Bluewaters-Wharf Retail (BW04) Architectural WIR, Date-29/09/2016

Bluewaters-Wharf Retail (6004) Employer:


Architect of Records : WSP Middle East Ltd. Contractor:

SL No IR Ref No Rev. Originator Stru/Arch Element Description Level Zone Grid WIR Reciving Date Submission Date Actual Submission to Status Of Submission QA/QC Inspector Site Engineer & Manager Remarks
WB
Inspection for Insulation Sheet Proir to Start Geotextile Zone-11 Roof TC Building Grid-G1-11-G1-15-G1-F-G1-K
1 6004-0100-IKK-0710-WR-12793 0 IKK Architectural Waterproofing Roof 11 G1-11-G1-15-G1-F-G1-K 25-Sep-16 25-Sep-16 28-Sep-16 Submited Akshay brandon Approved

Inspection for lining marking Arrow Zone-11 B1 Car Parking Aera


2 6004-0100-IKK-0100-WR-12817 0 IKK Architectural Lining Marking B1 11 N/A 25-Sep-16 25-Sep-16 28-Sep-16 Submited Akshay brandon Approved , arrow marking excluded

Inspection for Final Coat Epoxy paint Zone-11 B1


3 6004-0100-IKK-0100-WR-12818 0 IKK Architectural Final Coat paint B1 11 N/A 25-Sep-16 25-Sep-16 28-Sep-16 Submited Akshay brandon Approveed

Inspection for Waterproofing Membrance and Flood Test Water Filled Time 06.00am and Date-25-09-2016 Roof TB Building Zone-10 Grid-G1-24-G1-31-G1-C-G1-L
4 6004-0100-IKK-0710-WR-12849 0 IKK Architectural Waterproofing Roof 10 G1-24-G1-31-G1-C-G1-L 26-Sep-16 26-Sep-16 26-Sep-16 Submited Akshay brandon Flood test to be witnessed 29/09/16

Inspection for Plaster Completion Stair Case Wall Zone-05 Grid-G3-F-G-G2-1


5 6004-0100-ALE-0100-WR-12852 0 ALEC Architectural Plaster Completion GF & Roof 5 G3-F-G-G2-1 26-Sep-16 26-Sep-16 28-Sep-16 Submited Akshay sankar Approved

Inspection for Plaster Completion Stair Case Wall Zone-03 GF & Roof Grid-G3-T-U-G3-00B-G2-7
6 6004-0100-ALE-0100-WR-12853 0 ALEC Architectural Plaster Completion GF & Roof 3 G3-T-U-G3-00B-G2-7 26-Sep-16 26-Sep-16 28-Sep-16 Submited Akshay sankar Approved

Inspection for Plaster Preparation Proir to Plastring Zone-07 Grid-G1-J-L-G2-16


7 6004-0100-ALE-0100-WR-12856 0 ALEC Architectural Plaster Completion B1 7 N/A 26-Sep-16 26-Sep-16 Not Submit Akshay gokul Rejected. Plastering already done

Inspection for Plaster Preparation Proir to Plastering Zone-08 Grid-G1-L-G-70-71 B1


8 6004-0100-ALE-0100-WR-12857 0 ALEC Architectural Plaster Preparation B1 8 N/A 26-Sep-16 26-Sep-16 Not Submit Akshay gokul Rejected. Plastering already done

Inspection for Waterproofing membrance and Flood test Water Filled Time 09.00am and Date 09-27-2016 Zone-8 EC BuildinG Roof
9 6004-0100-IKK-0710-WR-12881 0 IKK Architectural Waterproofing Roof 8 N/A 27-Sep-16 27-Sep-16 28-Sep-16 Submited Akshay brandon Approved

Inspection for Mesh and Primer Finished to Continue With Texture and First Coat Paint Rooftop Parapet Zone-4 SM Building
10 6004-0100-NIS-0724-WR-12883 0 NIS Architectural EIFS Roof 4 N/A 27-Sep-16 27-Sep-16 28-Sep-16 Submited Akshay brandon Approved

