24 V DC
Figure 10 Redundant power connections
Figure 8 Conventional installation

Direct Supply with Power Supplies


Power supply with Power Rail A complete power solution for a K-System installation is
possible by using a 115/230 V AC to 24 V DC/4 A power
Supply with Power Feed Modules supply with the KFA6-STR-1.24.4 or by using the
KFA6-STR-1.24.500 that provides 24 V DC/500 mA. The
Analog Inputs

The Pepperl+Fuchs Power Rail eliminates wiring hassles and


reduces expense. The power feed module mounts on the power supplies snap-on the Power Rail to easily and
Power Rail for easy and reliable distribution of power to all efficiently distribute power to the signal conditioners.
connected signal conditioners. This method eliminates all of Power Supply
the parallel power wiring necessary on a conventional
installation without Power Rail.
Power
1 2 3 1 2 3
4 5 6 4 5 6 Rail
Power Feed
Module
Analog Outputs

1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 7 8 9 7 8 9
4 5 6 4 5 6 4 5 6 4 5 6 4 5 6
Power Rail 10 11 12 10 11 12

115/230 V AC

Figure 11 Integrated power supply (4 A)


11/2010
Accessories

7 8 9 7 8 9 7 8 9 7 8 9 7 8 9
10 11 12 10 11 12 10 11 12 10 11 12 10 11 12
13 14 15
908837 (US) / 208599 (EU)

24 V DC

Figure 9 Power Rail installation


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


570 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Signal Conditioners System Description

Power Supply Terminal blocks


Removable terminal blocks
1 2 3 1 2 3 1 2 3
4 5 6 4 5 6 4 5 6 The removable terminal blocks simplify
control cabinet construction and allow the
units to be replaced while they are energized.

K-System
PWR
These screw-secured, cage clamp terminals
allow space for the connection of leads with
core cross-sections of up to 2.5 mm2
(14 AWG). The connectors are coded with red
7 8 9
10 11 12
13 14 15
7 8 9
10 11 12
7 8 9
10 11 12 pins so misconnection of a terminal block is 1 2 3

eliminated. With the KF-CP coding pins 4 5 6

(available separately), additional terminal


block styles with test sockets or cage spring
release can be easily coded and inserted into
a signal conditioner.
115/230 V AC

Digital Inputs
Figure 12 Integrated power supply (500 mA) 7 8 9
10 11 12

Collective error messaging


Figure 14 K-System removable terminal blocks
Collective error messaging enables lead breakage and short-
circuit monitoring for isolator modules without additional wiring
expenses. During a fault condition of the field circuit, an

Digital Outputs
interrupt signal from an isolator module is transferred to the Terminal designation
Power Rail. The power feed module evaluates the signal and
Please reference appropriate model for terminal designation.
transfers the interrupt signal to the control system via a relay
contact.
1 2
Power Feed
Module 3 4
1 2
3 4

Analog Inputs
1 2 3 1 2 3 1 2 3 1 2 3 1 2 3
4 5 6 4 5 6 4 5 6 4 5 6 4 5 6

5 6
7 8
9 10
7 8 9
10 11 12
7 8 9
10 11 12
7 8 9
10 11 12
7 8 9
10 11 12
7 8 9
10 11 12
5 6

Analog Outputs
13 14 15

7 8

9 10

Figure 15 12.5 mm housing (KC module)


24 V DC

I/O
Fault signal output
11/2010

Accessories

Figure 13 Collective error message via power feed module


908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 571
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description Signal Conditioners

Color identification
1 2 3
The color identification of the devices has the following
4 5 6 meaning:
1 2 3
4 5 6 • green indicates devices with DC power supply
• black indicates devices with AC power supply
• grey indicates devices with universal power supply of
K-System

20 V DC to 90 V DC or 48 V AC to 253 V AC

7 8 9
10 11 12
13 14 15
7 8 9
1 2 3 1 2 3
4 5 6 4 5 6
1 2 3 4 5 6
10 11 12
KFU8-UFC-
1.D
KFD2-ER-1.W.LB KFA5-ER-1.W.LB
IN/
13 14 15 CH K
1 PWR
OUT
OUT CHK PWR OUT CHK PWR 1 2
Digital Inputs

ESC
3

sens. sens.
Figure 16 20 mm housing (KF module) RS 232
OK

7 8 9 10 11 12
13 14 15 16 17 18
19 20 21 22 23 24

7 8 9 7 8 9
10 11 12 10 11 12
13 14 15 13 14 15

1 2 3 4 5 6
Digital Outputs

1 2 3 4 5 6

green black grey

Figure 18 Color identification of devices

7 8 9 10 11 12
13 14 15 16 17 18
19 20 21 22 23 24
Analog Inputs

7 8 9 10 11 12

13 14 15 16 17 18

19 20 21 22 23 24

Figure 17 40 mm housing (KF module)


Analog Outputs

11/2010
Accessories

908837 (US) / 208599 (EU)


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


572 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Signal Conditioners System Description

Model number description


K – – Ex .
Position
8 Special function, if available

7 Number of channels

K-System
Isolated Barriers, not applicable to Signal Conditioners

6 Device generation (2 ... X)

5 Device function

4 Level of power supply

3 Type of power supply

2 Construction type

Position 1 K = K-System

Digital Inputs
Position 2 C = Version with removable terminals, 12.5 mm width
F = Version with removable terminals, 20 mm or 40 mm width
H = Version without removable terminals, 20 mm or 40 mm width
Position 3 D = DC power supply
A = AC power supply
U = AC-/DC power supply
Position 4 0 = without power supply
2 = 24 V
4 = 100 V
5 = 115 V
6 = 230 V

Digital Outputs
8 = 20 V DC to 90 V DC, 48 V AC to 253 V AC
Position 5 CC = Converter for current/voltage
CD = Current driver, active
CR = Transmitter power supply device, current output
CRG = Transmitter power supply device with limit value output
CS = Current driver, passive
DU = Switch amplifier, timer relay
DWB = Rotational speed monitor, logic control unit
EB = Power feed module
ELD = Ground fault detection
ER Conductivity switch amplifier
FF = RS 232 repeater

Analog Inputs
GS = Trip amplifier for current/voltage
GU = Universal trip amplifier
GUT = Temperature converter with trip values
HLC = HART Loop Converters
HMM = HART Multiplexer Master
HMS = HART Multiplexer Slave
PT = Potentiometer converter
RC = Converter for resistors
RCI = Solenoid driver
RO = Relay module
RR = Repeater for resistance measuring sensor

Analog Outputs
RSH = Relay module in safety application
SCD = SMART current driver
SCS = SMART current driver/repeater
SD = Solenoid driver
SH = Safety switch amplifier
SL = Solenoid driver module with logic input
SOT = Switch amplifier with passive, potential free transistor output
SR = Switch amplifier with relay output
SRA = Switch amplifier with relay output, 2:1 operation mode
SRT = Switch amplifier with active transistor and relay output
ST = Switch amplifier with active transistor output
STC = SMART transmitter power supply with current output
11/2010

Accessories

STR = Power supply


STV = SMART transmitter power supply with voltage output
TR = Converter for resistance measuring sensor
908837 (US) / 208599 (EU)

TT = Converter for thermocouple/mV


UFC = Universal frequency converter
UFT = Frequency converter with direction and synchronization monitoring
USC = Universal signal converter with trip values
UT = Universal temperature converter
VC = Converter for current/voltage
VCR = Transmitter power supply, repeater for current/voltage
VD = Solenoid driver
VM = Solenoid driver
VR = Voltage repeater
Edition

WAC = Converter for strain gauges

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 573
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description Signal Conditioners

Safety information For US and Canada installations, in Zone 2/Div. 2 follow the
NEC and CEC wiring methods. The enclosure must be able to
The corresponding data sheets, the Declaration of accept Zone 2/Div. 2 wiring methods. The referenced product
Conformity, the EC-Type Examination Certificate and certification control drawing must be observed.
applicable certificates (see data sheet) are an integral part of
this document. For all other applications, the devices should be installed in a
switch or junction box that:
Intended use
K-System

• meets at least IP54 in accordance to EN 60529.


• meets to the requirements of resistance to light and
Laws and regulations applicable to the usage or planned
purpose of usage must be observed. Devices are only resistance to impact according to EN 60079-0/
approved for proper usage in accordance with intended use. IEC 60079-0.
Improper handling will result in voiding of any warrantee or • meets to the requirements of thermal endurance
manufacturer's responsibility. according to EN 60079-15/IEC 60079-15.
These devices are used in C&I technology for the galvanic • must not cause ignition danger by electrostatic charge
isolation of C&I signals, such as 20 mA and 10 V unit signals, during intended use, maintenance and cleaning.
and also for the adaptation and/or standardization of signals. The EC-Type Examination Certificates, standard
The devices are not suitable for the isolation of signals in certificates/approvals or the manufacturer's Declaration of
Digital Inputs

power engineering, unless this is specifically referred to in the Conformity should be observed. It is especially important to
respective data sheet. observe the "special conditions" if these are included in the
certificates.
Protection of operating personnel and the system is not
ensured if the product is not used in accordance with its
intended use.
Repair and maintenance
The transfer characteristics of the devices remain stable over
Installation and commissioning long periods of time. This eliminates the need for regular
adjustment. Maintenance is not required.
Digital Outputs

Commissioning and installation must be carried out by


specially trained and qualified personnel only.
Fault elimination
Installation of the interface devices in the No changes can be made to devices that are operated in
safe area hazardous areas. Repairs on the device are not allowed.

The devices are constructed to satisfy the IP20 protection Isolation coordinates for installations for
classification and must be protected from adverse
environmental conditions such as water spray or dirt
galvanic isolation according to EN 50178
and EN 61140
Analog Inputs

exceeding the pollution degree 2.


The devices must be installed outside the hazardous area! The devices of the K-System are electronic equipment for use
in secluded electrical operating sites where only skilled
Installation and commissioning of the personnel or electrically instructed personnel will have
interface devices within Zone 2/Div. 2 of admission or access.

the hazardous area The devices are assessed for pollution degree 2 and
overvoltage category II according to EN 50178.
Only devices with the corresponding manufacturer's
Connect only power supplies to power feed modules, which
Analog Outputs

Declaration of Conformity or separate certificate of conformity


provide protection against direct contact (e. g. SELV or
can be installed in Zone 2/Div. 2.
PELV).
The individual data sheets indicate whether these conditions
For additional details, see data sheets.
are met.
11/2010
Accessories

908837 (US) / 208599 (EU)


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


574 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Signal Conditioners System Description

Technical data Connection


• KH*-modules:
Electrical data self-opening connection terminals for max. core diameter
of 1 x 2.5 mm2 (14 AWG)
Control circuit signals
• KF*-and KC*-modules:
• 0/4 mA to 20 mA signal level acc. to NE43 removable connector with integrated self opening device
terminals for leads of up to a max. of 1 x 2.5 mm2

K-System
• Current output HART compatible
(14 AWG)
• Current input HART compatible
• Digital output: active or, passive electronic output Fire protection class
100 mA/30 V, short circuit protected Housing: V2 according to UL 94 standard. (Unless stated
• Relay output 2 A, minimum load 1 mA/24 V otherwise all details relate to the reference conditions.)
• Logic level 24 V acc. to IEC 60946
• Functional isolation or safe isolation acc. to EN 50178 and
Labeling
NAMUR NE23 place for labeling on the front side, label:
For additional details, see data sheets. • KC-modules (12.5 mm): 22 mm x 9 mm

Digital Inputs
• KF-modules (20 mm): 22 mm x 16.5mm
Field circuit signals • KF-modules (40 mm): 18 mm x 8 mm
• Transmitter power supply up to 17 V DC
Ambient conditions
• Current input HART compatible
Ambient temperature
• Pt100, in 2-, 3-, (4-)wire technology
• Resistor 0 Ω to 400 Ω with freely definable characteristic -20 °C to 60 °C (-4 °F to 140 °F)

Digital Outputs
• Potentiometer Exceptions see data sheets.
• Thermocouples of all types, internal cold junction, external Storage temperature
reference
-40 °C to 90 °C (-40 °F to 194 °F)
• Current output HART compatible
Reference conditions for adjustment
• Digital input NAMUR EN 60947-5-6
For additional details, see data sheets. 20 °C (68 °F)
Relative humidity
Mechanical data

Analog Inputs
max. 95 % without moisture condensation
Mounting
Vibration resistance
• Snap-on 35 mm standard DIN rail acc. to EN 60715. Can
acc. to EN 60068-2-6, 10 Hz to 150 Hz, 1 g, high crossover
be mounted horizontally or vertically, side by side.
frequency
• Panel mount: The lugs on the base of the modules must
be extended and used for mounting purposes with 3 mm Shock resistance
screws. acc. to EN 60068-2-27, 15 g, 11 ms, half-sine
• K-MS mounting base for screw attachment

Analog Outputs
Housing material
Polycarbonate (PC)
Dimensions
Housing drawings please refer to www.pepperl-fuchs.com.
Protection degree
IP20 acc. to EN 60529
11/2010

Accessories
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 575
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
System Description Signal Conditioners

Conformity with standards and directives Digital inputs/outputs in accordance with NAMUR
General The standards references for this interface have changed
many times:
• EMC acc. to NAMUR NE21 and EN 61326
German standard (old): DIN 19234: Electrical distance
• LEDs acc. to NAMUR NE44 sensors – DC interface for distance sensors and switch
• Software acc. to NAMUR NE53 amplifiers; 1990-06
K-System

• Switch-on pulse suppression European standard (old): EN 50227: Low voltage switch gear
• Devices K*D2: and control gear – control devices and switching elements –
proximity switches, DC interface for proximity sensors and
– Supply voltage 20 V DC to 30 V DC via Power Rail or
switch amplifiers (NAMUR), 1996-10
supply terminals
– Fault signals via Power Rail German version (old): DIN EN 50227: Low voltage switch
• Devices K*A and K*U: gear – control devices and switching elements – proximity
switches, DC interface for proximity sensors and switch
– Supply voltage 115 V/230 V AC ±10 % amplifiers (NAMUR), 1997, German nomenclature VDE 0660,
• Safety devices acc. to VDE 0660 T.209, AK acc. to part 212
DIN 19250
Current designation: DIN EN 60947-5-6: Low voltage switch
Digital Inputs

gear – control devices and switching elements – proximity


switches, DC interface for proximity sensors and switch
amplifiers (NAMUR), 2000, German nomenclature. VDE 0660
part 212
Current IEC designation: IEC 60947-5-6: Low voltage
switch gear and control gear – part 5-6: Control circuit devices
and switching elements – DC interface for proximity sensors
and switching amplifiers (NAMUR), 1999.
Digital Outputs
Analog Inputs
Analog Outputs

11/2010
Accessories

908837 (US) / 208599 (EU)


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


576 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Signal Conditioners Selection Tables
Switch Amplifiers

Model Number Input (Field) Output Supply Page


(Control System)

NAMUR Sensor/
Function Timer

Error Message
3-wire Sensor
Dry Contact

Line Fault

115 V AC/
Detection
Channels

230 V AC

K-System
24 V DC
Output
Relay

SIL
KCD2-SR-1.LB 1   2   2 579

KCD2-SR-2 2   2  2 580

KFD2-SR2-2.2S 2   2x2  2 581

KFU8-SR-1.3L.V 1   2   582

KFA6-SR-2.3L 2  2  583

Digital Inputs
Frequency Converters

Model Number Functions Input (Field) Output Supply Page


(Control System)
Special Functions

NAMUR Sensor/

0/4 mA ... 20 mA

Digital Outputs
Speed Monitor

Error Message
Dry Contact
Conversion
Frequency

Transistor
Line Fault

115 V AC/
Detection

(Passive)

230 V AC
24 V DC
Output
Relay

SIL
KFD2-SR2-2.W.SM     2  2 584

KFD2-DWB-1.D    2   2 585

Analog Inputs
KFU8-DWB-1.D    2    2 586

KFD2-UFC-1.D      2 1  1  2 587

KFU8-UFC-1.D      2 1  1   2 588

KFD2-UFT-2.D      2 2  1  589

KFU8-UFT-2.D      2 2  1   590

Analog Outputs
11/2010

Accessories
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 577
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Selection Tables Signal Conditioners

Conductivity Switch Amplifiers

Model Number Input (Field) Output Supply Page


(Control System)

Measurement of Conductivity
K-System

Error Message
Resistance
Line Fault

115 V AC/
Detection
Channels

230 V AC
Function

24 V DC
Output
Relay

SIL
KFD2-ER-1.5 1  1  591

KFD2-ER-1.6 1  1  592
Digital Inputs

KFA5-ER-1.5 1  1  593

KFA5-ER-1.6 1  1  594

KFA6-ER-1.5 1  1  595

KFA6-ER-1.6 1  1   596

KFD2-ER-1.W.LB 1    2   597
Digital Outputs

KFD2-ER-2.W.LB 2    2   598

KFA5-ER-1.W.LB 1    2   599

KFA5-ER-2.W.LB 2    2   600

KFA6-ER-1.W.LB 1    2   601

KFA6-ER-2.W.LB 2    2   602
Analog Inputs
Analog Outputs

11/2010
Accessories

908837 (US) / 208599 (EU)


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


578 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Switch Amplifier KCD2-SR-1.LB

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 19 ... 30 V DC
• 24 V DC supply (Power Rail)
Power consumption ≤ 500 mW
Input
• Dry contact or NAMUR inputs
Rated values acc. to EN 60947-5-6 (NAMUR) • Relay contact output
• Fault relay contact output

K-System
Open circuit voltage/short-circuit approx. 10 V DC/approx. 8 mA
current • Line fault detection (LFD)
Switching point/switching hysteresis 1.2 ... 2.1 mA/approx. 0.2 mA
• Housing width 12.5 mm
Line fault detection breakage I ≤ 0.1 mA, short-circuit I ≥ 6.5 mA
Pulse/Pause ratio ≥ 20 ms/≥ 20 ms • Up to SIL2 acc. to IEC 61508
Output
Output I signal; relay Function
Output II signal or error message; relay
Contact loading 253 V AC/2 A/cos Φ > 0.7; 126.5 V AC/4 A/cos Φ > 0.7;
This signal conditioner transfers digital
30 V DC/2 A resistive load signals (NAMUR sensors/mechanical
Minimum switch current 2 mA/24 V DC contacts) from the field to the control

Digital Inputs
Energized/De-energized delay ≤ 20 ms/≤ 20 ms system.
Mechanical life 107 switching cycles The proximity sensor or switch controls a
Transfer characteristics form A normally open relay contact for the
Switching frequency ≤ 10 Hz load. The normal output state is reversed
Ambient conditions using switch S1. Switch S2 allows
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) output II to be switched between a signal
Mechanical specifications output and an error message output.
Protection degree IP20 Switch S3 enables or disables line fault
Mass approx. 100 g detection of the field circuit.

Digital Outputs
Dimensions 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 in), During an error condition, relays revert to
housing type A2
their de-energized state and LEDs
indicate the fault according to
NAMUR NE44.
A unique collective error messaging
feature is available when used with the
Power Rail system.
Due to its compact housing design and

Analog Inputs
low heat dissipation, this device is useful
for detecting positions, end stops, and
switching states in space-critical
applications.

Analog Outputs
Diagrams

Front view Removable terminal


green

KCD2-SR-1.LB
LED green:
1 2
1+ 5 3 4 Power supply
10 kΩ I
2- 6
400 Ω ≤ R ≤ 2 kΩ KCD2-SR- LED yellow/red:
1.LB
Status output/
Fault signal
11/2010

Accessories

7 PWR

II OUT/CHK

8
S1
S2
908837 (US) / 208599 (EU)

S3
S4
I II

Switch 1 ... 4

5 6
7 8
9+ 9 10 Place for labeling
10-
24 V DC

Removable terminals
ERR 24 V DC
green
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KCD2-SR-1.LB

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 579
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KCD2-SR-2 Switch Amplifier

Features Technical data


• 2-channel signal conditioner Supply
Rated voltage 19 ... 30 V DC
• 24 V DC supply (Power Rail)
Power consumption ≤ 600 mW
• Dry contact or NAMUR inputs Input
• Relay contact output Rated values acc. to EN 60947-5-6 (NAMUR)
• Line fault detection (LFD)
K-System

Open circuit voltage/short-circuit approx. 10 V DC/approx. 8 mA


• Housing width 12.5 mm current
Switching point/switching hysteresis 1.2 ... 2.1 mA/approx. 0.2 mA
• Up to SIL2 acc. to IEC 61508
Line fault detection breakage I ≤ 0.1 mA, short-circuit I ≥ 6.5 mA
Pulse/Pause ratio ≥ 20 ms/≥ 20 ms
Function
Output
Output I signal; relay
This signal conditioner transfers digital
Output II signal; relay
signals (NAMUR sensors/mechanical
Contact loading 253 V AC/2 A/cos Φ > 0.7; 126.5 V AC/4 A/cos Φ > 0.7;
contacts) from the field to the control
30 V DC/2 A resistive load
system.
Minimum switch current 2 mA/24 V DC
Digital Inputs

The proximity sensor or switch controls a Energized/De-energized delay ≤ 20 ms/≤ 20 ms


form A normally open relay contact for the Mechanical life 107 switching cycles
load. The normal output state can be Transfer characteristics
reversed using switches S1 and S2. Switching frequency ≤ 10 Hz
Switch S3 is used to enable or disable line Ambient conditions
fault detection of the field circuit. Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
During an error condition, relays revert to Mechanical specifications
their de-energized state and LEDs Protection degree IP20
Digital Outputs

indicate the fault according to Mass approx. 100 g


NAMUR NE44. Dimensions 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 in),
housing type A2
A unique collective error messaging
feature is available when used with the
Power Rail system.
Due to its compact housing design and
low heat dissipation, this device is useful
for detecting positions, end stops, and
switching states in space-critical
Analog Inputs

applications.
Analog Outputs

Diagrams

Front view Removable terminals


green

KCD2-SR-2
LED green:
1 2
3 4 Power supply 1+ 5
I 10 kΩ I
2- 6
KCD2-SR-2 LED yellow/red: 400 Ω ≤ R ≤ 2 kΩ
Status output/
error channel I
11/2010
Accessories

PWR
3+ 7
II II
1
OUT/CHK 10 kΩ
2 LED yellow/red: 4- 8
S1 Status output/ 400 Ω ≤ R ≤ 2 kΩ
S2
error channel II
908837 (US) / 208599 (EU)

S3
S4
I II

Switch 1 ... 4

5 6
7 8
9 10 Place for labeling 9+
10-
24 V DC

Removable terminals
ERR 24 V DC
green
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KCD2-SR-2

580 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Switch Amplifier KFD2-SR2-2.2S

Technical data Features


Supply • 2-channel signal conditioner
Rated voltage 20 ... 30 V DC
• 24 V DC supply (Power Rail)
Power consumption < 1.3 W
Input
• Dry contact or NAMUR inputs
Rated values acc. to EN 60947-5-6 (NAMUR) • 2 x 2 relay contact outputs with
AND logic

K-System
Open circuit voltage/short-circuit approx. 8 V DC/approx. 8 mA
current • Line fault detection (LFD)
Switching point/switching hysteresis 1.2 ... 2.1 mA/approx. 0.2 mA • Reversible mode of operation
Line fault detection breakage I ≤ 0.1 mA, short-circuit I > 6 mA
• Up to SIL2 acc. to IEC 61508
Pulse/Pause ratio ≥ 20 ms/≥ 20 ms
Output
Function
Collective error message Power Rail
Output I, II, III, IV channel 1, 2; relay
This signal conditioner transfers digital
Contact loading 50 V AC/1 A/cos Φ > 0.7; 40 V DC/1 A resistive load
signals (NAMUR sensors/mechanical
Minimum switch current 1 mA/24 V DC
contacts).
Energized/De-energized delay approx. 20 ms/approx. 20 ms

Digital Inputs
Mechanical life 108 switching cycles Each sensor or switch controls two form A
Transfer characteristics normally open relay contacts. The normal
Switching frequency ≤ 10 Hz output state can be reversed using
Ambient conditions switches S1 and S2. Switch S3 is used to
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) enable or disable line fault detection of the
Mechanical specifications field circuit.
Protection degree IP20 During an error condition, the relays
Mass approx. 150 g revert to their de-energized state and the

Digital Outputs
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2 LEDs indicate the fault according to
NAMUR NE44.
A unique collective error messaging
feature is available when used with the
Power Rail system.

Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminals
green
KFD2-SR2-2.2S
1 2 3
4 5 6
1+ 7
I LED yellow: LED green:
I 10 kΩ 2+ 8 Relay output Ι KFD2-SR2-2.2S Power supply
10 kΩ II
3- 9
1
400 Ω ≤ R ≤ 2 kΩ
11/2010

Accessories

LED red: OUT CHK PWR

LB/SC channel Ι
2

S1
Switch S1
4+ 10 S2 (Mode of operation channel Ι)
III LED yellow: S3

II 10 kΩ 5+ 11 Relay output ΙΙ I II
908837 (US) / 208599 (EU)

Switch S2
10 kΩ IV
6- 12 (Mode of operation channel ΙΙ)
400 Ω ≤ R ≤ 2 kΩ LED red: 7 8 9
LB/SC channel ΙΙ 10 11 12
Switch S3
13 14 15

14+ (LB/SC-monitoring)
15-
24 V DC

Removable terminals
ERR 24 V DC
green
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-SR2-2.2S

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 581
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFU8-SR-1.3L.V Switch Amplifier, Timer Relay

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 20 ... 48 V DC or 90 ... 253 V AC, 45 ... 65 Hz
• AC/DC wide range supply
Power consumption ≤ 4.5 W
• 3-wire PNP/NPN sensor or Input
push-pull input Rated values 22 ... 24 V DC/100 mA
• 2 relay contact outputs ≤ 125 mA
K-System

Short-circuit current
• Adjustable energized/de-energized Switching point PNP:
delay 0-signal: < 12.5 V, 1-signal: > 13.5 V
NPN and push-pull output:
0-signal: < 4.5 V, 1-signal: > 5.5 V
Function
Output
Output I, II signal; relay
This signal conditioner converts the state
Contact loading 250 V AC/2 A/cos Φ ≥ 0.7; 125 V AC/4 A/cos Φ > 0.7;
of 3-wire sensors (PNP or NPN) or
40 V DC/2 A
sensors with push-pull output stages into
Mechanical life 20 x 106 switching cycles
two relay outputs.
Electrical life 0.2 x 106 switching cycles (40 V DC, 2 A, ohmic)
It has one input and two form C 0.4 x 106 switching cycles (253 V AC, 2 A, cos Φ = 1)
Digital Inputs

changeover relay outputs. 0.25 x 106 switching cycles (253 V AC, 2 A, cos Φ = 0.7)
The switch amplifier has an adjustable Minimum load 50 mW, 5 V DC
energized/de-energized delay for the Energized/De-energized delay ≤ 90 ms/≤ 90 ms
relay outputs. Transfer characteristics
Switching frequency ≤ 5 Hz for delay 0 s
adjustable energized/de-energized delay: 0 ... 79 s
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Digital Outputs

Mechanical specifications
Protection degree IP20
Mass approx. 166 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
Analog Inputs
Analog Outputs

Diagrams

Front view
Removable terminal
green
Rotary switch S6, S7:
KFU8-SR-1.3L.V
Time adjustment
1 2 3
4 5 6 LED green:
Power supply
LED yellow: KFU8-SR-1.3L.V
Switch S3: 7
Relay output Ι 8 I
(energized/de-energized
LED yellow: 9
1+
11/2010
Accessories

OUT1 OUT2 PWR


delay)
Relay output ΙΙ S1
2
S2
S3
Switch S4:
S4 (mode of operation 3-
S5 10
Switch S1: I II
output Ι) 11 II
908837 (US) / 208599 (EU)

(sensor type) Switch S5: 12


(mode of operation
7 8 9 output ΙΙ)
Switch S2: 10 11 12
(Time base 0.1 s/1 s) 13 14 15

14
15
AC/DC

Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFU8-SR-1.3L.V

582 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Switch Amplifier KFA6-SR-2.3L

Technical data Features


Supply • 2-channel signal conditioner
Rated voltage 90 ... 253 V AC, 45 ... 65 Hz
• 230 V AC supply
Power consumption ≤7 W
Input
• 3-wire PNP/NPN sensor or
Rated values 22 ... 24 V DC/100 mA push-pull input
• Relay contact output

K-System
Short-circuit current 110 mA
Switching point 0-signal: < 5 V • DIP switch selectable functions
1-signal: > 13 V • Minimum/maximum control
Output
Output I, II Function
Contact loading 250 V AC/4 A/cos Φ > 0.7; 40 V DC/2 A resistive load
Energized/De-energized delay max. 6 ms This signal conditioner converts the state
Mechanical life 107 switching cycles of 3-wire sensors (PNP or NPN) or
Transfer characteristics sensors with push-pull output stages into
Switching frequency ≤ 10 Hz a relay output.
Ambient conditions
It has two inputs and two form C

Digital Inputs
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
changeover relay outputs.
Mechanical specifications
Protection degree IP20 The device can be used either as dual
Mass approx. 150 g channel signal conditioner or as a two-
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2 point level controller.

