EXTENDED ALARM

P O W E R I N G T E C H N O L O G Y
BOARD
ACC Extended Controller
Introduction
The Extended Alarm Board is used for wiring of
alarm outputs and signal connections from the
ACC Extended controller. Separate from the
Standard Alarm Board, it offers 6 extra alarm
outputs. It is usually located on the right side
of system PBDU and has dimensions of 4.25”
(108mm) x 3.15” (80mm).

ORDERING PART NUMBER


1-157758G

Connections

Pin Function
XC2, XC3 12 analog inputs are used for battery symmetry measurements or as Multi Purposes. Maximum input voltage
100 VDC.
XC4 * 2 inputs for temperature sensor measurement. Temperature sensor 1 measures the Battery temperature while
the controller adjusts the float / charge voltage according to the temperature compensation factor set in the
controller. Temperature sensor 2 measures the ambient temperature around the system.
XC5, XC6 There are 4 potential free alarm contacts available (Alarm relay 1 - Alarm relay 4). Alarm connections are Form
C relays and can be monitored either Normally Closed (NC) or Normally Open (NO). When the power is OFF,
NC is closed and when the power is ON, the NC is open.
XC7 Pin connector XC7 provides 2 digital inputs (Logic 0 < 8 V, Logic 1 > 10 V) and 5 VDC output.
XC8 Pin connector XC8 provides 2 digital outputs and System voltage output.
XC9, XC10 Additional 4 potential free alarm contacts available (Alarm relay 5 - Alarm relay 8). Alarm connections are
Form C relays and can be monitored either Normally Closed (NC) or Normally Open (NO).
XC11 Depending on Configuration file setup and jumper setting, it can be used either
as additional 2 potential free alarm contacts or as PLD 2 controls.
XC12, XC13 RS485 communications.
* NOTE: Temperature compensation factor is set only for temperature sensor 1
NO
1 2 3 4 5 6

NC NO
3
Alarm contacts are s hown in alarm position

C Alarm 5 NC
2 XC5 Alarm 1
C
XC9

NO 1
3 Multi purpose 3
NC NO
Alarm 6 6 2 XC2 Multi purpose 2
C NC 5 XC5 Alarm 2 1 Multi purpose 1
C
4
6 Multi purpose 6
NO NO 5 XC2 Multi purpose 5
3
1 2 3 4 5 6

NC NC 2 Multi purpose 4
Alarm 7 XC6 Alarm 3 4
C C 1 3 Multi purpose 9
XC1 0

NO NO 6 2 XC3 Multi purpose 8


NC NC 5 1 Multi purpose 7
Alarm 8 XC6 Alarm 4
C C 4 6 Multi purpose 12
4 GND 5 XC3 Multi purpose 11
3 +5V 4 Multi purpose 10
NO XC7
+
1 2 3 4 5 6

NC 2 Digital Input 2 3
Alarm 9 / PLD 2 reconnected 1 Digital Input 1 Temperature T Battery
C 2 XC4
sensor - Temperature
XC1 1

NO 4 -Sys.Voltage In 1
3 +Sys.Voltage In +
XC8 6
acc_alarm-ds-revC-0616.indd

NC
Alarm 10 / PLD 2 disconnected 2 Digital Output 2 Temperature T XC4 Ambient
C 5
1 Digital Output 1 sensor - Temperature
4

www.unipowerco.com