HR PN 0.

1
Gas pressure regulator
Inlet pressure 100 mbar
DN 25, 32, 40, 50, 65, 80, 100

Applications Main features


Pressure reducing for • Fully inlet pressure balanced
- utilisation
• Inlet pressure resistant up to 16 bar
- domestic application
• Excellent outlet pressure control
• Minimum differential pressure 4 mbar
Brief information
The HR series of service regulators is intended for use with several meters in small, me- • Firesafe according to DIN 33822
dium and large consumption units. They are available with or without an integrated
• Operation temperature -20 °C to +60 °C
low-pressure cut-off valve, which has an automatic reset.
The units are DVGW approved according to DIN 33822. • Safety diaphragm
Registration number: NG-4330CL0336
• Omnidirectional installation
horizontal/vertical
Technical data
- Inlet pressure range pu 22 mbar to 100 mbar • Tamper-proof
- Outlet pressure range pds 18 to 50 mbar - crimped (DN 25 – DN 32)
- Design with low pressure cut-off pds 18 to 30 mbar (HR 25/32) - screwed (DN 40 – DN 50)
(different setting springs necessary) • Housing cathodic immersion coated
- Minimum differential pressure Δpmin 4 mbar
- Excess flow valve (GS): VN 2.5, 4, 6, 10, 16 m3/h • Sieve in inlet
(optional for HR 25, HR 32) Options
- Factory-adjusted and tested
- Cut-off range 115% to 180% of VN • Low pressure cut-off
Omnidirectional installation horizontal/vertical. • Integrated excess flow valve (GS)
(DN 25/32)
Pressure ranges & accuracy classes
• Flood resistant
Type / Diameter HR 25 HR 32 HR 40 HR 50 HR 65 HR 80 HR 100
Control pressure range 18 – 50 (GMS: 18 – 30) 18 – 50
Control accuracy class AC 10
Look up pressure class SG 30

Ordering example
HR 25 GS4 with low pressure cut-off and integrated excess flow valve
- Inlet pressure ... to ... mbar
- Outlet pressure ... mbar
- Nominal cut-off capacity of excess flow valve (optional)
- Orientation

Design
HR... Standard design without low pressure cut-off
HR...S Design with low pressure cut-off
HR...GS Design with integrated excess flow valve and low pressure cut-off

Instromet
HR PN 0,1: Gas pressure regulator, inlet pressure 100 mbar, DN 25, 32, 40, 50, 65, 80, 100

Technical data and dimensions


Type Capacities natural gas [stcm/h] Connection Dimensions Weight D
Qmax, pu min Qmax, pu max Line Thread Flange LG LF H1 D [kg]
HR 25 15 62 DN 25 G 1½ - 140 - 110 111 approx. 1.7

H1
HR 32 15 62 DN 32 G2 - 140 - 110 111 approx. 1.9
HR 40 40 130 DN 40 G 2¼ - 210 - 158 185 approx. 4.0
HR 50 45 150 DN 50 G 2¾ - 210 - 158 185 approx. 4.2 LG
HR 65 V 120 640 DN 65 - PN 16 - 310 259 262 approx.22.2 LF

HR 80 V 150 700 DN 80 - PN 16 - 310 259 262 approx.23.2


HR 100 V 205 750 DN 100 - PN 16 - 350 259 262 approx.28.0

Flanges to EN 1092-2, form B; thread to ISO 228-1

Maximum capacity
'p [mbar]
100

10
2

0V
/3

/5

V
V
25

40

65
80

10
HR

HR

HR
HR

HR

1
10 20 50 100 200 500 1000
Flow rate stcmh for natural gas (AC10)

Inlet pressure range GS


Type GS 2.5 GS 4 GS 6 GS 10 GS 16
Colour code green yellow red blue purple
HR 25 Inlet pressure range pu [mbar]
HR 25
pd +4 to 100 pd +4 to 100 pd +4 to 100 pd +4 to 100 35 to 100
HR 32 Colour coding of the regulators in accordance with table

Your contacts
Germany Belgium Singapore
Elster GmbH Elster NV/SA Elster-Instromet Sdn. Bhd. (Singapore Branch)
Steinern Str. 19 - 21 Rijkmakerlaan 9 29 Tai Seng Avenue
55252 Mainz-Kastel 2910 Essen #06-05A Natural Cool Lifestyle Hub
T +49 6134 605 0 T +32 3 670 0700 Singapore 534119
F +49 6134 605 223 F +32 3 667 6940 T +65 6247 7728
www.elster-instromet.com www.elster-instromet.com F +65 6848 9003
Vital Connections info@elster-instromet.com info@elster-instromet.com sales@elster-instromet.com.sg

73030219 Copyright 2012 Elster GmbH


HR EN04 All rights reserved.
A07.05.2012 Subject to change without prior notice

You might also like