Digital Outputs
Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminals
green
KFA6-SR-2.3L
1 2 3
4 5 6 LED green:
Power supply
LED yellow:
1+ 7 Relay output Ι KFA6-SR-2.3L

I 2 8 I
3- 9 LED yellow:
11/2010

Switch S3:
Accessories

OUT1 OUT2 PWR

Relay output ΙΙ S1
(dual channel or min/max)
S2
S3
4+ 10
S4
Switch S1: S5 Switch S4:
II 5 11 II (mode of operation I II
(sensor type input Ι)
908837 (US) / 208599 (EU)

12
6- input Ι)
Switch S5:
Switch S2: 7 8 9 (sensor type input ΙΙ)
10 11 12
(mode of operation 13 14 15
input ΙΙ)
14+
15-
230 V AC

Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFA6-SR-2.3L

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 583
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD2-SR2-2.W.SM Standstill and Rotational Direction Monitor

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 20 ... 30 V DC
• 24 V DC supply
Power consumption ≤ 1.5 W
• PNP/push-pull, dry contacts or Input
NAMUR inputs Rated values acc. to EN 60947-5-6 (NAMUR)
• Selectable frequency trip values x ≤ 1.2 mA or x ≥ 2.1 mA/approx. 0.9 mA
K-System

Switching point/switching hysteresis


• 2 relay contact outputs Control input sensor power supply approx. 8.2 V, impedance 1.2 kΩ
• Start-up override Lead monitoring not available
Pulse duration > 200 μs for standstill monitoring,
• Selectable mode of operation
> 250 μs for rotation direction detecion
• Up to SIL2 acc. to IEC 61508 Output
Relay 2 changeover contacts
Function Contact loading 253 V AC/2 A/cos Φ > 0.7; 40 V DC/2 A resistive load
Energized/De-energized delay approx. 20 ms/approx. 20 ms
This signal conditioner is a zero Mechanical life 5 x 106 switching cycles
speed/standstill monitor that accepts Trip value fmax for standstill monitoring:
Digital Inputs

input frequency pulses and triggers an 0.1 Hz; 0.5 Hz; 2 Hz; 10 Hz
output when the frequency drops below a adjustable via DIP switch (S1 and S2)
selected value. Transfer characteristics
Two startup override values are available. Accuracy ±5%
This unit can also be used to determine Start-up override 5 seconds or 20 seconds, programmable
rotation direction. Frequency range ≤ 2 kHz
Rotation direction detection 90° phase difference between pulse input signal
During an error condition, relays revert to
1 and 2, overlapping ≥ 125 μs
their de-energized state and LEDs
Ambient conditions
Digital Outputs

indicate the fault according to


Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
NAMUR NE44.
Mechanical specifications
The available diagnostic LEDs show Protection degree IP20
rotation detection, limit trip indicator, Connection plug-in terminals
power on, and hardware error indication. Mass approx. 150 g
The unit is easily programmed via Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
switches mounted on the front of the unit.
For additional information, refer to
Analog Inputs

www.pepperl-fuchs.com.
Analog Outputs

Diagrams

Front view Removable terminals


green

KFD2-SR2-2.W.SM
24 V
1 2 3
4 5 6 - 1+
LED green: I + 2+ 7
KFD2-SR2-2.W.SM
Power supply Q
8 I
3- 9
1
11/2010
Accessories

LED yellow: 2
OUT CHK PWR
24 V
Relay output I S1
Switch S1:
- 4+ 10
S2
Trip value frequency
LED yellow:
S3 11 II
I II II + 5+ 12
908837 (US) / 208599 (EU)

Relay output II Switch S2:


Trip value frequency Q
6-
7 8 9
LEDs flashing red: 10 11 12 Switch S3:
13 14 15
Hardware error Start-up override/
Rotation direction detection 14+
15-
24 V DC

Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-SR2-
2.W.SM
584 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Overspeed/Underspeed Monitor KFD2-DWB-1.D

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 20 ... 30 V DC
• 24 V DC supply (Power Rail)
Power loss/power consumption ≤ 1.8 W/1.8 W
Input
• Dry contact or NAMUR inputs
Input I sensor acc. to EN 60947-5-6 (NAMUR) or • Input frequency 1 mHz ... 12 kHz
mechanical contact • 2 relay contact outputs

K-System
Open circuit voltage/short-circuit 22 V/40 mA • Start-up override
current
Input resistance 4.7 kΩ
• Configurable by keypad
Switching point/switching logic 1: > 2.5 mA; logic 0: < 1.9 mA • Line fault detection (LFD)
hysteresis • Up to SIL2 acc. to IEC 61508
Pulse duration > 50 μs
Input frequency 0.001 ... 12000 Hz Function
Lead monitoring breakage I ≤ 0.15 mA; short-circuit I > 4 mA
Input II startup override: 1 ... 1000 s, adjustable in steps of 1 s This signal conditioner monitors for an
Active/Passive I > 4 mA (for min. 100 ms)/I < 1.5 mA overspeed or underspeed condition of a

Digital Inputs
Open circuit voltage/short-circuit 18 V/5 mA digital signal (NAMUR sensor/mechanical
current contact) by comparing the input frequency
Output to the user programmed reference
Collective error message Power Rail frequency.
Output I, II signal; relay
An overspeed or underspeed condition is
Contact loading 250 V AC/2 A/cos Φ ≥ 0.7; 40 V DC/2 A
signaled via the relay outputs. Line fault
Mechanical life 5 x 107 switching cycles
detection of the field circuit is indicated by
Energized/De-energized delay approx. 20 ms/approx. 20 ms
a red LED, Power Rail and/or relay. The
Transfer characteristics

Digital Outputs
startup override feature sets relay outputs
Input I
to default conditions programmed by the
Measurement range 0.001 ... 12000 Hz
user for up to 1,000 seconds.
Output I, II
Response delay ≤ 200 ms The unit is easily programmed by the use
Ambient conditions of a keypad located on the front of the
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) unit.
Mechanical specifications A unique collective error messaging
Protection degree IP20 feature is available when used with the
Mass 300 g Power Rail system.

Analog Inputs
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in), housing type C3 For additional information, refer to the
Data for application in connection manual and www.pepperl-fuchs.com.
with Ex-areas
Statement of conformity Pepperl+Fuchs
Group, category, type of protection, ¬ II 3G Ex nA nC IIC T4
temperature classification

Analog Outputs
Diagrams
Front view
Removable terminal
green

KFD2-DWB-1.D

400 Ω ≤ R ≤ 2 kΩ LED green: 1 2 3 4 5 6


+ 10
LC display
+ + + + 1 11 I Power supply KFD2-DWB-
1.D
12 IN/
10 kΩ 10 kΩ CH K

- - - - 16 LED yellow/red: OUT


1 PWR
11/2010

Accessories

3 17 II Input pulses/ 1 2

18 fault signal ESC

- LED yellow: OK

2 13+ Keypad
Output Ι
908837 (US) / 208599 (EU)

14-
7 8 9 10 11 12
13 14 15 16 17 18
LED yellow: 19 20 21 22 23 24
Output ΙΙ

23+
24-
24 V DC Removable terminals
green

ERR 24 V DC Zone 2
Power Rail Div. 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-DWB-1.D

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 585
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFU8-DWB-1.D Overspeed/Underspeed Monitor

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 20 ... 90 V DC/48 ... 253 V AC 50 ... 60 Hz
• AC/DC wide range supply
Power loss/power consumption ≤ 1.8 W; 2 VA/1.8 W; 2 VA
• Dry contact or NAMUR inputs Input
• Input frequency 1 mHz ... 12 kHz Lead monitoring breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
• 2 relay contact outputs
K-System

Input I sensor acc. to EN 60947-5-6 (NAMUR) or


• Start-up override mechanical contact
Open circuit voltage/short-circuit 22 V/40 mA
• Configurable by keypad current
• Line fault detection (LFD) Input resistance 4.7 kΩ
• Up to SIL2 acc. to IEC 61508 Switching point/switching logic 1: > 2.5 mA; logic 0: < 1.9 mA
hysteresis
Function Pulse duration > 50 μs
Input frequency 0.001 ... 12000 Hz
This signal conditioner monitors an Lead monitoring breakage I ≤ 0.15 mA; short-circuit I > 4 mA
overspeed or underspeed condition of a Input II startup override: 1 ... 1000 s, adjustable in steps of 1 s
Digital Inputs

digital signal (NAMUR sensor/mechanical Active/Passive I > 4 mA (for min. 100 ms)/I < 1.5 mA
contact) by comparing the input frequency Open circuit voltage/short-circuit 18 V/5 mA
to the user programmed reference current
frequency. Output
Output I, II signal; relay
An overspeed or underspeed condition is
Contact loading 250 V AC/2 A/cos Φ ≥ 0.7; 40 V DC/2 A
signaled via the relay outputs. Line fault
Mechanical life 5 x 107 switching cycles
detection of the field circuit is indicated by
Energized/De-energized delay approx. 20 ms/approx. 20 ms
a red LED and/or relay. The startup
Transfer characteristics
Digital Outputs

override feature sets relay outputs to


Input I
default conditions programmed by the
Measurement range 0.001 ... 12000 Hz
user for up to 1,000 seconds.
Output I, II
The unit is easily programmed by the use Response delay ≤ 200 ms
of a keypad located on the front of the Ambient conditions
unit. Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
For additional information, refer to the Mechanical specifications
manual and www.pepperl-fuchs.com. Protection degree IP20
Mass 300 g
Analog Inputs

Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in), housing type C3


Analog Outputs

Diagrams
Front view
Removable terminal
green

KFU8-DWB-1.D

LED green: 1 2 3 4 5 6
+ + + + + 10
LC display
Power supply KFU8-DWB-
1.D
1 11 I
IN/
12
CH K
LED yellow/red: OUT
1 PWR
- - - - 16
11/2010
Accessories

Input pulses/ 1 2 3 17 II
fault signal ESC
18

LED yellow: OK - 13+


Keypad 2
Output Ι 14-
908837 (US) / 208599 (EU)

7 8 9 10 11 12
13 14 15 16 17 18
LED yellow: 19 20 21 22 23 24
Output ΙΙ

23
24
AC/DC
Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFU8-DWB-1.D

586 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Frequency Converter with Trip Values KFD2-UFC-1.D

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 20 ... 30 V DC
• 24 V DC supply (Power Rail)
Power loss/power consumption ≤ 2 W/2.2 W
Input
• Dry contact or NAMUR inputs
Input I sensor acc. to EN 60947-5-6 (NAMUR) or • Input frequency 1 mHz ... 12 kHz
mechanical contact • Current output 0/4 mA ... 20 mA

K-System
Pulse duration > 50 μs • Relay and transistor output
Input frequency 0.001 ... 12000 Hz
• Start-up override
Lead monitoring breakage I ≤ 0.15 mA; short-circuit I > 4 mA
Input II startup override: 1 ... 1000 s, adjustable in steps of 1 s • Line fault detection (LFD)
Active/Passive I > 4 mA (for min. 100 ms)/I < 1.5 mA • Up to SIL2 acc. to IEC 61508
Output
Collective error message Power Rail Function
Output I, II signal; relay
Contact loading 250 V AC/2 A/cos Φ ≥ 0.7; 40 V DC/2 A This signal conditioner is an universal
Energized/De-energized delay approx. 20 ms/approx. 20 ms frequency converter that changes a digital

Digital Inputs
Output III electronic output, passive input (NAMUR sensor/mechanical
Contact loading 40 V DC contact) into a proportional free
Signal level 1-signal: (L+) -2.5 V adjustable 0/4 mA ... 20 mA analog
(50 mA, short-circuit/overload proof) output and functions as a switch amplifier
0-signal: blocked output (off-state current ≤ 10 μA) and a trip alarm.
Output IV analog
Also the functions of the switch outputs
Current range 0 ... 20 mA or 4 ... 20 mA
(2 relay outputs and 1 potential free
Open loop voltage ≤ 24 V DC
transistor output) are easily adjustable
Load ≤ 650 Ω

Digital Outputs
[trip value display (min/max alarm),
Fault signal downscale I ≤ 3.6 mA, upscale ≥ 21.5 mA
serially switched output, pulse divider
(acc. NAMUR NE43)
output, error signal output].
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) The unit is easily programmed by the use
Mechanical specifications of a keypad located on the front of the unit
Protection degree IP20 or with the PACTware™ configuration
Mass 300 g software.
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in), housing type C3 Line fault detection of the field circuit is
Data for application in connection indicated by a red LED and through the

Analog Inputs
with Ex-areas collective error output via Power Rail.
Statement of conformity Pepperl+Fuchs
For additional information, refer to the
Group, category, type of protection, ¬ II 3G Ex nA nC IIC T4
manual and www.pepperl-fuchs.com.
temperature classification

Analog Outputs
Diagrams
Front view
Removable terminal
green

KFD2-UFC-1.D
+ 400 Ω ≤ R ≤ 2 kΩ 10
+ + + +
1 11 I LED green: 1 2 3 4 5 6
12 KFD2-UFC- LC display
10 kΩ 10 kΩ Power supply 1.D

- - - - 16 IN/
CH K
3 17 II LED yellow/red: OUT
1 PWR

18
11/2010

Accessories

Input pulses/ 1 2

- 19+ III fault signal 3


ESC

2 20- RS 232
LED yellow: OK
Keypad
8+ IV
mA Output Ι ... ΙΙΙ
908837 (US) / 208599 (EU)

7- 7 8 9 10 11 12
13 14 15 16 17 18
13+ 19 20 21 22 23 24

14-

23+
24-
24 V DC Programming jack Removable terminals
green

ERR 24 V DC Zone 2
Power Rail Div. 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-UFC-1.D

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 587
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFU8-UFC-1.D Frequency Converter with Trip Values

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 20 ... 90 V DC/48 ... 253 V AC 50 ... 60 Hz
• AC/DC wide range supply
Power loss/power consumption ≤ 2 W; 2.5 VA/2.2 W; 3 VA
• Dry contact or NAMUR inputs Input
• Input frequency 1 mHz ... 12 kHz Input I sensor acc. to EN 60947-5-6 (NAMUR) or
• Current output 0/4 mA ... 20 mA mechanical contact
K-System

• Relay and transistor output Pulse duration > 50 μs


Input frequency 0.001 ... 12000 Hz
• Start-up override
Lead monitoring breakage I ≤ 0.15 mA; short-circuit I > 4 mA
• Line fault detection (LFD) Input II startup override: 1 ... 1000 s, adjustable in steps of 1 s
• Up to SIL2 acc. to IEC 61508 Active/Passive I > 4 mA (for min. 100 ms)/I < 1.5 mA
Output
Function Output I, II signal; relay
Contact loading 250 V AC/2 A/cos Φ ≥ 0.7; 40 V DC/2 A
This signal conditioner is an universal Mechanical life 5 x 107 switching cycles
frequency converter that changes a digital Energized/De-energized delay approx. 20 ms/approx. 20 ms
Digital Inputs

input (NAMUR sensor/mechanical Output III electronic output, passive


contact) into a proportional free Contact loading 40 V DC
adjustable 0/4 mA ... 20 mA analog Signal level 1-signal: (L+) -2.5 V
output and functions as a switch amplifier (50 mA, short-circuit/overload proof)
and a trip alarm. 0-signal: blocked output (off-state current ≤ 10 μA)
Output IV analog
Also the functions of the switch outputs
Current range 0 ... 20 mA or 4 ... 20 mA
(2 relay outputs and 1 potential free
Open loop voltage ≤ 24 V DC
transistor output) are easily adjustable
Load ≤ 650 Ω
Digital Outputs

[trip value display (min/max alarm),


Fault signal downscale I ≤ 3.6 mA, upscale ≥ 21.5 mA
serially switched output, pulse divider
(acc. NAMUR NE43)
output, error signal output].
Ambient conditions
The unit is easily programmed by the use Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
of a keypad located on the front of the unit Mechanical specifications
or with the PACTware™ configuration Protection degree IP20
software. Mass 300 g
Line fault detection of the field circuit is Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in), housing type C3
indicated by a red LED.
Analog Inputs

For additional information, refer to the


manual and www.pepperl-fuchs.com.
Analog Outputs

Diagrams
Front view
Removable terminal
green

KFU8-UFC-1.D
+ 400 Ω ≤ R ≤ 2 kΩ 10
LED green: 1 2 3 4 5 6 1 11 I
+ + + +
KFU8-UFC- LC display 12
Power supply 1.D 10 kΩ 10 kΩ
IN/
CH K
- - - - 16
LED yellow/red: 1 PWR 3 17 II
OUT
18
11/2010
Accessories

Input pulses/ 1 2

fault signal 3
ESC
- 19+ III
RS 232
2 20-
LED yellow: OK
Keypad 7- IV
Output Ι ... ΙΙΙ mA
908837 (US) / 208599 (EU)

7 8 9 10 11 12
8+
13 14 15 16 17 18
19 20 21 22 23 24 13+
14-

Removable terminals 23
Programming jack 24
AC/DC
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFU8-UFC-1.D

588 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Frequency Converter with Direction and Synchronization Monitor KFD2-UFT-2.D

Technical data Features


Supply • 2-channel signal conditioner
Rated voltage 20 ... 30 V DC
• 24 V DC supply (Power Rail)
Power consumption 2.5 W
Input
• Dry contact or NAMUR inputs
Input I, II sensor acc. to EN 60947-5-6 (NAMUR) or • Input frequency 1 mHz ... 1 kHz
mechanical contact • Current output 0/4 mA ... 20 mA

K-System
Open circuit voltage/short-circuit 8.2 V/10 mA • Relay and transistor output
current
Switching point/switching logic 1: > 2.5 mA; logic 0: < 1.9 mA
• Start-up override
hysteresis • Line fault detection (LFD)
Pulse duration ≥ 250 μs,
overlap on direction of rotation signal: ≥ 125 μs Function
Input frequency rotation direction monitoring 0.001 ... 1000 Hz
slip monitoring 10 ... 1000 Hz This signal conditioner analyzes 2 digital
Lead monitoring breakage I ≤ 0.15 mA; short-circuit I > 4 mA signals (NAMUR sensor/mechanical
Input III, IV contact) and functions as a rotation

Digital Inputs
Active/Passive I > 4 mA (for min. 100 ms)/I < 1.5 mA direction indicator, slip monitor, frequency
Open circuit voltage/short-circuit 18 V/5 mA monitor or synchronization monitor.
current
Each proximity sensor or switch controls a
Output
passive transistor output. The 2 relay
Collective error message Power Rail
outputs indicate if the input signal is
Output I, II signal; relay
above or below the trip value or the
Contact loading 250 V AC/2 A/cos Φ ≥ 0.7; 40 DC/2 A
rotational direction.
Energized/De-energized delay approx. 20 ms/approx. 20 ms
Output III and IV signal; electronic output, passive The analog output can be programmed to

Digital Outputs
Contact loading 40 V DC be proportional to the input frequency or
Output V analog slip differential.
Current range 0 ... 20 mA or 4 ... 20 mA The unit is easily programmed by the use
Open loop voltage max. 24 V DC of a keypad located on the front of the unit
Load max. 650 Ω or with the PACTware™ configuration
Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA software.
(acc. NAMUR NE43)
Line fault detection of the field current is
Programming interface
indicated by a red LED and through the
Interface RS 232
collective error output via Power Rail.

Analog Inputs
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) For additional information, refer to the
Mechanical specifications manual and www.pepperl-fuchs.com.
Protection degree IP20
Mass 300 g
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in), housing type C3

Analog Outputs
Diagrams
Front view
Removable terminals
green

KFD2-UFT-2.D
400 Ω ≤ R ≤ 2 kΩ 10 LED green:
1+ 11 I Power supply 1 2 3 4 5 6
12 KFD2-UFT- LC display
I 10 kΩ 10 kΩ 16 2.D

17 II LED yellow/red: IN/


CH K
3- 18 Input pulses/ 1 2 PWR
OUT
11/2010

Accessories

19+ fault signal 1 2

400 Ω ≤ R ≤ 2 kΩ III 3 4
ESC

4+ 20- LED yellow:


Output Ι ... IV
RS 232
IV OK
Keypad
II 10 kΩ 10 kΩ 21+
908837 (US) / 208599 (EU)

7- V 7 8 9 10 11 12
6- mA 13 14 15 16 17 18
8+ 19 20 21 22 23 24
13+
14-
15+
23+
24-
24 V DC Programming jack Removable terminals
green

ERR 24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-UFT-2.D

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 589
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFU8-UFT-2.D Frequency Converter with Direction and Synchronization Monitor

Features Technical data


• 2-channel signal conditioner Supply
Rated voltage 20 ... 90 V DC/48 ... 253 V AC 50 ... 60 Hz
• AC/DC wide range supply
Power consumption 2.5 W/4 VA
• Dry contact or NAMUR inputs Input
• Input frequency 1 mHz ... 1 kHz Input I, II sensor acc. to EN 60947-5-6 (NAMUR) or
• Current output 0/4 mA ... 20 mA mechanical contact
K-System

• Relay and transistor output Open circuit voltage/short-circuit 8.2 V/10 mA


current
• Start-up override Switching point/switching logic 1: > 2.5 mA; logic 0: < 1.9 mA
• Line fault detection (LFD) hysteresis
Pulse duration ≥ 250 μs,
Function overlap on direction of rotation signal: ≥ 125 μs
Input frequency rotation direction monitoring 0.001 ... 1000 Hz
This signal conditioner analyzes 2 digital slip monitoring 10 ... 1000 Hz
signals (NAMUR sensor/mechanical Lead monitoring breakage I ≤ 0.15 mA; short-circuit I > 4 mA
contact) and functions as a rotation Input III, IV
Digital Inputs

direction indicator, slip monitor, frequency Active/Passive I > 4 mA (for min. 100 ms)/I < 1.5 mA
monitor or synchronization monitor. Open circuit voltage/short-circuit 18 V/5 mA
current
Each proximity sensor or switch controls a
Output
passive transistor output. The 2 relay
Output I, II signal; relay
outputs indicate if the input signal is
Contact loading 250 V AC/2 A/cos Φ ≥ 0.7; 40 DC/2 A
above or below the trip value or the
Energized/De-energized delay approx. 20 ms/approx. 20 ms
rotational direction.
Output III and IV signal; electronic output, passive
The analog output can be programmed to Contact loading 40 V DC
Digital Outputs

be proportional to the input frequency or Output V analog


slip differential. Current range 0 ... 20 mA or 4 ... 20 mA
The unit is easily programmed by the use Open loop voltage max. 24 V DC
of a keypad located on the front of the unit Load max. 650 Ω
or with the PACTware™ configuration Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA
software. (acc. NAMUR NE43)
Programming interface
Line fault detection of the field current is
Interface RS 232
indicated by a red LED.
Ambient conditions
Analog Inputs

For additional information, refer to the Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
manual and www.pepperl-fuchs.com. Mechanical specifications
Protection degree IP20
Mass 300 g
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in), housing type C3
Analog Outputs

Diagrams
Front view
Removable terminals
green

KFU8-UFT-2.D
LED green: 400 Ω ≤ R ≤ 2 kΩ 10
Power supply 1 2 3 4 5 6 1+ 11 I
KFU8-UFT- LC display 12
2.D I 10 kΩ 10 kΩ 16
LED yellow/red: IN/
17 II
CH K
Input pulses/ 1 2 PWR 3- 18
OUT
11/2010
Accessories

fault signal 1 2
19+
3 4
ESC 400 Ω ≤ R ≤ 2 kΩ III
LED yellow: 4+ 20-
Output Ι ... IV
RS 232
OK
Keypad IV
II 10 kΩ 10 kΩ 21+
908837 (US) / 208599 (EU)

7 8 9 10 11 12 7- V
13 14 15 16 17 18 6- mA
19 20 21 22 23 24 8+
13+
14-
15+
23
Programming jack Removable terminals 24
AC/DC
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFU8-UFT-2.D

590 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Conductivity Switch Amplifier KFD2-ER-1.5

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 20 ... 30 V DC
• 24 V DC supply (Power Rail)
Input
Open circuit voltage/short-circuit approx. 10 V AC (approx. 1 Hz)/approx. 5 mA
• Level sensing input
current • Adjustable range 1 kΩ ... 30 kΩ
Control input min./max. control system: terminals 1, 2, 3 • Latching relay output

K-System
on/off control system: terminals 1, 3
• Minimum/maximum control
Response sensitivity 1 ... 30 kΩ, adjustable via potentiometer (20 turns)
Output
Function
Output 1 changeover contact
Contact loading 253 V AC/2 A/cos Φ > 0.7; 40 V DC/2 A resistive load
This signal conditioner provides the
Energized/De-energized delay approx. 1 s/approx. 1 s
AC measuring voltage for the level-
Ambient conditions
sensing electrodes.
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Once the measured medium reaches the
Protection degree IP20 electrodes, the unit reacts by energizing a
form C changeover relay contact.

Digital Inputs
Mass approx. 110 g
Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in), housing type B1 The module is voltage and temperature
stabilized and guarantees defined
switching characteristics. An electronic
holding circuit is used that allows
minimum/maximum control. Since the
conductance of the media may vary, the
relay response sensitivity is adjustable.

Digital Outputs
The normal output state can be reversed
through the mode of operation switch S1.

Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminal
green
KFD2-ER-1.5
1 2 3
4 5 6
2
7
3 8 KFD2-ER-1.5

9
1 LED green:
11/2010

Accessories

100 % LED yellow: OUT PWR Power supply


Relay output S1 I II

0% SENSITIVITY

Switch S1
908837 (US) / 208599 (EU)

Mode of operation
Potentiometer
Response sensitivity
7 8 9
10 11 12

11+
12-
24 V DC
Removable terminals
green
24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-ER-1.5

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 591
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD2-ER-1.6 Conductivity Switch Amplifier

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 20 ... 30 V DC
• 24 V DC supply (Power Rail)
Input
• Level sensing input Open circuit voltage/short-circuit approx. 10 V AC (approx. 1 Hz)/approx. 5 mA
• Adjustable range 5 kΩ ... 150 kΩ current
• Latching relay output Control input min./max. control system: terminals 1, 2, 3
K-System

on/off control system: terminals 1, 3


• Minimum/maximum control
Response sensitivity 5 ... 150 kΩ, adjustable via potentiometer (20 turns)
Output
Function
Output 1 changeover contact
Contact loading 253 V AC/2 A/cos Φ > 0.7; 40 V DC/2 A resistive load
This signal conditioner provides the
Energized/De-energized delay approx. 1 s/approx. 1 s
AC measuring voltage for the level-
Ambient conditions
sensing electrodes.
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Once the measured medium reaches the Mechanical specifications
electrodes, the unit reacts by energizing a Protection degree IP20
form C changeover relay contact.
Digital Inputs

Mass approx. 110 g


The module is voltage and temperature Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in), housing type B1
stabilized and guarantees defined
switching characteristics. An electronic
holding circuit is used that allows
minimum/maximum control. Since the
conductance of the media may vary, the
relay response sensitivity is adjustable.
Digital Outputs

The normal output state can be reversed


through the mode of operation switch S1.
Analog Inputs
Analog Outputs

Diagrams

Front view
Removable terminal
green
KFD2-ER-1.6
1 2 3
4 5 6
2
7
KFD2-ER-1.6 3 8
9
LED green: 1
11/2010
Accessories

LED yellow: OUT PWR Power supply 100 %


Relay output S1 I II

SENSITIVITY 0%
Switch S1
908837 (US) / 208599 (EU)

Mode of operation
Potentiometer
Response sensitivity
7 8 9
10 11 12

11+
12-
24 V DC
Removable terminals
green
24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-ER-1.6

592 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Conductivity Switch Amplifier KFA5-ER-1.5

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 103.5 ... 126 V AC, 45 ... 65 Hz
• 115 V AC supply
Power consumption approx. 0.8 W
Input
• Level sensing input
Open circuit voltage/short-circuit approx. 10 V AC (approx. 1 Hz)/approx. 5 mA • Adjustable range 1 kΩ ... 30 kΩ
current • Latching relay output

K-System
Control input min./max. control system: terminals 1, 2, 3 • Minimum/maximum control
on/off control system: terminals 1, 3
Response sensitivity 1 ... 30 kΩ, adjustable via potentiometer (20 turns)
Function
Output
Output 1 changeover contact
This signal conditioner provides the
Contact loading 253 V AC/2 A/cos Φ > 0.7; 40 V DC/2 A resistive load
AC measuring voltage for the level-
Energized/De-energized delay approx. 1 s/approx. 1 s
sensing electrodes.
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Once the measured medium reaches the
Mechanical specifications electrodes, the unit reacts by energizing a
form C changeover relay contact.