Inspection for EIFS-EPS and Dowels Finished to Continue With Mesh and Plaster Rooftop Parapet Zone-5 SB Building
11 6004-0100-NIS-0724-WR-12885 0 NIS Architectural EIFS Roof 5 N/A 27-Sep-16 27-Sep-16 28-Sep-16 Submited Akshay brandon Approved

Inspection for Mesh and Primer Finished to Continue With Texture and First Coat Paint Rooftop Parapet Zone-3 SD Building
12 6004-0100-NIS-0724-WR-12886 0 NIS Architectural EIFS Roof 3 N/A 27-Sep-16 27-Sep-16 28-Sep-16 Submited Akshay brandon Approved with minor comments

Inspection for Mesh and Primer Finished to Continue With Texture and First Coat Paint Rooftop Parapet Zone-5 SQ Building
13 6004-0100-NIS-0724-WR-12887 0 NIS Architectural EIFS Roof 5 N/A 27-Sep-16 27-Sep-16 28-Sep-16 Submited Akshay brandon Approved

Inspection for Mesh and Primer Finished to Continue With Texture and First Coat Paint Rooftop Parapet Zone-5 SC Building
14 6004-0100-NIS-0724-WR-12888 0 NIS Architectural EIFS Roof 5 N/A 27-Sep-16 27-Sep-16 28-Sep-16 Submited Akshay brandon Approved

Inspection for Mesh and Primer Finished to Continue With Texture and First Coat Paint Rooftop Parapet Zone-3 SP Building
15 6004-0100-NIS-0724-WR-12889 0 NIS Architectural EIFS Roof 3 N/A 27-Sep-16 27-Sep-16 28-Sep-16 Submited Akshay brandon Approved

16 6004-0100-NIS-0724-MR-0887 0 NIS Architectural Material Inspection Material Inspection for EIFS Installation to Parapet Walls Wharf Retail Roof Site Wide N/A Site Wide N/A 27-Sep-16 27-Sep-16 28-Sep-16 Submited Akshay brandon Approved

17 6004-0100-ALE-0100-WR-12897 0 ALEC Architectural Roof Ballast Inspection for Roof Ballast Zone-4 SM Building Roof 4 N/A 28-Sep-16 28-Sep-16 29-Sep-16 Not Submit Akshay brandon

18 6004-0100-ALE-0100-WR-12899 0 ALEC Architectural Plaster Completion Inspection for Plaster Completion Zone-06 Grid-G2-E-G-G2-2-5 B1-GF 6 G2-E-G-G2-2-5 28-Sep-16 28-Sep-16 29-Sep-16 Not Submit Akshay gokul

19 6004-0100-IKK-0100-WR-12908 0 IKK Architectural Surface Preparation Inspection for Surface Preparation Proir to Epoxy Paint Zone-02 B2 Car Parking Area B2 2 N/A 28-Sep-16 28-Sep-16 29-Sep-16 Not Submit Akshay brandon

20 6004-0100-IKK-0100-WR-12909 0 IKK Architectural Final Coat paint Inspection for Final Coat Epoxy Paint Zone-6 Lvl-1 SR Building Elec Room Colodour lvl-1 6 N/A 28-Sep-16 28-Sep-16 29-Sep-16 Not Submit Akshay brandon

21 6004-0100-IKK-0100-WR-12910 0 IKK Architectural Surface Preparation Inspection for Surface Preparation Proir to Epoxy Paint Zone-08 B2 Car Parking Area B2 8 N/A 28-Sep-16 28-Sep-16 29-Sep-16 Not Submit Akshay brandon

22 6004-0100-ALE-0100-WR-12911 0 ALEC Architectural Plaster Preparation Inspection for Plaster Preparation Zone-11 Grid-G1-G-H-G1-13-17 GF 11 N/A 28-Sep-16 28-Sep-16 29-Sep-16 Not Submit Akshay Lalu

Inspection for the Installation for GRC Cladding Panels on SS Building Elve-1,2,3,4 Zone-2 Grid-G2-Q-R-G2-7-8
23 6004-0100-NFG-0349-WR-12762 0 NFG Architectural Wall Cladding GF 2 G2-Q-R-G2-7-8 22-Sep-16 22-Sep-16 24-Sep-16 Submited Azhar Ziyad send to WB