Digital Inputs
Protection degree IP20
Mass approx. 110 g The module is voltage and temperature
Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in), housing type B1 stabilized and guarantees defined
switching characteristics. An electronic
holding circuit is used that allows
minimum/maximum control. Since the
conductance of the media may vary, the
relay response sensitivity is adjustable.

Digital Outputs
The normal output state can be reversed
through the mode of operation switch S1.

Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminal
green
KFA5-ER-1.5
1 2 3
4 5 6
2
7
3 8 KFA5-ER-1.5
9
1
LED green:
11/2010

Accessories

100 % LED yellow: OUT PWR Power supply


Relay output S1 I II

0% SENSITIVITY

Switch S1
908837 (US) / 208599 (EU)

Mode of operation
Potentiometer
Response sensitivity
7 8 9
10 11 12

11
12
115 V AC
Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFA5-ER-1.5

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 593
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFA5-ER-1.6 Conductivity Switch Amplifier

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 103.5 ... 126 V AC, 45 ... 65 Hz
• 115 V AC supply
Power consumption approx. 0.8 W
• Level sensing input Input
• Adjustable range 5 kΩ ... 150 kΩ Open circuit voltage/short-circuit approx. 10 V AC (approx. 1 Hz)/approx. 5 mA
• Latching relay output current
K-System

• Minimum/maximum control Control input min./max. control system: terminals 1, 2, 3


on/off control system: terminals 1, 3
Response sensitivity 5 ... 150 kΩ, adjustable via potentiometer (20 turns)
Function
Output
Output 1 changeover contact
This signal conditioner provides the
Contact loading 253 V AC/2 A/cos Φ > 0.7; 40 V DC/2 A resistive load
AC measuring voltage for the level-
Energized/De-energized delay approx. 1 s/approx. 1 s
sensing electrodes.
Ambient conditions
Once the measured medium reaches the Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
electrodes, the unit reacts by energizing a Mechanical specifications
form C changeover relay contact.
Digital Inputs

Protection degree IP20


The module is voltage and temperature Mass approx. 110 g
stabilized and guarantees defined Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in), housing type B1
switching characteristics. An electronic
holding circuit is used that allows
minimum/maximum control. Since the
conductance of the media may vary, the
relay response sensitivity is adjustable.
Digital Outputs

The normal output state can be reversed


through the mode of operation switch S1.
Analog Inputs
Analog Outputs

Diagrams

Front view
Removable terminal
green
KFA5-ER-1.6
1 2 3
4 5 6
2
7
KFA5-ER-1.6 3 8
9
1
LED green:
11/2010
Accessories

LED yellow: OUT PWR Power supply 100 %


Relay output S1 I II

SENSITIVITY 0%
Switch S1
908837 (US) / 208599 (EU)

Mode of operation
Potentiometer
Response sensitivity
7 8 9
10 11 12

11
12
115 V AC
Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFA5-ER-1.6

594 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Conductivity Switch Amplifier KFA6-ER-1.5

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 207 ... 253 V AC, 45 ... 65 Hz
• 230 V AC supply
Power consumption approx. 0.8 W
Input
• Level sensing input
Open circuit voltage/short-circuit approx. 10 V AC (approx. 1 Hz)/approx. 5 mA • Adjustable range 1 kΩ ... 30 kΩ
current • Latching relay output

K-System
Control input min./max. control system: terminals 1, 2, 3 • Minimum/maximum control
on/off control system: terminals 1, 3
Response sensitivity 1 ... 30 kΩ, adjustable via potentiometer (20 turns)
Function
Output
Output 1 changeover contact
This signal conditioner provides the
Contact loading 253 V AC/2 A/cos Φ > 0.7; 40 V DC/2 A resistive load
AC measuring voltage for the level-
Energized/De-energized delay approx. 1 s/approx. 1 s
sensing electrodes.
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Once the measured medium reaches the
Mechanical specifications electrodes, the unit reacts by energizing a
form C changeover relay contact.

Digital Inputs
Protection degree IP20
Mass approx. 110 g The module is voltage and temperature
Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in), housing type B1 stabilized and guarantees defined
switching characteristics. An electronic
holding circuit is used that allows
minimum/maximum control. Since the
conductance of the media may vary, the
relay response sensitivity is adjustable.

Digital Outputs
The normal output state can be reversed
through the mode of operation switch S1.

Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminal
green
KFA6-ER-1.5
1 2 3
4 5 6
2
7
3 8 KFA6-ER-1.5
9
1
LED green:
11/2010

Accessories

100 % LED yellow: OUT PWR Power supply


Relay output S1 I II

0% SENSITIVITY

Switch S1
908837 (US) / 208599 (EU)

Mode of operation
Potentiometer
Response sensitivity
7 8 9
10 11 12

11
12
230 V AC
Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFA6-ER-1.5

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 595
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFA6-ER-1.6 Conductivity Switch Amplifier

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 207 ... 253 V AC, 45 ... 65 Hz
• 230 V AC supply
Power consumption approx. 0.8 W
• Level sensing input Input
• Adjustable range 5 kΩ ... 150 kΩ Open circuit voltage/short-circuit approx. 10 V AC (approx. 1 Hz)/approx. 5 mA
• Latching relay output current
K-System

• Minimum/maximum control Control input min./max. control system: terminals 1, 2, 3


on/off control system: terminals 1, 3
Response sensitivity 5 ... 150 kΩ, adjustable via potentiometer (20 turns)
Function
Output
Output 1 changeover contact
This signal conditioner provides the
Contact loading 253 V AC/2 A/cos Φ > 0.7; 40 V DC/2 A resistive load
AC measuring voltage for the level-
Energized/De-energized delay approx. 1 s/approx. 1 s
sensing electrodes.
Ambient conditions
Once the measured medium reaches the Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
electrodes, the unit reacts by energizing a Mechanical specifications
form C changeover relay contact.
Digital Inputs

Protection degree IP20


The module is voltage and temperature Mass approx. 110 g
stabilized and guarantees defined Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in), housing type B1
switching characteristics. An electronic
holding circuit is used that allows
minimum/maximum control. Since the
conductance of the media may vary, the
relay response sensitivity is adjustable.
Digital Outputs

The normal output state can be reversed


through the mode of operation switch S1.
Analog Inputs
Analog Outputs

Diagrams

Front view
Removable terminal
green
KFA6-ER-1.6
1 2 3
4 5 6
2
7
KFA6-ER-1.6 3 8
9
1
LED green:
11/2010
Accessories

LED yellow: OUT PWR Power supply 100 %


Relay output S1 I II

SENSITIVITY 0%
Switch S1
908837 (US) / 208599 (EU)

Mode of operation
Potentiometer
Response sensitivity
7 8 9
10 11 12

11
12
230 V AC
Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFA6-ER-1.6

596 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Conductivity Switch Amplifier KFD2-ER-1.W.LB

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 20 ... 30 V DC
• 24 V DC supply (Power Rail)
Input
Control input min./max. control system: terminals 1, 2, 3
• Level sensing input
on/off control system: terminals 1, 3 • Adjustable range 1 kΩ ... 150 kΩ
Response sensitivity 1 ... 150 kΩ, adjustable via potentiometer • Latching relay output

K-System
Output • Adjustable time delay up to 10 s
Switch power max. 192 W, 2000 VA
• Minimum/maximum control
Output relay
Contact loading 253 V AC/2 A/cos Φ > 0.7; 40 V DC/2 A resistive load • Line fault detection (LFD)
Time constant for signal damping 0.5 s, 2 s, 5 s, 10 s
Ambient conditions Function
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
This signal conditioner provides the
Protection degree IP20
AC measuring voltage for the level
Mass approx. 150 g
sensing electrodes.

Digital Inputs
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2 Once the measured medium reaches the
electrodes, the unit reacts by energizing a
form C changeover relay contact.
The module is voltage and temperature
stabilized and guarantees a defined
switching characteristic.
It can be used for on/off control or
minimum/maximum control. A signal

Digital Outputs
delay feature is available and is
adjustable between 0.5 s and 10 s.
This module can also monitor the field
circuit for lead breakage (LB). LB is
indicated by a red LED. If LB monitoring is
selected, output II serves as the fault
signal output; otherwise, it will follow the
function of output I.

Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminal
green
KFD2-ER-1.W.LB
7 1 2 3

I
4 5 6
2 8
9 LED green:
3 DIP switches S1
KFD2-ER-1.W.LB Power supply
430 kΩ 10
1 11 II
12
11/2010

Accessories

100 % LED yellow:


OUT CHK PWR

Relay output
sens.
0%
LED red: LB
908837 (US) / 208599 (EU)

Potentiometer
Response sensitivity
7 8 9
calibration 10 11 12
13 14 15

14+
15-
24 V DC
Removable terminals
green
24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-ER-
1.W.LB
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 597
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD2-ER-2.W.LB Conductivity Switch Amplifier

Features Technical data


• 2-channel signal conditioner Supply
Rated voltage 20 ... 30 V DC
• 24 V DC supply (Power Rail)
Input
• Level sensing input Control input min./max. control system: terminals 1, 2, 3; 4, 5. 6
• Adjustable range 1 kΩ ... 150 kΩ on/off control system: terminals 1, 3; 4, 6
• Latching relay output Response sensitivity 1 ... 150 kΩ, adjustable via potentiometer
K-System

• Adjustable time delay up to 10 s Output


Switch power max. 192 W, 2000 VA
• Minimum/maximum control
Output relay
• Line fault detection (LFD) Contact loading 253 V AC/2 A/cos Φ > 0.7; 40 V DC/2 A resistive load
Time constant for signal damping 0.5 s, 2 s, 5 s, 10 s
Function Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
This signal conditioner provides the Mechanical specifications
AC measuring voltage for the level Protection degree IP20
sensing electrodes. Mass approx. 150 g
Digital Inputs

Once the measured medium reaches the Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
electrodes, the unit reacts by energizing a
form C changeover relay contact.
The module is voltage and temperature
stabilized and guarantees a defined
switching characteristic.
It can be used for on/off control or
minimum/maximum control. A signal
Digital Outputs

delay feature is available and is


adjustable between 0.5 s and 10 s.
This module can also monitor the field
circuit for lead breakage (LB). LB is
indicated by a red LED. This function can
be deactivated with DIP switches.
Analog Inputs
Analog Outputs

Diagrams

Front view
Removable terminals
green
KFD2-ER-2.W.LB
1 2 3 7
4 5 6

LED green:
2 8 I
DIP switches S1/S2 9
KFD2-ER-2.W.LB Power supply I 3
430 kΩ 10
1
1 11 II
11/2010
Accessories

LED yellow:
OUT CHK PWR
100 % 12
2

Relay output Ι LED red: LB channel Ι


sens.1
LED yellow: 0%
sens.2
Relay output ΙΙ
908837 (US) / 208599 (EU)

5
Potentiometer LED red: LB channel ΙΙ
II 6
Response sensitivity 430 kΩ
7 8 9
calibration Ι 10 11 12 4
13 14 15
100 %
Potentiometer 14+
15-
24 V DC
Response sensitivity 0%
calibration ΙΙ Removable terminals
green
24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-ER-
2.W.LB
598 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Conductivity Switch Amplifier KFA5-ER-1.W.LB

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 103.5 ... 126 V AC, 45 ... 65 Hz
• 115 V AC supply
Power consumption < 1.2 W
Input
• Level sensing input
Control input min./max. control system: terminals 1, 2, 3 • Adjustable range 1 kΩ ... 150 kΩ
on/off control system: terminals 1, 3 • Latching relay output

K-System
Response sensitivity 1 ... 150 kΩ, adjustable via potentiometer • Adjustable time delay up to 10 s
Output
• Minimum/maximum control
Switch power max. 192 W, 2000 VA
Output relay • Line fault detection (LFD)
Contact loading 253 V AC/2 A/cos Φ > 0.7; 40 V DC/2 A resistive load
Time constant for signal damping 0.5 s, 2 s, 5 s, 10 s Function
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
This signal conditioner provides the
Mechanical specifications
AC measuring voltage for the level
Protection degree IP20
sensing electrodes.

Digital Inputs
Mass approx. 150 g Once the measured medium reaches the
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2 electrodes, the unit reacts by energizing a
form C changeover relay contact.
The module is voltage and temperature
stabilized and guarantees a defined
switching characteristic.
It can be used for on/off control or
minimum/maximum control. A signal

Digital Outputs
delay feature is available and is
adjustable between 0.5 s and 10 s.
This module can also monitor the field
circuit for lead breakage (LB). LB is
indicated by a red LED. If LB monitoring is
selected, output II serves as the fault
signal output; otherwise, it will follow the
function of output I.

Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminal
green
KFA5-ER-1.W.LB
7 1 2 3

I
4 5 6
2 8
9 LED green:
3 DIP switches S1
KFA5-ER-1.W.LB Power supply
430 kΩ 10
1 11 II
12
11/2010

Accessories

100 % LED yellow:


OUT CHK PWR

Relay output
sens.
0%
LED red: LB
908837 (US) / 208599 (EU)

Potentiometer
Response sensitivity
7 8 9
calibration 10 11 12
13 14 15

14
15
115 V AC
Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFA5-ER-
1.W.LB
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 599
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFA5-ER-2.W.LB Conductivity Switch Amplifier

Features Technical data


• 2-channel signal conditioner Supply
Rated voltage 103.5 ... 126 V AC, 45 ... 65 Hz
• 115 V AC supply
Power consumption < 1.2 W
• Level sensing input Input
• Adjustable range 1 kΩ ... 150 kΩ Control input min./max. control system: terminals 1, 2, 3; 4, 5. 6
• Latching relay output on/off control system: terminals 1, 3; 4, 6
K-System

• Adjustable time delay up to 10 s Response sensitivity 1 ... 150 kΩ, adjustable via potentiometer
Output
• Minimum/maximum control
Switch power max. 192 W, 2000 VA
• Line fault detection (LFD) Output relay
Contact loading 253 V AC/2 A/cos Φ > 0.7; 40 V DC/2 A resistive load
Function Time constant for signal damping 0.5 s, 2 s, 5 s, 10 s
Ambient conditions
This signal conditioner provides the Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
AC measuring voltage for the level Mechanical specifications
sensing electrodes. Protection degree IP20
Digital Inputs

Once the measured medium reaches the Mass approx. 150 g


electrodes, the unit reacts by energizing a Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
form C changeover relay contact.
The module is voltage and temperature
stabilized and guarantees a defined
switching characteristic.
It can be used for on/off control or
minimum/maximum control. A signal
Digital Outputs

delay feature is available and is


adjustable between 0.5 s and 10 s.
This module can also monitor the field
circuit for lead breakage (LB). LB is
indicated by a red LED. This function can
be deactivated with DIP switches.
Analog Inputs
Analog Outputs

Diagrams

Front view
Removable terminals
green
KFA5-ER-2.W.LB
1 2 3 7
I
4 5 6
2 8
LED green: 9
DIP switches S1/S2
KFA5-ER-2.W.LB Power supply I 3
430 kΩ 10
1
1 11 II
12
11/2010
Accessories

LED yellow: 2
OUT CHK PWR
100 %
Relay output Ι LED red: LB channel Ι
sens.1
LED yellow: 0%
sens.2
Relay output ΙΙ
908837 (US) / 208599 (EU)

5
Potentiometer LED red: LB channel ΙΙ
II 6
Response sensitivity 430 kΩ
7 8 9
calibration Ι 10 11 12 4
13 14 15
100 %
Potentiometer 14
15
115 V AC
Response sensitivity 0%
calibration ΙΙ Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFA5-ER-
2.W.LB
600 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Conductivity Switch Amplifier KFA6-ER-1.W.LB

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 207 ... 253 V AC, 45 ... 65 Hz
• 230 V AC supply
Power consumption < 1.2 W
Input
• Level sensing input
Control input min./max. control system: terminals 1, 2, 3 • Adjustable range 1 kΩ ... 150 kΩ
on/off control system: terminals 1, 3 • Latching relay output

K-System
Response sensitivity 1 ... 150 kΩ, adjustable via potentiometer • Adjustable time delay up to 10 s
Output
• Minimum/maximum control
Switch power max. 192 W, 2000 VA
Output relay • Line fault detection (LFD)
Contact loading 253 V AC/2 A/cos Φ > 0.7; 40 V DC/2 A resistive load
Time constant for signal damping 0.5 s, 2 s, 5 s, 10 s Function
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
This signal conditioner provides the
Mechanical specifications
AC measuring voltage for the level
Protection degree IP20
sensing electrodes.

Digital Inputs
Mass approx. 150 g Once the measured medium reaches the
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2 electrodes, the unit reacts by energizing a
form C changeover relay contact.
The module is voltage and temperature
stabilized and guarantees a defined
switching characteristic.
It can be used for on/off control or
minimum/maximum control. A signal

Digital Outputs
delay feature is available and is
adjustable between 0.5 s and 10 s.
This module can also monitor the field
circuit for lead breakage (LB). LB is
indicated by a red LED. If LB monitoring is
selected, output II serves as the fault
signal output; otherwise, it will follow the
function of output I.

Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminal
green
KFA6-ER-1.W.LB
7 1 2 3

I
4 5 6
2 8
9 LED green:
3 DIP switches S1
KFA6-ER-1.W.LB Power supply
430 kΩ 10
1 11 II
12
11/2010

Accessories

100 % LED yellow:


OUT CHK PWR

Relay output
sens.
0% LED red: LB
908837 (US) / 208599 (EU)

Potentiometer
Response sensitivity
7 8 9
calibration 10 11 12
13 14 15

14
15
230 V AC
Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFA6-ER-
1.W.LB
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 601
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFA6-ER-2.W.LB Conductivity Switch Amplifier

Features Technical data


• 2-channel signal conditioner Supply
Rated voltage 207 ... 253 V AC, 45 ... 65 Hz
• 230 V AC supply
Power consumption < 1.2 W
• Level sensing input Input
• Adjustable range 1 kΩ ... 150 kΩ Control input min./max. control system: terminals 1, 2, 3; 4, 5. 6
• Latching relay output on/off control system: terminals 1, 3; 4, 6
K-System

• Adjustable time delay up to 10 s Response sensitivity 1 ... 150 kΩ, adjustable via potentiometer
Output
• Minimum/maximum control
Switch power max. 192 W, 2000 VA
• Line fault detection (LFD) Output relay
Contact loading 253 V AC/2 A/cos Φ > 0.7; 40 V DC/2 A resistive load
Function Time constant for signal damping 0.5 s, 2 s, 5 s, 10 s
Ambient conditions
This signal conditioner provides the Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
AC measuring voltage for the level Mechanical specifications
sensing electrodes. Protection degree IP20
Digital Inputs

Once the measured medium reaches the Mass approx. 150 g


electrodes, the unit reacts by energizing a Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
form C changeover relay contact.
The module is voltage and temperature
stabilized and guarantees a defined
switching characteristic.
It can be used for on/off control or
minimum/maximum control. A signal
Digital Outputs

delay feature is available and is


adjustable between 0.5 s and 10 s.
This module can also monitor the field
circuit for lead breakage (LB). LB is
indicated by a red LED. This function can
be deactivated with DIP switches.
Analog Inputs
Analog Outputs

Diagrams

Front view
Removable terminals
green
KFA6-ER-2.W.LB
1 2 3 7
I
4 5 6
2 8
LED green: 9
DIP switches S1/S2
KFA6-ER-2.W.LB Power supply I 3
430 kΩ
1
1
11/2010
Accessories

LED yellow: 2
OUT CHK PWR
100 %
Relay output Ι LED red: LB channel Ι
sens.1
LED yellow: 0%
sens.2
Relay output ΙΙ 10
908837 (US) / 208599 (EU)

5 11 II
LED red: LB channel ΙΙ 12
Potentiometer II 6
Response sensitivity 430 kΩ
7 8 9
calibration Ι 10 11 12 4
13 14 15
100 %
Potentiometer 14
15
230 V AC
Response sensitivity 0%
calibration ΙΙ Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFA6-ER-
2.W.LB
602 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Signal Conditioners Selection Tables
Solenoid Drivers

Model Number Input Output (Field) Page


(Control System)

Max. Current (mA)

Supply 24 V DC
Loop Powered

Logic Input

Voltage (V)

K-System
Channels

SIL
KFD2-SL-4 4  24 600  2 604

Relay Outputs

Model Number Input Output (Field) Supply Page

Digital Inputs
(Control System)

Immune to DCS Test Pulses

DTS (De-energized to Safe)

DPS (Dual Pole Switching)


ETS (Energized to Safe)
Loop Powered

Loop Powered
Logic Input
Channels

Digital Outputs
24 V DC
Relay

SIL
KFD0-RSH-1 1   1   3 605

KFD0-RSH-1.4S.PS2 1   Yokogawa 2     3 606

KFD0-RSH-1-Y2 1   Triconex 1   3 607

Analog Inputs
Analog Outputs
11/2010

Accessories
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 603
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD2-SL-4 Solenoid Driver, Power Amplifier

Features Technical data


• 4-channel signal conditioner Supply
Rated voltage 20 ... 30 V DC
• 24 V DC supply (Power Rail)
Input
• Output 600 mA per channel Input current approx. 2 mA at 24 V DC
• Logic inputs Signal level 0-signal: 0 ... 5 V DC
• Common disable input 1-signal: 16 ... 30 V
K-System

• Line fault detection (LFD) Comon disable


Input current ≤ 50 mA at 24 V, depolarized
• Up to SIL2 acc. to IEC 61508 currentless state: downscale of the outputs
Switch on ≥ 15 V
Function Switch off ≤5 V
Output
This signal conditioner is a 4-channel
Open loop voltage 24 V DC
barrier with outputs that switch 600 mA to
Switching frequency f 1 kHz
high-power solenoids. It is also used as
Output rated operating current 600 mA, sustained short-circuit proof and
power amplifier up to a switching overload-proof
frequency of 1 kHz.
Digital Inputs

Off-state current Ir < 1 mA at 24 V DC


Two channels per module can be Ambient conditions
paralleled. The output current of a parallel Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
combination is 1.2 A. If the supply voltage Mechanical specifications
falls below 18 V, the outputs will be Protection degree IP20
switched off. Mass approx. 100 g
The outputs are sustained short-circuit Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
proofed and overload-proofed.
Digital Outputs

Lead breakage and short circuit, which is


selected via DIP switch, is indicated by a
red LED and through the collective error
output via Power Rail.
With the common disable input
(terminals 11 and 12), the auxiliary power
for all 4 channels can be switched off
simultaneously. This central switch-off is
also indicated by a red LED and reported
Analog Inputs

as an error signal to the Power Rail.


Analog Outputs

Diagrams

Front view Removable terminals


green

KFD2-SL-4
Lead monitoring switch
1 2 3
4 5 6 S1 up to S4
7+ I
I 1+
KFD2-SL-4

8+ II
II 2+
11/2010
Accessories

1 2 PWR
LED green:
LED yellow/red: Channel I-IV 3 4 OFF Power supply 9+ III
Switching status/ III 3+
Fault signal
IV
908837 (US) / 208599 (EU)

LED red: 10+


IV 4+
Common disable
11
7 8 9 V V
10 11 12 5- 12
13 14 15

14+ 24 V DC
6- 15-

Removable terminals ERR 24 V DC


green Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-SL-4

604 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Relay Module KFD0-RSH-1

Technical data Features


Supply • 1-channel signal conditioner
Power loss < 1.5 W
• 24 V DC supply (loop powered)
Power consumption < 1.5 W
Input
• Fail-safe relay contact output
Pulse/Pause ratio ≥ 20 ms/≥ 20 ms • Logic input 16 V DC ... 30 V DC,
non-polarized

K-System
Signal level 0-signal: 0 ... 5 V DC
1-signal: 16 ... 30 V • Up to SIL3 acc. to IEC 61508
Rated current Ii approx. 50 mA
Output Function
Contact loading 230 V AC/2 A/cos Φ 0.7; 40 V DC/2 A resistive load
Minimum switch current 2 mA/24 V DC This signal conditioner is a relay module
Energized/De-energized delay approx. 10 ms/approx. 5 ms that is suitable for safely switching
Mechanical life 5 x 106 switching cycles applications of a load circuit. The device
Transfer characteristics isolates load circuits up to 230 V and the
Switching frequency < 10 Hz 24 V control interface.
Ambient conditions The output is galvanically isolated from

Digital Inputs
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
the input and is protected against contact
Mechanical specifications welding by a fuse.
Protection degree IP20
Mass approx. 100 g
The three relays are of diverse design, but
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
have a common effect on the switch
output.

Digital Outputs
Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminal
green
KFD0-RSH-1
1 2 3
4 5 6

LED yellow:
KFD0-RSH-1
Relay output
2 7
11/2010

Accessories

OUT

V 24 V
3 8 (+/–)
908837 (US) / 208599 (EU)

7 8 9
10 11 12
13 14 15

Removable terminal
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD0-RSH-1

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 605
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD0-RSH-1.4S.PS2 Relay Module

Features Technical data


• 1-channel signal conditioner Supply
Power loss < 1.5 W
• 24 V DC supply (loop powered)
Power consumption < 1.5 W
• Fail-safe relay contact output for Input
de-energized and energized to safe Pulse/Pause ratio ≥ 20 ms/≥ 20 ms
function
K-System

Test input see Safety Manual


• Logic input 20 V DC ... 26.5 V DC, Signal level 0-signal: -3 ... 3 V DC
non-polarized 1-signal: 20 ... 26.5 V
• Immune to DCS test pulses Rated current Ii 45 ... 50 mA
(Yokogawa) Output
• Up to SIL3 acc. to IEC 61508 Contact loading 230 V AC/5 A/cos Φ 0.7; 24 V DC/5 A resistive load
Minimum switch current 2 mA/24 V DC
Function Energized/De-energized delay approx. 10 ms/approx. 5 ms
Mechanical life 5 x 106 switching cycles
This signal conditioner is a relay module Electrical life 2.5 x 105 switching cycles at 2 A
1 x 104 switching cycles at 5 A
that is suitable for safely switching
Digital Inputs

Fuse rating 2.5 A (max. 5 A)


applications of a load circuit. The device
recommended maximum utilization of the fuse: 80 %
isolates load circuits up to 230 V and the
Transfer characteristics
24 V control interface.
Switching frequency < 10 Hz
The energized to safe (ETS) function is Ambient conditions
permitted for SIL3 applications with Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
output I. The de-energized to safe (DTS) Mechanical specifications
function is permitted for SIL3 applications Protection degree IP20
with output II. Additionally a dual pole Mass approx. 100 g
Digital Outputs

switching (DPS) is possible by Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
combination of output I and II.
The relays are of diverse design, but have
a common effect on the individual switch
output. For checking of these relays,
terminals 10, 11 and 12 can be used. The
test mode will be indicated by LEDs
according to NAMUR NE44.
Analog Inputs

The outputs are galvanically isolated from


the input. Output II is protected against
contact welding by a fuse depending on
the used terminal.
Analog Outputs

Diagrams

Front view
Removable terminals
green
KFD0-RSH-1.4S.PS2
1 2 3
4 5 6

LED yellow: DPS DTS ETS


KFD0-RSH-1.4S.PS2
Relay output
max 5A 2 7
LED red: V I
11/2010
Accessories

Test 1 3
!
LED red: 24 V
Fuse carrier V
Test 2
OUT TST1 TST2
4 8 (+/–)
908837 (US) / 208599 (EU)

V II 5 10
7 8 9
6 12
10 11 12 Test 1
13 14 15 Test 2
11

Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD0-RSH-
1.4S.PS2
606 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Relay Module KFD0-RSH-1-Y2

Technical data Features


Supply • 1-channel signal conditioner
Power loss < 1.5 W
• 24 V DC supply (loop powered)
Power consumption < 1.5 W
Input
• Fail-safe relay contact output
Pulse/Pause ratio ≥ 35 ms/≥ 35 ms • Logic input 20 V DC ... 30 V DC,
non-polarized

K-System
Pulse/Pause ratio test pulse < 10 %
Test pulse length max. 2 ms • Immune to DCS test pulses
Signal level 0-signal: 0 ... 5 V DC (Triconex)
1-signal: 20 ... 30 V
• Up to SIL3 acc. to IEC 61508
Rated current Ii approx. 58 mA
Output Function
Contact loading 230 V AC/2 A/cos Φ 0.7; 40 V DC/2 A resistive load
Minimum switch current 2 mA/24 V DC This signal conditioner is a relay module
Energized/De-energized delay 5 ... 15 ms/5 ... 10 ms that is suitable for safely switching
Mechanical life 5 x 106 switching cycles applications of a load circuit. The device
Electrical life 2.5 x 105 switching cycles, at maximium load isolates load circuits up to 230 V and the

Digital Inputs
Transfer characteristics 24 V control interface.
Switching frequency < 10 Hz
The output is galvanically isolated from
Ambient conditions
the input and is protected against contact
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
welding by a fuse.
Mechanical specifications
Protection degree IP20 The three relays are of diverse design, but
Mass approx. 100 g have a common effect on the switch
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2 output.