Inspection for Block Work Complection Zone-11 Grid-G1-J-L-G1-11-14 submited haris AJAY approved
24 6004-0100-ALE-0320-WR-12696 0 ALEC Architectural Block Work Completion B2-GF 11 G1-J-L-H-G1-11-14 24-Sep-16 24-Sep-16 28-Sep-16

Inspection for Block Work Setting Out Proir to Start Block Work Zone-9 Grid-G1-L-G1-36-41 B1 Lvl Pour-09 submited haris ajay approved
25 6004-0100-ALE-0100-WR-12643 0 ALEC Architectural Block Work B1 9 G1-L-G1-36-41 25-Sep-16 25-Sep-16 28-Sep-16

Inspection for Block Work Setting Out proir to Start Rebar Work Zone-09 Grid-G1-C-E-G1-39-43 submited haris AJAY approved
26 6004-0100-ALE-0100-WR-12861 0 ALEC Architectural Block Work GF 9 G1-C-E-G1-39-43 26-Sep-16 26-Sep-16 28-Sep-16

Inspection for Block Work Setting Out proir to Start Rebar Work Zone-09 Pour-2 Grid-G1-D-E-G1-46-53 submited haris AJAY approved
27 6004-0100-ALE-0100-WR-12862 0 ALEC Architectural Block Work GF 9 G1-D-E-G1-46-53 26-Sep-16 26-Sep-16 28-Sep-16

Inspection for Blokc Work Setting Out Proir to Start Rebar Work Zone-09 Grid-G1-E-F-G1-43-53 submited haris AJAY approved
28 6004-0100-ALE-0100-WR-12863 0 ALEC Architectural Block Work GF 9 G1-E-F-G1-43-53 26-Sep-16 26-Sep-16 28-Sep-16

Inspection for Block Work Setting Out proir to Start Block Work Zone-09 Pour-9 Grid-G1-J-K-G1-37-39 submited haris AJAY approved
29 6004-0100-ALE-0100-WR-12877 0 ALEC Architectural Block Work B1 9 N/A 27-Sep-16 27-Sep-16 28-Sep-16

Inspection for Installation of Secondary Steel Zone-08 EC-5 GF & 1 Floor


30 6004-0100-JML-0880-WR-12773 0 JML Architectural Installation GF & 1 Floor 8 N/A 22-Sep-16 22-Sep-16 26-Aug-16 Submited Hesham Ziyad

Inspection for Curtain Wall System With Swing Doors Zone-6 GF & 1 Floor EA-07
31 6004-0100-JML-0880-WR-12843 0 JML Architectural Installation GF & 1 Floor 6 N/A 25-Sep-16 25-Sep-16 26-Sep-16 Submited Hesham Ziyad

Inspection for Curtain Wall System With Swing Doors Zone-6 GF SR-17
32 6004-0100-JML-0880-WR-12844 0 JML Architectural Installation GF 6 N/A 25-Sep-16 25-Sep-16 26-Sep-16 Submited Hesham Ziyad

Inspection for Curtain Wall System With Swing Door Zone-08 EC-05 GF & 1 Floor
33 6004-0100-JML-0880-WR-12864 0 JML Architectural Installation GF & 1 Floor 8 N/A 26-Sep-16 26-Sep-16 27-Sep-16 Submited Hesham Ziyad

34 6004-0100-JML-0880-WR-12914 0 JML Architectural Installation Inspection for Water Spray test on Curtain Wall System Zone-08 GF & 1 Floor GF & 1 Floor 8 N/A 28-Sep-16 28-Sep-16 29-Sep-16 Submited Hesham Ziyad

Inspection for Fire resistive Joints Application for Head of Wall and Wall to Wall Joints Fire Rated Zone-8 B2 Grid-G1-E-G1-G-G1-62-G1-64
35 6004-0100-FIR-0792-WR-12800 0 FIR Architectural Fire Sealant B2 8 G1-E-G1-G-G1-62-G1-64 26-Sep-16 26-Sep-16 27-Sep-16 Submited Ramsuresh murrey Approved

Inspection for Fire resistive Joints Application for Head of Wall and Wall to Wall Joints Fire Rated Zone-2 B2 Grid-G2-Q-G2-R-G2-8-G2-10
36 6004-0100-FIR-0792-WR-12801 0 FIR Architectural Fire Sealant B2 2 G2-Q-G2-R-G2-8-G2-10 26-Sep-16 26-Sep-16 27-Sep-16 Submited Ramsuresh murrey Approved

Inspection for Fire resistive Joints Application for Head of Wall and Wall to Wall Joints Fire Rated Zone-8 B2 Grid-G1-F-G1-G-G1-60-G1-61
37 6004-0100-FIR-0792-WR-12802 0 FIR Architectural Fire Sealant B2 8 G1-F-G1-G-G1-60-G1-61 26-Sep-16 26-Sep-16 27-Sep-16 Submited Ramsuresh murrey Approved

Inspection for Fire resistive Joints Application for Head of Wall and Wall to Wall Joints Fire Rated Zone-11 B2 Grid-G1-A-G1-C-G1-11-G1-12
38 6004-0100-FIR-0792-WR-12803 0 FIR Architectural Fire Sealant B2 11 G1-A-G1-C-G1-11-G1-12 26-Sep-16 26-Sep-16 27-Sep-16 Submited Ramsuresh murrey Approved

Inspection for Fire resistive Joints Application for Head of Wall and Wall to Wall Joints Fire Rated Zone-08 GF Grid-G1-G-G1-H-G1-61-G1-63
39 6004-0100-FIR-0792-WR-12804 0 FIR Architectural Fire Sealant GF 8 G1-G-G1-H-G1-61-G1-63 26-Sep-16 26-Sep-16 27-Sep-16 Submited Ramsuresh murrey Approved

Inspection for Fire resistive Joints Application for Head of Wall and Wall to Wall Joints Fire Rated Zone-10 GF Grid-G1-E-G1-D-G1-32-G1-33
40 6004-0100-FIR-0792-WR-12805 0 FIR Architectural Fire Sealant GF 10 G1-E-G1-D-G1-32-G1-33 26-Sep-16 26-Sep-16 Not Submit Ramsuresh murrey work in progress

Inspection for Fire resistive Joints Application for Head of Wall and Wall to Wall Joints Fire Rated Zone-11 GF Grid-G1-D-G1-K-G1-11-G1-15
41 6004-0100-FIR-0792-WR-12806 0 FIR Architectural Fire Sealant GF 11 G1-D-G1-K-G1-11-G1-15 26-Sep-16 26-Sep-16 Not Submit Ramsuresh murrey work in progress

Inspection for Fire resistive Joints Application for Head of Wall and Wall to Wall Joints Fire Rated Zone-11 GF Grid-G1-E-G1-C-G1-11-G1-14
42 6004-0100-FIR-0792-WR-12807 0 FIR Architectural Fire Sealant GF 11 G1-E-G1-C-G1-11-G1-14 26-Sep-16 26-Sep-16 Not Submit Ramsuresh murrey work in progress

Inspection for Fire resistive Joints Application for Head of Wall and Wall to Wall Joints Fire Rated Zone-06 GF Grid-G1-L-G1-M-G2-6-G2-4
43 6004-0100-FIR-0792-WR-12808 0 FIR Architectural Fire Sealant GF 6 G1-L-G1-M-G2-6-G2-4 26-Sep-16 26-Sep-16 27-Sep-16 Submited Ramsuresh murrey Approved

Inspection for Fire resistive Joints Application for Head of Wall and Wall to Wall Joints Fire Rated Zone-05 GF Grid-G3-L-G-3P-G3-2-2-G3-3
44 6004-0100-FIR-0792-WR-12809 0 FIR Architectural Fire Sealant GF 5 G3-L-G-3P-G3-2-2-G3-3 26-Sep-16 26-Sep-16 27-Sep-16 Submited Ramsuresh murrey Approved