Digital Outputs
Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminal
green
KFD0-RSH-1-Y2
1 2 3
4 5 6

LED yellow:
KFD0-RSH-1-Y2
Relay output
2 7
11/2010

Accessories

OUT

V 24 V
3 8 (+/–)
908837 (US) / 208599 (EU)

7 8 9
10 11 12
13 14 15

Removable terminal
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD0-RSH-1-Y2

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 607
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Notes Signal Conditioners
K-System
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs

11/2010
Accessories

908837 (US) / 208599 (EU)


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


608 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Signal Conditioners Selection Tables
Transmitter Power Supplies

Model Number Input (Field) Output Specials Supply Page


(Control System)

(1 Input – 2 Outputs)
2-wire Transmitter

3-wire Transmitter

0/4 mA ... 20 mA

0/4 mA ... 20 mA
Current Source

Signal Splitting

K-System
0/2 V ... 10 V

0/2 V ... 10 V

115 V AC/
Channels

1 V ... 5 V

230 V AC
(Source)

24 V DC
SMART
(Sink)

SIL
KCD2-STC-1 1     1   2 612

KFD2-STC4-1 1    1   2 613

KFD2-STC4-1-3 1    1   2 614

KFD2-STV4-1-1 1    1   2 615

Digital Inputs
KFD2-CR4-1 1    1  2 616

KFD2-STC4-1.2O 1    2    3 617

KFD2-STC4-1.2O-3 1    2    3 618

KFD2-CR4-1.2O 1    2   3 619

KFU8-VCR-1 1          620

Digital Outputs
KFD2-STC4-2 2  2   2 621

KFD2-STC4-2-3 2  2   2 622

KFD2-STV4-2-1 2  2   2 623

KFD2-CR4-2 2  2  2 624

Transmitter Power Supplies with Trip Values

Analog Inputs
Model Number Input (Field) Output Supply Page
(Control System)
2-wire Transmitter

3-wire Transmitter

0/4 mA ... 20 mA
Current Source

115 V AC/
Channels

230 V AC
(Source)

24 V DC
SMART
Relay

Analog Outputs
SIL

KFD2-CRG2-1.D 1    1 2  2 625

KFU8-CRG2-1.D 1    1 2   2 626
11/2010

Accessories
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 609
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Selection Tables Signal Conditioners

Current Repeaters

Model Number Input (Field) Output Page


(Control System)

Loop Powered
0 mA ... 40 mA

1 mA ... 20 mA

4 mA ... 20 mA

0 mA ... 40 mA

4 mA ... 20 mA
Fire Alarm
Channels

SMART

Supply
K-System

SIL
KFD0-SCS-1.55 1  1   2 627

KFD0-CS-1.50 1   1  2 628

KFD0-CS-2.50 2   2  2 629

KFD0-CS-2.51P 2   2  2 630
Digital Inputs

Current and Voltage Converters

Model Number Input (Field) Output Supply Page


(Control System)

0/4 mA ... 20 mA
0/4 mA ... 20 mA

Loop Powered
Strain Gauge
-10 V ... 10 V

0/2 V ... 10 V

0/2 V ... 10 V
0/1 V ... 5 V

115 V AC/
Channels

230 V AC
24 V DC
Digital Outputs

Relay
mV

SIL
KFD0-CC-1 1   1  631

KFD2-USC-1.D 1      1  632

KFU8-USC-1.D 1      1   633

KFD2-GS-1.2W 1   2  634
Analog Inputs

KFD2-WAC2-1.D 1   1 2  635

KFD0-VC-1.10 1  1  636

Temperature Converters and Repeaters

Model Number Input (Field) Output Supply Page


(Control System)
Analog Outputs

0/4 mA ... 20 mA

Loop Powered
Potentiometer

Resistance
0/1 V ... 5 V
Channels

24 V DC
RTD

SIL
TC

KFD2-UT2-1 1     1  2 637

KFD2-UT2-1-1 1     1  2 638
11/2010
Accessories

KFD2-UT2-2 2     2  2 639

    
908837 (US) / 208599 (EU)

KFD2-UT2-2-1 2 2 2 640

KFD0-TR-1 1  1  641

KFD0-TT-1 1  1  642
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


610 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Signal Conditioners Selection Tables
Temperature Converters with Trip Values

Model Number Input (Field) Output Supply Page


(Control System)

4 mA ... 20 mA
Potentiometer

115 V AC/
Channels

230 V AC
24 V DC

K-System
Relay
RTD

mA

SIL
TC

V
KFD2-GU-1 1     2  643

KFD2-GUT-1.D 1     1 2  2 644

KFU8-GUT-1.D 1     1 2   2 645

Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs
11/2010

Accessories
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 611
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KCD2-STC-1 SMART Transmitter Power Supply

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 19 ... 30 V DC
• 24 V DC supply (Power Rail)
Power consumption ≤ 1.1 W
• Input 2-wire SMART transmitters and Input
2-wire SMART current sources Input signal 4 ... 20 mA limited to approx. 30 mA
• Output 4 mA ... 20 mA or 1 V ... 5 V
K-System

Voltage drop Ud approx. 5 V on terminals 3+, 4-


• Sink or source mode Available voltage ≥ 15 V at 20 mA terminals 1+, 2-
• Housing width 12.5 mm Output
Load 0 ... 300 Ω (source mode)
• Up to SIL2 acc. to IEC 61508
Output signal 4 ... 20 mA or 1 ... 5 V (on 250 Ω, 0.1 % internal shunt)
4 ... 20 mA (sink mode), operating voltage 15.5 ... 26 V
Function
Ripple 20 mVrms
Transfer characteristics
This signal conditioner provides the
Deviation at 20 °C (68 °F)
isolation for non-intrinsically safe
≤ ± 0.1 % incl. non-linearity and hysteresis
applications. (source mode 4 ... 20 mA)
≤ ± 0.2 % incl. non-linearity and hysteresis
Digital Inputs

The device supplies 2-wire SMART


transmitters, and can also be used with 2- (sink mode 4 ... 20 mA)
≤ ± 0.2 % incl. non-linearity and hysteresis
wire SMART current sources.
(source mode 1 ... 5 V)
It transfers the analog input signal as an Influence of ambient temperature < 2 μA/K (0 ... 60 °C (32 ... 140 °F)); < 4 μA/K
isolated current value. (-20 ... 0 °C (-4 ... 32 °F))
(source mode and sink mode 4 ... 20 mA)
Digital signals may be superimposed on
< 0.5 mV/K (0 ... +60 °C (32 ... 140 °F)); < 1 mV/K
the input signal and are transferred bi- (-20 ... 0 °C (-4 ... 32 °F))
directionally. (source mode 1 ... 5 V)
Digital Outputs

Selectable output of current source, sink Frequency range bandwidth at 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
mode, or voltage output is available via Rise time 10 to 90 % ≤ 20 ms
DIP switches. Ambient conditions
If the HART communication resistance in Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
the loop is too low, the internal resistance Mechanical specifications
of 250 Ω between terminals 6 and 8 can Protection degree IP20
be used. Mass approx. 100 g
Dimensions 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 in),
Test sockets for the connection of HART housing type A2
Analog Inputs

communicators are integrated into the


terminals of the device.
Analog Outputs

Diagrams

Front view
Removable terminals
green

KCD2-STC-1

LED green:
1 2
3 4 Power supply 1+
HART

KCD2-STC-1 7-
11/2010
Accessories

PWR 2- 5-
HART

3+ V
6+
HART

S1
mA 8+
908837 (US) / 208599 (EU)

S2
S3
S4
I II 4-
Switch 1 ... 4

5 6
7 8
Place for labeling 9+
9 10
10-
24 V DC

Removable terminals 24 V DC
green Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KCD2-STC-1

612 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SMART Transmitter Power Supply KFD2-STC4-1

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 20 ... 35 V DC
• 24 V DC supply (Power Rail)
Power consumption 1.9 W
Input
• Input 2-wire and 3-wire SMART
Input signal 0/4 ... 20 mA transmitters and 2-wire SMART
≤ 2.4 V at 20 mA (terminals 5, 6)
current sources

K-System
Voltage drop Ud
Input resistance ≤ 64 Ω terminals 2-, 3; • Output 0/4 mA ... 20 mA
≤ 500 Ω terminals 1+, 3 (250 Ω load) • Terminals with test points
Available voltage ≥ 16 V at 20 mA, terminals 1+, 3 • Up to SIL2 acc. to IEC 61508
Output
Load 0 ... 800 Ω Function
Output signal 4 ... 20 mA (overload > 25 mA)
Ripple ≤ 50 μArms This signal conditioner provides the
Transfer characteristics isolation for non-intrinsically safe
Deviation at 20 °C (68 °F), 0/4 ... 20 mA applications.
≤ 10 μA incl. calibration, linearity, hysteresis, loads and
The device supplies 2-wire and 3-wire

Digital Inputs
fluctuations of supply voltage
Influence of ambient temperature ≤ 20 ppm/K SMART transmitters, and can also be
Frequency range input to output: used with 2-wire SMART current sources.
bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB) It transfers the analog input signal as an
output to input: isolated current value.
bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB)
Start-up time 200 μs Digital signals may be superimposed on
Ambient conditions the input signal and are transferred bi-
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) directionally.

Digital Outputs
Mechanical specifications If the HART communication resistance in
Protection degree IP20 the loop is too low, the internal resistance
Mass approx. 200 g of 250 Ω between terminals 8 and 9 can
Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in), housing type B2 be used.
Test sockets for the connection of HART
communicators are integrated into the
terminals of the device.

Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminals
green

KFD2-STC4-1

1+ 7- 1 2 3
4 5 6
HART

HART

2- 8+ KFD2-STC4-1
11/2010

Accessories

mA LED green:
3 9 PWR

250 Ω Power supply

5-
908837 (US) / 208599 (EU)

HART

mA
7 8 9
10 11 12
13 14 15
6+ 14+
15-
24 V DC

Removable terminals
24 V DC green
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-STC4-1

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 613
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD2-STC4-1-3 SMART Transmitter Power Supply, Output Current

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 20 ... 35 V DC
• 24 V DC supply (Power Rail)
Power consumption 2.5 W
• Input 2-wire and 3-wire SMART Input
transmitters and 2-wire SMART Input signal 0/4 ... 20 mA
current sources ≤ 2.4 V at 20 mA (terminals 5, 6)
K-System

Voltage drop Ud
• 0/4 mA ... 20 mA current sink output Input resistance ≤ 64 Ω terminals 2-, 3;
• Terminals with test points ≤ 500 Ω terminals 1+, 3 (250 Ω load)
• Up to SIL2 acc. to IEC 61508 Available voltage ≥ 16 V at 20 mA terminals 1+, 3
Output
Function Output signal 0/4 ... 20 mA (overload > 25 mA)
Ripple ≤ 50 μArms
This signal conditioner provides the External supply (loop) 11 ... 30 V DC
isolation for non-intrinsically safe Transfer characteristics
applications. Deviation at 20 °C (68 °F), 0/4 ... 20 mA
≤ 10 μA incl. calibration, linearity, hysteresis, loads and
The device supplies 2-wire and 3-wire
Digital Inputs

fluctuations of supply voltage


SMART transmitters, and can also be Influence of ambient temperature 0.25 μA/K
used with 2-wire SMART current sources. Frequency range input to output:
It transfers the analog input signal as an bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB)
isolated current value. output to input:
bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB)
Digital signals may be superimposed on Rise time 20 μs
the input or output signal and are Start-up time 200 μs
transferred bi-directionally. Ambient conditions
Digital Outputs

It is designed to provide a sink mode Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
output. Mechanical specifications
If the HART communication resistance in Protection degree IP20
the loop is too low, the internal resistance Mass approx. 200 g
of 250 Ω between terminals 8 and 9 can Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in), housing type B2
be used.
Test sockets for the connection of HART
communicators are integrated into the
terminals of the device.
Analog Inputs
Analog Outputs

Diagrams

Front view
Removable terminals
green

KFD2-STC4-1-3

1 2 3 1+ 7+
4 5 6
HART

V
HART

KFD2-STC4-1-3 2- 8-
11/2010
Accessories

LED green: mA
PWR
3 9
Power supply 250 Ω

5-
908837 (US) / 208599 (EU)
HART

mA
7 8 9
10 11 12
13 14 15
6+ 14+
15-
24 V DC

Removable terminals
green 24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-STC4-1-3

614 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SMART Transmitter Power Supply KFD2-STV4-1-1

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 20 ... 35 V DC
• 24 V DC supply (Power Rail)
Power consumption 1.9 W
Input
• Input 2-wire and 3-wire SMART
Input signal 0/4 ... 20 mA transmitters and 2-wire SMART
≤ 2.4 V at 20 mA (terminals 5, 6)
current sources

K-System
Voltage drop Ud
Input resistance ≤ 64 Ω terminals 2-, 3; • Output 0/1 V ... 5 V
≤ 500 Ω terminals 1+, 3 (250 Ω load) • Terminals with test points
Available voltage ≥ 16 V at 20 mA terminals 1+, 3 • Up to SIL2 acc. to IEC 61508
Output
Load output resistance: 250 Ω Function
Output signal 0/1 ... 5 V
Ripple ≤ 12.5 mV This signal conditioner provides the
Transfer characteristics isolation for non-intrinsically safe
Deviation at 20 °C (68 °F), 0/1 ... 5 V ≤ 5 mV incl. calibration, applications.
linearity, hysteresis, loads and fluctuations of supply
The device supplies 2-wire and 3-wire

Digital Inputs
voltage
Influence of ambient temperature ≤ 20 ppm/K SMART transmitters, and can also be
Frequency range hazardous area into the safe area: used with 2-wire SMART current sources.
bandwidth with 0.5 Vpp 0 ... 7.5 kHz (-3 dB) It transfers the analog input signal as an
safe area into the hazardous area: isolated voltage value.
bandwidth with 0.5 Vpp 0.3 ... 7.5 kHz (-3 dB)
Rise time 20 μs Digital signals may be superimposed on
Start-up time 200 μs the input signal and are transferred bi-
De-energized delay 20 μs directionally.

Digital Outputs
Ambient conditions If the HART communication resistance in
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) the loop is too low, the internal resistance
Mechanical specifications of 250 Ω between terminals 8 and 9 can
Protection degree IP20 be used.
Mass approx. 200 g Test sockets for the connection of HART
Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in), housing type B2 communicators are integrated into the
terminals of the device.

Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminals
green

KFD2-STV4-1-1

1+ 7- 1 2 3
4 5 6
HART

HART

2- 8+ KFD2-STV4-1-1
11/2010

Accessories

mA LED green:
3 9 PWR

250 Ω Power supply

5-
908837 (US) / 208599 (EU)

HART

mA
7 8 9
10 11 12
13 14 15
6+ 14+
15-
24 V DC

Removable terminals
24 V DC green
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-STV4-1-1

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 615
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD2-CR4-1 Transmitter Power Supply

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 20 ... 35 V DC
• 24 V DC supply (Power Rail)
Power consumption 1.6 W
• Input 2-wire and 3-wire transmitters Input
and 2-wire current sources Input signal 0/4 ... 20 mA
• Output 0/4 mA ... 20 mA ≤ 64 Ω terminals 2-, 3;
K-System

Input resistance
• Accuracy 0.1 % ≤ 500 Ω terminals 1+, 3 (250 Ω load)
• Up to SIL2 acc. to IEC 61508 Available voltage ≥ 15.7 V at 20 mA terminals 1+, 3
Ripple 50 mVpp at 20 mA
Function Output
Load 0 ... 800 Ω
This signal conditioner provides the Output signal 0/4 ... 20 mA
isolation for non-intrinsically safe Ripple ≤ 50 μArms
applications. Transfer characteristics
Deviation at 20 °C (68 °F), 0/4 ... 20 mA
The device supplies 2-wire and 3-wire ≤ 10 μA incl. calibration, linearity, hysteresis, loads and
transmitters, and can also be used with 2-
Digital Inputs

fluctuations of supply voltage


wire current sources. Influence of ambient temperature 0.25 μA/K
It transfers the analog input signal as an Rise time 20 μs
isolated current value. Start-up time 200 μs
De-energized delay 20 μs
The output provides a 0/4 mA ... 20 mA
Ambient conditions
current corresponding to the input signal.
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
The minimum available field voltage is
Mechanical specifications
16 V at 20 mA.
Protection degree IP20
Digital Outputs

If necessary, the internal resistance of Mass approx. 150 g


250 Ω between terminals 8, 9 can be Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
used for conversion into a 0 V ... 5 V
voltage signal.
Analog Inputs
Analog Outputs

Diagrams

Front view
Removable terminal
green
KFD2-CR4-1
1 2 3
4 5 6

1+ 7-
KFD2-CR4-1 8+
9
2- 250 Ω
11/2010
Accessories

PWR LED green:


mA
Power supply
3
908837 (US) / 208599 (EU)

7 8 9
10 11 12
13 14 15

14+
15-
24 V DC
Removable terminals
green
24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-CR4-1

616 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SMART Transmitter Power Supply KFD2-STC4-1.2O

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 20 ... 35 V DC
• 24 V DC supply (Power Rail)
Power consumption 2.5 W
Input
• Input 2-wire and 3-wire SMART
Input signal 0/4 ... 20 mA transmitters and 2-wire SMART
≤ 2.4 V at 20 mA (terminals 5, 6)
current sources

K-System
Voltage drop Ud
Input resistance ≤ 76 Ω terminals 2-, 3; • Dual output 0/4 mA ... 20 mA
≤ 500 Ω terminals 1+, 3 (250 Ω load) • Terminals with test points
Available voltage ≥ 16 V at 20 mA, terminals 1+, 3 • Up to SIL3 acc. to IEC 61508
Ripple 0
Output Function
Load 0 ... 550 Ω
Output signal 0/4 ... 20 mA (overload > 25 mA) This signal conditioner provides the
Ripple ≤ 50 μArms isolation for non-intrinsically safe
Transfer characteristics applications.
Deviation at 20 °C (68 °F), 0/4 ... 20 mA
The device supplies 2-wire and 3-wire

Digital Inputs
≤ ± 10 μA incl. calibration, linearity, hysteresis, loads
and supply voltage fluctuations SMART transmitters, and can also be
Influence of ambient temperature ≤ 20 ppm/K used with 2-wire SMART current sources.
Frequency range Input in output: It transfers the analog input signal to the
bandwidth with 1 mApp signal 0 ... 7.5 kHz (-3 dB) safe area as two isolated current values.
output in input:
band width with 1 Vpp signal 0.3 ... 7.5 kHz (-3 dB) Digital signals may be superimposed on
Rise time 20 μs the input signal and are transferred bi-
Start-up time 200 μs directionally.

Digital Outputs
De-energized delay 20 μs If the HART communication resistance in
Ambient conditions the loop is too low, the internal resistance
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) of 250 Ω between terminals 8, 9
Mechanical specifications and 11, 12 can be used.
Protection degree IP20 Test sockets for the connection of HART
Mass approx. 200 g communicators are integrated into the
Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in), housing type B2 terminals of the device.

Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminals
green

KFD2-STC4-1.2O

1+ 7- 1 2 3
4 5 6
HART

I
HART

2- 8+ KFD2-STC4-1.2O
11/2010

9
Accessories

mA 250 Ω LED green:


3 PWR

Power supply
10-
5-
HART
908837 (US) / 208599 (EU)

II
11+
HART

12
mA 250 Ω 7 8 9
10 11 12
13 14 15
6+ 14+
15-
24 V DC

Removable terminals
24 V DC green
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-STC4-
1.2O
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 617
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD2-STC4-1.2O-3 SMART Transmitter Power Supply, Output Current Sink

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 20 ... 35 V DC
• 24 V DC supply (Power Rail)
Power consumption 2.5 W
• Input 2-wire and 3-wire SMART Input
transmitters and 2-wire SMART Input signal 0/4 ... 20 mA
current sources ≤ 2.4 V at 20 mA (terminals 5, 6)
K-System

Voltage drop Ud
• Dual output 0/4 mA ... 20 mA Input resistance ≤ 76 Ω terminals 2-, 3;
• Terminals with test points ≤ 500 Ω terminals 1+, 3 (250 Ω load)
• Up to SIL3 acc. to IEC 61508 Available voltage ≥ 16 V at 20 mA terminals 1+, 3
Output
Function Output signal 0/4 ... 20 mA (overload > 25 mA)
Ripple ≤ 50 μArms
This signal conditioner provides the External supply (loop) 11 ... 30 V DC
isolation for non-intrinsically safe Transfer characteristics
applications. Deviation at 20 °C (68 °F), 0/4 ... 20 mA
≤ 10 μA incl. calibration, linearity, hysteresis, loads and
The device supplies 2-wire and 3-wire
Digital Inputs

fluctuations of supply voltage


SMART transmitters, and can also be Influence of ambient temperature 0.25 μA/K
used with 2-wire SMART current sources. Frequency range input to output:
It transfers the analog input signal as two bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB)
isolated current values. output to input:
bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB)
Digital signals may be superimposed on Rise time 20 μs
the input or the output signals and are Start-up time 200 μs
transferred bi-directionally. Ambient conditions
Digital Outputs

It is designed to provide sink mode Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
outputs. Mechanical specifications
If the HART communication resistance in Protection degree IP20
the loop is too low, the internal resistance Mass approx. 200 g
of 250 Ω between terminals 8, 9 Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in), housing type B2
and 11, 12 can be used.
Test sockets for the connection of HART
communicators are integrated into the
terminals of the device.
Analog Inputs
Analog Outputs

Diagrams

Front view
Removable terminals
green

KFD2-STC4-1.2O-3

1 2 3 1+ 7+
4 5 6
HART

I
HART

V
KFD2-STC4-1.2O-3 2- 8-
11/2010

9
Accessories

LED green: mA 250 Ω


PWR
3
Power supply
10+
5-
HART

908837 (US) / 208599 (EU)

V II
11-
HART

12
mA 250 Ω
7 8 9
10 11 12
13 14 15
6+ 14+
15-
24 V DC

Removable terminals
green 24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-STC4-
1.2O-3
618 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Transmitter Power Supply KFD2-CR4-1.2O

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 20 ... 32 V DC
• 24 V DC supply (Power Rail)
Power consumption approx. 2.5 W
Input
• Input 2-wire and 3-wire transmitters
Input signal 0/4 ... 20 mA and 2-wire current sources
≤ 85 Ω terminals 2-, 3 • Dual output 0/4 mA ... 20 mA

K-System
Input resistance
Available voltage ≥ 16 V at 20 mA terminals 1+, 3 • Accuracy 0.1 %
Ripple 50 mVpp at 20 mA • Up to SIL3 acc. to IEC 61508
Output
Load 0 ... 550 Ω Function
Output signal 0/4 ... 20 mA
Ripple ≤ 50 μArms This signal conditioner provides the
Transfer characteristics isolation for non-intrinsically safe
Deviation at 20 °C (68 °F), 0/4 ... 20 mA applications.
≤ 10 μA incl. calibration, linearity, hysteresis, loads and
fluctuations of supply voltage The device supplies 2-wire and 3-wire
transmitters, and can also be used with 2-

Digital Inputs
Influence of ambient temperature 0.25 μA/K
Rise time 20 μs
wire current sources.
Start-up time 200 μs It transfers the analog input signal as two
De-energized delay 20 μs isolated current values.
Ambient conditions Both outputs provide a 0/4 mA ... 20 mA
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) current corresponding to the input signal.
Mechanical specifications The minimum available field voltage is
Protection degree IP20 16 V at 20 mA.
Mass approx. 150 g

Digital Outputs
If necessary, the internal resistance of
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
250 Ω between terminals 8, 9 and 11, 12
can be used for conversion into a
0 V ... 5 V voltage signal.

Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminal
green
KFD2-CR4-1.2O
1 2 3
4 5 6

1+ 7-
8+ I KFD2-CR4-1.2O

9
2- 250 Ω
11/2010

Accessories

PWR LED green:


mA
10- Power supply
3 11+ II
12
908837 (US) / 208599 (EU)

250 Ω

7 8 9
10 11 12
13 14 15

14+
15-
24 V DC
Removable terminals
green
24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-CR4-1.2O

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 619
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFU8-VCR-1 Transmitter Power Supply

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 20 ... 90 V DC/48 ... 253 V AC
• AC/DC wide range supply
Power consumption ≤ 2.1 W/≤ 4 VA
• Current and voltage inputs Input
• Current or voltage output Input I
• Switch selectable ranges
K-System

Input signal 0/4 ... 20 mA


Available voltage > 15 V at 20 mA terminals 1+, 3-
Function Open circuit voltage/short-circuit 21 V/26 mA
current
This isolated signal conditioner is a signal Input resistance < 55 Ω terminals 2-, 3+
converter that is suitable for the Input II
connection of current and voltage signals Input signal 0/2 ... 10 V
and provides isolation for non-intrinsically Input resistance > 1 MΩ
safe applications. Output
Output I analog current output
The input ranges include
Output signal 0/4 ... 20 mA
0/4 mA ... 20 mA or 0/2 V ... 10 V.
Digital Inputs

Source load 0 ... 750 Ω open circuit voltage > 21 V


The output measuring signals are Sink voltage across terminals 5 ... 30 V.
0/4 mA ... 20 mA or 0/2 V ... 10 V. If the current is supplied from a source > 16.5 V, series
The measuring range is easily selected by resistance of ≥ (V - 16.5)/0.0215 Ω is needed, where V
switches located on the front of device. is the source voltage.
Output II analog voltage output
For additional information, refer to the
Output signal 0/2 ... 10 V
manual and www.pepperl-fuchs.com.
Load ≥ 2 kΩ
Transfer characteristics
Digital Outputs

Deviation 0.1 % of output signal range


Resolution/accuracy current: 7 μA/20 μA
voltage: 3.5 mV/10 mV
Influence of ambient temperature 0.01 %/K of output signal range
Reaction time 150 ms
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Protection degree IP20
Analog Inputs

Mass 150 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
Analog Outputs

Diagrams

Front view
Removable terminals
green
KFU8-VCR-1
1 2 3
4 5 6

1+ 7
KFU8-VCR-1

8+
I

LED green: 2-
?

V
11/2010
Accessories

PWR

Switch S1 S1 I II Power supply mA


9-
Accuracy 901 3
23
78

S2
456
10-
908837 (US) / 208599 (EU)

Switch S2 5-
Measuring range 11+
V
7 8 9
10 11 12
6+
13 14 15

14
15
AC/DC

Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFU8-VCR-1

620 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SMART Transmitter Power Supply KFD2-STC4-2

Technical data Features


Supply • 2-channel signal conditioner
Rated voltage 20 ... 35 V DC
• 24 V DC supply (Power Rail)
Power consumption ≤ 2.8 W
Input
• Input 2-wire SMART transmitters
Input signal 0/4 ... 20 mA • Output 0/4 mA ... 20 mA
≥ 16 V at 20 mA, terminals 1+, 3 • Terminals with test points

K-System
Available voltage
Output • Up to SIL2 acc. to IEC 61508
Load 0 ... 550 Ω
Output signal 4 ... 20 mA (overload > 25 mA) Function
Ripple ≤ 50 μArms
Transfer characteristics This signal conditioner provides the
Deviation at 20 °C (68 °F), 0/4 ... 20 mA isolation for non-intrinsically safe
≤ 10 μA incl. calibration, linearity, hysteresis, loads and applications.
fluctuations of supply voltage
Influence of ambient temperature 0.25 μA/K
The device supplies 2-wire SMART
Frequency range input to output: transmitters.

Digital Inputs
bandwidth with 1 Vpp signal 0 ... 7.5 kHz (-3 dB) It transfers the analog input signal as an
output to input: isolated current value.
bandwidth with 1 Vpp signal 0.3 ... 7.5 kHz (-3 dB)
Rise time 20 μs
Digital signals may be superimposed on
Start-up time 200 μs
the input signal and are transferred bi-
De-energized delay 20 μs
directionally.
Ambient conditions If the HART communication resistance in
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) the loop is too low, the internal resistance
Mechanical specifications of 250 Ω between terminals 8, 9

Digital Outputs
Protection degree IP20 and 11, 12 can be used.
Mass approx. 150 g Test sockets for the connection of HART
Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in), housing type B2 communicators are integrated into the
terminals of the device.

Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminals
green

KFD2-STC4-2

1+ 7- 1 2 3
HART

4 5 6
HART

I
3- 8+ KFD2-STC4-2
11/2010

9
Accessories

250 Ω PWR
LED green:
Power supply
4+ 10-
HART

II
HART
908837 (US) / 208599 (EU)

6- 11+
12
250 Ω 7 8 9
10 11 12
13 14 15
14+
15-
24 V DC

Removable terminals
24 V DC green
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-STC4-2

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 621
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD2-STC4-2-3 SMART Transmitter Power Supply, Output Current

Features Technical data


• 2-channel signal conditioner Supply
Rated voltage 20 ... 35 V DC
• 24 V DC supply (Power Rail)
Power consumption ≤ 2.8 W
• Input 2-wire SMART transmitters Input
• 0/4 mA ... 20 mA current sink output Input signal 0/4 ... 20 mA
• Terminals with test points ≥ 16 V at 20 mA, terminals 1+, 3
K-System

Available voltage
• Up to SIL2 acc. to IEC 61508 Output
Output signal 0/4 ... 20 mA (overload > 25 mA)
Function Ripple ≤ 50 μArms
External supply (loop) 11 ... 30 V DC
This signal conditioner provides the Transfer characteristics
isolation for non-intrinsically safe Deviation at 20 °C (68 °F), 0/4 ... 20 mA
applications. ≤ 10 μA incl. calibration, linearity, hysteresis, loads and
fluctuations of supply voltage
The device supplies 2-wire SMART Influence of ambient temperature 0.25 μA/K
transmitters. Frequency range input to output:
Digital Inputs

It transfers the analog input signal as an bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB)
isolated current value. output to input:
bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB)
Digital signals may be superimposed on Rise time 20 μs
the input or output signals and transferred Start-up time 200 μs
bi-directionally. Ambient conditions
It is designed to provide sink mode Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
outputs. Mechanical specifications
If the HART communication resistance in Protection degree IP20
Digital Outputs

the loop is too low, the internal resistance Mass approx. 200 g
of 250 Ω between terminals 8, 9 Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in), housing type B2
and 11, 12 can be used.
Test sockets for the connection of HART
communicators are integrated into the
terminals of the device.
Analog Inputs
Analog Outputs

Diagrams

Front view
Removable terminals
green

KFD2-STC4-2-3

1 2 3 1+ 7+
HART

4 5 6
HART

I V
KFD2-STC4-2-3 3- 8-
11/2010

9
Accessories

PWR
LED green: 250 Ω
Power supply
4+ 10+
HART

II
HART

908837 (US) / 208599 (EU)

V
6- 11-
12
7 8 9
250 Ω
10 11 12
13 14 15
14+
15-
24 V DC

Removable terminals
green 24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-STC4-2-3

622 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SMART Transmitter Power Supply KFD2-STV4-2-1

Technical data Features


Supply • 2-channel signal conditioner
Rated voltage 20 ... 35 V DC
• 24 V DC supply (Power Rail)
Power consumption ≤ 2.5 W
Input
• Input 2-wire SMART transmitters
Input signal 0/4 ... 20 mA • Output 0/1 V ... 5 V
≥ 16 V at 20 mA • Terminals with test points

K-System
Available voltage
Output • Up to SIL2 acc. to IEC 61508
Load output resistance: 250 Ω
Output signal 0/1 ... 5 V Function
Ripple ≤ 12.5 mV
Transfer characteristics This signal conditioner provides the
Deviation at 20 °C (68 °F), 0/1 ... 5 V ≤ 5 mV incl. calibration, isolation for non-intrinsically safe
linearity, hysteresis, loads and fluctuations of supply applications.
voltage
Influence of ambient temperature ≤ 20 ppm/K
The device supplies 2-wire SMART
Frequency range hazardous area into the safe area: transmitters.

Digital Inputs
bandwidth with 0.5 Vpp 0 ... 7.5 kHz (-3 dB) It transfers the analog input signal as an
safe area into the hazardous area: isolated voltage value.
bandwidth with 0.5 Vpp 0.3 ... 7.5 kHz (-3 dB)
Rise time 20 μs
Digital signals may be superimposed on
Start-up time 200 μs
the input signal and are transferred bi-
De-energized delay 20 μs
directionally.
Ambient conditions If the HART communication resistance in
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) the loop is too low, the internal resistance
Mechanical specifications of 250 Ω between terminals 8, 9

Digital Outputs
Protection degree IP20 and 11, 12 can be used.
Mass approx. 100 g Test sockets for the connection of HART
Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in), housing type B2 communicators are integrated into the
terminals of the device.

Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminals
green

KFD2-STV4-2-1

1+ 7- 1 2 3
HART

4 5 6
HART

I
3- 8+ KFD2-STV4-2-1
11/2010

9
Accessories

250 Ω PWR
LED green:
Power supply
4+ 10-
HART

II
HART
908837 (US) / 208599 (EU)

6- 11+
12
250 Ω 7 8 9
10 11 12
13 14 15
14+
15-
24 V DC

Removable terminals
24 V DC green
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-STV4-2-1

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 623
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD2-CR4-2 Transmitter Power Supply

Features Technical data


• 2-channel signal conditioner Supply
Rated voltage 20 ... 35 V DC
• 24 V DC supply (Power Rail)
Power consumption ≤ 2.8 W
• Input 2-wire transmitters Input
• Output 0/4 mA ... 20 mA Input signal 0/4 ... 20 mA
• Accuracy 0.1 % ≤ 500 Ω terminals 1+, 3- (250 Ω load)
K-System

Input resistance
• Up to SIL2 acc. to IEC 61508 Available voltage ≥ 15.7 V at 20 mA terminals 1+, 3
Ripple 50 mVpp at 20 mA
Function Output
Load 0 ... 550 Ω
This signal conditioner provides the Output signal 0/4 ... 20 mA
isolation for non-intrinsically safe Ripple ≤ 50 μArms
applications. Transfer characteristics
Deviation at 20 °C (68 °F), 0/4 ... 20 mA
The device supplies 2-wire transmitters.
≤ 10 μA incl. calibration, linearity, hysteresis, loads and
It transfers the analog input signal as an fluctuations of supply voltage
Digital Inputs

isolated current value. Influence of ambient temperature 0.25 μA/K


The output provides a 0/4 mA ... 20 mA Rise time 20 μs
current corresponding to the input signal. Start-up time 200 μs
The minimum available field voltage is De-energized delay 20 μs
16 V at 20 mA. Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
If necessary, the internal resistance of
Mechanical specifications
250 Ω between terminals 8, 9 and 11, 12
Protection degree IP20
can be used for conversion into a
Digital Outputs

Mass approx. 150 g


0 V ... 5 V voltage signal.
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
Analog Inputs
Analog Outputs

Diagrams

Front view
Removable terminals
green
KFD2-CR4-2
1 2 3
4 5 6
1+ 7-
I
KFD2-CR4-2
3- 8+ I
9
250 Ω
11/2010
Accessories

PWR LED green:


Power supply 4+ 10-
II 6- 11+ II
12
908837 (US) / 208599 (EU)

250 Ω

7 8 9
10 11 12
13 14 15

14+
15-
24 V DC
Removable terminals
green
24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-CR4-2

624 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Transmitter Power Supply KFD2-CRG2-1.D

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 20 ... 30 V DC
• 24 V DC supply (Power Rail)
Power consumption 2.5 W
Input
• Input 2-wire and 3-wire transmitters
Input I and 2-wire current sources
• Output 0/4 mA ... 20 mA

K-System
Input signal 0/4 ... 20 mA
Available voltage ≥ 15 V at 20 mA • 2 relay contact outputs
Open circuit voltage/short-circuit 24 V/33 mA • Programmable high/low alarm
current
• Linearization function
Input resistance 45 Ω (terminals 2, 3)
(max 20 points)
Lead monitoring breakage I < 0.2 mA; short-circuit I > 22 mA
acc. to NAMUR NE43 • Up to SIL2 acc. to IEC 61508
Output
Output signal 0 ... 20 mA or 4 ... 20 mA Function
Output I, II signal, relay
Contact loading 250 V AC/2 A/cos Φ ≥ 0.7; 40 V DC/2 A This signal conditioner provides the

Digital Inputs
Mechanical life 5 x 107 switching cycles isolation for non-intrinsically safe
Energized/De-energized delay approx. 20 ms/approx. 20 ms applications.
Output III signal, analog The device supplies 2-wire and 3-wire
Current range 0 ... 20 mA or 4 ... 20 mA transmitters, and can also be used with
Open loop voltage ≤ 24 V DC active current sources.
Load ≤ 650 Ω Two relays and an active
Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA 0/4 mA ... 20 mA current source are
(acc. NAMUR NE43)
available as outputs. The relay contacts
Ambient conditions

Digital Outputs
and the current output can be integrated
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
in security-relevant circuits. The current
Mechanical specifications
output is easily scaled.
Protection degree IP20
Mass 300 g On the display the measured value can be
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in), housing type C3 indicated in various physical units.
The unit is easily programmed by the use
of a keypad located on the front of the unit
or with the PACTware™ configuration
software.

Analog Inputs
The input has a line fault detection.
A unique collective error messaging
feature is available when used with the
Power Rail system.
For additional information, refer to the
manual and www.pepperl-fuchs.com.

Analog Outputs
Diagrams
Front view
Removable terminal
green

KFD2-CRG2-1.D
10
1+ 11 I LED green: 1 2 3 4 5 6
12 KFD2-CRG2- LC display
Power supply 1.D
HART

2- 16
17 II OUT
ERR PWR

18
11/2010

Accessories

mA
LED red: 1 2

3 Fault signal ESC

7- III
mA
8+ LED yellow:
RS 232
OK
Keypad
Output Ι ... ΙΙ
908837 (US) / 208599 (EU)

7 8 9 10 11 12
13 14 15 16 17 18
19 20 21 22 23 24

23+
24-
24 V DC Programming jack Removable terminals
green

ERR 24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-CRG2-1.D

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 625
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFU8-CRG2-1.D Transmitter Power Supply

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 20 ... 90 V DC or 48 ... 253 V AC
• AC/DC wide range supply
Power consumption 2.2 W/4 VA
• Input 2-wire and 3-wire transmitters Input
and 2-wire current sources Input I
• Output 0/4 mA ... 20 mA
K-System

Input signal 0/4 ... 20 mA


• 2 relay contact outputs Available voltage > 15 V at 20 mA
• Programmable high/low alarm Open circuit voltage/short-circuit 24 V/33 mA
current
• Linearization function (max 20
Input resistance 45 Ω (terminals 2, 3)
points)
Lead monitoring breakage I < 0.2 mA; short-circuit I > 22 mA
• Up to SIL2 acc. to IEC 61508 acc. to NAMUR NE43
Output
Function Output signal 0 ... 20 mA or 4 ... 20 mA
Output I, II signal, relay
This signal conditioner provides the Contact loading 250 V AC/2 A/cos Φ ≥ 0.7; 40 V DC/2 A
Digital Inputs

isolation for non-intrinsically safe Mechanical life 5 x 107 switching cycles


applications. Energized/De-energized delay approx. 20 ms/approx. 20 ms
The device supplies 2-wire and 3-wire Output III Signal, analog
transmitters, and can also be used with Current range 0 ... 20 mA or 4 ... 20 mA
active current sources. Open loop voltage ≤ 24 V DC
Two relays and an active Load ≤ 650 Ω
0/4 mA ... 20 mA current source are Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA
(acc. NAMUR NE43)
available as outputs.
Ambient conditions
Digital Outputs

The relay contacts and the current output Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
can be integrated in security-relevant Mechanical specifications
circuits. The current output is easily Protection degree IP20
scaled. Mass 300 g
On the display the measured value can be Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in), housing type C3
indicated in various physical units.
The unit is easily programmed by the use
of a keypad located on the front of the unit
Analog Inputs

or with the PACTware™ configuration


software.
The input has a line fault detection.
For additional information, refer to the
manual and www.pepperl-fuchs.com.
Analog Outputs

Diagrams
Front view
Removable terminal
green

KFU8-CRG2-1.D
10
LED green: 1 2 3 4 5 6 1+ 11 I
KFU8-CRG2- LC display 12
Power supply 1.D
HART

2- 16
OUT
ERR PWR 17 II
18
11/2010
Accessories

LED red: 1 2
mA
Fault signal ESC 3
7- III
mA
LED yellow:
RS 232
OK 8+
Keypad
Output Ι ... ΙΙ
908837 (US) / 208599 (EU)

7 8 9 10 11 12
13 14 15 16 17 18
19 20 21 22 23 24

23
Programming jack Removable terminals AC/DC
24
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFU8-CRG2-1.D

626 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SMART Current Driver/Repeater KFD0-SCS-1.55

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage loop powered
• 24 V DC supply (loop powered)
Field circuit
Available voltage ≥ 16 V for supply voltage > 21 V
• Current input/output 4 mA ... 20 mA
Current 4 ... 20 mA (linear transmission 1 ... 22 mA) • HART I/P or transmitter power
≤ 800 Ω (at 20 mA) supply

K-System
Load
Supply circuit • Low voltage drop
Voltage max. 30 V DC • Line fault detection (LFD)
Current 4 ... 20 mA (quiescent current < 0.5 mA)
• Up to SIL2 acc. to IEC 61508
Power loss 150 mW at 20 mA and UE < 24 V
Transfer characteristics
Function
Deviation
After calibration ≤ ± 80 μA linearity, load and voltage dependence This signal conditioner is loop powered
at 20 °C (68 °F)
and isolates a 4 mA ... 20 mA signal for
Influence of ambient temperature < 0.5 μA/K
transmitters and positioners and is HART
Damping approx. 3 dB
compatible.

Digital Inputs
Rise time ≤ 20 μs at 0 Ω, ≤ 600 μs with 800 Ω load
Ambient conditions The low voltage drop of 5 V in comparison
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) to active signal conditioners also allows
Mechanical specifications transmitter applications with unstable
Protection degree IP20 power sources between
Mass approx. 120 g 20 V DC ... 30 V DC.
Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in), housing type B2 Line fault detection of the field circuit is
possible if the control loop in the safe area

Digital Outputs
is monitored for overscale or underscale
conditions of the 4 mA ... 20 mA range.
The module can also be used for
controlling solenoid valves and discrete
outputs, such as LEDs. In this case,
terminals 8- and 9+ are driven with a 24 V
signal.

Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminal
green

KFD0-SCS-1.55

1+ 8- 1 2 3
4 5 6
HART
HART

mA
V
P

KFD0-SCS-1.55

9+
11/2010

Accessories

2-
3-
908837 (US) / 208599 (EU)

7 8 9
10 11 12
13 14 15

Removable terminal
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD0-SCS-1.55

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 627
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD0-CS-1.50 Current Driver/Repeater

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage loop powered
• 24 V DC supply (loop powered)
Input
• Current input/output 4 mA ... 20 mA Rated voltage Ui 10 ... 35 V
• I/P or transmitter power supply Rated current Ii 4 ... 20 mA
• Accuracy 0.1 %
K-System

Power loss < 150 mW per channel at 25 mA and U < 26.1 V


• Up to SIL2 acc. to IEC 61508 < 400 mW per channel at 25 mA and U > 26.1 V
Output
Function Voltage ≥ 0.9 x Uin - (0.23 x current in mA) - 0.7
for 10 V < Uin < 26.1 V
≥ 23 V - (0.23 x current in mA) for Uin > 26.1 V
This signal conditioner transfers DC
Short-circuit current ≤ 100 mA
signals from fire alarms, smoke alarms,
Transfer current ≤ 25 mA
and temperature sensors and provides
Transfer characteristics
isolation for non-intrinsically safe
Deviation
applications. It can also be used to control
After calibration Uin ≥ 5 V ± 20 μA/Uin ≤ 5 V ± 50 μA incl. calibration,
I/P converters, power solenoids, LEDs,
Digital Inputs

linearity, hysteresis and output load fluctuations


and audible alarms. at 20 °C (68 °F)
Since this isolator is loop powered, use Influence of ambient temperature ≤ 2 μA/K (0 ... 50 °C (32 ... 122 °F));
the technical data to verify that proper ≤ 5 μA/K (-20 ... 60 °C (-4 ... 140 °F))
voltage is available to the field devices. Rise time ≤ 5 ms at 4 ... 20 mA and Uin = input voltage < 26 V
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Protection degree IP20
Digital Outputs

Mass approx. 100 g


Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in), housing type B1
Analog Inputs
Analog Outputs

Diagrams

Front view
Removable terminal
green
KFD0-CS-1.50
1 2 3
4 5 6
1+ 11+
I

KFD0-CS-1.50
P

mA
V
2- 12-
11/2010
Accessories

908837 (US) / 208599 (EU)

7 8 9
10 11 12
Removable terminal
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD0-CS-1.50

628 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Current Driver/Repeater KFD0-CS-2.50

Technical data Features


Supply • 2-channel signal conditioner
Rated voltage loop powered
• 24 V DC supply (loop powered)
Input
Rated voltage Ui 10 ... 35 V
• Current input/output 4 mA ... 20 mA
Rated current Ii 4 ... 20 mA • I/P or transmitter power supply
• Accuracy 0.1 %

K-System
Power loss < 150 mW per channel at 25 mA and U < 26.1 V
< 400 mW per channel at 25 mA and U > 26.1 V • Up to SIL2 acc. to IEC 61508
Output
Voltage ≥ 0.9 x Uin - (0.23 x current in mA) - 0.7 Function
for 10 V < Uin < 26.1 V
≥ 23 V - (0.23 x current in mA) for Uin > 26.1 V
This signal conditioner transfers DC
Short-circuit current ≤ 100 mA
signals from fire alarms, smoke alarms,
Transfer current ≤ 25 mA
and temperature sensors and provides
Transfer characteristics
isolation for non-intrinsically safe
Deviation
applications. It can also be used to control
After calibration Uin ≥ 5 V ± 20 μA/Uin ≤ 5 V ± 50 μA incl. calibration,
I/P converters, power solenoids, LEDs,

Digital Inputs
linearity, hysteresis and output load fluctuations
at 20 °C (68 °F) and audible alarms.
Influence of ambient temperature ≤ 2 μA/K (0 ... 50 °C (32 ... 122 °F)); Since this isolator is loop powered, use
≤ 5 μA/K (-20 ... 60 °C (-4 ... 140 °F)) the technical data to verify that proper
Rise time ≤ 5 ms at 4 ... 20 mA and Uin = input voltage < 26 V voltage is available to the field devices.
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Protection degree IP20

Digital Outputs
Mass approx. 100 g
Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in), housing type B1

Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminals
green
KFD0-CS-2.50
1 2 3
1+ 11+ 4 5 6
I

I KFD0-CS-2.50
P

mA
V
2- 12-
11/2010

Accessories

4+ 9+
I

II
908837 (US) / 208599 (EU)

mA
V
5- 10-
8- 7 8 9
10 11 12
Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD0-CS-2.50

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 629
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD0-CS-2.51P Current Driver/Repeater

Features Technical data


• 2-channel signal conditioner Supply
Rated voltage loop powered
• 24 V DC supply (loop powered)
Input
• Current input/output 0 mA ... 40 mA Rated voltage Ui 4 ... 35 V
• I/P or transmitter power supply Rated current Ii 0 ... 40 mA
• Accuracy 1 %
K-System

Power loss at 40 mA and Uin < 22 V: 700 mW per channel


• Reverse polarity protection at 40 mA and Uin > 22 V: 1.2 W per channel
Output
• Up to SIL2 acc. to IEC 61508
Voltage for 4 V < Uin < 24 V:
≥ 0.9 x Uin - (0.37 x current in mA) - 1.0
Function for Uin > 24 V: ≥ 21 V - (0.36 x current in mA)
Short-circuit current at Uin > 24 V: ≤ 65 mA
This signal conditioner transfers DC Transfer current ≤ 40 mA
signals from fire alarms, smoke alarms, Transfer characteristics
and temperature sensors to the control Deviation
and provides isolation for non-intrinsically After calibration ≤ ± 200 μA; incl. calibration, linearity, hysteresis and
safe applications. It can also be used to
Digital Inputs

load fluctuations at the output up to a load of 1 kΩ and


control I/P converters, power solenoids, current ≤ 20 mA at 20 °C (68 °F)
LEDs, and audible alarms. Influence of ambient temperature ≤ ± 2 μA/K at Uin ≤ 20 V; ≤ ± 5 μA/K at Uin > 20 V
Reverse polarity protection prevents Rise time ≤ 5 ms at 4 ... 20 mA step and Uin < 24 V
damage to the isolator caused by faulty Ambient conditions
wiring. Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Since this isolator is loop powered, use
Protection degree IP20
the technical data to verify that proper
Mass approx. 100 g
Digital Outputs

voltage is available to the field devices.


Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in), housing type B1
Analog Inputs
Analog Outputs

Diagrams

Front view
Removable terminals
green
KFD0-CS-2.51P
1 2 3
4 5 6
1+ 11+
I

KFD0-CS-2.51P
I
P

mA
V
2- 12-
11/2010
Accessories

4+ 9+
I

II
908837 (US) / 208599 (EU)
P

mA
V
5- 10-
7 8 9 8-
10 11 12
Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD0-CS-2.51P

630 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Current/Voltage Converter KFD0-CC-1

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 12 ... 35 V DC loop powered
• 24 V DC supply (loop powered)
Input
Current range 0 ... 20 mA, load ≤ 50 Ω
• Current or voltage input
Voltage range 0 ... 10 V, load ≥ 100 kΩ • Output: 4 ... 20 mA
• Potentiometer or DIP switch

K-System
Output
Load (U -12 V)/0.02 A selectable ranges
Current output 4 ... 20 mA, limited to ≤ 35 mA • Line fault detection (LFD)
Fault signal downscaling ≤ 3 mA
Transfer characteristics Function
Deviation
After calibration 0.1 % of full-scale value This signal conditioner converts a 2-wire
Temperature effect span: 0.050 % of span/K; voltage or current to a 4 mA ... 20 mA
zero point: 0.060 % of span/K signal and provides isolation for non-
Linearization ≤ 0.04 % of full-scale value intrinsically safe applications.
Influence of supply voltage 6.5 ppm/V
The device can be used to double signals

Digital Inputs
Rise time 250 ms
in 20 mA measurement circuits due to the
Ambient conditions
limited current signal input load of 50 Ω.
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications DIP switches and potentiometers make
Protection degree IP20 field calibration easy.
Mass approx. 100 g Since this isolator is loop-powered, use
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2 the technical data to verify that the proper
voltage is available to the field devices.

Digital Outputs
Analog Inputs
Analog Outputs
Diagrams

Front view Removable terminal


green

KFD0-CC-1
1 2 3
1+ 8- 4 5 6

Span fine adjustment


V mA V KFD0-CC-1

2- 9+ Zero point
fine adjustment
11/2010

Accessories

SPAN

ZERO

DIP switch
range, zero point
908837 (US) / 208599 (EU)

coarse adjustment

7 8 9
10 11 12
13 14 15

Removable terminal
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD0-CC-1

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 631
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD2-USC-1.D Signal Converter with Trip Value

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 20 ... 30 V DC
• 24 V DC supply (Power Rail)
Power consumption ≤ 1.6 W
• Scaleable current or voltage input Input
• Current or voltage output Input resistance voltage: 1 MΩ, current: ≤ 100 Ω
• Relay contact output
K-System

Limit 30 V
• Configurable by keypad Current 0 ... 20 mA
Voltage 0 ... 10 V/0 ... 60 mV
• Line fault detection (LFD)
Resolution 15 Bit
Output
Function
Output I signal, relay
This signal conditioner is suitable for the Contact loading 250 V AC/2 A/cos Φ 0.7; 40 V DC/2 A
connection of current and voltage signals Mechanical life 2 x 107 switching cycles
and provides isolation for non-intrinsically Energized/De-energized delay approx. 10 ms/approx. 10 ms
safe applications. Output II analog
Load current: ≤ 550 Ω, voltage: ≥ 1 kΩ
Digital Inputs

The input ranges include 0 mA ... 20 mA,


Analog voltage output 0/1 ... 5 V, 0/2 ... 10 V
0 V ... 10 V or 0 mV ... 60 mV. Subranges
Analog current output 0/4 ... 20 mA
from the input ranges are selectable.
Transfer characteristics
The output measuring signals are Deviation 0.1 % of full-scale value
0/4 mA ... 20 mA, 0/2 V ... 10 V or Resolution/accuracy current: 1 μA/20 μA
0/1 V ... 5 V. voltage: 0.5 mV/10 mV
mV: 3 μV/60 μV
The output relay serves as trip value
Influence of ambient temperature 0.003 %/K (30 ppm)
contact.
≥ 150 ms/≤ 300 ms
Digital Outputs

Reaction time
On the display the measured value can be Ambient conditions
indicated in various physical units. Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
The unit is easily programmed by the use Mechanical specifications
of a keypad located on the front of the Protection degree IP20
unit. Mass 150 g
For additional information, refer to the Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B3
manual and www.pepperl-fuchs.com.
Analog Inputs
Analog Outputs

Diagrams

Front view

Removable terminal
green
KFD2-USC-1.D

1 2 3
10
LC display 1+ 11 I
12
11/2010

KFD2-USC-
Accessories

1.D
2+ 7-
V mA
II
ESC
8+
V
OK
mA 9-
Keypad 3-
908837 (US) / 208599 (EU)

7 8 9
10 11 12
13 14 15

14
15
24 V DC
Removable terminals
green
24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-USC-1.D

632 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Signal Converter with Trip Value KFU8-USC-1.D

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 20 ... 90 V DC/48 ... 253 V AC
• AC/DC wide range supply
Power consumption ≤ 1.6 W/≤ 2.6 VA
Input
• Scaleable current or voltage input
Input resistance voltage: 1 MΩ, current: ≤ 100 Ω • Current or voltage output
• Relay contact output

K-System
Limit 30 V
Current 0 ... 20 mA • Configurable by keypad
Voltage 0 ... 10 V/0 ... 60 mV
• Line fault detection (LFD)
Resolution 15 Bit
Output
Function
Output I signal, relay
Contact loading 250 V AC/2 A/cos Φ 0.7; 40 V DC/2 A This signal conditioner is suitable for the
Mechanical life 2 x 107 switching cycles connection of current and voltage signals
Energized/De-energized delay approx. 10 ms/approx. 10 ms and provides isolation for non-intrinsically
Output II analog safe applications.
Load current: ≤ 550 Ω, voltage: ≥ 1 kΩ

Digital Inputs
The input ranges include 0 mA ... 20 mA,
Analog voltage output 0/1 ... 5 V, 0/2 ... 10 V
0 V ... 10 V or 0 mV ... 60 mV. Subranges
Analog current output 0/4 ... 20 mA
from the input ranges are selectable.
Transfer characteristics
Deviation 0.1 % of full-scale value The output measuring signals are
Resolution/accuracy current: 1 μA/20 μA 0/4 mA ... 20 mA, 0/2 V ... 10 V or
voltage: 0.5 mV/10 mV 0/1 V ... 5 V.
mV: 3 μV/60 μV
The output relay serves as trip value
Influence of ambient temperature 0.003 %/K (30 ppm)
contact.
Reaction time ≥ 150 ms/≤ 300 ms

Digital Outputs
Ambient conditions On the display the measured value can be
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
indicated in various physical units.
Mechanical specifications The unit is easily programmed by the use
Protection degree IP20 of a keypad located on the front of the
Mass 150 g unit.
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B3 For additional information, refer to the
manual and www.pepperl-fuchs.com.

Analog Inputs
Analog Outputs
Diagrams

Front view

Removable terminal
green
KFU8-USC-1.D

1 2 3
10
LC display
1+ 11 I
12
11/2010

KFU8-USC-
Accessories

2+ 7- 1.D
V mA
II
ESC
8+
V
mA 9- OK
3- Keypad
908837 (US) / 208599 (EU)

7 8 9
10 11 12
13 14 15

14
15
AC/DC Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFU8-USC-1.D

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 633
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD2-GS-1.2W Current/Voltage Trip Value

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 20 ... 30 V DC
• 24 V DC supply (Power Rail)
Power consumption 2.25 W (typ. 1.68 W)
• Current and voltage inputs Input
• 2 relay contact outputs Measurement range terminals 1+, 3-; voltage: 0/1 ... 5 V; 50 kΩ
• Programmable high/low alarm or 0/2 ... 10 V; 100 kΩ
K-System

terminals 2+, 3-; current: 0/4 ... 20 mA; 50 Ω


• DIP switch programmable
Output
• Terminals with test points Output I trip value: terminals 7, 8, 9
Output II trip value: terminals 10, 11, 12
Function Contact loading 250 V AC/5 A/1250 VA; 125 V DC/5 A/150 W
Transfer characteristics
This signal conditioner is a trip alarm with
Deviation ≤ 0.5 %
two independently adjustable trip points
Influence of ambient temperature 0.01 %/K of adjusted trip value
that provides isolation for non-intrinsically
Input delay 100 ms
safe applications.
Ambient conditions
Digital Inputs

The unit actuates a relay output when it Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
reaches a user-programmed input level. Mechanical specifications
DIP switches are used to program voltage Protection degree IP20
input low alarms and high alarms. Mass approx. 120 g
Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in), housing type B2
The hysteresis, the operating mode of the
relay outputs, and the type of alarm are
selectable for each trip point.
For addtional information, refer to
Digital Outputs

www.pepperl-fuchs.com.
Analog Inputs
Analog Outputs

Diagrams

Front view
Removable terminal
green
KFD2-GS-1.2W

1 2 3 LED green:
4 5 6 1+ 7
Power supply 8 I
V 2+ 9
LED yellow: KFD2-GS-1.2W
mA
Relay output 1 3-
11/2010
Accessories

OUT CHK PWR

DIP switch 10
LED yellow: 0%

Relay output 2
1
60% T1 11 II
0% Potentiometer 12
908837 (US) / 208599 (EU)

2
60% T2
Trip value 1

Potentiometer Potentiometer
Hysteresis 1 7 8 9 Trip value 2
10 11 12
13 14 15 14+
15-
24 V DC
Potentiometer
Hysteresis 2
Removable terminals
green 24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-GS-1.2W

634 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Strain Gauge Converter KFD2-WAC2-1.D

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 20 ... 35 V DC
• 24 V DC supply (Power Rail)
Power consumption ≤3 W
Interface
• Strain gauge input
Connection Power Rail or terminals 19+, 20 GND, 21- • Output 0 mA ... ± 20 mA or
0 V ... ± 10 V

K-System
Type RS 485
Programming interface RS 232 programming jack • Relay contact output
Field circuit • Programmable high/low alarm
Lead resistance ≤ 25 Ω per lead
• RS 485 interface
Input I
• Line fault detection (LFD)
Connection terminals 1+, 2-
Sensor supply 1 ... 5 V
Function
Connection terminals 3+, 4-, 5+, 6-
Short-circuit current 50 mA
This signal conditioner is used with strain
Load ≥ 116 Ω up to 5V, ≥ 85 Ω up to 4V
gauges, load cells and resistance
Input

Digital Inputs
measuring bridges and provides isolation
Programmable Tare 0 ... 500 % of span
for non-intrinsically safe applications.
Input I signal, analog
Input signal -100 ... 100 mV Designed to provide 5 V excitation
Input resistance > 1 MΩ for voltage measurement voltage, this barrier’s high quality A/D
Input II, III tare adjustment, calibration and zero converter allows it to be used with those
Active/Passive I > 4 mA/I < 1.5 mA devices requiring 10 V.
Output The unit is easily programmed by the use
Output I, II relay output of a keypad located on the front of the unit

Digital Outputs
Mechanical life 2 x 107 switching cycles or with the PACTware™ configuration
Output III Analog output software. The actual measurement for
Current range -20 ... 20 mA tare, zero point, and final value can be
Load ≤ 550 Ω entered in this manner.
Line fault detection downscale -21.5 mA (-10.75 V) or 2 mA (1 V), A unique collective error messaging
upscale 21.5 mA (10.75 V)
feature is available when used with the
Ambient conditions
Power Rail system.
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications For additional information, refer to the
manual and www.pepperl-fuchs.com.

Analog Inputs
Protection degree IP20
Mass approx. 250 g
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in), housing type C3

Analog Outputs
Diagrams
Front view
Removable terminals
green

KFD2-WAC2-1.D
10
3+ 11 I LED green: 1 2 3 4 5 6
12 KFD2-WAC2- LC display
5+ Power supply 1.D
16
17 II ERR PWR
1+ 18 OUT
11/2010

Accessories

2- 7- LED red: 1 2

mA 8+ III Fault signal ESC

9- RS 232
6- 13+ LED yellow: OK
Keypad
4- Output Ι ... ΙΙ
908837 (US) / 208599 (EU)

14-
7 8 9 10 11 12
15+ 13 14 15 16 17 18
19 20 21 22 23 24
19+
20 GND RS 485
21-
23+
24-
24 V DC Programming jack Removable terminals
green

RS 485 ERR 24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-WAC2-
1.D
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 635
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD0-VC-1.10 Current Converter

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 12 ... 35 V DC loop powered
• 24 V DC supply (loop powered)
Input
• Voltage input -10 V ... 10 V Voltage range -10 ... 10 V (factory adjustment)
• Output 4 mA ... 20 mA Output
• Span and zero point adjustment ≤ (supply voltage -12 V)/0.02 A
K-System

Load
Current output 4 ... 20 mA, limited to ≤ 35 mA
Function Transfer characteristics
Measurement range fn -10 ... +10 V,
This signal conditioner receives a - zero point ± 1 % of full-scale value,
10 V ... 10 V voltage input, produces a span ± 1.5 % of full-scale value
4 mA ... 20 mA signal output. It also Deviation
provides isolation for non-intrinsically safe After calibration 0.1 % of full-scale value
applications. Temperature effect span: 0.050 % of span/K
zero point: 0.060 % of span/K
Fine adjustment for zero and span are Linearization ≤ 0.04 % of full-scale value
performed with the potentiometers on top
Digital Inputs

Influence of supply voltage 6.5 ppm/V


of the unit. Rise time 250 ms
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Protection degree IP20
Mass approx. 100 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
Digital Outputs
Analog Inputs
Analog Outputs

Diagrams

Front view Removable terminal


green

KFD0-VC-1.10
1 2 3
4 5 6 1+ 8-
mV
KFD0-VC-1.10
Span fine adjustment 2-
Zero point V
9+
fine adjustment
11/2010
Accessories

SPAN

ZERO
908837 (US) / 208599 (EU)

7 8 9
10 11 12
13 14 15

Removable terminal
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD0-VC-1.10

636 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Universal Temperature Converter KFD2-UT2-1

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 20 ... 30 V DC
• 24 V DC supply (Power Rail)
Power loss/power consumption ≤ 0.95 W/0.95 W
Input
• TC, RTD, potentiometer or voltage
RTD type Pt10, Pt50, Pt100, Pt500, Pt1000 input
(EN 60751: 1995) • Current output 0/4 mA ... 20 mA

K-System
type Pt10GOST, Pt50GOST, Pt100GOST, • Sink or source mode
Pt500GOST, Pt1000GOST (6651-94)
type Cu10, Cu50, Cu100 (P50353-92) • Line fault (LFD) and sensor burnout
type Ni100 (DIN 43760) detection
Measuring current approx. 200 μA with RTD • Up to SIL2 acc. to IEC 61508
Types of measuring 2-, 3-, 4-wire connection
Lead resistance ≤ 50 Ω per lead Function
Measuring circuit monitoring sensor burnout, sensor short-circuit
Thermocouples type B, E, J, K, N, R, S, T (IEC 584-1: 1995) This signal conditioner is designed to
type L (DIN 43710: 1985) connect RTDs, thermocouples, or
type TXK, TXKH, TXA (P8.585-2001) potentiometers, and provide a

Digital Inputs
Cold junction compensation external and internal proportional 0/4 mA ... 20 mA signal.
Measuring circuit monitoring sensor burnout
The barrier offers 3-port isolation between
Voltage selectable within the range -100 ... 100 mV
input, output, and power supply.
Potentiometer 0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ
(3-wire connection) A removable terminal block K-CJC-** is
Input resistance ≥ 1 MΩ (-100 ... 100 mV) available for thermocouples when internal
Output cold junction compensation is desired.
Output analog current output A fault is indicated by a red flashing LED

Digital Outputs
Current range 0 ... 20 mA or 4 ... 20 mA per NAMUR NE44 and user-configured
Fault signal downscale 0 or 2 mA, fault outputs.
upscale 21.5 mA (acc. NAMUR NE43)
Source load 0 ... 550 Ω
The unit is easily programmed with the
open-circuit voltage ≤ 18 V PACTware™ configuration software.
Sink voltage across terminals 5 ... 30 V. A unique collective error messaging
If the current is supplied from a source > 16.5 V, feature is available when used with the
series resistance of ≥ (V - 16.5)/0.0215 Ω is needed, Power Rail system.
where V is the source voltage. The maximum value of
the resistance is (V - 5)/0.0215 Ω. For additional information, refer to the

Analog Inputs
Ambient conditions manual and www.pepperl-fuchs.com.
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Protection degree IP20
Mass approx. 130 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2

Analog Outputs
Diagrams

Front view Removable terminals


green

KFD2-UT2-1
K-CJC-**
1 2 3

+ 1 7 4 5 6
+
V - 2 8+
- T
KFD2-UT2-1 LED green:
T T V
9- Power supply
3
11/2010

Accessories

LED red:
4 Fault signal ERR PWR

PROGRAM
Programming jack
908837 (US) / 208599 (EU)

7 8 9
10 11 12
13 14 15

14+
15-
24 V DC
Removable terminals
green
ERR 24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-UT2-1

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 637
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD2-UT2-1-1 Universal Temperature Converter

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 20 ... 30 V DC
• 24 V DC supply (Power Rail)
Power loss/power consumption ≤ 0.64 W/0.64 W
• TC, RTD, potentiometer or voltage Input
input RTD type Pt10, Pt50, Pt100, Pt500, Pt1000
• Voltage output 0/1 V ... 5 V (EN 60751: 1995)
K-System

• Line fault (LFD) and sensor burnout type Pt10GOST, Pt50GOST, Pt100GOST,
Pt500GOST, Pt1000GOST (6651-94)
detection
type Cu10, Cu50, Cu100 (P50353-92)
• Up to SIL2 acc. to IEC 61508 type Ni100 (DIN 43760)
Measuring current approx. 200 μA with RTD
Function Types of measuring 2-, 3-, 4-wire connection
Lead resistance ≤ 50 Ω per lead
This signal conditioner is designed to Measuring circuit monitoring sensor burnout, sensor short-circuit
connect RTDs, thermocouples, or Thermocouples type B, E, J, K, N, R, S, T (IEC 584-1: 1995)
potentiometers, and provide a type L (DIN 43710: 1985)
proportional 0/1 V ... 5 V signal. type TXK, TXKH, TXA (P8.585-2001)
Digital Inputs

Cold junction compensation external and internal


The barrier offers 3-port isolation between
Measuring circuit monitoring sensor burnout
input, output, and power supply.
Voltage selectable within the range -100 ... 100 mV
A removable terminal block K-CJC-** is Potentiometer 0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ
available for thermocouples when internal (3-wire connection)
cold junction compensation is desired. Input resistance ≥ 1 MΩ (-100 ... 100 mV)
A fault is indicated by a red flashing LED Output
per NAMUR NE44 and user-configured Voltage output 0 ... 5 V or 1 ... 5 V;
output resistance: ≤ 5 Ω; load: ≥ 10 kΩ
Digital Outputs

fault outputs.
Fault signal downscale 0 V or 0.5 V, upscale 5.375 V
The unit is easily programmed with the
Ambient conditions
PACTware™ configuration software.
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
A unique collective error messaging Mechanical specifications
feature is available when used with the Protection degree IP20
Power Rail system. Mass approx. 130 g
For additional information, refer to the Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
manual and www.pepperl-fuchs.com.
Analog Inputs
Analog Outputs

Diagrams

Front view Removable terminals


green

KFD2-UT2-1-1
K-CJC-**
1 2 3
4 5 6
+ 1 7-
+
V - 2 8+
KFD2-UT2-1-1 LED green: - T T T
Power supply
3
11/2010
Accessories

LED red:
Fault signal 4
ERR PWR

PROGRAM
Programming jack
908837 (US) / 208599 (EU)

7 8 9
10 11 12
13 14 15

14+
15-
24 V DC
Removable terminals
green
ERR 24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-UT2-1-1

638 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Universal Temperature Converter KFD2-UT2-2

Technical data Features


Supply • 2-channel signal conditioner
Rated voltage 20 ... 30 V DC
• 24 V DC supply (Power Rail)
Power loss/power consumption ≤ 1.5 W/1.5 W
Input
• TC, RTD, potentiometer or voltage
RTD type Cu10, Cu50, Cu100, Pt10, Pt50, Pt100, Pt500, input
Pt1000, Ni100 (EN 60751: 1995) • Current output 0/4 mA ... 20 mA

K-System
type Pt10GOST, Pt50GOST, Pt100GOST, • Sink or source mode
Pt500GOST, Pt1000GOST (P50353-92)
Measuring current approx. 200 μA with RTD
• Line fault (LFD) and sensor burnout
Types of measuring 2-, 3-wire connection
detection
Lead resistance ≤ 50 Ω per lead • Up to SIL2 acc. to IEC 61508
Measuring circuit monitoring sensor burnout, sensor short-circuit
Thermocouples type B, E, J, K, N, R, S, T (IEC 584-1: 1995) Function
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001) This signal conditioner is designed to
Cold junction compensation external and internal connect RTDs, thermocouples, or
potentiometers, and provide a

Digital Inputs
Measuring circuit monitoring sensor burnout
Voltage selectable within the range -100 ... 100 mV proportional 0/4 mA ... 20 mA signal.
Potentiometer 0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ The barrier offers 3-port isolation between
(3-wire connection)
input, output, and power supply.
Input resistance ≥ 1 MΩ (-100 ... 100 mV)
Output A removable terminal block K-CJC-** is
Output I, II analog current output available for thermocouples when internal
Current range 0 ... 20 mA or 4 ... 20 mA
cold junction compensation is desired.
Fault signal downscale 0 or 2 mA, upscale 21.5 mA A fault is indicated by a red flashing LED

Digital Outputs
(acc. NAMUR NE43) per NAMUR NE44 and user-configured
Source load 0 ... 550 Ω fault outputs.
open-circuit voltage ≤ 18 V
The unit is easily programmed with the
Sink voltage across terminals 5 ... 30 V.
If the current is supplied from a source > 16.5 V,
PACTware™ configuration software.
series resistance of ≥ (V - 16.5)/0.0215 Ω is needed, A unique collective error messaging
where V is the source voltage. The maximum value of feature is available when used with the
the resistance is (V - 5)/0.0215 Ω. Power Rail system.
Ambient conditions
For additional information, refer to the
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)

Analog Inputs
manual and www.pepperl-fuchs.com.
Mechanical specifications
Protection degree IP20
Mass approx. 130 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2

Analog Outputs
Diagrams

Front view Removable terminals


green

KFD2-UT2-2
K-CJC-**
1 2 3

+ 1 7 4 5 6
+
I V - 2 8+ LED green:
- T
KFD2-UT2-2
T T V Power supply
9-
3
11/2010

Accessories

LED red: 1 2

+ + 4 10 Fault signal channel 1 ERR ERR PWR

II V - 5 11+ LED red:


- T T V
Fault signal channel 2 PROGRAM
908837 (US) / 208599 (EU)

12- Programming jack


6

7 8 9
10 11 12
13 14 15

14+
15-
24 V DC
Removable terminals
green
ERR 24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-UT2-2

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 639
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD2-UT2-2-1 Universal Temperature Converter

Features Technical data


• 2-channel signal conditioner Supply
Rated voltage 20 ... 30 V DC
• 24 V DC supply (Power Rail)
Power loss/power consumption ≤ 0.8 W/0.8 W
• TC, RTD, potentiometer or voltage Input
input RTD type Pt10, Pt50, Pt100, Pt500, Pt1000
• Voltage output 0/1 V ... 5 V (EN 60751: 1995)
K-System

• Line fault (LFD) and sensor burnout type Pt10GOST, Pt50GOST, Pt100GOST,
Pt500GOST, Pt1000GOST (6651-94)
detection
type Cu10, Cu50, Cu100 (P50353-92)
• Up to SIL2 acc. to IEC 61508 type Ni100 (DIN 43760)
Measuring current approx. 200 μA with RTD
Function Types of measuring 2-, 3-wire connection
Lead resistance ≤ 50 Ω per lead
This signal conditioner is designed to Measuring circuit monitoring sensor burnout, sensor short-circuit
connect RTDs, thermocouples, or Thermocouples type B, E, J, K, N, R, S, T (IEC 584-1: 1995)
potentiometers, and provide a type L (DIN 43710: 1985)
proportional 0/1 V ... 5 V signal. type TXK, TXKH, TXA (P8.585-2001)
Digital Inputs

Cold junction compensation external and internal


The barrier offers 3-port isolation between
Measuring circuit monitoring sensor burnout
input, output, and power supply.
Voltage selectable within the range -100 ... 100 mV
A removable terminal block K-CJC-** is Potentiometer 0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ
available for thermocouples when internal (3-wire connection)
cold junction compensation is desired. Input resistance ≥ 1 MΩ (-100 ... 100 mV)
A fault is indicated by a red flashing LED Output
per NAMUR NE44 and user-configured Voltage output 0 ... 5 V or 1 ... 5 V;
output resistance: ≤ 5 Ω; load: ≥ 10 kΩ
Digital Outputs

fault outputs.
Fault signal downscale 0 V or 0.5 V, upscale 5.375 V
The unit is easily programmed with the
Ambient conditions
PACTware™ configuration software.
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
A unique collective error messaging Mechanical specifications
feature is available when used with the Protection degree IP20
Power Rail system. Mass approx. 130 g
For additional information, refer to the Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
manual and www.pepperl-fuchs.com.
Analog Inputs
Analog Outputs

Diagrams

Front view Removable terminals


green

KFD2-UT2-2-1
K-CJC-**
1 2 3
4 5 6
+ 1 7-
+
LED green: I V - 2 8+
KFD2-UT2-2-1 - T T T
Power supply
3
11/2010
Accessories

LED red: 1 2
10-
Fault signal channel 1 + + 4
ERR ERR PWR
11+
LED red: II V - 5
- T T
Fault signal channel 2 PROGRAM
908837 (US) / 208599 (EU)

Programming jack 6

7 8 9
10 11 12
13 14 15

14+
15-
24 V DC
Removable terminals
green
ERR 24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-UT2-2-1

640 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
RTD Converter KFD0-TR-1

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 12 ... 35 V DC loop powered
• 24 V DC supply (loop powered)
Input
Lead resistance ≤ 100 Ω per lead
• 2- or 3-wire Pt100 RTD input
Measuring current approx. 1 mA • Output 4 mA ... 20 mA, temperature
linearization selectable

K-System
Output
Load (U -12 V)/0.02 A • DIP switch selectable ranges
Current output 4 ... 20 mA, limited to ≤ 35 mA • Sensor breakage detection
Fault signal Sensor burnout: upscaling ≥ 22 mA, limited to ≤ 35 mA
Transfer characteristics Function
Measurement range fn span without linearization 25 ... 800 °C (77 ... 1472 °F)/
with linearisation 25 ... 375 °C (77 ... 707 °F) This isolated signal conditioner is a loop-
zero point without linearization -200 ... 400 °C
powered isolator that converts the
(-328 ... 752 °F)/
with linearisation -30 ... 375 °C (-22 ... 707 °F)
resistance from a 3-wire RTD to a
span and zero point adjustable 4 mA ... 20 mA signal and provides
isolation for non-intrinsically safe

Digital Inputs
Deviation
After calibration 0.1 % of full-scale value applications.
Influence of ambient temperature span and zero point 0.015 %/K or ± 10 mΩ/K A selectable analog linearization ensures
Influence of supply voltage 6.5 ppm/V a temperature linear 4 mA ... 20 mA
Rise time 250 ms output between 25 °C ... 375 °C.
Ambient conditions
It also features conveniently located DIP
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
switches and potentiometers to make field
Mechanical specifications
calibration easy.
Protection degree IP20

Digital Outputs
Mass approx. 150 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2

Analog Inputs
Analog Outputs
Diagrams

Front view Rotary switch


range, zero point
coarse adjustment
KFD0-TR-1
Removable terminal 1 2 3
2- 8- green
4 5 6

1 KFD0-TR-1
Span fine adjustment
T T
V Zero point
3+ 9+
fine adjustment
11/2010

Accessories

SPAN

ZERO
908837 (US) / 208599 (EU)

DIP switch
linearization

7 8 9
10 11 12
13 14 15

Removable terminal
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD0-TR-1

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 641
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD0-TT-1 Thermocouple Converter

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 12 ... 35 V DC loop powered
• 24 V DC supply (loop powered)
Input
• Thermocouple input Lead resistance ≤ 100 Ω per lead
• Output 4 mA ... 20 mA Current lead monitoring ON: ≤ 15 nA; OFF: ≤ 1 nA
• Internal cold junction compensation
K-System

Output
• Sensor breakage detection Load (U -12 V)/0.02 A
Current output 4 ... 20 mA, limited to ≤ 35 mA
• DIP switch selectable ranges
Fault signal downscaling ≤ 3 mA, upscaling ≥ 22 mA
Transfer characteristics
Function
Measurement range fn span 4 ... 100 mV, zero point -12 ... 60 mV,
both adjustable
This isolated signal conditioner is a loop-
Deviation
powered isolator that converts
After calibration 0.1 % of full-scale value ± 1 K for the cold junction
thermocouple inputs to a 4 mA ... 20 mA
Temperature effect temperature deviation 0.015 % of the span/K
signal and provides isolation for non-
or 1.5 μV/K cold junction ± 2 K
intrinsically safe applications.
Digital Inputs

(calibrated at Tamb = 20 °C (68 °F))


The internal cold junction compensation Influence of supply voltage 6.5 ppm/V
can be bypassed by using terminals 1 Characteristic curve the output voltage is linearly proportionate to the input
and 3. voltage (not to temperature)
Rise time 250 ms
The output current is linear to input
Ambient conditions
voltage, not proportional to temperature.
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Zero, span, and burnout detection are
Mechanical specifications
field-configurable.
Protection degree IP20
Digital Outputs

Mass approx. 150 g


Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
Analog Inputs
Analog Outputs

Diagrams

Front view Rotary switch


range, zero point
coarse adjustment
KFD0-TT-1
Removable terminal 1 2 3
4 5 6 1+ 8-
green
Span fine adjustment 2-
KFD0-TT-1 mV
Zero point V
3- 9+
fine adjustment
11/2010
Accessories

SPAN

ZERO

DIP switch
908837 (US) / 208599 (EU)

LB, thermocouple type

7 8 9
10 11 12
13 14 15

Removable terminal
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD0-TT-1

642 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Temperature Trip Value KFD2-GU-1

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 19 ... 35 V DC
• 24 V DC supply (Power Rail)
Power consumption 0.8 W
Input
• Thermocouple, RTD, voltage or
RTD or resistance type Pt100 (EN 60751: 1995) current input
type Ni100 (DIN 43760) • 2 relay contact outputs

K-System
0 ... 500 Ω (including lead resistance) • Programmable high/low alarm
Measuring current approx. 400 μA with RTD
• Sensor breakage detection
Lead resistance ≤ 50 Ω per lead
Thermocouples type B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
Function
Load 20 Ω for 20 mA; 200 kΩ for 10 V
This signal conditioner accepts a variety
Output
of inputs including RTDs or
Output I, II
thermocouples and provides a relay trip
Contact loading 253 V AC/2 A/500 VA/cos Φ min. 0.7; 40 V DC/2 A
resistive load whenever it reaches a user-programmed
2 x 107 switching cycles set point. It also provides isolation for non-

Digital Inputs
Mechanical life
Transfer characteristics
intrinsically safe applications.
Deviation A removable terminal block K-CJC-** is
Voltage input ± 0.02 % of 10 V measuring range available for thermocouples when internal
Resistance input ± 0.025 % of measuring range (4-wire connection) cold junction compensation is desired.
Current input ± 0.02 % of 20 mA measuring range A fault is indicated by a red flashing LED
Pt100 ± 0.01 % of abs. temperature value of switching point in per NAMUR NE44 and user-configured
K + 0.2 K (4-wire connection)
fault outputs.
Thermocouple ± 0.05 % of abs. temperature value of switching point in

Digital Outputs
K + 1.1 K (1.2 K for thermocouple types R and S) this The unit is easily programmed with the
includes ± 0.8 K error of the cold junction compensation PACTware™ configuration software.
(+0.9 K for thermocouple types R and S). For additional information, refer to the
Ambient conditions manual and www.pepperl-fuchs.com.
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Protection degree IP20
Mass approx. 150 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2

Analog Inputs
Analog Outputs
Diagrams

Front view Removable terminals


green

KFD2-GU-1
7 1 2 3

I
4 5 6
+ 6 8
9 LED green:
+ 5 KFD2-GU-1
10 Power supply
K-CJC-** 4 11 II LED yellow: LED red:
11/2010

12
Accessories

OUT OUT PWR/

3 Relay output I 1 2 FAULT Fault signal


V
T T T
mA
LED yellow: PROGRAM

1 Programming jack
908837 (US) / 208599 (EU)

+ Relay output II
- - - 2
7 8 9
10 11 12
13 14 15

14+
15-
24 V DC
Removable terminals
green
24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-GU-1

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 643
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD2-GUT-1.D Temperature Converter with Trip Values

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 20 ... 30 V DC
• 24 V DC supply (Power Rail)
Power loss/power consumption ≤ 2 W/2.2 W
• TC, RTD, potentiometer or voltage Input
input RTD Pt100, Pt500, Pt1000, Ni100, Ni1000
• Redundant TC input
K-System

Types of measuring 2-, 3-, 4-wire technology


• Current output 0/4 mA ... 20 mA Lead resistance ≤ 50 Ω
• 2 relay contact outputs Measuring circuit monitoring sensor burnout, sensor short-circuit
Thermocouples type B, E, J, K, L, N, R, S, T
• Line fault (LFD) and sensor burnout
Cold junction compensation external and internal
detection
Measuring circuit monitoring sensor burnout
• Up to SIL2 acc. to IEC 61508
Voltage 0 ... 10 V, 2 ... 10 V, 0 ... 1 V, -100 ... 100 mV
Potentiometer 0.8 ... 20 kΩ
Function
Types of measuring 2-, 3-, 5-wire technology
Input resistance ≥ 250 kΩ (0 ... 10 V)
This signal conditioner is a universal input ≥ 1 MΩ (0 ... 1 V, -100 ... 100 mV)
Digital Inputs

trip alarm that converts the signal of an Measuring current approx. 400 μA with resistance measuring sensor
RTD, thermocouple, potentiometer, or Output
voltage source to a proportional output Output I, II relay
current. It also provides a relay trip value Contact loading 250 V AC/2 A/cos Φ ≥ 0.7; 40 DC/2 A
and isolation for non-intrinsically safe Mechanical life 5 x 107 switching cycles
applications. Energized/De-energized delay approx. 20 ms/approx. 20 ms
A removable terminal block K-CJC-** is Output III analog current output
available for thermocouples when internal Current range 0 ... 20 mA or 4 ... 20 mA
cold junction compensation is desired. ≤ 24 V DC
Digital Outputs

Open loop voltage


The unit is easily programmed by the use Load ≤ 650 Ω
of a keypad located on the front of the unit Fault signal downscale I ≤ 3.6 mA,
or with the PACTware™ configuration upscale I ≥ 21 mA (acc. NAMUR NE43)
software. Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
A unique collective error messaging
Mechanical specifications
feature is available when used with the
Protection degree IP20
Power Rail system.
Mass 300 g
For additional information, refer to the Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in), housing type C3
Analog Inputs

manual and www.pepperl-fuchs.com.


Analog Outputs

Diagrams
Front view
Removable terminals
green

KFD2-GUT-1.D
10
LED green: 1 2 3 4 5 6
+ 6 11 I
KFD2-GUT- LC display 12
Power supply 1.D 4
K-CJC-**
16
OUT
ERR PWR 3 17 II
18
11/2010
Accessories

LED red: 1 2
T T T
mV
Fault signal ESC

1 mA
7- III
RS 232 + 8+
LED yellow: OK
Keypad
Output Ι ... ΙΙ 2
908837 (US) / 208599 (EU)

- -
7 8 9 10 11 12
13 14 15 16 17 18
19 20 21 22 23 24

23+
Programming jack Removable terminals 24-
24 V DC
green

ERR 24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-GUT-1.D

644 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Temperature Converter with Trip Values KFU8-GUT-1.D

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 20 ... 90 V DC/48 ... 253 V AC
• AC/DC wide range supply
Power loss/power consumption ≤ 2 W; 2.5 VA/2.2 W; 3 VA
Input
• TC, RTD, potentiometer or voltage
RTD Pt100, Pt500, Pt1000, Ni100, Ni1000 input
• Redundant TC input

K-System
Types of measuring 2-, 3-, 4-wire technology
Lead resistance ≤ 50 Ω • Current output 0/4 mA ... 20 mA
Measuring circuit monitoring sensor burnout, sensor short-circuit • 2 relay contact outputs
Thermocouples type B, E, J, K, L, N, R, S, T
• Line fault (LFD) and sensor burnout
Cold junction compensation external and internal
detection
Measuring circuit monitoring sensor burnout
• Up to SIL2 acc. to IEC 61508
Voltage 0 ... 10 V, 2 ... 10 V, 0 ... 1 V, -100 ... 100 mV
Potentiometer 0.8 ... 20 kΩ
Function
Types of measuring 2-, 3-, 5-wire technology
Input resistance ≥ 250 kΩ (0 ... 10 V)
≥ 1 MΩ (0 ... 1 V, -100 ... 100 mV)
This signal conditioner is a universal input

Digital Inputs
Measuring current approx. 400 μA with resistance measuring sensor
trip alarm that converts the signal of an
Output
RTD, thermocouple, potentiometer, or
Output I, II relay
voltage source to a proportional output
Contact loading 250 V AC/2 A/cos Φ ≥ 0.7; 40 DC/2 A
current. It also provides a relay trip value
Mechanical life 5 x 107 switching cycles
and isolation for non-intrinsically safe
Energized/De-energized delay approx. 20 ms/approx. 20 ms
applications.
Output III analog current output A removable terminal block K-CJC-** is
Current range 0 ... 20 mA or 4 ... 20 mA available for thermocouples when internal
≤ 24 V DC cold junction compensation is desired.