Inspection for Fire resistive Joints Application for Head of Wall and Wall to Wall Joints Fire Rated Zone-07 B1 Grid-G1-A-G1-B-G1-68-G1-72
45 6004-0100-FIR-0792-WR-12810 0 FIR Architectural Fire Sealant B1 7 G1-A-G1-B-G1-68-G1-72 26-Sep-16 26-Sep-16 27-Sep-16 Submited Ramsuresh murrey Approved

Inspection for Fire resistive Joints Application for Head of Walll to Wall Joints Fire Rated Zone-04 GF Grid-G2-D-G2-D-G2-14-G2-13
46 6004-0100-FIR-0792-WR-12811 0 FIR Architectural Fire Sealant GF 4 G2-D-G2-D-G2-14-G2-13 26-Sep-16 26-Sep-16 27-Sep-16 Submited Ramsuresh murrey Approved

Inspection for Fire resistive Joints Application for Head of Wall of Wall to Wall Joints Fire Rated Zone-07 B1 Grid-G1-E-G1-L-G2-11-G2-14
47 6004-0100-FIR-0792-WR-12812 0 FIR Architectural Fire Sealant GF 7 G1-E-G1-L-G2-11-G2-14 26-Sep-16 26-Sep-16 27-Sep-16 Submited Ramsuresh murrey Approved

Inspection for Fire resistive Joints Application for Head of Wall and Wall to Wall Joints Fire Rated Zone-07 GF Grid-G1-D-G1-L-G2-9-G2-5
48 6004-0100-FIR-0792-WR-12813 0 FIR Architectural Fire Sealant GF 7 G1-D-G1-L-G2-9-G2-5 26-Sep-16 26-Sep-16 Not Submit Ramsuresh murrey work in progress

Inspection for Surface Preparation for Men Hole in side Proir to GRP Zone-2 Pour-2 B2
49 6004-0100-ALE-0710-WR-12854 0 ALEC Architectural Surface Preparation B2 2 N/A 26-Sep-16 26-Sep-16 27-Sep-16 Submited Ramsuresh sankar Approved

Inspection for Surface Preparation for Men Hole in side Proir to Painting Zone-3 Pour-2 B2-GF
50 6004-0100-ALE-0710-WR-12855 0 ALEC Architectural Surface Preparation B2-GF 3 N/A 26-Sep-16 26-Sep-16 27-Sep-16 Submited Ramsuresh sankar Approved

Inspection for Surface Preparation Proir to Screed Zone-08 Grid-G1-L-G1-68-71


51 6004-0100-ALE-0100-WR-12867 0 ALEC Architectural Screed Preparation B2 8 G1-L-G1-68-71 26-Sep-16 26-Sep-16 27-Sep-16 Submited Ramsuresh gokul Approved

Inspection for Surface Preparation Proir to screed Zone-02 Grid-G2-S-T-G-28-10


52 6004-0100-ALE-0100-WR-12891 0 ALEC Architectural Screed Preparation B2 2 G2-S-T-G-28-10 27-Sep-16 27-Sep-16 Not Submit Ramsuresh gokul work in progress

Inspection for Surface Preparation Proir to screed Zone-03 Grid-G2-S-T-G2-7-8


53 6004-0100-ALE-0100-WR-12892 0 ALEC Architectural Screed Preparation B2 3 G2-S-T-G2-7-8 27-Sep-16 27-Sep-16 Not Submit Ramsuresh gokul work in progress

54 6004-0100-FIR-0792-WR-12826 0 FIR Architectural Fire Sealant Inspection for Fire Resistive Joints Application for Head of And Wall an Wall to Wall Joints Fire Rated Zone-4 Grid-G1-L-G2-M-G2-8-G2-10 GF 4 G1-L-G2-M-G2-8-G2-10 28-Sep-16 28-Sep-16 29-Sep-16 Submited Ramsuresh murrey

55 6004-0100-ALE-0100-WR-12879 0 ALEC Architectural Surface Preparation Inspection for Surface Preparation Slab Soffit Proir to Primer Zone-09 Grid-G1-F-J-G1-36-41 B1 9 N/A 28-Sep-16 28-Sep-16 29-Sep-16 Submited Ramsuresh Lalu