Digital Outputs
Open loop voltage
Load ≤ 650 Ω The unit is easily programmed by the use
Fault signal downscale I ≤ 3.6 mA, of a keypad located on the front of the unit
upscale I ≥ 21 mA (acc. NAMUR NE43) or with the PACTware™ configuration
Ambient conditions software.
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
For additional information, refer to the
Mechanical specifications
manual and www.pepperl-fuchs.com.
Protection degree IP20
Mass 300 g
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in), housing type C3

Analog Inputs
Analog Outputs
Diagrams
Front view
Removable terminals
green

KFU8-GUT-1.D
10
+ 6 11 I LED green: 1 2 3 4 5 6
12 KFU8-GUT- LC display
4 Power supply 1.D
K-CJC-**
16
3 17 II OUT
ERR PWR

18
11/2010

Accessories

T T T LED red: 1 2
mV
Fault signal ESC

1 mA
7- III
+ 8+ RS 232
LED yellow: OK
Keypad
2 Output Ι ... ΙΙ
908837 (US) / 208599 (EU)

- -
7 8 9 10 11 12
13 14 15 16 17 18
19 20 21 22 23 24

23
24
AC/DC Programming jack Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFU8-GUT-1.D

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 645
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Notes Signal Conditioners
K-System
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs

11/2010
Accessories

908837 (US) / 208599 (EU)


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


646 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Signal Conditioners Selection Tables
Current Drivers

Model Number Input Output (Field) Supply Page


(Control System)

Loop Powered
0 mA ... 40 mA

4 mA ... 20 mA

Fire Alarm

Line Fault
Detection
Channels

24 V DC

K-System
SMART
mA

SIL
KCD2-SCD-1 1     2 648

KFD2-SCD2-1.LK 1      2 649

KFD2-SCD2-2.LK 2      2 650

KFD0-SCS-1.55 1      2 651

KFD0-CS-1.50 1     2 652

Digital Inputs
KFD0-CS-2.50 2     2 653

KFD0-CS-2.51P 2     2 654

Digital Outputs
Analog Inputs
Analog Outputs
11/2010

Accessories
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 647
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KCD2-SCD-1 SMART Current Driver

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage 19 ... 30 V DC
• 24 V DC supply (Power Rail)
Power consumption ≤ 700 mW
• Current output up to 650 Ω load Input
• HART I/P and valve positioner Input signal 4 ... 20 mA limited to approx. 30 mA
• Lead breakage monitoring approx. 6 V or internal resistance 300 Ω at 20 mA
K-System

Voltage drop Ud
• Accuracy 0.1 % Input resistance > 100 kΩ at max. 23 V, with field wiring open
Output
• Housing width 12.5 mm
Current 4 ... 20 mA
• Up to SIL2 acc. to IEC 61508
Load 0 ... 650 Ω
Voltage ≥ 13 V at 20 mA
Function
Ripple 20 mVrms
Transfer characteristics
This signal conditioner drives SMART I/P
Deviation at 20 °C (68 °F), 0/4 ... 20 mA
converters, electrical valves, and ≤ ± 0.1 % incl. non-linearity and hysteresis
positioners and provides isolation for non- Influence of ambient temperature < 2 μA/K (0 ... 60 °C (32 ... 140 °F));
Digital Inputs

intrinsically safe applications. < 4 μA/K (-20 ... 0 °C (-4 ... 32 °F))
Digital signals are superimposed on the Frequency range bandwidth at 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
analog values at the field or control side Rise time 10 to 90 % ≤ 100 ms
and are transferred bi-directionally. Ambient conditions
Current transferred across the DC/DC Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
converter is repeated at terminals 1 Mechanical specifications
and 2. Protection degree IP20
Mass approx. 100 g
An open field circuit presents a high input
Digital Outputs

Dimensions 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 in),


impedance to the control side to allow housing type A2
lead breakage monitoring by control
system.
If the loop resistance for the digital
communication is too low, an internal
resistor of 250 Ω between terminals 6
and 8 is available, which may be used as
the HART communication resistor.
Analog Inputs

Sockets for the connection of a HART


communicator are integrated into the
terminals of the device.
Analog Outputs

Diagrams

Front view Removable terminal


green

KCD2-SCD-1
LED green:
1 2
3 4 Power supply
1+ 7-
KCD2-SCD-1
HART

5-
I

mA
HART

11/2010
P
Accessories

PWR
6+
2-
8+
250 Ω
908837 (US) / 208599 (EU)

5 6
7 8
9 10 Place for labeling 9+
10-
24 V DC

Removable terminals
24 V DC
green
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KCD2-SCD-1

648 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SMART Current Driver KFD2-SCD2-1.LK

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage 10 ... 35 V DC
• 24 V DC supply (Power Rail)
Power consumption 1 W at 20 mA
Input
• Current output up to 700 Ω load
Voltage drop Ud approx. 4 V or internal resistance 200 Ω at 20 mA • HART I/P and valve positioner
• Line fault detection (LFD)

K-System
Input resistance > 100 kΩ, when wiring resistance in the field > 16 V
(equivalent to 800 Ω at 20 mA) • Accuracy 0.05 %
Current 4 ... 20 mA limited to approx. 25 mA
• Terminals with test points
Output
Current 4 ... 20 mA • Up to SIL2 acc. to IEC 61508
Load 100 ... 700 Ω
Voltage ≥ 14 V at 20 mA Function
Transfer characteristics
Deviation
This signal conditioner drives SMART I/P
After calibration at 20 °C (68 °F): 10 μA incl. non-linearity, calibration,
converters, electrical valves, and
hysteresis, supply and load changes positioners and provides isolation for non-

Digital Inputs
Influence of ambient temperature 1 μA/K intrinsically safe applications.
Rise time < 100 μs (bounce from 10 ... 90 %) Digital signals are superimposed on the
Ambient conditions analog values at the field or control side
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) and are transferred bi-directionally.
Mechanical specifications Current transferred across the DC/DC
Protection degree IP20 converter is repeated at terminals 1
Mass approx. 150 g and 2.
Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in), housing type B2
An open and shorted field circuit presents

Digital Outputs
a high input impedance to the control side
to allow line fault detection by control
system.
If the loop resistance for digital
communication is too low, an internal
resistor of 250 Ω between terminals 8
and 9 is available, which may be used as
the HART communication resistor.

Analog Inputs
Sockets for the connection of a HART
communicator are integrated into the
terminals of the device.
A unique collective error messaging
feature is available when used with the
Power Rail system.

Analog Outputs
Diagrams

Front view
Removable terminal
green

KFD2-SCD2-1.LK

1+ 7- 1 2 3
4 5 6
HART
HART
I

mA
P

KFD2-SCD2-1.LK

8+
11/2010

Accessories

2- 9+ LED red: LED green:


CHK1 PWR
250 Ω LB and SC Power supply
908837 (US) / 208599 (EU)

Switch S1:
HART communication
7 8 9
10 11 12
13 14 15
14+
15-
24 V DC

Removable terminals
ERR 24 V DC green
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-SCD2-
1.LK
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 649
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD2-SCD2-2.LK SMART Current Driver

Features Technical data


• 2-channel signal conditioner Supply
Rated voltage 10 ... 35 V DC
• 24 V DC supply (Power Rail)
Power consumption 1.8 W at 20 mA
• Current output up to 700 Ω load Input
• HART I/P and valve positioner Voltage drop Ud approx. 4 V or internal resistance 200 Ω at 20 mA
• Line fault detection (LFD)
K-System

Input resistance > 100 kΩ, when wiring resistance in the field > 16 V
• Accuracy 0.05 % (equivalent to 800 Ω at 20 mA)
Current 4 ... 20 mA limited to approx. 25 mA
• Terminals with test points
Output
• Up to SIL2 acc. to IEC 61508 Current 4 ... 20 mA
Load 100 ... 700 Ω
Function Voltage ≥ 14 V at 20 mA
Transfer characteristics
This signal conditioner drives SMART I/P Deviation
converters, electrical valves, and After calibration at 20 °C (68 °F): 10 μA incl. non-linearity, calibration,
positioners and provides isolation for non- hysteresis, supply and load changes
Digital Inputs

intrinsically safe applications. Influence of ambient temperature 1 μA/K


Digital signals are superimposed on the Rise time < 100 μs (bounce from 10 ... 90 %)
analog values at the field or control side Ambient conditions
and are transferred bi-directionally. Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Current transferred across the DC/DC Mechanical specifications
converter is repeated at terminals 1, 2 Protection degree IP20
and 4, 5. Mass approx. 150 g
Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in), housing type B2
An open and shorted field circuit presents
Digital Outputs

a high input impedance to the control side


to allow line fault detection by control
system.
If the loop resistance for digital
communication is too low, an internal
resistor of 250 Ω between terminals 8, 9
and 11, 12 is available, which may be
used as the HART communication
resistor.
Analog Inputs

Sockets for the connection of a HART


communicator are integrated into the
terminals of the device.
A unique collective error messaging
feature is available when used with the
Power Rail system.
Analog Outputs

Diagrams

Front view
Removable terminals
green

KFD2-SCD2-2.LK

1 2 3 1+ 7-
4 5 6
HART
HART
I

I mA
P

KFD2-SCD2-2.LK

8+
11/2010
Accessories

LED red: LED green: 2- 9+


CHK1 CHK2 PWR

LB and SC Power supply 250 Ω


4+ 10-
HART
HART

908837 (US) / 208599 (EU)


I

II mA
P

Switch S1, S2: 11+


HART communication 5- 12
7 8 9 250 Ω
10 11 12
13 14 15
14+
15-
24 V DC

Removable terminals
green ERR 24 V DC
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-SCD2-
2.LK
650 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SMART Current Driver/Repeater KFD0-SCS-1.55

Technical data Features


Supply • 1-channel signal conditioner
Rated voltage loop powered
• 24 V DC supply (loop powered)
Field circuit
Available voltage ≥ 16 V for supply voltage > 21 V
• Current input/output 4 mA ... 20 mA
Current 4 ... 20 mA (linear transmission 1 ... 22 mA) • HART I/P or transmitter power
≤ 800 Ω (at 20 mA) supply

K-System
Load
Supply circuit • Low voltage drop
Voltage max. 30 V DC • Line fault detection (LFD)
Current 4 ... 20 mA (quiescent current < 0.5 mA)
• Up to SIL2 acc. to IEC 61508
Power loss 150 mW at 20 mA and UE < 24 V
Transfer characteristics
Function
Deviation
After calibration ≤ ± 80 μA linearity, load and voltage dependence This signal conditioner is loop powered
at 20 °C (68 °F)
and isolates a 4 mA ... 20 mA signal for
Influence of ambient temperature < 0.5 μA/K
transmitters and positioners and is HART
Damping approx. 3 dB
compatible.

Digital Inputs
Rise time ≤ 20 μs at 0 Ω, ≤ 600 μs with 800 Ω load
Ambient conditions The low voltage drop of 5 V in comparison
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) to active signal conditioners also allows
Mechanical specifications transmitter applications with unstable
Protection degree IP20 power sources between
Mass approx. 120 g 20 V DC ... 30 V DC.
Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in), housing type B2 Line fault detection of the field circuit is
possible if the control loop in the safe area

Digital Outputs
is monitored for overscale or underscale
conditions of the 4 mA ... 20 mA range.
The module can also be used for
controlling solenoid valves and discrete
outputs, such as LEDs. In this case,
terminals 8- and 9+ are driven with a 24 V
signal.

Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminal
green

KFD0-SCS-1.55

1+ 8- 1 2 3
4 5 6
HART
HART

mA
V
P

KFD0-SCS-1.55

9+
11/2010

Accessories

2-
3-
908837 (US) / 208599 (EU)

7 8 9
10 11 12
13 14 15

Removable terminal
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD0-SCS-1.55

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 651
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD0-CS-1.50 Current Driver/Repeater

Features Technical data


• 1-channel signal conditioner Supply
Rated voltage loop powered
• 24 V DC supply (loop powered)
Input
• Current input/output 4 mA ... 20 mA Rated voltage Ui 10 ... 35 V
• I/P or transmitter power supply Rated current Ii 4 ... 20 mA
• Accuracy 0.1 %
K-System

Power loss < 150 mW per channel at 25 mA and U < 26.1 V


• Up to SIL2 acc. to IEC 61508 < 400 mW per channel at 25 mA and U > 26.1 V
Output
Function Voltage ≥ 0.9 x Uin - (0.23 x current in mA) - 0.7
for 10 V < Uin < 26.1 V
≥ 23 V - (0.23 x current in mA) for Uin > 26.1 V
This signal conditioner transfers DC
Short-circuit current ≤ 100 mA
signals from fire alarms, smoke alarms,
Transfer current ≤ 25 mA
and temperature sensors and provides
Transfer characteristics
isolation for non-intrinsically safe
Deviation
applications. It can also be used to control
After calibration Uin ≥ 5 V ± 20 μA/Uin ≤ 5 V ± 50 μA incl. calibration,
I/P converters, power solenoids, LEDs,
Digital Inputs

linearity, hysteresis and output load fluctuations


and audible alarms. at 20 °C (68 °F)
Since this isolator is loop powered, use Influence of ambient temperature ≤ 2 μA/K (0 ... 50 °C (32 ... 122 °F));
the technical data to verify that proper ≤ 5 μA/K (-20 ... 60 °C (-4 ... 140 °F))
voltage is available to the field devices. Rise time ≤ 5 ms at 4 ... 20 mA and Uin = input voltage < 26 V
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Protection degree IP20
Digital Outputs

Mass approx. 100 g


Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in), housing type B1
Analog Inputs
Analog Outputs

Diagrams

Front view
Removable terminal
green
KFD0-CS-1.50
1 2 3
4 5 6
1+ 11+
I

KFD0-CS-1.50
P

mA
V
2- 12-
11/2010
Accessories

908837 (US) / 208599 (EU)

7 8 9
10 11 12
Removable terminal
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD0-CS-1.50

652 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Current Driver/Repeater KFD0-CS-2.50

Technical data Features


Supply • 2-channel signal conditioner
Rated voltage loop powered
• 24 V DC supply (loop powered)
Input
Rated voltage Ui 10 ... 35 V
• Current input/output 4 mA ... 20 mA
Rated current Ii 4 ... 20 mA • I/P or transmitter power supply
• Accuracy 0.1 %

K-System
Power loss < 150 mW per channel at 25 mA and U < 26.1 V
< 400 mW per channel at 25 mA and U > 26.1 V • Up to SIL2 acc. to IEC 61508
Output
Voltage ≥ 0.9 x Uin - (0.23 x current in mA) - 0.7 Function
for 10 V < Uin < 26.1 V
≥ 23 V - (0.23 x current in mA) for Uin > 26.1 V
This signal conditioner transfers DC
Short-circuit current ≤ 100 mA
signals from fire alarms, smoke alarms,
Transfer current ≤ 25 mA
and temperature sensors and provides
Transfer characteristics
isolation for non-intrinsically safe
Deviation
applications. It can also be used to control
After calibration Uin ≥ 5 V ± 20 μA/Uin ≤ 5 V ± 50 μA incl. calibration,
I/P converters, power solenoids, LEDs,

Digital Inputs
linearity, hysteresis and output load fluctuations
at 20 °C (68 °F) and audible alarms.
Influence of ambient temperature ≤ 2 μA/K (0 ... 50 °C (32 ... 122 °F)); Since this isolator is loop powered, use
≤ 5 μA/K (-20 ... 60 °C (-4 ... 140 °F)) the technical data to verify that proper
Rise time ≤ 5 ms at 4 ... 20 mA and Uin = input voltage < 26 V voltage is available to the field devices.
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Protection degree IP20

Digital Outputs
Mass approx. 100 g
Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in), housing type B1

Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminals
green
KFD0-CS-2.50
1 2 3
1+ 11+ 4 5 6
I

I KFD0-CS-2.50
P

mA
V
2- 12-
11/2010

Accessories

4+ 9+
I

II
908837 (US) / 208599 (EU)

mA
V
5- 10-
8- 7 8 9
10 11 12
Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD0-CS-2.50

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 653
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD0-CS-2.51P Current Driver/Repeater

Features Technical data


• 2-channel signal conditioner Supply
Rated voltage loop powered
• 24 V DC supply (loop powered)
Input
• Current input/output 0 mA ... 40 mA Rated voltage Ui 4 ... 35 V
• I/P or transmitter power supply Rated current Ii 0 ... 40 mA
• Accuracy 1 %
K-System

Power loss at 40 mA and Uin < 22 V: 700 mW per channel


• Reverse polarity protection at 40 mA and Uin > 22 V: 1.2 W per channel
Output
• Up to SIL2 acc. to IEC 61508
Voltage for 4 V < Uin < 24 V:
≥ 0.9 x Uin - (0.37 x current in mA) - 1.0
Function for Uin > 24 V: ≥ 21 V - (0.36 x current in mA)
Short-circuit current at Uin > 24 V: ≤ 65 mA
This signal conditioner transfers DC Transfer current ≤ 40 mA
signals from fire alarms, smoke alarms, Transfer characteristics
and temperature sensors to the control Deviation
and provides isolation for non-intrinsically After calibration ≤ ± 200 μA; incl. calibration, linearity, hysteresis and
safe applications. It can also be used to
Digital Inputs

load fluctuations at the output up to a load of 1 kΩ and


control I/P converters, power solenoids, current ≤ 20 mA at 20 °C (68 °F)
LEDs, and audible alarms. Influence of ambient temperature ≤ ± 2 μA/K at Uin ≤ 20 V; ≤ ± 5 μA/K at Uin > 20 V
Reverse polarity protection prevents Rise time ≤ 5 ms at 4 ... 20 mA step and Uin < 24 V
damage to the isolator caused by faulty Ambient conditions
wiring. Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Since this isolator is loop powered, use
Protection degree IP20
the technical data to verify that proper
Mass approx. 100 g
Digital Outputs

voltage is available to the field devices.


Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in), housing type B1
Analog Inputs
Analog Outputs

Diagrams

Front view
Removable terminals
green
KFD0-CS-2.51P
1 2 3
4 5 6
1+ 11+
I

KFD0-CS-2.51P
I
P

mA
V
2- 12-
11/2010
Accessories

4+ 9+
I

II
908837 (US) / 208599 (EU)
P

mA
V
5- 10-
7 8 9 8-
10 11 12
Removable terminals
green
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD0-CS-2.51P

654 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Signal Conditioners Selection Tables
Supply and Installation

Model Number Description Page

KFA6-STR-1.24.500 Power Supply, 24 V, 500 mA 657

KFA6-STR-1.24.4 Power Supply, 24 V, 4 A 658

KFD2-EB2 Power Feed Module 659

K-System
KFD2-EB2.R4A.B Redundant Power Feed Module 660

UPR-03-* Universal Power Rail, insert for DIN rail, 3-lead 661

UPR-05-* Universal Power Rail, insert for DIN rail, 5-lead 662

UPR-E End Cap for Universal Power Rail UPR-**-* 661, 662

UPR-I Insulation Spacer for Universal Power Rail UPR-**-* 665

K-DUCT-GY-UPR-03 Profile Rail with UPR-03-* insert, 3-lead, wiring comb field side grey 663

K-DUCT-GY-UPR-05 Profile Rail with UPR-05-* insert, 5-lead, wiring comb field side grey 664

Digital Inputs
E/AL-NS35 End Bracket 666

TS 35 Typ 12 End Bracket 666

K-MS Mounting Socket 665

Terminal Blocks

Digital Outputs
Model Number Description Type Module Packaging Unit, Page
Color
Number of Poles
Screw Terminal

Compensation
Cold Junction
Test Sockets
KC-Modules
Cage Clamp

KF-Modules
Terminal

Green

Black

Red

Analog Inputs
K-CJC-BK Terminal Block   3  1 667

KC-ST-5GN Terminal Block   2 5 667

KF-ST-5GN Terminal Block   3 5 668

KC-STP-5GN Terminal Block   2  5 668

KF-STP-5GN Terminal Block   3  5 669

KC-CTT-5GN Terminal Block   2  5 669

Analog Outputs
KF-CTT-5GN Terminal Block   3  5 670

KF-CP Coding Pins   20 x 6 670

Commissioning

Model Number Description Page


11/2010

Accessories

PACTware TM 4.X FDT-Framework 671

K-ADP-USB Adapter with USB Interface 672


908837 (US) / 208599 (EU)

K-ADP1 Adapter with RS 232 Interface 673


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 655
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Selection Tables Signal Conditioners

Further Accessories

Model Number Description Page

K-500R0%1 Measuring Resistor 674

KF-SEAL Adhesive Sticker 674

KFD0-LGH-GN Place Holder Barrier, KF Module 675


K-System

KFD0-LGH-Y34868 Place Holder Barrier, KF Module 676


Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs

11/2010
Accessories

908837 (US) / 208599 (EU)


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


656 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Power Supply KFA6-STR-1.24.500

Technical data Features


Supply • 115/230 V AC supply
Rated voltage 90 ... 253 V AC, 48 ... 63 Hz
• Output 24 V DC, 500 mA
Power loss 2.5 W
Output
• Electronic short circuit protection
Current 500 mA at 60 °C (140 °F), permanent short-circuit • Power Rail connection
protection (electronic)

K-System
Voltage 24 V ± 0.5 V Function
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) This regulated power supply provides
Mechanical specifications 24 V DC, at 500 mA.
Protection degree IP20 The KFA6-STR-1.24.500 features
Mass approx. 140 g removable terminals and mounts directly
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2 on the Power Rail. This allows usage as
Power Rail supply as well as stand alone
power supply.

Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs
Diagrams

Front view

KFA6-STR-1.24.500
1 2 3
4 5 6

LED green:
KFA6-STR-1.24.500
Power supply
11/2010

Accessories

14 115 V AC/ PWR

15 230 V AC
908837 (US) / 208599 (EU)

~ 7+
24 V DC 7 8 9
8- 10 11 12
13 14 15

Removable terminals
24 V DC
green
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFA6-STR-
1.24.500
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 657
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFA6-STR-1.24.4 Power Supply

Features Technical data


• 115/230 V AC supply Supply
Rated voltage 92 ... 265 V AC, 47 ... 63 Hz
• Output 24 V DC, 4 A
Rated current 2.1 ... 0.84 A
• Fused output Failure override time > 75 ms/230 V AC; 5 ms/115 V AC
• Power Rail connection Output
K-System

Current 0 ... 4 A, Power Rail limiting by means of fuse 4 AT,


Function electron. limitation typ. 4.6 A
Voltage 23.28 ... 24.72 V DC
This regulated power supply provides Ripple < 100 mVpp
24 V DC, at 4 A. It features removable Efficiency typ. 87 %
terminals, LED fault indication, and Overvoltage protected < 28 V DC
mounts directly on the Power Rail. Electromagnetic compatibility
Designed with a replaceable fuse and Safety acc. to VDE 0805/EN 60950
LED, it will provide a green visual Radio-interference supression acc. to VDE 0875 Part 11, EN 55011 class B
indication for normal operation or a Electrostatic discharge acc. to IEC 60801-2
flashing red indication if a fault occurs. Contact discharging 8 kV
Digital Inputs

Air discharging 15 kV
Attention: Ignoring the safety instructions
Electromagnetic fields acc. to IEC 801-3, 10 V/m
(i. e., touching hot sections when the
Burst IEC 60801-4 Input: 4 kV; output/capacitively coupled: 2 kV
device is open, handling malpractices)
Surge IEC 60801-5 asymmetrical: L, N -> PE 4 kV;
can be extremely dangerous.
symmetrical: L -> N 2 kV
When exceeding the values stated in the Ambient conditions
technical data, there is a danger of Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
overheating. As a result, the operation of Mechanical specifications
the power supply and its electrical safety Protection degree IP20
Digital Outputs

may be impaired. Mass approx. 800 g


Before starting installation or service, Dimensions 140 x 103.5 x 99 mm (5.5 x 4.1 x 3.9 in)
switch mains off. Do not plug or unplug Mounting mounting clips for snap-mounting on DIN rail as
powered! per DIN EN 60715
Connection possibilities self-opening connection terminals,
max. core cross-section 2 x 2.5 mm2
Data for application in connection
with Ex-areas
UL approval UL recognized E185902
Analog Inputs
Analog Outputs

Diagrams

Front view
LED green indicates output voltage, KFA6-STR-1.24.4
flashing red indicates a fault exists
11/2010
Accessories

230 V AC
908837 (US) / 208599 (EU)

4 AT
~ 4+
24 V DC
6-

24 V DC
Fuse carrier Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFA6-STR-
1.24.4
658 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Power Feed Module KFD2-EB2

Technical data Features


Supply • Interface for Power Rail
Rated voltage 20 ... 30 V DC
The maximum rated operational voltage of the devices
• Supply rating 4 A, external fused
plugged onto the Power Rail must not be exceeded. • Relay contact output, reversible
Power loss ≤1 W • LED status indication
Output

K-System
Power Rail feed output current: ≤ 4 A Function
Fault signal relay output: NO
Contact loading 40 V DC; 2 A The power feed module interfaces
Energized/De-energized delay approx. 20 ms/approx. 20 ms 24 V DC power to the Power Rail at a
Fusing 5 AT maximum current of 4 A. The twin input
Ambient conditions terminals allow for daisy-chaining of
Ambient temperature -25 ... 60 °C (-13 ... 140 °F) supply (max. 10 A).
Mechanical specifications A green LED on the front of the unit
Protection degree IP20 indicates that power is on, and a red LED
Mass approx. 100 g illuminates during error conditions.

Digital Inputs
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
In the event of a field wiring or barrier fault
Data for application in connection
with Ex-areas from any barrier on the Power Rail, the
Statement of conformity TÜV 00 ATEX 1618 X integral collective error messaging relay
Group, category, type of protection, ¬ II 3G Ex nA nC IIC T4 alerts the controller via a single discrete
temperature classification I/O point.
FM approval This relay can be configured as normally
Control drawing 116-0160 open or normally closed.
Approved for Class I, Division 2, Groups A, B, C, D;

Digital Outputs
In the sense of functional safety (SIL) the
Class I, Zone 2, IIC
device provides no dangerous failures.
CSA approval
Thereby the safe condition of the supplied
Control drawing 116-0160
barrier must be defined as the powerless
Approved for Class I, Division 2, Groups A, B, C, D;
Class I, Zone 2, IIC
state. Thus the device will not influence
the safety calculation or the SIL value.
This device is compatible with all versions
of the Power Rail.

Analog Inputs
Analog Outputs
Diagrams

Front view

KFD2-EB2
1 2 3
4 5 6
7 LED red:
Fault signal KFD2-EB2
10
Switch S1
mode of operation
11/2010

Accessories

ERR PWR

LED green: S1 I II
Position I: ON
Power supply 5 AT
Position II: OFF

!
908837 (US) / 208599 (EU)

Fuse carrier
5 AT
8+ 7 8 9
11+ 10 11 12
13 14 15
24 V DC
9-
12-

Removable terminals
ERR 24 V DC Zone 2 green
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-
EB2
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 659
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD2-EB2.R4A.B Redundant Power Feed Module

Features Technical data


• Interface for Power Rail Supply
Rated voltage 20 ... 30 V DC
• Used for redundant configuration The maximum rated operational voltage of the devices
• Supply rating 4 A, external fused plugged onto the Power Rail must not be exceeded.
• Relay contact output, reversible Power loss ≤ 2.4 W
Output
K-System

Function Power Rail feed output current: ≤ 4 A


Fault signal relay output: NO
The power feed module interfaces Contact loading 40 V DC; 2 A
24 V DC power to the Power Rail at a Energized/De-energized delay approx. 20 ms/approx. 20 ms
maximum current of 4 A and is designed Fusing 5 AT
for applications requiring redundant Ambient conditions
power. The twin input terminals allow for Ambient temperature -25 ... 60 °C (-13 ... 140 °F)
daisy-chaining of supply (max. 10 A). Mechanical specifications
A green LED on the front of the unit Protection degree IP20
indicates that power is on, and a red LED Mass approx. 100 g
Digital Inputs

illuminates during error conditions. Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in), housing type B2
Data for application in connection
In the event of a field wiring or barrier fault with Ex-areas
from any barrier on the Power Rail, the Statement of conformity TÜV 00 ATEX 1618 X
integral collective error messaging relay Group, category, type of protection, ¬ II 3G Ex nA nC IIC T4
alerts the controller via a single digital temperature classification
I/O point. This relay can be configured as FM approval
normally open or normally closed. Control drawing 116-0160
Additionally, the bus implemented in the Approved for Class I, Division 2, Groups A, B, C, D;
Digital Outputs

Power Rail is forwarded to the outside Class I, Zone 2, IIC


terminals 13 and 15 for usage with KFD2- CSA approval
WAC2-Ex1.D RS 485 connection. Control drawing 116-0160
Terminal 14 is only for test purposes. Approved for Class I, Division 2, Groups A, B, C, D;
Class I, Zone 2, IIC
In the sense of functional safety (SIL) the
device provides no dangerous failures.
Thereby the safe condition of the supplied
barrier must be defined as the powerless
Analog Inputs

state. Thus the device will not influence


the safety calculation or the SIL value.
This device is compatible with all versions
of the Power Rail and provides group
fusing.
Note: Redundant systems require two
KFD2-EB.R4A.B modules.
Analog Outputs

Diagrams

Front view

KFD2-EB2.R4A.B
1 2 3
4 5 6

LED red: 7
Fault signal KFD2-EB2.R4A.B
10
Switch S1
mode of operation
11/2010
Accessories

ERR PWR

LED green: S1 I II
Position I: ON 14 ERR
Power supply 5 AT
Position II: OFF
13 BUS
! 15
908837 (US) / 208599 (EU)

Fuse carrier
5 AT
7 8 9
8+
10 11 12 11+
13 14 15
24 V DC
9-
12-

Removable terminals
green BUS ERR 24 V DC Zone 2
Power Rail
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD2-
EB2.R4A.
660 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Universal Power Rail UPR-03-*

Dimensions Features
• Gold plated 3-conductor insert in
2 conductors for power supply 1 conductor for 35 mm DIN rail acc. to EN 60715
collective • Provides DC supply voltage to all
error message
Cover equipped K-System modules
• Standard length 0.8 m (2.6 ft) or

K-System
2 m (6 ft), simple to customize to
application space
• Eliminates daisy-chains

Function

Universal Power Rail


The universal Power Rail is a plastic
insert with integral gold-plated conductors
Mount using M4
that fits into its own integral, 35 mm
screws with DIN rail and supplies components with

Digital Inputs
washers per power.
DIN 125
End cap UPR-E It has two conductors for power and one
conductor for collective error messaging.
m
5m DIN rail It reduces wiring and maintenance costs
12 35 mm x 15 mm
because it eliminates the need to daisy-
Slot for holding chain the wires. It also simplifies
Universal Power Rail expansion – just snap in a new module
when you’re ready to expand a system.

Digital Outputs
It comes in 2 m segments (UPR-03) or in
0.8 m segments (UPR-03-S) but can be
Technical data cut to any size.
Electrical specifications
It is delivered with two UPR-E end caps.
Rated voltage 24 V DC
More end caps can be ordered
Rated current 4A
separately.
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
In conjunction with K-System modules the
Mechanical specifications universal Power Rail can be mounted in
Zone 2.

Analog Inputs
Dimensions UPR-03-S: 35 x 15 x 800 mm (1.4 x 0.6 x 31.5 in)
UPR-03: 35 x 15 x 2000 mm (1.4 x 0.6 x 78.7 in)

Accessories
UPR-E
End cap for UPR-03-* and UPR-05-*

Analog Outputs
11/2010

Accessories
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


UPR-03

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 661
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
UPR-05-* Universal Power Rail

Features Dimensions
• Gold plated 5-conductor insert in
35 mm DIN rail acc. to EN 60715 2 conductors for power supply 1 conductor for
• Provides DC supply voltage and the collective
error message
bus connection to all equipped Cover
K-System modules
K-System

• Standard length 0.8 m (2.6 ft) or


2 m (6 ft), simple to customize to
application space
• Eliminates daisy-chains 2 conductors for
bus connection
Function
Universal Power Rail
The universal Power Rail is a plastic
insert with integral gold-plated conductors
that fits into its own integral, 35 mm Mount using M4
Digital Inputs

DIN rail and supplies components with screws with washers


power. per DIN 125
End cap UPR-E
It has two conductors for power, one
conductor for collective error messaging, DIN rail
and two conductors for bus connections. 35 mm x 15 mm

It reduces wiring and maintenance costs Slot for holding


because it eliminates the need to daisy- Universal Power Rail
chain the wires. It also simplifies
Digital Outputs

expansion – just snap in a new module


when you’re ready to expand a system.
It comes in 2 m segments (UPR-05) or in Technical data
0.8 m segments (UPR-05-S) but can be Electrical specifications
cut to any size. Rated voltage 24 V DC
Rated current 4A
It is delivered with two UPR-E end caps.
Ambient conditions
More end caps can be ordered
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
separately.
Mechanical specifications
In conjunction with K-System modules the
Analog Inputs

Dimensions UPR-05-S: 35 x 15 x 800 mm (1.4 x 0.6 x 31.5 in)


universal Power Rail can be mounted in UPR-05: 35 x 15 x 2000 mm (1.4 x 0.6 x 78.7 in)
Zone 2.

Accessories
UPR-E
End cap for UPR-03-* and UPR-05-*
Analog Outputs

11/2010
Accessories

908837 (US) / 208599 (EU)


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


UPR-05

662 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Profile Rail K-DUCT-GY-UPR-03

Dimensions Features
• Cable trunking with integrated
Power Rail UPR-03
35
Power Rail • Safe spacious separation of field and
insert control signals
Wiring comb • No additional cable guides

K-System
grey necessary
• Provides DC supply voltage to all
equipped K-System modules
• Standard length 1.8 m (5.8 ft), simple
to customize to application space

114.4
Wiring comb
grey

100
Function

The profile rail can be used to provide


space-saving mounting for interface

Digital Inputs
Isolating wall modules and accommodate the
associated wiring. The system and field
cables are easily installed in the integral
130 cable ducts of the profile rail. Thus no
additional cable guides are necessary.
Compartment for Compartment for
connection cable connection cable The power supply to the individual
Field side Control side modules is preferably provided via the
Power Rail UPR-03 that is integrated into

Digital Outputs
the system. Additionally the Power Rail
UPR-03 has one lead for collective error
Technical data messaging.
Mechanical specifications The asymmetrical segmented connection
Dimensions 130 x 114.4 x 1800 mm (5 x 4.5 x 71 in) compartment can be changed dependent
on the required space by turning the
profile rail. Please note that the
Power Rail insert must be also rotated.
In conjunction with K-System modules the

Analog Inputs
profile rail can be mounted in Zone 2.

Analog Outputs
11/2010

Accessories
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


K-DUCT-GY-
UPR-03
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 663
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K-DUCT-GY-UPR-05 Profile Rail

Features Dimensions
• Cable trunking with integrated
Power Rail UPR-05
35
• Safe spacious separation of field and Power Rail
control signals insert

• No additional cable guides Wiring comb


K-System

necessary grey
• Provides DC supply voltage and the
bus connection to all equipped
K-System modules
• Standard length 1.8 m (5.8 ft), simple

114.4
Wiring comb
to customize to application space grey

100
Function

The profile rail can be used to provide


Digital Inputs

space-saving mounting for interface Isolating wall


modules and accommodate the
associated wiring. The system and field
cables are easily installed in the integral 130
cable ducts of the profile rail. Thus no
Compartment for Compartment for
additional cable guides are necessary. connection cable connection cable
The power supply to the individual Field side Control side
modules is preferably provided via the
Digital Outputs

Power Rail UPR-05 that is integrated into


the system. Additionally the Power Rail
UPR-05 has one lead for collective error Technical data
messaging and two leads for bus Mechanical specifications
connections. Dimensions 130 x 114.4 x 1800 mm (5 x 4.5 x 71 in)
The asymmetrical segmented connection
compartment can be changed dependent
on the required space by turning the
profile rail. Please note that the
Analog Inputs

Power Rail insert must be also rotated.


In conjunction with K-System modules the
profile rail can be mounted in Zone 2.
Analog Outputs

11/2010
Accessories

908837 (US) / 208599 (EU)


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


K-DUCT-GY-
UPR-05
664 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Signal Conditioners Accessories

57.2 4 Insulation Spacer for UPR-**-*


UPR-I
Features
• Electrical insulation of segmented
60.1 Power Rail inserts

K-System
Function
The insulation spacer mounts onto a
35 mm DIN rail. It is used for electrical
insulation of segmented Power Rail
inserts.
Technical data
Mechanical specifications
Material Polycarbonate
Mass approx. 20 g

Digital Inputs
Dimensions 4 x 57 x 60 mm (0.16 x 2.24 x 2.36 in)
Mounting mounting on 35 mm DIN rail acc. to DIN EN 60715

79 20 Mounting Socket
K-MS
Features
20

Digital Outputs
• 1-channel
• KF module DIN rail isolation block
50
• Snaps on to 35 mm DIN rail
acc. to EN 60715
• Easy panel mounting
ø5
ø8

Function
This mounting socket enables the "snap-

Analog Inputs
on" mounting of K devices on a 35 mm
DIN rail when there is not enough space
to install the Power Rail device contacts.
Sockets can be mounted in rows, so
mounting can be accomplished with a
minimum loss of space. The socket may
also be used to cover unused mounting
positions on the Power Rail.

Analog Outputs
11/2010

Accessories

35 mm DIN rail per EN 60715

Technical data
908837 (US) / 208599 (EU)

Mechanical specifications
Material Polyamide PA 66
Mass approx. 30 g
Dimensions 20 x 20 x 79 mm (0.8 x 0.8 x 3.1 in)
Mounting mounting on 35 mm DIN rail acc. to DIN EN 60715
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 665
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Accessories Signal Conditioners

End Bracket 59

E/AL-NS35
Features
• For end support

44
Function
K-System

The end bracket is used for end support of


devices on the 35 mm DIN rail. It is
pushed onto DIN rail and fixed with two

10
screws.
Note: This component is not supplied by
Pepperl+Fuchs. Technical data
Supplier: Phoenix Contact Mechanical specifications
Material aluminium
Mass approx. 25 g
Digital Inputs

Dimensions 10 x 44 x 59 mm (0.4 x 1.7 x 2.3 in)


Mounting mounting on 35 mm DIN rail acc. to DIN EN 60715

End Bracket 40
TS 35 Typ 12 27 10

Features
Digital Outputs

• End terminal as termination for

34
DIN rail

26
Function
TS 35 Type 12 end brackets are used as
terminations when K devices are mounted Technical data
on the DIN rail. Mechanical specifications
Note: This component is not supplied by Mass approx. 10 g
Pepperl+Fuchs. Dimensions 10 x 34 x 40 mm (0.4 x 1.34 x 1.57 in)
Analog Inputs

Mounting mounting on 35 mm DIN rail acc. to DIN EN 60715


Supplier: Wago
Analog Outputs

11/2010
Accessories

908837 (US) / 208599 (EU)


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


666 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Signal Conditioners Accessories

18 15.16
Terminal Block with Cold Junction
Compensation
K-CJC-BK
Features

15
• 3-pin screw terminal

K-System
• For KF modules
Potted Pt100 RTD • Integrated Cold Junction
in a 2-wire configuation
Compensation
• Packaging unit: 1 piece, black
Technical data
Mechanical specifications Function
Core cross-section max. 2.5 mm2
Mass approx. 5 g The terminal block is suitable for
Dimensions 15.2 x 15 x 18 mm (0.6 x 0.6 x 0.7 in) K-System applications.
Construction type removable screw terminal with integrated cold junction The blue terminal block is used for
compensation

Digital Inputs
connection of signals from or in the
hazardous area.
The black terminal block is used for
connection of field signals as well as the
connection of control signals.
This terminal block has an integrated
encapsulated Pt100 RTD for cold junction
compensation.

Digital Outputs
The terminal block can be coded with the
provided coding pins KF-CP.

18.2 10.1
Terminal Block
KC-ST-5GN
Features
15

• 2-pin screw terminal

Analog Inputs
• For KC modules
• Packaging unit: 5 pieces green
Technical data
Function
Mechanical specifications
Core cross-section max. 2.5 mm2 The terminal block is suitable for K-
Mass approx. 4 g System applications.
Dimensions 10.1 x 15 x 18.2 mm (0.4 x 0.5 x 0.7 in) The blue terminal block is used for

Analog Outputs
Construction type removable screw terminal connection of signals from or in the
hazardous area.
Notes The green terminal block is used for
connection of field signals as well as the
The removable terminals guarantee protection from direct contact by means of connection of control signals.
a strengthened insulation. This applies to design insulation voltages with the
The terminal block can be coded with the
occurrence of maximum overvoltages in accordance with overvoltage
provided coding pins KF-CP.
category III of EN 50178 (1500 V AC).
The voltage is to be switched off in the case of design insulation voltages greater
11/2010

Accessories

than 50 V AC before connecting or disconnecting the device connectors.


908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 667
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Accessories Signal Conditioners

Terminal Block 18.2 15.1


KF-ST-5GN
Features

15
• 3-pin screw terminal
• For KF modules
K-System

• Packaging unit: 5 pieces green

Function Technical data


Mechanical specifications
The terminal block is suitable for K- Core cross-section max. 2.5 mm2
System applications. Mass approx. 5 g
The blue terminal block is used for Dimensions 15.1 x 15 x 18.2 mm (0.5 x 0.5 x 0.7 in)
connection of signals from or in the Construction type removable screw terminal
hazardous area.
The green terminal block is used for Notes
connection of field signals as well as the
Digital Inputs

connection of control signals. The removable terminals guarantee protection from direct contact by means of
The terminal block can be coded with the a strengthened insulation. This applies to design insulation voltages with the
provided coding pins KF-CP. occurrence of maximum overvoltages in accordance with overvoltage
category III of EN 50178 (1500 V AC).
The voltage is to be switched off in the case of design insulation voltages greater
than 50 V AC before connecting or disconnecting the device connectors.
Digital Outputs

Terminal Block with Test Points Test socket for


21.3 10.1
KC-STP-5GN 2/2.3 mm connector

Features

15
• 2-pin screw terminal
• For KC modules
• Integrated test points for connection
of HART communicators Technical data
Analog Inputs

• Packaging unit: 5 pieces green Mechanical specifications


Core cross-section max. 2.5 mm2
Function
Mass approx. 4 g
The terminal block is suitable for K- Dimensions 10.1 x 15 x 21.3 mm (0.4 x 0.5 x 0.84 in)
System applications. Construction type removable screw terminal with integrated test points

The blue terminal block is used for


connection of signals from or in the Notes
hazardous area.
Analog Outputs

The green terminal block is used for The removable terminals guarantee protection from direct contact by means of
connection of field signals as well as the a strengthened insulation. This applies to design insulation voltages with the
connection of control signals. occurrence of maximum overvoltages in accordance with overvoltage
category III of EN 50178 (1500 V AC).
This terminal block has integrated test
points for connection of HART The voltage is to be switched off in the case of design insulation voltages greater
communicators. than 50 V AC before connecting or disconnecting the device connectors.
The terminal block can be coded with the
provided coding pins KF-CP.
11/2010
Accessories

908837 (US) / 208599 (EU)


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


668 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Signal Conditioners Accessories

Test socket for


Terminal Block with Test Points
21 15.16
2/2.3 mm connector KF-STP-5GN
Features
• 3-pin screw terminal

15
• For KF modules

K-System
• Integrated test points for connection
of HART communicators
• Packaging unit: 5 pieces green
Technical data
Mechanical specifications Function
Core cross-section max. 2.5 mm2
Mass approx. 5 g The terminal block is suitable for
Dimensions 15.2 x 15 x 21 mm (0.6 x 0.6 x 0.83 in) K-System applications.
Construction type removable screw terminal with integrated test points The blue terminal block is used for
connection of signals from or in the
hazardous area.

Digital Inputs
Notes
The green terminal block is used for
The removable terminals guarantee protection from direct contact by means of connection of field signals as well as the
a strengthened insulation. This applies to design insulation voltages with the connection of control signals.
occurrence of maximum overvoltages in accordance with overvoltage This terminal block has integrated test
category III of EN 50178 (1500 V AC). points for connection of HART
The voltage is to be switched off in the case of design insulation voltages greater communicators.
than 50 V AC before connecting or disconnecting the device connectors. The terminal block can be coded with the

Digital Outputs
provided coding pins KF-CP.

Terminal Block with Test Points


25.6 10.1 Test socket for
Test point 2/2.3 mm connector KC-CTT-5GN
Features
15

• 2-pin cage clamp terminal


• For KC modules

Analog Inputs
• Integrated test points for connection
of HART communicators
Technical data • Packaging unit: 5 pieces green
Mechanical specifications
Core cross-section max. 2.5 mm2 Function
Mass approx. 4 g
Dimensions 10.1 x 15 x 25.6 mm (0.4 x 0.5 x 1 in) The terminal block is suitable for
Construction type removable cage clamp terminal with integrated test K-System applications.

Analog Outputs
points
The blue terminal block is used for
connection of signals from or in the
Notes hazardous area.
The green terminal block is used for
The removable terminals guarantee protection from direct contact by means of connection of field signals as well as the
a strengthened insulation. This applies to design insulation voltages with the connection of control signals.
occurrence of maximum overvoltages in accordance with overvoltage
This terminal block has integrated test
category III of EN 50178 (1500 V AC).
points for connection of HART
The voltage is to be switched off in the case of design insulation voltages greater communicators.
11/2010

Accessories

than 50 V AC before connecting or disconnecting the device connectors.


The terminal block can be coded with the
provided coding pins KF-CP.
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 669
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Accessories Signal Conditioners

Terminal Block with Test Points


25.1 15.9 Test socket for
KF-CTT-5GN Test point 2/2.3 mm connector

Features

15
• 3-pin cage clamp terminal
• For KF modules
K-System

• Integrated test points for connection


of HART communicators
• Packaging unit: 5 pieces green
Technical data
Mechanical specifications
Function Core cross-section max. 2.5 mm2
Mass approx. 5 g
The terminal block is suitable for K- Dimensions 15.9 x 15 x 25.1 mm (0.63 x 0.6 x 1 in)
System applications. Construction type removable cage clamp terminal with integrated test
points
The blue terminal block is used for
connection of signals from or in the
hazardous area. Notes
Digital Inputs

The green terminal block is used for


The removable terminals guarantee protection from direct contact by means of
connection of field signals as well as the
a strengthened insulation. This applies to design insulation voltages with the
connection of control signals.
occurrence of maximum overvoltages in accordance with overvoltage
This terminal block has integrated test category III of EN 50178 (1500 V AC).
points for connection of HART
The voltage is to be switched off in the case of design insulation voltages greater
communicators.
than 50 V AC before connecting or disconnecting the device connectors.
The terminal block can be coded with the
Digital Outputs

provided coding pins KF-CP.

Coding Pins
KF-CP
Features
• Coding of K-System terminal blocks
• Packaging unit: 20 x 6 coding pins
Analog Inputs

Function
The terminals can be coded with an Technical data
coding pin by inserting the red tab into a Mechanical specifications
particular slot of the terminal block. Material red insulating material
Mass approx. 1 g per coding pin
Dimensions 0.5 x 2 x 8 mm (0.02 x 0.08 x 0.3 in)
Analog Outputs

11/2010
Accessories

908837 (US) / 208599 (EU)


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


670 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
FDT-Framework PACTware 4.X

Technical data Features


Interface • Universal DTM host platform
Connection adapter with RS 232 interface K-ADP1 or USB interface
• For all DTMs of Pepperl+Fuchs
K-ADP-USB (for K-System)
adapter for gateways with RS 232 intrface K-ADP2 • Approved FDT/DTM technology
(for RPI-System) • Free of charge
adapter for gateways with RS 485 interface K-ADP4
• Internet download possible

K-System
(for RPI-System)
USB/RS 485 interface converter (for LB-System)
Software Function
Hardware requirements PACTware requires 50 MBytes hard drive memory and
a minimum of 40 MBytes main memory. Depending on Manufacturer and fieldbus independent
the complexity of the projects and the DTMs used, the configuration tool with FDT interface
main memory requirement can be greater. A computer
(Field Device Tool)
with a Pentium IV 450 MHz processor or better is
recommended, XGA graphics, and a Microsoft- • Based on FDT technology
compatible mouse or equivalent pointing device arealso • Device Type Manager (DTMs)
required. available for all Pepperl+Fuchs
Software requirements PACTware runs in operating systems Windows

Digital Inputs
devices and systems
XP/Vista/7. The software .NET Framework 2.0 must be
• Commissioning, configuration and
installed. For printing and online help, MS
Internet Explorer 4.0 or higher is required
parameter assignment independent of
Languages German, English, French, Spanish, Russian can be
the process control system
selected • Communication DTMs available for
Licensing PACTware does not require licensing. Please take the serial interfaces and fieldbus systems
license conditions of the DTMs out of the data sheets of • Maintenance, diagnostics and error
the corresponding DTMs. correction
Configuration • In accordance with VDI/VDE 2187

Digital Outputs
Representation of the system Graphic representation of all communication and device
configuration DTMs in the tree structure. In case of online operation
colour code for identification of defective units and
Accessories
simulation operation. Multiple windows can be open Microsoft .NET
simultaneously. It is therefore possible to view the set
device parameters, to monitor the measurement value
and to display the device diagnostic simultaneously.
System planning, application Generation of a configuration by means of a graphical
processing application processing menu. Editing of available
projects. Selection switch markings for each channel.

Analog Inputs
Offline configuration, saving of project data to hard disk
or disk. Automatic comparison of the project plan to the
actual available system when establishing connections
on the device and parameter levels.
Associated products CD-ROM with PACTware and complete DTM-Collection
of all available DTMs of the Pepperl+Fuchs H-, K-, and
E-System devices, HART Multiplexers, Remote I/O-
Systems, FieldConnex devices, and level devices.

Analog Outputs
11/2010

Accessories
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


PACTware 4.X

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 671
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K-ADP-USB Adapter with USB Interface

Features Dimensions
• Isolated USB interface cable
• Used with K-, E- and H-System
devices
• Used with PACTwareTM

32
10.4
K-System

Ø3.8 2
Function L=3m

22
The K-ADP-USB is a programming
adapter that connects the USB interface 55

of a PC/notebook for the PACTware™

12
configuration software and can be used to
program K-, E- and H system barriers via
the programming socket on the front
panel of these barriers. 3

9
12
As K-, E- and H-System devices have 1
Digital Inputs

formerly been equipped with

21
27
21
programming sockets with different
standard dimensions (3.55 mm x

18.3
14

12
18.3 mm, see drawing, pos. 3 – newer
devices 3.5 mm x 14 mm, pos. 1), an Ø3.5 Ø3.55
adapter (pos. 2) for the parameterisation 10.4 10.5
of all devices is attached to K-ADP-USB.
The 18.3 mm version can still be used for
urgent service assignments. However,
Digital Outputs

the user must be aware of the fact that the


plug protrudes from new units by approx. Technical data
4 mm. Extensive pushing of the plug may Electrical specifications
lead to damage on units. Current consumption 50 mA (via USB)
For information about programming and Electrical isolation functional insulation acc. to IEC 62103, rated insulation
software, refer to www.pepperl- voltage 50 Veff
fuchs.com. Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Analog Inputs

Mechanical specifications
Connection to the PC: USB type A
to the device: connector 3.5 mm and 3.55 mm
Cable
Length L 3m
Analog Outputs

11/2010
Accessories

908837 (US) / 208599 (EU)


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


K-ADP-USB

672 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Adapter with RS 232 Interface K-ADP1

Dimensions Features
• Isolated RS 232 interface cable
• Used with K-, E- and H-System
33
devices
Ø3.8 • Used with PACTwareTM
L=3m
10.4

K-System
2 Function

61.5

22
52
The K-ADP1 is an interface adapter that
connects the serial interface of a
PC/notebook for the PACTware™

12
configuration software and can be used to
55
program K-, H-, and E-System barriers via
the programming socket on the front
3 panel of these barriers.
12

1 As K-, E- and H-System devices have

Digital Inputs
formerly been equipped with

21
21

programming sockets with different


standard dimensions (3.55 mm x

18.3
14

18.3 mm, see drawing, pos. 3 – newer


Ø3.5 Ø3.55
devices 3.5 mm x 14 mm, pos. 1), an
10.4 10.5 adapter (pos. 2) for the parameterisation
of all devices is attached to K-ADP1.
The 18.3 mm version can still be used for
urgent service assignments. However,

Digital Outputs
the user must be aware of the fact that the
Technical data plug protrudes from new units by approx.
Electrical specifications 4 mm. Extensive pushing of the plug may
Electrical isolation functional insulation acc. to IEC 62103, rated insulation
lead to damage on units.
voltage 50 Veff For information about programming and
Ambient conditions software, refer to www.pepperl-
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) fuchs.com.
Mechanical specifications

Analog Inputs
Connection to the PC: 9-pin and 25-pin
to the device: connector 3.5 mm and 3.55 mm
Cable
Length L 3m

Analog Outputs
11/2010

Accessories
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


K-ADP1

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 673
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Accessories Signal Conditioners

Measuring Resistor
K-500R0%1

Ø10
Features
• 1-channel 18
28
• High precision resistor
K-System

• Conversion of
4 mA ... 20 mA/2 V ... 10 V Technical data
Electrical specifications
Function Measuring resistor 500 Ω, 0.1 %, TK10
A 500 Ω 0.1% high-precision resistor that Mechanical specifications
can be used to convert 4 mA ... 20 mA to Dimensions Ø10 x 28 mm (0.4 x 1.1 in)
2 V ... 10 V.

Adhesive Sticker
Digital Inputs

KF-SEAL
!

13
Features
• Destructive, removable Scotchmark
sticker 3812, white, matte 16
• Rectangular shape, 16 mm x 13 mm
• For securing front-side Technical data
programming switches and sockets
Mechanical specifications
Digital Outputs

as well as potentiometers, designed


Dimensions 16 x 13 mm (0.63 x 0.5 in)
to match the K-system
• Packaging unit: 20 pieces
Analog Inputs
Analog Outputs

11/2010
Accessories

908837 (US) / 208599 (EU)


Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


674 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Place Holder Barrier KFD0-LGH-GN

Technical data Features


Electrical specifications • Non-IS K-System place holder
Rated voltage ≤ 50 V module
Rated current ≤2 A
• Housing width 20 mm
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F) • Marshalling for field and control side
circuits

K-System
Mechanical specifications
Protection degree IP20 • Jumper configurable
Mass approx. 120 g
Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in), housing type B1 Function
Data for application in connection
with Ex-areas This place holder barrier is a module for
Statement of conformity Pepperl+Fuchs use in cable distribution cables. It
Group, category, type of protection, ¬ II 3G Ex nA II T4 X improves accessibility and compactness
temperature classification within a control cabinet.
Different configurations are possible by
using solder bridges.

Digital Inputs
Safe area circuits can be connected to the
terminals.

Digital Outputs
Analog Inputs
Analog Outputs
Diagrams

Front view
Removable terminals
green
KFD0-LGH-GN
1 2 3
1 7 4 5 6

S6 S11
2 8 KFD0-LGH-GN

S7 S10
3 9
11/2010

Accessories

S3 S2 S1 S16 S15 S14


908837 (US) / 208599 (EU)

6 12
S5 S13
7 8 9
5 11 10 11 12
S4 S12 Removable terminals
4 10 green

Zone 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD0-LGH-GN

Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 675
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
KFD0-LGH-Y34868 Place Holder Barrier

Features Technical data


• IS K-System place holder module Electrical specifications
Rated voltage ≤ 50 V
• Housing width 20 mm
Rated current ≤2 A
• Marshalling for field and control side Ambient conditions
circuits Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
• No electrical function: empty
K-System

Mechanical specifications
housing Protection degree IP20
Mass approx. 100 g
Function Dimensions 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 in), housing type B1
Data for application in connection
This place holder barrier is an empty with Ex-areas
housing that fills unused space on DIN rail Statement of conformity Pepperl+Fuchs
or Power Rail. Group, category, type of protection, ¬ II 3G Ex nA II T4 X
temperature classification
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs

Diagrams

Front view

KFD0-LGH-Y34868
1 2 3
4 5 6
1 7

KFD0-LGH-Y34868 2 8
3 9
11/2010
Accessories

4 10
908837 (US) / 208599 (EU)

5 11
6 12
7 8 9
10 11 12

Zone 2 Zone 2
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


KFD0-LGH-
Y34868
676 Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Signal Conditioners Notes

K-System
Digital Inputs
Digital Outputs
Analog Inputs
Analog Outputs
11/2010

Accessories
908837 (US) / 208599 (EU)
Edition

Subject to modifications without notice Copyright Pepperl+Fuchs


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 677
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com