56 6004-0100-ALE-0100-WR-12906 0 ALEC Architectural Surface Preparation Inspection for Surface Preparation Slab Soffit & Column Wall Proir to Primer Zone-09 Grid-G1-G-L-G1-44-49 B1 9 G1-G-L-G1-44-49 28-Sep-16 28-Sep-16 29-Sep-16 Submited Ramsuresh Lalu

Inspection for steel Door Installation with Ironmongery. Door type DM 001-01 No's DM-011-02 Nos Zone-5 GF
57 6004-0100-MCI-0811-WR-12675 0 MCI Architectural Steel Door GF 5 N/A 18-Sep-16 18-Sep-16 Not Submit sabareesh Micheal QC Comments

Inspection for steel Door Installation with Ironmongery. Door type DM 001-01 No's DM-011-02 Nos Zone-5 LVL-1
58 6004-0100-MCI-0811-WR-12676 0 MCI Architectural Steel Door LVL-1 5 N/A 18-Sep-16 18-Sep-16 Not Submit sabareesh Micheal QC Comments

Inspection for Kerbstone Setting Out Zone-15 Tunnel


59 Tunnel N/A Open regarding setting out drawing
6004-0100-ALE-0100-WR-12384 0 ALEC Architectural Kerb Stone 15 14-Sep-16 14-Sep-16 18-Sep-16 Submited selvan Brendon
approval
Inspection for Galvanized Paint finish Wall Handrail Zone-06 SR Building B2 - GF
60 6004-0100-ACS-0112-WR-12644 0 ACS Architectural Supply and Installation B2-GF 6 N/A 18-Sep-16 18-Sep-16 18-Sep-16 Submited selvan Micheal QC Comments still not rectified

Inspection for Galvanized Wall Mounted Handrail Zone-06 EA Building Srair 8A B2 - GF


61 6004-0100-ACS-0112-WR-12645 0 ACS Architectural Supply and Installation B2-GF 6 N/A 18-Sep-16 18-Sep-16 18-Sep-16 Submited selvan Micheal QC Comments still not rectified

Inspection for Galvanized Wall Mounted Handrail Zone-06 EA Building Srair 8A B2 - GF


62 6004-0100-ACS-0112-WR-12646 0 ACS Architectural Supply and Installation B2-GF 6 N/A 18-Sep-16 18-Sep-16 18-Sep-16 Submited selvan Micheal QC Comments still not rectified

Material Inspection for 1. Jotashield Filler 2.Jotashied Penterating Primer, 3 Jotashield tex Ultra Ral 7038 & ral-0964 4 Stucco Putty 5 Fenomastic Dilk My Home Ral 5018 ral 4005 With Attached Delivery
63 6004-0100-RGM-0990-MR-0876 0 RGM Architectural Material Inspection Note Zone-14 & 16 B2 N/A 14 & 16 25-Sep-16 25-Sep-16 Not Submit selvan Brendon Found ok will submit tomorrow

Inspection for 60*60*6mm GLTrunch Langle Fixing ON Transformer Room D As per Drw RMU Room Zone-4
64 6004-0100-ACS-1112-WR-12730 0 ACS Architectural Supply and Installation GF 4 N/A 26-Sep-16 26-Sep-16 27-Sep-16 Submited selvan Brendon concrete already done

Material Inspection Promat H Fire Rated Bord With Attached Delivery Note & Promat Certificate of Conformance Zone-14 & 15 B2
65 6004-0100-RGM-0990-MR-0877 0 RGM Architectural Material Inspection B2 15 & 14 N/A 26-Sep-16 26-Sep-16 27-Sep-16 Submited selvan Brendon Approved with comments

Material Inspection for Duct Protection qty 7 Nos Zone-4 B1 lvl


66 6004-0100-ACS-1112-MR-0878 0 ACS Architectural Supply & Install B1 4 N/A 26-Sep-16 26-Sep-16 Not Submit selvan Arun Found ok will submit tomorrow

Inspection of fixing of Secondery supportes for Electical Panels on LV Room C Zone-08 B1


67 6004-0100-ACS-11112-WR-12873 0 ACS Structrul Supply and installation B1 8 N/A 27-Sep-16 27-Sep-16 Not Submit selvan Arun

Inspection for Surface Preparation Proir to Start Primer Zone-09 Grid-G1-H-L-G1-34-40 B2


68 6004-0100-RGM-0990-WR-12882 0 RGM Architectural Surface Preparation B2 9 N/A 27-Sep-16 27-Sep-16 Not Submit selvan Micheal Found ok will submit tomorrow

Inspection for Fixing Secondary Supports for Electrical Panels on LV Room D Zone-7 B1
69 6004-0100-ACS-1112-WR-12890 0 ACS Architectural Supply and installation B1 7 N/A 27-Sep-16 27-Sep-16 Not Submit selvan Micheal offered to alvin but he didn’t comment yet

Inspection for Mock up for 1 Hour Fire Rated Partition teranches Zone-08 Madame Tussaused EC-001 GF
70 6004-0100-RGM-0990-WR-12896 0 RGM Architectural Mock UP GF 8 N/A 27-Sep-16 27-Sep-16 28-Sep-16 Submited selvan Micheal Found ok tomorrow it will be approved

71 6004-0100-ACS-1112-MR-0879 0 ACS Architectural Supply & Install Material Inspection for EDGE Angle 60mm*60mm*6mm Oty=51Nos total Qty 306MTR N/A Site Wide N/A 27-Sep-16 27-Sep-16 Not Submit selvan Micheal offered to alvin but he didn’t comment yet

72 6004-0100-ACS-1112-MR-0880 0 ACS Architectural Material Inspection Material Inspection for 1 Beam 178*102*19kg/m qty=52 nos Total qty=55.2 mtr 2. MS Bracket Oty 53 No's 3. Channel Galvanized Qty-31 Nos Total Qty 21.99MTR N/A 8 LV ROOM 27-Sep-16 27-Sep-16 Not Submit selvan Micheal offered to alvin but he didn’t comment yet

73 6004-0100-ACS-1112-MR-0722 1 ACS Architectural Material Inspection Material Inspection for Bravkets for Secondery Beams Zone-07 Room N/A 7 N/A 27-Sep-16 27-Sep-16 Not Submit selvan Micheal offered to alvin but he didn’t comment yet

Bluewaters-Wharf Retail (BW04) Snagging IR,


SL No SNAG Ref. No. Rev. Orginator Arch/ Struc Activity Description Area Building Zone IR Received Date MLD Submital Date Actual Submission to Status Of Submission QA/QC Inspector Site Engineer & Manager Remarks
MLD
1 6004-0100-ALE-0100-SL-0018 1 ALEC Architectural De-Snagging De-Snagging of : Retail LOO.SK0004 Zone-4 GF SK Building GF 4 17-Sep-16 Submit
SK Building 18-Sep-16 18-Sep-16 hesham Samir Mulla
2 6004-0100-ALE-0100-SL-0021 1 ALEC Architectural De-Snagging De-Snagging of : Retail LOO.SK0001 Zone-4 GF SK Building GF 4 17-Sep-16 Submit
SK Building 18-Sep-16 18-Sep-16 hesham Samir Mulla
3 6004-0100-ALE-0100-SL-0022 1 ALEC Architectural De-Snagging De-Snagging of : Retail LOO.SK0002 Zone-4 GF SK Building GF 4 17-Sep-16 Submit
SK Building 18-Sep-16 18-Sep-16 hesham Samir Mulla
4 6004-0100-ALE-0100-SL-0066 0 ALEC Architectural Snaging Snagging of : Completion of Snagging to be Inspected Room-L00.SF001 Zone-4 GF GF 5 17-Sep-16
SF Building hesham Samir Mulla
5 6004-0100-ALE-0100-SL-0044 1 ALEC Architectural Snaging Snagging of : Retail-L00.SF002 Zone-5 GF GF 5 19-Sep-16 19-Sep-16 19-Sep-16 Submit
SF Building hesham Samir Mulla